. PUBLIC WORKS WATERPLAN GENERAL NOTES
DEPARTMENT
MARCH 2010
SANITARY SEWER NOTES AND SPECIFICA'
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING /PUBLIC WORKS
DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND
SPECIFICATIONS, AS APPROVED 'AND MODIFIED BY THE CITY OF RENTON IN THE RENTON
STANDARD PLANS .& SPEGFlCATIONS. ASET OF APPROVED PLANS SHALL BE KEPT ON
SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS
ON WEEKDAYS UNLESS.OTHERWISE'APPROVED -IN WRITING BY THE
`.PLANNING/BUILDING /PUBLIC WORKS DEPARTMENT, AN APPROVED TRAFFIC CONTROL PLAN
MUST BE OBTAINED PRIOR TO BEGINNING ANY WORK WITHIN PUBLIC RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTORS - RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO
AVOID DAMAGE OR DISTURBANCE.
4. APRE- CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR
TO STARTING NEW :CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
.SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL
BE ACCOMPLISHED BYA- REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE PUBUC WORKS INSPECTOR 24 HOURS IN
ADVANCE OF'BACKFIWNG ALL CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION
SITE
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND
ANY 07HER RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS..
& A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER
CONSTRUCTION 1S IN PROGRESS.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF
THE SANITARY SEWER SYSTEM, WHICH HAS BEEN. STAMPED AND SIGNED BY A LICENSED
PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A
LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY
TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS
MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF
THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS
DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY
SHALL BE BACKFILLED NTH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS
_ OTHERWISE APPROVED BY.
W 64003
A PORTION OF SEC. 4, TWP. 23 N., RGE. E., W.M., KING COUNTY WASHINGTON
EXISTING WATER LINE
ALAN VIEW
TESTING DETAIL
s8 FT
NEW WATER LINE
VERTICAL CROSS(MJxFL) FOR FULYFIGGMG
ONE BLIND RANGE ON TOP N:TH 2'TAP B 2'PWG
LINE BLIND FI. ANGE ON 30TTOM
LINE (RAJ) PLUG WITH Z' TAP 6 2' TEMPORARY ELUW-(I11
TEMPORARY RIDCK
CUT -IN (BY CITY FORCES)
iCC fTE VA V LONG BLOCK
2- GATE VALVES OLD 2- SOLID R 0`1 SLEEVES tMJ) pR RG -MAC COUPL:rv6S
I- ADAPTER (FL X MJ)
1- PLUG (NJ) N /2'iAP fl TEMP. BLOW -0OFF
tEMP. BLOCK
EXISTING WATER LINE
EXISTING WATER LINE
FINAL CONNECTION DETAIL
AFTER ALL TESTING, CLEANING BY P01.YPIG, AND DISINFECTION,
REMOVE TEMP. FLOOR B BLOW-OFF 6 CONNECT
VITH SLEEVE (M.) 6 D4, SPOOLS
FINAL CONNECTION BY CITY FORCES
EXISTING WATER LINE
PUBLIC WORKS CONNECTION TO WATER MAIN CUT • PLAN - 300.3
DEPAR'CMEN'1' IN -LINE TEE & TWO VALVES
t• MARCH 2010
U11UTY SPECIFICA110NS:
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988
METERS, AND FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991
METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO
THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION
AFTER THE COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION
IN ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING /BUILDING /PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE
WISDOT /APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE
CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL
INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE
FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED
BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WALL
BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE
PEA GRAVEL 6 INCHES ABOVE AND BELOW THE PIPE.
15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D
3034, SDR 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE
WASTEWATER UTILITY.
16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12
INCHES ABOVE FINISHED GRADE OR MUST HAVE MINIMUM2'DIAMETER CONCRETE RING
POURED AT GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH
PAVING.
