GENERALSTRUCTURALNOTES
GENERAL
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE 2006 INTERNATIONAL
BUILDING CODE (2007 WASHINGTON ADMINISTRATIVE CODE), AND THE
REFERENCED BUILDING CODE STANDARDS.
2. THESE NOTES AS WELL AS THE TYPICAL DETAILS APPLY TO ALL PARTS OF
THE PROJECT, UNLESS NOTED OTHERWISE.
3. SHOP DRAWINGS FOR THIS CONTRACT SHALL BE COORDINATED WITH
FAVORABLY REVIEWED EQUIPMENT MANUFACTURER'S DRAWINGS.
4. DIMENSIONS NOTED WITH AN ASTERISK, " * ARE TO BE COORDINATED
WITH FAVORABLY REVIEWED EQUIPMENT MANUFACTURER.
PERMITS AND INSPECTIONS
1. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS AND
INSPECTIONS REQUIRED BY THE LOCAL BUILDING INSPECTOR AND AS
DESCRIBED IN THE SPECIFICATIONS.
2. THE CONTRACTOR SHALL SELECT, INSTALL AND MAINTAIN SHORING,
SHEETING, BRACING AND SLOPING AS NECESSARY TO MAINTAIN SAFE
EXCAVATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING
FULL COMPLIANCE WITH 29 CFR PART 1926 OSHA SUBPART P EXCAVATIONS
AND TRENCHES REQUIREMENTS. ALL EARTHWORK SHALL BE PERFORMED IN
STRICT ACCORDANCE WITH APPLICABLE LAW, INCLUDING LOCAL ORDINANCES,
WASHINGTON STATE DEPARTMENT OF LABOR AND INDUSTRIES TITLE 296,
WASHINGTON ADMINISTRATIVE CODE REQUIREMENTS, AND APPLICABLE OSHA
REQUIREMENTS.
SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS
1. THE CONTRACTOR SHALL NOTIFY THE ENGINEER 48 -HOURS BEFORE
PLACEMENT OF REINFORCING STEEL AND CONCRETE SO THAT THE SUBGRADE
OF EXCAVATIONS MAY BE INSPECTED BY THE GEOTECHNICAL ENGINEER.
2. THE GEOTECHNICAL ENGINEER SHALL VERIFY BACKFILL MATERIAL AND
BACKFILLING PROCEDURES AND PROVIDE SOIL COMPACTION TESTS.
3. STRUCTURAL OBSERVATION SHALL BE PROVIDED BY THE DESIGN ENGINEER(S)
OF RECORD OR THEIR AUTHORIZED REPRESENTATIVES IN ACCORDANCE WITH
IBC 2006, SECTION 1709. STRUCTURAL OBSERVATION SHALL CONSIST OF
SITE VISITS AT INTERVALS APPROPRIATE TO THE STAGE OF CONSTRUCTION
TO OBSERVE CONSTRUCTION IN PROGRESS AND REVIEW OF TESTING AND
INSPECTION REPORTS FOR GENERAL COMPLIANCE WITH THE CONSTRUCTION
DOCUMENTS RELATING TO THE STRUCTURAL WORK AND THE NONSTRUCTURAL
COMPONENTS AND EQUIPMENT ANCHORAGE.
4. SPECIAL INSPECTION IN ACCORDANCE WITH IBC 2006, SECTION 1704, SHALL
BE REQUIRED AS INDICATED IN THE SPECIAL INSPECTION AND TESTING
SCHEDULE ON THIS SHEET.
SOIL AND FOUNDATIONS
1. GEOTECHNICAL INVESTIGATIONS FOR DESIGN PURPOSES FOR THIS PROJECT
WERE MADE FOR THE CITY OF RENTON BY HWA GEOSCIENCES INC. IN A
REPORT DATED 11/07/08.
2. IN ACCORDANCE WITH THE IBC CHAPTER 18 THE SOILS IN RENTON ARE
REINFORCING STEEL WOOD
FRAMING:
STRENGTH
1. REINFORCING BARS SHALL BE ASTM A615 -GRADE 60. 1.
FRAMING LUMBER SHALL BE DOUGLAS FIR -LARCH AND BE GRADE
2. ARRANGEMENT AND DETAILING OF REINFORCING STEEL, INCLUDING BAR
MARKED PER W.C.L.I.B. SPECIFICATIONS:
SUPPORTS AND SPACERS, SHALL BE IN ACCORDANCE WITH THE LATEST
A)
STUDS:
ACI 315 DETAILING MANUAL.
WOOD
2" TO 4" THICK, 2" TO 4" WIDE, INTERIOR, NON- BEARING
3. REINFORCING SHALL LAP A MINIMUM OF OF 1.3 Ld AT SPLICES UNLESS
BEARING CAPACITY OF SOILS ARE FOR DEAD
PARTITIONS, STUD GRADE.
