GENERAL NOTES
THESE DRAWINGS ARE FOR THE SCOPE OF WORK OF THE STRUCTURAL WORK. REFER TO ESM DRAWINGS AND
DOCUMENTS FOR ADDITIONAL SCOPE OF WORK. ANY DISCREPANCIES FOUND AMONG THE DRAWINGS, THE
SPECIFICATIONS, THESE GENERAL NOTES AND THE SITE CONDITIONS SHALL SHALL BE REPORTED TO THE
ENGINEER, WHO SHALL CORRECT SUCH DISCREPANCY IN WRITING. ANY WORK DONE BY THE CONTRACTOR
AFTER DISCOVERY OF SUCH DISCREPANCY SHALL BE DONE AT THE CONTRACTOR'S RISK. THE CONTRACTOR
SHALL VERIFY AND COORDINATE DIMENSIONS AMONG ALL DRAWINGS PRIOR TO PROCEEDING WITH ANY WORK
OR FABRICATION. THE STRUCTURE HAS BEEN DESIGNED TO RESIST CODE REQUIRED VERTICAL AND LATERAL
FORCES AFTER THE CONSTRUCTION OF ALL STRUCTURAL ELEMENTS HAS BEEN COMPLETED. STABILITY OF THE
STRUCTURE PRIOR TO COMPLETION IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. THIS RESPONSIBILITY
INCLUDES BUT IS NOT LIMITED TO JOBSITE SAFETY, ERECTION MEANS, METHODS, AND SEQUENCES,
TEMPORARY SHORING, FORMWORK, AND BRACING; USE OF EQUIPMENT AND CONSTRUCTION PROCEDURES.
COORDINATE SCOPE OF WORK AND ADDITIONAL REQUESTS WITH OWNER.
CONSTRUCTION OBSERVATION BY THE ENGINEER IS FOR CONFORMANCE WITH DESIGN ASPECTS ONLY AND IS NOT
INTENDED IN ANY WAY TO REVIEW THE GENERAL CONTRACTOR'S CONSTRUCTION PROCEDURES.
STANDARDS
ALL METHODS, MATERIALS AND WORKMANSHIP SHALL CONFORM TO CITY OF RENTON PUBLIC WORKS, 2010
WSDOT STANDARD SPECIFATIONS, 2006 ACI 350 ENVIROMENTAL ENGINEERING CONCRETE STRUCTURES.
VAULT SURFACE LIVE LOAD: 250 PSF
ROOF SNOW: 25 PSF
FOUNDATIONS
REFER TO GEOTECHNICAL REPORT BY AESI 8/2010
SOIL BEARING: 3000 PSF
GENERAL : VAULT BOTTOM SLAB SHALL BEAR ON COMPACTED ROCK (95% ASTM D1557) OVER COMPETENT
APPROVED NATIVE DENSE EARTH BEARING. CONTRACTOR SHALL EXERCISE EXTREME CARE DURING EXCAVATION
TO AVOID DAMAGE TO BURIED LINES, TANKS, AND OTHER CONCEALED ITEMS. UPON DISCOVERY, DO NOT
PROCEED WITH WORK UNTIL RECEIVING WRITTEN INSTRUCTIONS FROM ENGINEER. EXCAVATIONS TO BE INSPECTED
BY GEO TECHNICAL ENGINEER FOR SUITABILITY OF BEARING SURFACES PRIOR TO PLACEMENT OF REINFORCING
STEEL PROVIDE DRAINAGE AND DEWATERING AROUND ALL WORK TO AVOID WATER - SOFTENED EARTH.
BACKFILL : BACKFILL AROUND THE VAULT TO CONFORM TO WSDOT 9 -03.12 (2) GRAVEL BACKFILL FOR WALLS, OR
MATERIAL AS APPROVED BY THE GEOTECHNICAL ENGINEER. 95% COMPACTION PER ASTM D1557, USING LIGHT
EQUIPMENT. DO NOT BACKFILL UNTIL ALL THE CONCRETE HAS CURED TO DESIGN STRENGTH.
ROCK BASE: WSDOT 4 -03.12 (4) 95% COMPACTION PER ASTM D1557.
CONCRETE
CONCRETE AND PLACEMENT: SHALL MEET THE REQUIREMENTS OF WSDOT STANDARD SPECIFICATION 6 -02.
SUBMIT PROPOSED MIX DESIGNS FOR REVIEW. MEET THE REQUIREMENTS OF 6- 02.3(2)A. PROVIDE A MIX AND
PLACEMENT TECHNIQUES COMPATIBLE WITH REINFORCING LAYOUT.