REVISION
Y
L
TESTING DETAIL
110 FT I
EXISTING WATER LINE -
EXISTING TEE DEAD END LINE CAP OR PLUG
R
DO NOT DISTURB BLOCKING
NEW WATER -INE\
C_'00-'
VERTICAL CROSS (MJXFL) FOR POLYP13GING
1 -BLIND FLANGE ON TOP WITH 2'TAP& 2 "P' -UG
1 -BLIND FLANGE ON BOTTOM
1- PLUO(MJ) W/2 °TAP & 2" BLOW -OFF
TEMP. BLOCK
FINAL CONNECTION DETAIL
NEW MATER LINE
FXIST. WATER LINE
AFTER ALL TESTING, CLEANING BY POLYPIG AND DISINFECTION,
REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT
TO EXISTING WATFR LINE WITH SLFEVF (MJj
AND C.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
�'
®� PUBLIC WORKS CONNECTION TO WATER MAIN STD. PLAN - 300.5
DEPARTMENT EXISTING TEE OR END LINE CAP MARCH 2010
NOT TO SCALE
MANHOLE FRAME AND COVER
SEE STD. PLAN 401
ADJUSTMENT RINGS (2" MIN.)
SEE NOTE 6
MORTAR JOINT(S) (3/8" MIN.)
SEE NOTE 5
CONE (ECCENTRIC)
RUBBER GASKETED JOINTS IN
ACCORDANCE WITH ASTM C -443
STEPS - POLYPROPYLENE STEPS
SHALL BE INCLUDED
CONCRETE RISER BY PIPE INC..
OR APPROVED EQUAL
LADDER - POLYPROPYLENE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIZE - 'E'
CONCRETE SHELF
PRECAST BASE SECTION
OR CAST IN SHELF.
''1^
'B'
WATER PLAN GENERAL NOTES Standard Plan ND. 3D0
'D'
U)
48" MH
48"
6" MIN. _
5 "MIN
24" MIN.
CALL WORK AND MATERIAISSHALL BE IN ACCORDANCE WITH THE LATEST EDITION OFTHECIIYOF RENTON PUBLIC WORKS
54" MH
54"
8" MIN.
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONSAND WSDOT/APWASTANDARD SPECIFICATIONS, LATESTEDMONAS
24" MIN.
1
60" MH
AMENDED BYTHE CITY OF RENTON. ASET OF CITY APPROVED PLANS SHALL BE KEPTATTHEJOBSI EWHENEVER CONSTRUCTION
B" MIN:
6" MIN.
42" MIN.
ISINPROGRESS. A PRE-CONSTRUCTION CONFERENCE SHALL BE HELD PRIORTOTHESTARTOFCONSTRUcnotLTHE CONTRACTOR
CL
MUELLER 00. A- 2600 -6 WIN BALL
AND OR DEVELOPERSHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIORTO CONSTRUCTION.
\
DRIP VALVE At BOTTOM
INCLUDED AS PART OF ME DETECTOR
INSTALL EPDXY NON- SHRINK
DOUBLE CHECK VALVE ASSEMBLY.
TB" FOR 10' ASSEMBLY
2. ALL EXLS'TING UTILmESSHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESSOTHERWI3ENOTED . THECON7RAOTORSHALL
5/8 -x3/4 MNSUS END (TR /PL) METER
I7 1/2- 'OR 8" ASSEMDLY
CALL1 100 474- SSSSTOVERIFY UTILITY LOCATIONS BEFORE BEGW 41NG EXCAVATION,
18 1/2' FOR 6' ASSEUBLY
3' 0" IN PIPE FL .x FL 3'O' LM'C
tltt PR VnR
3. ALL MATERIALS USED FORTHE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED,AND
6 "& W ASSEMBLY 6' SHORT
• -
'CATALOG COW FORALL MATERIALS SHALL BE APPROVED IN WRITING BYTHECTTYOF RENTON PRIORTO BRINGING ANY
AP PWWG
f0" ASSEMBLY 90' 6' %6'
MATERULSON-SITE.