OTHERWISE SHOWN. WHERE Ld IS THE TENSION DEVELOPMENT LENGTH.
SUBMIT CONCRETE AND MASONRY LIFT DRAWINGS SHOWING THE LOCATION
2" TO 4" THICK, 2" AND WIDER, EXTERIOR, BEARING WALLS, NO. 1
WHEN BARS OF DIFFERENT SIZE LAP TO EACH OTHER, SPLICE LENGTH
AND BETTER GRADE.
FOR THE SMALLER BAR CAN BE USED. DOWELS SHALL HAVE THE SAME
B)
JOISTS AND RAFTERS:
SIZE AND SPACING AS THAT OF THE REINFORCING STEEL THEY ARE
PROVIDE WASHERS UNDER HEADS AND NUTS OF ALL BOLTS BEARING ON
4.
SPLICED AND SHALL HAVE A MINIMUM LAP AS NOTED ABOVE. BAR
ANCHOR BOLT
2" TO 4" THICK, 2" TO 4" WIDE, SELECT STRUCTURAL GRADE.
SPLICES SHALL BE STAGGERED.
WOOD.
2" TO 4" THICK, 5" AND WIDER, NO. 1 AND BETTER GRADE.
4. HOOK REINFORCING BARS INTERUPTED BY OPENINGS.
C)
BEAMS AND HEADERS:
5. NO WELDING OF REINFORCING BARS SHALL BE PERMITTED, UNLESS
2.
2" TO 4" THICK, 5" AND WIDER, NO. 1 AND BETTER GRADE.
APPROVAL IN WRITING IS OBTAINED FROM THE ENGINEER PRIOR TO
INDICATED ON THE DRAWINGS AND SPECIFICATIONS
5" THICK AND GREATER, ALL WIDTHS, NO. 1 AND BETTER GRADE.
CONSTRUCTION.
D)
POSTS AND COLUMNS:
6. DIMENSIONS TO REINFORCING ARE TO BAR CENTERLINES, UNLESS NOTED
LONG LEG VERTICAL
2" TO 4" THICK, 2" TO 4" WIDE, NO. 1 AND BETTER GRADE.
OTHERWISE BAR COVER IS CLEAR DISTANCE BETWEEN THE BAR AND THE
HORIZONTAL CONSTRUCTION JOINTS SHALL HAVE A STANDARD KEYWAY
5" THICK AND GREATER, ALL WIDTHS, SELECT STRUCTURAL GRADE.
CONCRETE SURFACE. UNLESS NOTED OR SHOWN OTHERWISE BAR COVER
E)
TOP PLATES:
FOR REINFORCING STEEL SHALL BE AS FOLLOWS:
ADJ
AND SHALL BE FAVORABLY REVIEWED BY THE ENGINEER. REFER TO
4.
PLATES USED IN ROOF FRAMING SHALL BE ASTM A36 OR ASTM A572
2" THICK X 4" WIDE, INTERIOR, NON- BEARING PARTITIONS, STUD
FOOTINGS AND BASE SLABS:
COMPETENT MATERIAL OR
GRADE.
FORMED SURFACES AND BOTTOMS ON CONCRETE
STEEL CONSTRUCTION
2" THICK X 4" WIDE, EXTERIOR, BEARING WALLS, NO. 1 AND BETTER
WORK MAT 2 -INCH
COMPACTED STRUCTURAL FILL.
GRADE.
BOTTOMS AND SIDES IN CONTACT WITH EARTH 3 -INCH
F)
BLOCKING:
BEAMS AND COLUMNS:
LOADING
2" TO 4" THICK, 2" AND WIDER, STUD GRADE.
DRY CONDITIONS:
G)
SILL PLATES:
STIRRUPS, SPIRALS, AND TIES 1 1/2 -INCH
THE MANUFACTURER'S RECOMMENDATIONS.
2" THICK X 4" WIDE, INTERIOR, NON- BEARING PARTITIONS,
PRINCIPAL REINFORCEMENT 2 -INCH
MACHINE BOLT
PRESSURE TREATED STUD GRADE.
EXPOSED TO EARTH, WATER, OR WEATHER:
6.
2" TO 4" THICK, 4" AND WIDER, EXTERIOR, PRESSURE TREATED NO.
STIRRUPS, SPIRALS, AND TIES 2 -INCH
MINIMUM LOADING REQUIREMENTS PER CHAPTER 16 OF THE 2006 INTERNATIONAL
1 AND BETTER GRADE.
PRINCIPAL REINFORCEMENT 2 1/2 -INCH 2.
