HomeMy WebLinkAboutS-347349HVAC /PLUMBING LEGEND
24x12 S 24x12
DUCT — FIRST FIGURE IS SIDE SHOWN
12x12
12x12 -
DUCT WITH ACOUSTICAL LINING
DIMENSIONS ARE FREE
i
DIRECTION OF FLOW
SUPPLY DUCT — ELBOW UP OR DOWN
�
)NET AREA
ARROW DINRDIRETR IIONR DROP FD),
BELT DRIVE
STANDARD BRANCH WITH SPUTTER DAMPER
NOTES
BFP
BACKFLOW PREVENTER
GPM
RETURN DUCT — ELBOW UP OR DOWN
BR
BOILER
650
0.25
s' BTU
BRITISH THERMAL UNIT
MANUAL VOLUME DAMPER
( 'i�'I
JJJ- -- Lij
�/
STANDARD BRANCH WITH SPUTTER DAMPER
AND TURNING VANES
---D —i BD
BACK DRAFT DAMPER
i�
FD
FIRE DAMPER (PROVIDE ACCESS DOOR FOR
INSPECTION AND LINK REPLACEMENT.)
T t _
ED' � ED
GRILLE AND REGISTER CONNECTION WITH
EXTRACTION DAMPER
BCD
CONTROL DAMPER
AD
'�� AD[j ' AD
DUCT ACCESS DOOR
CENTRIFUGAL
HS
HAND SWITCH
CER
FC
FLEXIBLE DUCT CONNECTION
`—�12x1 ,, Ml2x122
SC p 0�— (W SC ID 00
CEILING SUPPLY DIFFUSER INDICATING
NECK SIZE, THROW, & AIR QUANTITY
®
SUPPLY DUCT IN SECTION
z
EXHAUST OR RETURN DUCT IN SECTION
��I�12x12p 12x17,2
CER 200 EC R 00
CEILING EXHAUST OR RETURN REGISTER
INDICATING NECK SIZE, THROW, & AIR QUANTITY
OT
THERMOSTAT
CHILLED WATER SUPPLY
2
12x120
WSD2p
1217200
WSDp
WALL SUPPLY DIFFUSER INDICATING
NECK SIZE, THROW, & AIR QUANTITY
O
TEMPERATURE SENSOR
IIOII
1220012 200
WER ����-- --IIIIIIII WEIR
WALL EXHAUST OR RETURN REGISTER
INDICATING NECK SIZE, THROW, &AIR QUANTITY
HS
HAND SWITCH
CSD
CEILING SUPPLY DIFFUSER
IN.
FLOW METER
5�
I
1
COEFFICIENT, VALVE FLOW
TURNING DUCT
�
WATER HEATER
—N HB
HOSE BIBB
OI
INTERLOCK
LAVATORY
GATE VALVE
OM
MOTOR
POUNDS
IOI
LOSS IN FEET
BALL VALVE
LEAVING WATER TEMPERATURE
HVAC AND PLUMBING ABBREVIATIONS
;I AC AIR CONDITIONING F FAN
AH
AIR HANDLING UNIT
FC
FAN COIL
TYPE
DRIVE
FD
FLOOR DRAIN
BD
BELT DRIVE
VOLTS /PHASE
NOTES
BFP
BACKFLOW PREVENTER
GPM
GALLONS PER MINUTE
BR
BOILER
650
0.25
s' BTU
BRITISH THERMAL UNIT
H
HEATING
i
BUILDING
HC
HEATING COIL
- CC
COOLING COIL
HOA
HAND /OFF /AUTO
CD
CONTORL DAMPER
HP
HORSEPOWER
CENT
CENTRIFUGAL
HS
HAND SWITCH
CER
CEILING EXHAUST RETURN
HSPF
HEATING SEASONAL PROFICIENCY FACTOR
CFM
CUBIC FEET PER MINUTE
HTG
HEATING
CH
CHILLER
HVAC
HEATING VENTILATING AIR CONDITIONING
'- CHWS
CHILLED WATER SUPPLY
HWR
HEATING WATER RETURN
1 CHWR
CHILLED WATER RETURN
HWS
HEATING WATER SUPPLY
CO
CLEAN OUT
CSD
CEILING SUPPLY DIFFUSER
IN.
INCHES
CV
COEFFICIENT, VALVE FLOW
L
LOUVER
D
DRAIN
LAV
LAVATORY
> DB
DRY BULB
LBS
POUNDS
DH
LOSS IN FEET
LWT
LEAVING WATER TEMPERATURE
EER
ENERGY EFFICIENCY RATIO
MBH
BTU PER HOUR (THOUSANDS)
> EF
EXHAUST FAN
MFGR.
MANUFACTURER
ESP
EXTERNAL STATIC PRESSURE
EWT
ENTERING WATER TEMPERATURE
ELECTRICAL INSTALLATION BY THE ELECTRICAL CONTRACTOR IS LIMITED TO THE CONDUIT AND WIRE
NECESSARY TO PROVIDE POWER TO THE UNITS. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL
NECESSARY CONDUIT, WIRING, CONTROLS AND APPURTENANCES FOR A COMPLETE AND OPERABLE
HVAC SYSTEM.