> FINISH AND FORMWORK: CLASS 2. SNAP TIES SHALL HAVE GROUTED CONCRETE PLUGS. INSIDE OF VAULT
zo CONSIDERED "EXPOSED ".
z
MASONRY
o MASONRY ASSEMBLIES: SHALL BE CONSTRUCTED IN COMPLIANCE WITH THE REQUIREMENTS OF 2008
a ACI 530. MINIMUM SPECIFIED COMPRESSIVE STRENGTH, f'm, SHALL BE 1500 PSI FOR CONCRETE
MASONRY ASSEMBLIES.
o+
PLASTICITY IN A MANNER TO FILL THE GROUT SPACE. GROUT POURS GREATER THAN 12 INCHES SHALL
MAX. SLUMP
MAXIMUM
MAXIMUM
ITEM
CONCRETE
(INCHES)
AGGREGATE
W/C
GRADE N, MEDIUM WEIGHT
CLASS
m
SIZE
RATIO
ALL CONCRETE
4000
4.5
3/4"
.45
SUBMIT PROPOSED MIX DESIGNS FOR REVIEW. MEET THE REQUIREMENTS OF 6- 02.3(2)A. PROVIDE A MIX AND
PLACEMENT TECHNIQUES COMPATIBLE WITH REINFORCING LAYOUT.
> FINISH AND FORMWORK: CLASS 2. SNAP TIES SHALL HAVE GROUTED CONCRETE PLUGS. INSIDE OF VAULT
zo CONSIDERED "EXPOSED ".
z
MASONRY
o MASONRY ASSEMBLIES: SHALL BE CONSTRUCTED IN COMPLIANCE WITH THE REQUIREMENTS OF 2008
a ACI 530. MINIMUM SPECIFIED COMPRESSIVE STRENGTH, f'm, SHALL BE 1500 PSI FOR CONCRETE
MASONRY ASSEMBLIES.
o+
PLASTICITY IN A MANNER TO FILL THE GROUT SPACE. GROUT POURS GREATER THAN 12 INCHES SHALL
a
BE RECONSOLIDATED BY MECHANICAL VIBRATION 15 TO 20 MINUTES AFTER PLACEMENT TO MINIMIZE
v
HOLLOW CONCRETE MASONRY UNITS (CMU): SHALL CONFORM TO
ASTM C90. MINIMUM FACE
SHELL
O
THICKNESS AS DEFINED BY ASTM C90, SECTION 5.3.1. PROVIDE
GRADE N, MEDIUM WEIGHT
BLOCK
m
WITH MINIMUM SPECIFIED COMPRESSIVE STRENGTH AS NOTED ABOVE. CMU CONSTRUCTION
SHALL BE
N
SOLID GROUTED UNLESS NOTED OTHERWISE.
REQUEST WRITTEN APPROVAL A MINIMUM OF (10) DAYS PRIOR TO PROCEEDING SITE MOBILIZATION.
0
n
EQ.
CONTRACTOR SHALL SUBMIT QUALIFICATIONS TO PERFORM HIGH LIFT GROUTING.
5TD
O
E/W
EA5T / WE5T
TYP.
j
MORTAR: SHALL BE TYPE S PER IBC. CONFORM TO ASTM C270.
MINIMUM COMPRESSIVE STRENGTH =
0
1800 PSI.
6ALV.
GALVANIZED
3
%
GROUT: GROUT FOR POURING SHALL BE A FLUID CONSISTENCY.
CONFORM TO ASTM C476
AND ACI
0
530. f'g =2000 PSI MINIMUM AT 28 DAYS.
U)
0. 1 GROUT SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION DURING PLACEMENT AND BEFORE LOSS OF
E
PLASTICITY IN A MANNER TO FILL THE GROUT SPACE. GROUT POURS GREATER THAN 12 INCHES SHALL
a
BE RECONSOLIDATED BY MECHANICAL VIBRATION 15 TO 20 MINUTES AFTER PLACEMENT TO MINIMIZE
o
VOIDS DUE TO WATER LOSS. GROUT POURS 12 INCHES OR LESS IN HEIGHT SHALL BE MECHANICALLY
o
VIBRATED, OR PUDDLED. COVER AND KEEP DRY ALL MASONRY WORK DURING CONSTRUCTION AND
3
PREVENT MOISTURE ABSORPTION INTO MASONRY UNTIL THE ROOFING IS COMPLETE.