STRUCTURAL PLYWOOD SHALL BE DOUGLAS FIR CONFORMING TO
WALLS:
COMMERCIAL STANDARDS PSI -74 AND GRADE STAMPED N.F.P.A. ALL
LESS THAN 12- INCHES THICK 1 1/2 -INCH
ROOFS AND WALLS SHALL BE SHEATHED AND ALL UNSUPPORTED EDGES
12 INCHES OR OVER IN THICKNESS 2 1/2 -INCH
SHALL BE BLOCKED ACCORDING TO THE TYPICAL NAILING SCHEDULE:
CONCRETE:
A)
ROOF SHEATHING:
MIN
MINIMUM
EAVES - 4'x8'x3/4" SHEETS, APPEARANCE GRADE A -C EXT (A
1. CEMENT SHALL BE ASTM C150 TYPE II FOR ALL STRUCTURES. CONCRETE
MISC
SIDE DOWN).
SHALL HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH AS NOTED IN THE
AMERICAN SOCIETY FOR
OTHER - 4'x8'x3/4" SHEETS, APPEARANCE GRADE C -D EXT.
TABLE BELOW AND AS FURTHER DEFINED IN THE SPECIFICATIONS: 3.
ALL
LUMBER HARDWARE (HANGERS, FRAMING ANCHORS, STRAPS, ETC)
CONCRETE STRENGTH (PSI)
TYPE
STRENGTH
LOCATION
C
4,000
BUILDING BASIC CONC - CONTROL BUILDING
E
2,500
MISCELLANEOUS STRUCTURES AND SITEWORK
AS SHOWN ARE STRONG -TIE CONNECTORS AS MANUFACTURED BY
SIMPSON COMPANY OF SAN LEANDRO, CALIFORNIA. APPROVED EQUAL
HARDWARE MAY BE SUBSTITUTED IF FAVORABLY REVIEWED BY THE
ENGINEER.
4. NO STRUCTURAL MEMBER SHALL BE CUT, NOTCHED, OR DRILLED UNLESS
SPECIFICALLY SHOWN OR APPROVED BY THE ENGINEER.
5. MAXIMUM MOISTURE CONTENT OF LUMBER SHALL NOT EXCEED 19% FOR
ALL FRAMING LUMBER.
ROTI- 'MILL
Roth Hill, LLC Te1425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
SPECIAL INSPECTION AND
TESTING SCHEDULE
I. GUNGKIL IL
[X] CONTINUOUS PLACEMENT INSPECTION
[X] EXCEPTIONS: 2,500 PSI OR TYPE E
CONCRETE
[X] 4 CYLINDERS PER 100 CUBIC YARDS*
TEST: 2 ® 7 DAYS, 2 @ 28 DAYS.
*EACH MIX PLACED, EACH DAY PLACED
2. BOLTS INSTALLED IN CONCRETE
[X] ALL BOLTS
[I LOCATION: _
3. SPECIAL MOMENT - RESISTING CONCRETE FRAME
NOT USED
4. REINFORCING STEEL AND PRESTRESSING TENDONS
[X] PLACEMENT INSPECTION
STRESSING AND GROUTING OF TENDONS
5. STRUCTURAL WELDING
PERIODIC VISUAL INSPECTION:
[X] SINGLE PASS FILLET WELDS < 5/16"
[ ] STEEL DECK
[ ] WELDED STUDS
[ ] COLD FORMED STUDS AND JOINTS
[X] STAIR AND RAILING SYSTEMS
CONTINUOUS VISUAL INSPECTION
[] ALL OTHER WELDING
[X] REINFORCING STEEL
[] OTHER
SPECIAL MOMENT - RESISTING FRAMES:
NOT USED
SPLICES > 3/4"
[] UT COLUMN FLANGES AT BEAM FLANGES
WELDS
[I NDT RATE REDUCTION PER IBC 1703.1
APPLIES
OTHER
6. HIGH STRENGTH BOLTING
SNUG TIGHT: [ ] ALL
[X] AS INDICATED
FULL PRETENSION: [ ] ALL
[X] AS INDICATED
7. STRUCTURAL MASONRY f'm =1,500 psi
FULL STRESSES
VERIFCAT10N OF f'm:
[ ] PRISM TEST RECORD
[X] UNIT STRENGTH
[X] LEVEL II
[ ] LEVEL I
TEST BEFORE DURING
PRISMS [ ] [X] 3/5,000 sf
UNITS [X] [ ]
GROUT 1XI [XI 3/WEEK
MORTAR I [X] 3 /WEEK
8. SPECIAL CASES
[X] SHEAR WALL /DIAPHRAGM NAILING
[X] ANCHORAGE TO EXISTING
CONCRETE /MASONRY (SPEC 05100):
[X] INSTALLATION INSPECTION
[X] PROOF LOAD TEST TO TWICE ALLOWABLE
TENSION VALUE: (SUBMIT TEST LOADS TO ENGINEER
PRIOR TO TEST)
- 10% OF ANCHORS FOR DOWELS
- 10% OF ANCHORS FOR SILL PLATE BOLTS
- 50% OF ANCHORS FOR EQUIP ANCHORAGE
- 100% OF ANCHORS FOR HOLD -DOWN BOLTS
- 100% FOR ALL OTHER ANCHORS
[X] EXCAVATION SUPPORT /SHORING AS REQUIRED
BY CONTRACTOR'S ENGINEER, TO BE
PROVIDED BY CONTRACTOR
[ ] UNDERPINNING
NOTE: POST- INSTALLED FASTENERS ARE ONLY TO
BE INSTALLED WHERE SPECIFCIALLY INDICATED AND
SHALL RECEIVE SPECIAL INSPECTION IN
ACCORDANCE WITH SECTION 10.05100.