2. ALL SPACE CONDITIONING EQUIPMENT SHALL MEET THE REQUIREMENTS OF THE WASHINGTON STATE
ENERGY CODE AND SECTION 10.15800.
3. PROVIDE PLUMBING AND DRAIN PIPING IN ACCORDANCE WITH SECTION 10.15400.
PROVIDE SERVICE CONNECTION AND METER IN ACCORDANCE WITH KING COUNTY WATER DISTRICT NO.
90 STANDARD DETAILS. SEE CIVIL DRAWINGS FOR LOCATION.
PHILL
Roth Hill, LLC Te1425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
FAN SCHEDULE
TAG NO.
LOCATION
AREA SERVED
TYPE
DRIVE
RPM
CFM
ESP (IN. W.C.)
HP
VOLTS /PHASE
NOTES
EF -1
CONTROL BUILDING
CONTROL
SIDEWALL
DIRECT
1550
650
0.25
1/8
120/1
1,2,3
2
208/1
BUILDING
EXHAUST
BUILDING
PRESSURE
NOTES:
1. PROVIDE BACK DRAFT DAMPER.
2. ALL ONE —PHASE FRACTIONAL HP MOTORS TO BE FURNISHED WITH FACTORY — MOUNTED DISCONNECT SWITCHES.
3. THERMOSTAT — CONTROLLED.
ELECTRIC HEATER SCHEDULE
SCHEDULE
TAG NO.
LOCATION
AREA SERVED
TYPE
AIRFLOW
(CFM)
kW
VOLTS/
PHASE
NOTES
LOCATION
SERVED
EXHAUST
(CFM)
(IN)
(IN)
PHASE
CD -1
EH -1
CONTROL BUILDING
CONTROL BUILDING
UNIT
700
2
208/1
1
NOTES:
1. REMOTE THERMOSTAT CONTROLLED.
CONTROL DAMPER SCHEDULE
SCHEDULE
TAG NO.
LOUVER
INTAKE/
AIRFLOW
WIDTH
HEIGHT
VOLTS/
TAG NO.
LOCATION
SERVED
EXHAUST
(CFM)
(IN)
(IN)
PHASE
CD -1
CONTROL BUILDING
L -1
INTAKE
650
24
24
120/1
LOUVER
SCHEDULE
TAG NO.
LOCATION
AREA SERVED
INTAKE/
EXHAUST
AIRFLOW
(CFM)
WIDTH
(IN)
HEIGHT
(IN)
TYPE
L -1
CONTROL BUILDING
CONTROL BUILDING
INTAKE
650
24
24
6" ACOUSTIC
L -2
CONTROL BUILDING
CONTROL BUILDING
EXHAUST
650
24
24
6" ACOUSTIC
NOTES:
1. SEE SECTION 10.10200 FOR ADDITIONAL REQUIREMENTS.
650 CFM
L -2
BACKFLOW PREVENTER
SCHEDULE
SQ. FT.
SQUARE FEET
V
SIZE
PRESSURE
VOLUME DAMPER
TAG NO.
LOCATION
TYPE
(INCHES)
RATING
NOTES
WC
WATER CLOSET
WEIR
WALL EXHAUST OR RETURN
WG
WATER GAUGE
RPBA
CONTROL
REDUCED
1
175
1
BUILDING
PRESSURE
NOTES:
1. SEE SECTION 10.15400 FOR ADDITIONAL REQUIREMENTS.
NC NORMALLY CLOSED
NO NORMALLY OPEN I SP =60 F
OSA OUTSIDE AIR I
P PUMP
PD PRESSURE DROP i CONTROL BUILDING CONTROL BUILDING
PROP PROPELLER I
PW POTABLE WATER I
RF RETURN FAN
RPBA REDUCED PRESSURE BACKFLOW ASSEMBLY
RPM REVOLUTIONS PER MINUTE
02173
SP
STATIC PRESSURE /SET POINT
SQ. FT.
SQUARE FEET
V
VENTILATING
VD
VOLUME DAMPER
VTR
VENT —TO —ROOF
VVT
VARIABLE VOLUME /TEMPERATURE
WB
WET BULB
WC
WATER CLOSET
WEIR
WALL EXHAUST OR RETURN
WG
WATER GAUGE
WH
WATER HEATER
WSD
WALL SUPPLY DIFFUSER
Kennedy /Jenks Consultants
32001 32nd Avenue South, Suite 100
Federal Way, WA 98001
Ph. 253 - 8358400
Fax 253 - 952 -3435
HVAC SCHEMATIC
650 CFM
HOT BOX
W,
1" PW RPBA
PLUMBING SCHEMATIC
RECORD DRAWING
ihma Record Drawings haw from paW brad m mfmmo5on provided
by the cmtrockr aM off m Kennedy /Jenks W WEmh ham not wrife0 the
ocmwM a cmVWWt of i fomMm provided to them and dm not
•arrant the aaamay ar a Oetemm of them Reomd Dmwk* . Ue of
thma Racard Drawings mama all rIBk of Im romMM flan their me.
av� ` 5 -3 �3 