0
U)
MINIMUM
(n
HIGH LIFT GROUTING: HIGH LIFT GROUTING SHALL ONLY BE ALLOWED WITH PRIOR WRITTEN APPROVAL OF
=
THE STRUCTURAL ENGINEER AND THE LOCAL BUILDING OFFICIAL. THE MASONRY CONTRACTOR SHALL
C
REQUEST WRITTEN APPROVAL A MINIMUM OF (10) DAYS PRIOR TO PROCEEDING SITE MOBILIZATION.
0
THIS SHALL APPLY TO UNIT MASONRY GROUTED IN LIFTS HIGHER THAN 5 FEET. THE MASONRY
EQ.
CONTRACTOR SHALL SUBMIT QUALIFICATIONS TO PERFORM HIGH LIFT GROUTING.
N
M
O
m
0
0
O
O
N
/
0
IBbuoara�SoWObns
xxx�
ir�xw�xrx
rxYaY
senez,o 1w 1w iw l
F¢er Way.WAWW3
w �W WIV
www.esmcivil.com
= awe w.�m
ESM JOB #1655- 001 -009
NO.
METAL REINFORCEMENT
SHALL MEET THE REQUIREMENTS OF WSDOT STANDARD SPECIFICATION 6 -02.2 AND 9 -07 ALL BARS GRADE 60. LAP
SPLICE ONLY WHERE INDICATED.
66I
FRAMING CONNECTORS: SHALL HAVE ICC APPROVAL AND BE MANUFACTURED BY SIMPSON
STRONG -TIE COMPANY, SAN LEANDRO, CA., OR PRE - APPROVED EQUAL. PROVIDE MAXIMUM SIZE AND
QUANTITY OF NAILS OR BOLTS PER MANUFACTURER, EXCEPT AS NOTED OTHERWISE. PROVIDE LEAD
HOLES AS REQUIRED TO PREVENT SPLITTING OF WOOD MEMBERS.
METAL PLATE CONNECTED WOOD TRUSSES: SHALL BE MANUFACTURED BY AN APPROVED TRUSS
MANUFACTURER IN ACCORDANCE WITH APPROVED SHOP AND INSTALLATION DRAWINGS IN
CONFRRMANCE WITH IBC 2303.4. TRUSS CALCULATION PACKAGE SHALL BE DESIGNED UNDER THE
DIRECT SUPERVISION OF A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF WASHINGTON. ROOF
TRUSSES SHALL BE PROVIDED TO COMPLETE THE ROOF FRMAING FROM THE ROOF SHEATHING TO THE
SUPPORTING MEMBERS BELOW. PROVIDE SHOP AND INSTALLATION DRAWINGS AND CALCULATIONS.
DETAIL DRAWINGS TO INDICATE ALL INFORAMTION AS REQUIRED: KEYPLAN; INDIVIDUAL TRUSS
DESIGNS; PERMANENT BRACING AND CONNECTION DETAILS.
WOOD PANEL SHEATHING: SHEATHING CD -X VENEER PLYWOOD. WOOD SHEATHING SHALL BE
"STRUCTURAL I" CONFORMING TO PS1 -07 AND /OR PS2 -04. ALL PANELS SHALL BEAR THE STAMP
OF AN APPROVED GRADING AGENCY.
SHOP DRAWINGS & SUBMITTALS
THE FOLLOWING SHOP DRAWINGS /SUBMITTALS SHALL BE PROVIDED FOR REVIEW AND APPROVAL BY THE
STRUCTURAL ENGINEER PRIOR TO FABRICATION OR DELIVERY.
1. CONCRETE MIX DESIGNS
2. REBAR SHOP DRAWINGS
3. ROOF TRUSSES
STRUCTURAL ENGINEER CITY
X X
X X
X X
SPECIAL INSPECTION: PER CITY OF RENTON PUBLIC WORKS
ABBREVIATION LIST
SOT.
BOTTOM
J5T
J015T
CENTERLINE
MAX.
MAXIMUM
CLR.
CLEARANCE
MIN.
MINIMUM
GONG.
CONCRETE
N/5
NORTH / 5OUTH
EA.
EACH
51IT'G
5HEATHIN6
EQ.
EQUAL
5TD
5TANDARD
E/W
EA5T / WE5T
TYP.
TYPICAL
FT6
FOOTING
W/
WITH
6ALV.
GALVANIZED
MY OF RENTON
BY I DATE I APPR
ARF
nr ruu scue
s not ax xx
5t.VE /LCOfAW0.Y
CITY OF
RENTON
DATUM
Planning /Building /Public Works Dept.
5 -3516
ISSAQUAH SCHOOL DISTRICT
LIBERTY HIGH SCHOOL
PUMP STATION
C-0 S - 35`1 (008
2010 -09 -1
S1.0
sur. 8 nr'21