Tlave Record Drawings Have bw prepared bond w II onmrtion KwAded
by the conbador and oeiere. Kern dy /JaYO ConevBmb here sot verified the
awurury or c Oefenm of infamm8m, provided to them and does not
emmit the ocauary or oompbtereve of IAm Record Drmingm, Usars of
then Record DmwhVs see ens at risk of love reeu" Lerri 9sdr m.
Kennedy /Jenks Consultants
vmrcu_ euw ,sm
1/2'= l • -0" xoimoraw wn ,sw /,ee,
32001 32nd Avenue South, Suite 100 Er
Federal Way, WA 98001 ET
Ph. 253.835 -6400 t RECORD DRAWING RFB 7/20/1 JMF mmnao: I DATUM
Fax 253 - 952-3435 DUB it wr"�o,axm
NO. REVISION BY DATE APPR
s CITY OF
RENTON
Planning /Building /Public Works Dept.
STRUCTURAL ABBREVIATIONS
&
GENERALLY CLASSIFIED DENSE, SILTY SAND.
JT
2.
CONCRETE CONSTRUCTION SHALL CONFORM TO ACI 318 (LATEST EDITION)
AT
3.
THE DESIGN BEARING CAPACITY OF THE SOILS IS 2,000 PSF FOR FOOTINGS.
NUMBER
INCLUDING BAR BENDS AND HOOKS, UNLESS DETAILED OTHERWISE.
WOOD
FASTENERS,
DIAMETER
BEARING CAPACITY OF SOILS ARE FOR DEAD
AND LIVE LOADS FOR
3.
SUBMIT CONCRETE AND MASONRY LIFT DRAWINGS SHOWING THE LOCATION
FOUNDATIONS.
L,L
ANGLE
OF CONSTRUCTION JOINTS, WATERSTOPS AND OTHER TYPES OF JOINTS
1.
PROVIDE WASHERS UNDER HEADS AND NUTS OF ALL BOLTS BEARING ON
4.
SOILS SHALL BE EXCAVATED TO THE ELEVATIONS INDICATED ON THE
ANCHOR BOLT
OTHER THAN SPECIFIED OR SHOWN ON THE DRAWINGS FOR FAVORABLE
POUND(S) PER SQUARE
WOOD.
AGGREGATE BASE
DRAWINGS FOR FOUNDATIONS. THE SUBGRADE
SHALL BE PREPARED AS
REVIEW BY THE ENGINEER BEFORE START OF WORK ON FORMS,
2.
ALL NAILING SHALL BE STAGGERED TO AVOID SPLITTING OF MEMBERS.
ACI
INDICATED ON THE DRAWINGS AND SPECIFICATIONS
AND APPROVED BY THE
LONG LEG HORIZONTAL
REINFORCING STEEL OR PLACING CONCRETE. ANY ADDITIONAL VERTICAL OR
3.
BOLTS USED IN FRAMING SHALL BE ASTM A307 WITH STANDARD HEX
LONG LEG VERTICAL
GEOTECHNICAL ENGINEER. EXCAVATED MATERIAL SHALL BE REPLACED WITH
ADDITIONAL
HORIZONTAL CONSTRUCTION JOINTS SHALL HAVE A STANDARD KEYWAY
LONG LEG
HEAD DIMENSIONS CONFORMING TO ANSI /ASME 318.2.1.
STRUCTURAL FILL AS SHOWN ON THE DRAWINGS.
FOUNDATIONS SHALL BE
ADJ
AND SHALL BE FAVORABLY REVIEWED BY THE ENGINEER. REFER TO
4.