REDUCING DEND FL
K1uv FL)
3 2
4. ALL WATER MAIN PIPE MATERMILSSHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CASS52 PER AW WAC 151ANDC
0 Wn. vµN (N. . MS)
?-1 6'-90' BE FL
100. PIPEJOINTS SHALLBE PUSH -ON OR MECHANICALl01NT. CAST IRON OR DUCDIEIRON PIPE FFMNGSSWILLBE C ASS250AS
LEI
PER ANSI/AW WA 0110 /A21.104M ALLDUCRLE IRON PIPE AND FITTINGSSHALLBE WRAPPED WITH BAAIL BIACKTUBETYPE,
2
W
POLYETHYLENE PLASTIC PER AWWACWSSTANDARDS.
r
I-
S. MINIMUM COVER FROM TOP OF WATER MAINSTO FINISHED GRADE SHALL BE 36 INCHES FORPIPE DIAMETEROF 104NCH ORLESS
W
Z
AND 48 INCHES FOR PIPE DIAMETEROF I2 -INCH AND LARGER. MAYJMUM COVER FORALLWATER MAINSSHALLBE 60 INCHES.
ANYDEVIATIONS MUSTBE APPROVED BYTHE CTTYOF RENTON PRIORTO CONSTRUCTION. WHEREUTILIIYCONFUCrSOCCUK
w W
U
THE PROFILE OFTHE WATER MAINSHALL BEADJUSTED AS NECESSMIYTO CLEAR C ONPU CTSANDTO PROVIDE MINIMUM COVER.
0_.
PIPE DEFLECTION SHALL NOTEX CEEDONE- HAEF OF PIPE MANUFACTURER'SSPEQHCATION FORSUEOFPIPEUSED. ALLTRENCH
/T�
DEFMMWBVTHE MODINEDPROCTORTEST
BACKFILLSHALL BECOMPACTEDT095 PERCEW MAXIMUM DRY DENSITYAS EO
V
METHOD(MOD)IN ROADWAYS, ROADWAYSHOULDERS, ROADWAY PRISM AND DRIVEWAYS, ARDIS PERCENT MOD IN UNPAVED
Z
AREAS. ALL PIPE ZONECOMPACNON SXALLBE 95 MOD.
Z
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POUREDIN PLACE "ACCORDANCE WITH CITY OF
UNION STANDARD DETA UAND SPECIHrAMONSANO SHALL BE INSTALLED ATALLVERHCALANDHORMWALSENDS FrMNGS
AND BASE OF HYDRANTS.. MEGAdUGS (OR SIMILAR PRODUCT) MAYBE REQUIREDONALLME iANICALJOINTSINAM MINTO
W
CONCRETE BLOCKING.
J
7. ALL NEW WATER MAIN PIPESAND FITTINGS SHALL HAVEA FOAM PIPE PIG RUNTHROUGH THEM PRIORTO BEING FLUSHED,
DISINFECTED, ANDTESTED.CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE INTHE PRESENCEOFAND UNDERTHE
SUPERVISION OF AC17Y.OF RENTON UnUTY INSPECTOR. THE CONTRACTOR SHALLSUPPLY INSTALLAND REMOVE PLUGS,
0
CORPORATION STOPS, BLOW -0FF ASSEMBLIES, AND THRUST RESTRAINT/ BLOCKING FORTESTING ANDPURITACCEPTANCE .NO
0
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WETTAPVAWEYOAN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM"PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESRIREAND PUROYTESDN G.
r
&NEW WATER MAINS INCLUDING SERVICE LATERALS SHALLBE TESTEDATA STATIC PRESSUREOF ISO PSIABOVEWORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH AMAXIMUM OFS PSIFRESSURE DROP DURING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OFTHE PRESSURETFST, THE UNESHALLBE DISINFECTED, FLUSHED,
ANDTHEN WATER SAMPLES SHALL BETAKEN FOR PURITY TESTING BYTHE PUBUC WORKiINSPECTOR
V
9. THE CONTRACTORSHALLNOTIFYTHE CRY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENRATI EAST SOWORKING
DAYS PRIORTO MAKING CONNECTIONSTOTHE METING WATER SYSTEM. THE CONTRACTORSHALL EXPOSETHE EXISTING WATER
MAIN AND FITTINGSATTHECONNECTION POINT BEFORE ORDERING THE NECESSARYADAPTORSANDFITTINGS REQUIRED FOR
�)
THEFINALCONNECT(ON. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROADESHORING AND
ALL MATERIALS REQUIRED FORTHE CITY OF RENTON TO PERFORM THE CONNECTIONTOTHE EXISTING WATERSYSTEM. THE
Q
CONTRACTORSHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCYJNG,ANDCOMPIETESURFACE RESTORATION.