PLATES USED IN ROOF FRAMING SHALL BE ASTM A36 OR ASTM A572
AISC
CONSTRUCTED AGAINST UNDISTURBED NATIVE
COMPETENT MATERIAL OR
LIGHT
SPECIFICATIONS AND TYPICAL DETAILS FOR ADDITIONAL INFORMATION.
STEEL CONSTRUCTION
GRADE 50.
LIGHT WEIGHT
COMPACTED STRUCTURAL FILL.
AMERICAN IRON AND
CONSTRUCTION JOINTS SHALL BE ROUGHENED TO 1/4 -INCH AMPLITUDE.
5.
PROVIDE AND INSTALL ALL BOLTS AND NAILS TO ALL CONNECTORS PER
LOADING
CRITERIA
AITC
4.
OPENINGS, PIPE SLEEVES, CONDUITS, INSERTS AND OTHER EMBEDDED
MAXIMUM
THE MANUFACTURER'S RECOMMENDATIONS.
TIMBER CONSTRUCTION
MB
MACHINE BOLT
ALUM
ITEMS SHALL BE IN PLACE BEFORE CONCRETE IS PLACED. IT IS THE
6.
ALL NAILING SHALL BE IN ACCORDANCE WITH CHAPTER 23 OF THE 2006
1.
MINIMUM LOADING REQUIREMENTS PER CHAPTER 16 OF THE 2006 INTERNATIONAL
MC
CONTRACTOR'S RESPONSIBILITY TO COORDINATE ARCHITECTURAL, CIVIL,
APA
INTERNATIONAL BUILDING CODE. USE COMMON TYPE NAILS UNLESS
MECH
BUILDING CODE INCLUDING LATEST REVISION.
ASSOCIATION
MECHANICAL, ELECTRICAL, LANDSCAPING, HVAC, PLUMBING,
MANUFACTURER
OTHERWISE SPECIFIED. ALL FASTNERS IN CONTACT WITH PRESSURE
APPROXIMATE
MIN
MINIMUM
ARCH
INSTRUMENTATION AND OTHER PLANS FOR ITEMS REQUIRING SLEEVES AND
MISC
TREATED WOOD SHALL BE HOT DIPPED GALVANIZED FASTENERS (MEETING
ASTM
AMERICAN SOCIETY FOR
MTL
METAL
EMBEDMENTS IN CONCRETE WHICH ARE NOT INDICATED OR SHOWN ON
TESTING AND MATERIALS
ASTM A153) AND CONNECTORS (ASTM A653 CLASS G185 SHEET), OR
2.
DEAD LOAD:
AS CALCULATED
(N)
STRUCTURAL DRAWINGS. NO PIPES OR SLEEVES SHALL PASS THROUGH
BETTER.
3.
LIVE LOADS:
STRUCTURAL MEMBERS (UNLESS SHOWN ON STRUCTURAL DRAWINGS).
TEST(ING)
B/
BOTTOM OF
CATWALKS FOR MAINTENANCE ACCESS
40 PSF UNIFORM, 300 LBS POINT
BLKG
COORDINATE WITH EQUIPMENT MANUFACTURERS DRAWINGS FOR ANCHORING
NO.
NUMBER
BLDG
ELEVATED SLABS & WALKWAYS
100 PSF UNIFORM
NOMINAL
DEVICES.
BEAM
NS
NEAR SIDE
FIXED LADDERS
300 LBS POINT
5.
UNLESS OTHERWISE NOTED, ALL EXPOSED EDGES AND CORNERS SHALL BE
BN
BOUNDARY NAILING
NTS
HANDRAILS, GUARDRAILS AND GRAB BARS
50 PLF AT TOP RAIL, 200 LBS POINT
BOTTOM
CHAMFERED 3/4 -INCH. INTERIOR FLOOR SLABS AND EXTERIOR SIDEWALKS
DEFERRED
SUBMITTALS:
BASE PLATE
FLOOR - HEAVY MANUFACTURING /STORAGE
250 PSF UNIFORM, 3,000 LBS POINT
BS
SHALL HAVE TOOLED 3/8 -INCH RADIUS CONSTRUCTION JOINT.
1.
TRUSSES
BTWN
FLOOR - GARAGE (TRUCKS)
AASHTO HS20 -44
6.
EACH FACE CONCRETE SHALL BE REINFORCED A MINIMUM OF NO. 5 BARS
OVERHEAD
ROOF (REDUCTION FOR UNIFORM LOAD)
20 PSF UNIFORM, 2,000 LBS POINT
OPNG(S)
AT 12- INCHES EACH WAY.
C
CHANNEL
OPP
CEILING - WITH STORAGE AREA
20 PSF UNIFORM
7.
CONCRETE ENCASE ALL PIPES AND CONDUITS UNDER CONCRETE SLABS
CC,C /C
CENTER -TO- CENTER
GRATING, CHECKERED PLATE,
POWDER ACTUATED
AND FOOTINGS.
FASTENER
CJ
ACCESS HATCHES
EQUAL TO FLOOR LIVE LOAD
PLATE
CJP
COMPLETE JOINT PENETRATION
PLF
POUND PER LINEAL FOOT
SIDEWALKS & VEHICULAR DRIVEWAYS
250 PSF UNIFORM, 8,000 LBS POINT
PP
PARTIAL PENETRATION
CLR
CLEAR
PSF
POUND PER SQUARE FOOT
AASHTO
CONTROL JOINT
PSI
POUND PER SQUARE INCH
COL
COLUMN
UNRESTRICTED VEHICULAR ACCESS
HS20 -44
CONC
CONCRETE
PT
PRESSURE TREATED
CONST
CONCRETE VAULTS AND COVERS
AASHTO HS20 -44
CONT
CONTINUOUS
R, RAD
4.
WIND LOAD:
RECT
RECTANGLE, RECTANGULAR
DBL
DOUBLE
REINF
IMPORTANCE FACTOR, Iw
1.15
DIAMETER
REQ'D
REQUIRED
DIM
DIMENSION
BASIC WIND SPEED
85 MPH
DL
DEAD LOAD
SCH
SCHEDULE
ON
EXPOSURE
C
SQUARE FOOT
DWG(S)
DRAWINGS
SHT
5.
SNOW LOAD:
SIM
SIMILAR
(E)
EXISTING
SLBB
IMPORTANCE FACTOR,1
1.2
BACK -TO -BACK
EA
EACH
BASIC GROUND SNOW LOAD, Pg
20 PSF
EF
EACH FACE
SLV
SHORT LEG VERTICAL
EL
SNOW EXPOSURE COEFFICIENT, Ce
0.9
SHEET METAL SCREW
EMBED
EMBEDMENT
SPEC(S)
SPECIFICATION(S)
THERMAL FACTOR, Ct
1.2
SQ
SQUARE
EQ
EQUAL
6.
SEISMIC LOAD:
EQUIP
EQUIPMENT
SSD
SATURATED SURFACE DRY
ES
EACH SIDE
OCCUPANCY CATEGORY
III
EW
EACH WAY
STD
STANDARD
EXP
SEISMIC IMPORTANCE FACTOR, 1
1.25
STIFFENER
EXT
EXTERIOR
STL
STEEL
SEISMIC IMPORTANCE FACTOR, Ip
1.0
STRUC
STRUCTURE
(A)
FUTURE
SUSP
SOIL PROFILE TYPE
SD
FLOOR DRAIN
SYM
SYMMETRICAL
FF
FINISH FLOOR
SEISMIC DESIGN RESPONSE PARAMATER SDs
0.933
FIN
FINISH
T/
TOP OF
FLR
SEISMIC DESIGN RESPONSE PARAMATER Sot
0.48
TOP AND BOTTOM
FN
FIELD NAILING
TS
STRUCTURAL TUBING
SEISMIC DESIGN CATEGORY
D
TYP
TYPICAL
FRP
FIBERGLASS REINFORCED
SITE COEFFICIENT Fo
1.0
PLASTIC
UBC
UNIFORM BUILDING CODE
FT
FOOT /FEET
SITE COEFFICIENT Fv
1.5
FTG
FOOTING
UT
ULTRASONIC TESTING
GA
OVERSTRENGTH AND DUCTILITY
VERT
VERTICAL
GALV
GALVANIZED
VIF
VERIFY IN FIELD
COEFFICIENT, R
5
RECORD DRAWING
ROTI- 'MILL
Roth Hill, LLC Te1425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
SPECIAL INSPECTION AND
TESTING SCHEDULE
I. GUNGKIL IL
[X] CONTINUOUS PLACEMENT INSPECTION
[X] EXCEPTIONS: 2,500 PSI OR TYPE E
CONCRETE
[X] 4 CYLINDERS PER 100 CUBIC YARDS*
TEST: 2 ® 7 DAYS, 2 @ 28 DAYS.