W
STD. PLAN - 300.0
. PUBLIC WORKS WATERPLAN GENERAL NOTES
DEPARTMENT
MARCH 2010
SANITARY SEWER NOTES AND SPECIFICA'
1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING /PUBLIC WORKS
DEPARTMENT AND THE LATEST EDITION OF THE WSDOT /APWA STANDARDS AND
SPECIFICATIONS, AS APPROVED 'AND MODIFIED BY THE CITY OF RENTON IN THE RENTON
STANDARD PLANS .& SPEGFlCATIONS. ASET OF APPROVED PLANS SHALL BE KEPT ON
SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS
ON WEEKDAYS UNLESS.OTHERWISE'APPROVED -IN WRITING BY THE
`.PLANNING/BUILDING /PUBLIC WORKS DEPARTMENT, AN APPROVED TRAFFIC CONTROL PLAN
MUST BE OBTAINED PRIOR TO BEGINNING ANY WORK WITHIN PUBLIC RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE
CONTRACTORS - RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO
AVOID DAMAGE OR DISTURBANCE.
4. APRE- CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR
TO STARTING NEW :CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
.SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL
BE ACCOMPLISHED BYA- REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE PUBUC WORKS INSPECTOR 24 HOURS IN
ADVANCE OF'BACKFIWNG ALL CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF
CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION
SITE
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND
ANY 07HER RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE
PRECEDENCE OVER ALL OTHER PLANS..
& A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER
CONSTRUCTION 1S IN PROGRESS.
9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF
THE SANITARY SEWER SYSTEM, WHICH HAS BEEN. STAMPED AND SIGNED BY A LICENSED
PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A
LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY
TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS
MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF
THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS
DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY
SHALL BE BACKFILLED NTH CRUSHED ROCK AND MECHANICALLY COMPACTED UNLESS
_ OTHERWISE APPROVED BY.
W 64003
A PORTION OF SEC. 4, TWP. 23 N., RGE. E., W.M., KING COUNTY WASHINGTON
EXISTING WATER LINE
ALAN VIEW
TESTING DETAIL
s8 FT
NEW WATER LINE
VERTICAL CROSS(MJxFL) FOR FULYFIGGMG
ONE BLIND RANGE ON TOP N:TH 2'TAP B 2'PWG
LINE BLIND FI. ANGE ON 30TTOM
LINE (RAJ) PLUG WITH Z' TAP 6 2' TEMPORARY ELUW-(I11
TEMPORARY RIDCK
CUT -IN (BY CITY FORCES)
iCC fTE VA V LONG BLOCK
2- GATE VALVES OLD 2- SOLID R 0`1 SLEEVES tMJ) pR RG -MAC COUPL:rv6S
I- ADAPTER (FL X MJ)
1- PLUG (NJ) N /2'iAP fl TEMP. BLOW -0OFF
tEMP. BLOCK
EXISTING WATER LINE
EXISTING WATER LINE
FINAL CONNECTION DETAIL
AFTER ALL TESTING, CLEANING BY P01.YPIG, AND DISINFECTION,
REMOVE TEMP. FLOOR B BLOW-OFF 6 CONNECT
VITH SLEEVE (M.) 6 D4, SPOOLS
FINAL CONNECTION BY CITY FORCES
EXISTING WATER LINE
PUBLIC WORKS CONNECTION TO WATER MAIN CUT • PLAN - 300.3
DEPAR'CMEN'1' IN -LINE TEE & TWO VALVES
t• MARCH 2010
U11UTY SPECIFICA110NS:
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988
METERS, AND FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991
METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO
THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION
AFTER THE COMPLETION OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION
IN ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING /BUILDING /PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE
WISDOT /APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE
CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL
INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE
FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED
BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WALL
BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE
PEA GRAVEL 6 INCHES ABOVE AND BELOW THE PIPE.