*EACH MIX PLACED, EACH DAY PLACED
2. BOLTS INSTALLED IN CONCRETE
[X] ALL BOLTS
[I LOCATION: _
3. SPECIAL MOMENT - RESISTING CONCRETE FRAME
NOT USED
4. REINFORCING STEEL AND PRESTRESSING TENDONS
[X] PLACEMENT INSPECTION
STRESSING AND GROUTING OF TENDONS
5. STRUCTURAL WELDING
PERIODIC VISUAL INSPECTION:
[X] SINGLE PASS FILLET WELDS < 5/16"
[ ] STEEL DECK
[ ] WELDED STUDS
[ ] COLD FORMED STUDS AND JOINTS
[X] STAIR AND RAILING SYSTEMS
CONTINUOUS VISUAL INSPECTION
[] ALL OTHER WELDING
[X] REINFORCING STEEL
[] OTHER
SPECIAL MOMENT - RESISTING FRAMES:
NOT USED
SPLICES > 3/4"
[] UT COLUMN FLANGES AT BEAM FLANGES
WELDS
[I NDT RATE REDUCTION PER IBC 1703.1
APPLIES
OTHER
6. HIGH STRENGTH BOLTING
SNUG TIGHT: [ ] ALL
[X] AS INDICATED
FULL PRETENSION: [ ] ALL
[X] AS INDICATED
7. STRUCTURAL MASONRY f'm =1,500 psi
FULL STRESSES
VERIFCAT10N OF f'm:
[ ] PRISM TEST RECORD
[X] UNIT STRENGTH
[X] LEVEL II
[ ] LEVEL I
TEST BEFORE DURING
PRISMS [ ] [X] 3/5,000 sf
UNITS [X] [ ]
GROUT 1XI [XI 3/WEEK
MORTAR I [X] 3 /WEEK
8. SPECIAL CASES
[X] SHEAR WALL /DIAPHRAGM NAILING
[X] ANCHORAGE TO EXISTING
CONCRETE /MASONRY (SPEC 05100):
[X] INSTALLATION INSPECTION
[X] PROOF LOAD TEST TO TWICE ALLOWABLE
TENSION VALUE: (SUBMIT TEST LOADS TO ENGINEER
PRIOR TO TEST)
- 10% OF ANCHORS FOR DOWELS
- 10% OF ANCHORS FOR SILL PLATE BOLTS
- 50% OF ANCHORS FOR EQUIP ANCHORAGE
- 100% OF ANCHORS FOR HOLD -DOWN BOLTS
- 100% FOR ALL OTHER ANCHORS
[X] EXCAVATION SUPPORT /SHORING AS REQUIRED
BY CONTRACTOR'S ENGINEER, TO BE
PROVIDED BY CONTRACTOR
[ ] UNDERPINNING
NOTE: POST- INSTALLED FASTENERS ARE ONLY TO
BE INSTALLED WHERE SPECIFCIALLY INDICATED AND
SHALL RECEIVE SPECIAL INSPECTION IN
ACCORDANCE WITH SECTION 10.05100.
Tlave Record Drawings Have bw prepared bond w II onmrtion KwAded
by the conbador and oeiere. Kern dy /JaYO ConevBmb here sot verified the
awurury or c Oefenm of infamm8m, provided to them and does not
emmit the ocauary or oompbtereve of IAm Record Drmingm, Usars of
then Record DmwhVs see ens at risk of love reeu" Lerri 9sdr m.
Kennedy /Jenks Consultants
vmrcu_ euw ,sm
1/2'= l • -0" xoimoraw wn ,sw /,ee,
32001 32nd Avenue South, Suite 100 Er
Federal Way, WA 98001 ET
Ph. 253.835 -6400 t RECORD DRAWING RFB 7/20/1 JMF mmnao: I DATUM
Fax 253 - 952-3435 DUB it wr"�o,axm
NO. REVISION BY DATE APPR
s CITY OF
RENTON
Planning /Building /Public Works Dept.
STRUCTURAL ABBREVIATIONS
&
AND
JT
JOINT
®
AT
#
NUMBER
KIP
1,000 POUNDS
0
DIAMETER
KSI
KIPS PER SQUARE INCH
AASHTO
AMERICAN ASSOCIATION
OF STATE HIGHWAY
L,L
ANGLE
TRANSPORTATION OFFICIALS
LB(S)
POUNDS
AB
ANCHOR BOLT
LB /SF
POUND(S) PER SQUARE
AGGREGATE BASE
FOOT
LL
LIVE LOAD
ACI
AMERICAN CONCRETE
LLH
LONG LEG HORIZONTAL
INSTITUTE
LLV
LONG LEG VERTICAL
ADDIT
ADDITIONAL
LLBB
LONG LEG
BACK -TO -BACK
ADJ
ADJACENT
LONGIT
LONGITUDINAL
AISC
AMERICAN INSTITUTE OF
LT
LIGHT
STEEL CONSTRUCTION
LW
LIGHT WEIGHT
AISI
AMERICAN IRON AND
STEEL INSTITUTE
MATL
MATERIAL
AITC
AMERICAN INSTITUTE OF
MAX
MAXIMUM
TIMBER CONSTRUCTION
MB
MACHINE BOLT
ALUM
ALUMINUM
MC
MOISTURE CONTENT
ALT
ALTERNATE
MC
MISCELLANEOUS CHANNEL
APA
AMERICAN PLYWOOD
MECH
MECHANICAL
ASSOCIATION
MFR
MANUFACTURER
APROX
APPROXIMATE
MIN
MINIMUM
ARCH
ARCHITECTURAL
MISC
MISCELLANEOUS
ASTM
AMERICAN SOCIETY FOR
MTL
METAL
TESTING AND MATERIALS
AWS
AMERICAN WELDING SOCIETY
(N)
NEW
NDT
NON- DESTRUCTIVE
TEST(ING)
B/
BOTTOM OF
NIC
NOT IN CONTACT
BLKG
BLOCKING
NO.