15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D
3034, SDR 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE
WASTEWATER UTILITY.
16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12
INCHES ABOVE FINISHED GRADE OR MUST HAVE MINIMUM2'DIAMETER CONCRETE RING
POURED AT GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH
PAVING.
REVISION
Y
L
TESTING DETAIL
110 FT I
EXISTING WATER LINE -
EXISTING TEE DEAD END LINE CAP OR PLUG
R
DO NOT DISTURB BLOCKING
NEW WATER -INE\
C_'00-'
VERTICAL CROSS (MJXFL) FOR POLYP13GING
1 -BLIND FLANGE ON TOP WITH 2'TAP& 2 "P' -UG
1 -BLIND FLANGE ON BOTTOM
1- PLUO(MJ) W/2 °TAP & 2" BLOW -OFF
TEMP. BLOCK
FINAL CONNECTION DETAIL
NEW MATER LINE
FXIST. WATER LINE
AFTER ALL TESTING, CLEANING BY POLYPIG AND DISINFECTION,
REMOVE TEMP. BLOCK & BLOW -OFF & CONNECT
TO EXISTING WATFR LINE WITH SLFEVF (MJj
AND C.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
�'
®� PUBLIC WORKS CONNECTION TO WATER MAIN STD. PLAN - 300.5
DEPARTMENT EXISTING TEE OR END LINE CAP MARCH 2010
NOT TO SCALE
MANHOLE FRAME AND COVER
SEE STD. PLAN 401
ADJUSTMENT RINGS (2" MIN.)
SEE NOTE 6
MORTAR JOINT(S) (3/8" MIN.)
SEE NOTE 5
CONE (ECCENTRIC)
RUBBER GASKETED JOINTS IN
ACCORDANCE WITH ASTM C -443
STEPS - POLYPROPYLENE STEPS
SHALL BE INCLUDED
CONCRETE RISER BY PIPE INC..
OR APPROVED EQUAL
LADDER - POLYPROPYLENE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIZE - 'E'
CONCRETE SHELF
PRECAST BASE SECTION
OR CAST IN SHELF.
NOSES:
1. STEPS TO BE POLYPROPYLENE SAFETY STEPS.
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASTING SHALL BE PER STD. PLAN 401.
4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS. BRICKS AND CASTING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED NTH A COMBINATION OF
ADJUSTMENT RINGS, BRICKS AND MORTAR ON" BRICKS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1/2 BOND. THE USE OF SHIMS IS PROHIBITED
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING,
COATED (SEALED) NTH A HIGH SOLIDS URETHANE COATING; WASSER MC- AROSHIELD OR
APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE NTH ASTM C -443.
9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE.
To. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR -N -SEAL BOOTS OR
APPROVED EQUAL.
it. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM OF 12"
ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS. COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING.
T
PUBLIC WORKS STANDARD SANITARY MANHOLE SID PLAN - 400.1
DEPARTMENT
SEPTEMBER :oil
DESIGNER . KELLY
DMxTB TDS
0. NASON
APPROVED
D. GAVIN
MINA: PAID t
AS NOTED NORQgRN: °iT°B1
DIVE INCH DATUM
AT FULL SCALE
IF NOT ONE aKx
SCALE �Y
POST INDICATOR
PRECA51 CONCRETE VAULT WITH 3 - 34 3
'A'
'B'
'C'
'D'
E'
48" MH
48"
6" MIN. _
5 "MIN
24" MIN.
1 21" I.O.
54" MH
54"
8" MIN.
-5.5 "MIN.
24" MIN.
1 24" I.D.
60" MH
60"
B" MIN:
6" MIN.
42" MIN.
I 30" In
NOSES:
1. STEPS TO BE POLYPROPYLENE SAFETY STEPS.
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASTING SHALL BE PER STD. PLAN 401.
4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS. BRICKS AND CASTING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED NTH A COMBINATION OF
ADJUSTMENT RINGS, BRICKS AND MORTAR ON" BRICKS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1/2 BOND. THE USE OF SHIMS IS PROHIBITED
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING,
COATED (SEALED) NTH A HIGH SOLIDS URETHANE COATING; WASSER MC- AROSHIELD OR
APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE NTH ASTM C -443.
9. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE.
To. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR -N -SEAL BOOTS OR
APPROVED EQUAL.
it. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAXIMUM OF 12"
ABOVE FINISHED GRADE OR MUST HAVE A MINIMUM 2' DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS. COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING.
T
PUBLIC WORKS STANDARD SANITARY MANHOLE SID PLAN - 400.1
DEPARTMENT
SEPTEMBER :oil
DESIGNER . KELLY
DMxTB TDS
0. NASON
APPROVED
D. GAVIN
MINA: PAID t
AS NOTED NORQgRN: °iT°B1
DIVE INCH DATUM
AT FULL SCALE
IF NOT ONE aKx
SCALE �Y
POST INDICATOR
PRECA51 CONCRETE VAULT WITH 3 - 34 3
ONE EACH SIDE
rX 2 1/2. FIRE DEPARTMENT DOUBLE
HINGED STEEL PLATE COVERS. DIMEN90N5
CONNECTION FOR STAND PIPE YOUR
5 -81 11' -Yx 7' -2" EQUAL i0 UTILIN
4" ADAPIEF, AL.. SCREWED
BREAKABLE CAST IRON HOSE CAPS
VAULT OR EQUAL
9'x4'x6- BULL READ TEE. FL
ONE EACH SIDE EQUAL TO GINNIE
TOUCH READ PIT LID SENSOR
FIG. 1682 MTH HOSE CAPS FIG. 1333.
MOUNTED
RO GH 2E DR.
COVER THROUGH 2. CIA.
6' PIPE FL.x
6' SIANG TYPE GRAVITY OPERATES
IN
DRILLED NOTE IN COVER..
FL T -0' LO
CHECK VALVE, FL. EQUAL TO
MUELLER 00. A- 2600 -6 WIN BALL
ME SY -PASS ASSEMBLY SHALL BE
\
DRIP VALVE At BOTTOM
INCLUDED AS PART OF ME DETECTOR
INSTALL EPDXY NON- SHRINK
DOUBLE CHECK VALVE ASSEMBLY.
TB" FOR 10' ASSEMBLY
GROUT CPP.)
5/8 -x3/4 MNSUS END (TR /PL) METER
I7 1/2- 'OR 8" ASSEMDLY
WHY, ICE REGISTER
18 1/2' FOR 6' ASSEUBLY
3' 0" IN PIPE FL .x FL 3'O' LM'C
tltt PR VnR
\ 1f- 2
6 "& W ASSEMBLY 6' SHORT
• -
RADIUS 90' BEND R.
AP PWWG
f0" ASSEMBLY 90' 6' %6'
REDUCING DEND FL
K1uv FL)
3 2
0 Wn. vµN (N. . MS)
?-1 6'-90' BE FL
71
12' ALL AROUND
`-1086 FLxM A
Atl DE U'S DOUBLE CHECK VALVE
J DAPiOR
OR 6' FL., PE.
aS5EM9L1E5 $MALL INCLUDE RESILIENT
SEATED SHUNFF VALVES Np TEST PLAN Lt0' A$$EMBLY 10':10 " +8 "TEE FL.
PIPE WRE COLLAR 18" COCKS ND APPROVED 6' ASSEMBLY 8 "x8 "x6" TfE, f4 6"
FROM P.E, CRO55- CONNECTION CONTROL
10 "- 3'-8` LONG L ASSEMBLY 6v6 "z6- TEE IL.