NUMBER
BLDG
BUILDING
NOM
NOMINAL
BM
BEAM
NS
NEAR SIDE
BM -1
BEAM MEMBER 1
NSG
NON- SHRINK GROUT
BN
BOUNDARY NAILING
NTS
NOT TO SCALE
BOT
BOTTOM
BP
BASE PLATE
OC
ON CENTERS
BS
BOTH SIDES
OD
OUTSIDE DIAMETER
BTWN
BETWEEN
OH
OPPOSITE HAND,
OVERHEAD
OPNG(S)
OPENING(S)
C
CHANNEL
OPP
OPPOSITE
CALC'S
CALCULATIONS
CC,C /C
CENTER -TO- CENTER
PAF
POWDER ACTUATED
FASTENER
CJ
CONSTRUCTION JOINT
PL
PLATE
CJP
COMPLETE JOINT PENETRATION
PLF
POUND PER LINEAL FOOT
CL
CENTERLINE
PP
PARTIAL PENETRATION
CLR
CLEAR
PSF
POUND PER SQUARE FOOT
CNJ
CONTROL JOINT
PSI
POUND PER SQUARE INCH
COL
COLUMN
PT(S)
POINT(S)
CONC
CONCRETE
PT
PRESSURE TREATED
CONST
CONSTRUCTION
CONT
CONTINUOUS
R, RAD
RADIUS
RECT
RECTANGLE, RECTANGULAR
DBL
DOUBLE
REINF
REINFORCING, -MENT
DIA
DIAMETER
REQ'D
REQUIRED
DIM
DIMENSION
DL
DEAD LOAD
SCH
SCHEDULE
ON
DOWN
SF
SQUARE FOOT
DWG(S)
DRAWINGS
SHT
SHEET
SIM
SIMILAR
(E)
EXISTING
SLBB
SHORT LEGS
BACK -TO -BACK
EA
EACH
SLH
SHORT LEG HORIZONTAL
EF
EACH FACE
SLV
SHORT LEG VERTICAL
EL
ELEVATION
SMS
SHEET METAL SCREW
EMBED
EMBEDMENT
SPEC(S)
SPECIFICATION(S)
EN
EDGE NAILING
SQ
SQUARE
EQ
EQUAL
SS
STAINLESS STEEL
EQUIP
EQUIPMENT
SSD
SATURATED SURFACE DRY
ES
EACH SIDE
STAG
STAGGER
EW
EACH WAY
STD
STANDARD
EXP
EXPANSION
STIFF
STIFFENER
EXT
EXTERIOR
STL
STEEL
STRUC
STRUCTURE
(A)
FUTURE
SUSP
SUSPENDED
FD
FLOOR DRAIN
SYM
SYMMETRICAL
FF
FINISH FLOOR
FIN
FINISH
T/
TOP OF
FLR
FLOOR
T &B
TOP AND BOTTOM
FN
FIELD NAILING
TS
STRUCTURAL TUBING
FNDN
FOUNDATION
TYP
TYPICAL
FRP
FIBERGLASS REINFORCED
PLASTIC
UBC
UNIFORM BUILDING CODE
FT
FOOT /FEET
LION
UNLESS OTHERWISE NOTED
FTG
FOOTING
UT
ULTRASONIC TESTING
GA
GAGE /GAUGE
VERT
VERTICAL
GALV
GALVANIZED
VIF
VERIFY IN FIELD
GLB
GLULAM BEAM
W/
WITH
HORIZ
HORIZONTAL
W/O
WITHOUT
HSS
HOLLOW STRUCTURAL SECTION
W
WIDE FLANGE
HT
HEIGHT
WP
WORK POINT
HWL
HIGH WATER LEVEL
WT
WEIGHT, STRUCTURAL TEE
WALL THICKNESS
IBC
INTERNATIONAL BUILDING CODE
WWF
WELDED WIRE FABRIC
ICC
INTERNATIONAL CODE COUNCIL
IN
INCH
YD
YARD
INT
INTERIOR
STONEGATE
LIFT STATION REPLACEMENT
GENERAL STRUCTURAL NOTES