AR. DoS PER DEPARTMENT OF
8" S -6" LONG HEALTH LATEST APPROVED LIST. 10 , V. OR 6" CATE VALVE, FL. MP
6 4 0" LONG WITH INDICATOR POT INDICATOR
DOUBLE CHECK VALVE ASSEMBLY POST VALVE SAME SUE CO. OR
SHUTOFF MU RESIDENT SEATED CHECK VALVE (MUELLER C. OR
SHUTOFF VALVES. EQUAL), PRINTED RED.
10', 8', OR 6" FLANGED MUPUNG
ADAPTER EQUAL TO RWAC. 10', 8, OR 6- DUCTILE IRON
CLASS 52 NIPPLE PIPE,
(2) 2 HOSE WALK CEMENT LINED, LENGIYI TO FIT.
TOUCH READ PIT UO SENSOR MOUNTED
NOTE: DRILNEEMMEU COKR. THROUGM2 DIA. -�-
1. LOCATE VAULT IN PLANTING AREA, NOT IN PAVING. 3 J6'i0 42'
(2) 2 r HOSE WALK s' PIPE ..
2. a' AND LARGER BENDS AND TEES 70 BE CAST pL SCREW
IRON CEMENT LINED. W FOR 10- ASSEMBLY 17
1/2' FOR 8- ASSEMMY 18 II
3. hMPORARY SUPPORT SHALL BE PROVIDED UNDER 1/2" FDA 6' ASSEMBLY 6 3
VALVES Ai THE TIME OF INSTALLATION TO CENTER
THE PIPE IN VAULT OPENING. AFTER COMPLETE z3/4' INVENSYS
INSTALLATION REMOVE THE TEMPORARY SUPPORT TR_pL METER PoM T -Y
AND INSTAL ADJUSTABLE PIPE SUPPORT. ICE REGISTER
T INSTALL GALVANIZED LADDER FOR ACCESS, 6" MIN BRAIN TO DAYOGHT Ofl
STOP. DRAW SYSTEM WTIH 6" 90' BEND il.
5. AFTER FIELD INSTALLATION. MAIN ODCVA AND CATCH BASIN OR MANHq.E p`_1y
BY -PASS DCVA MUST BE TESTED SATISFACTORILY
BY A DEPT. OF HEALTH CERTIFIED SACKFLOW GALVANIZED
ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED 4" FSE AND ELBOW SIEEI LAOOfR
10 CMY OF RENTON WATER UTUTY ENGINEERING
DEPT. PRIOR TO ACDVA ➢ON OF NEW ONE. COMPACTED FOUNDATION
6. INSTALL BRASS A' FLARE TEST COCKS WITH A- GRAVEL
FLARE CAPS. ST NCHRONS BOLTED PIPE
70 FLOOR. T
END VIEW
' ` 6 ",8" & 10" DOUBLE DETECTOR CHECK SID. P�360.2 A� 4 PUBLIC WORKS ASSEMBLY WITH STANDPIPE OUTSIDE re Q DEPARTMENT INSTALLATION MA
IU�1
=
GATE VALVE--\�
r>, r
�(i1P1IU76T[E�pI�1�O
THRUST �` G
BLOCK °
GRADE
1AA RODS
PIPE MATERIAL AND FITTINGS
AS PER SPECIFICATIONS
POST INDICATOR VALVE -" -
TACOMA • SEATTLE
NOTICE
NOT TO SCALE , �,.;m, 2215 North 30th Street, Suite 300, Tacoma, WA 98403
oiewn�"tNU°f011LS4°a'pmia N 253.383.2422 TEL
MIT, N16EM WRIiDNAE TIIEBM
ND NIATT,O BE ISO fG RAN{ BIGB. A7 1200 Sixth Avenue, Suite 1620, Seattle, WA 98101
mmlroiwTNmEnaFce Arr ollw lapin. 206.267.2425 TEL
are
CITY OF EARLY CHILDHOOD LEARNING CENTER s -22 -2012
RENTON RENTON SCHOOL DISTRICT P
Planning /Building /Public Works Dept. SANITARY SEWER AND WATER DETAILS Ci8.4A
Izz, -