SEE CITY OF RENTON SPECIAL PROVISIONS
FOR BOLT SPECIFICATION. LENGTH OF BOLT
MAY BE SHORTENED IF IT MEETS MANUFACTURERS
RECOMMENDED LENGTH.
I— I � —1
18" MIN. � I j I
I I�� I I
�J'_I
CLASS 3000 CONCRETE I I � 4' -6"
8 �7 BARS I I I
EVENLY SPACED I I
#4 HOOPS I I I I
12" CENTERS — — — �
–� 2 "CLEARANCE
3' SQ OR RND
FOUNDATION DETAIL � I
o
N �
I�
`� 3 I M
rr��
�1 �
f
i
I3
IZ
3
i
o
v
ro
_�
X
W
I
CONSTRUCTION NOTES
0 CONSTRUCT SERVICE /ILLUMINATION CABINET FOUNDTION. INSTALL SERVICE /ILLUMINATION
CABINET.
O2 CONSTRUCT LUMINAIRE POLE FOUNDATION WITH CONCRETE PAD AND TYPE 1 JUNCTION BOX
(SEE DETAIL, SHEET 4) INSTALL 25 FT. LIGHT STANDARD WITH 100 WATT HPS
LUMINAIRE.
O3 CONSTRUCT LUMINAIRE POLE FOUNDATION WITH CONCRETE PAD AND TYPE 2 JUNCTION. BOX
(SEE DETAIL, SHEET 4) INSTALL 25 FT. LIGHT STANDARD WITH 100 WATT HPS
LUMINAIRE.
® INS�ALLTYPE 1 JUNCTION BOX WITH CONCRETE PAC (SEE DETAIL, SHEET 4).
5� CONNECT TO TRANSFORMER VAULT IN ACCORDANCE WITH PUGET SOUND ENERGY REQUIREMENTS,
r�Ao- ai -�'sr
LUMINAIRE SCHEDULE
LUMINAIRE
N0.
CITY OF RENTON
LUMINAIR I.D.
NUMBER 1
LAMP
WATTAGE
POLE
LOCATION
CL OF POLE
CURBFACE
MOUNTING
HEIGHT
CIRCUIT
N0.
REMARKS
1
21166
100 WATT
0 +56 RT
6 FT.
25 FT.
1
TYPE III LIGHT DISTRIBUTION
2
21 186
100 WATT
2 +03 RT
6 FT.
25 FT.
1
TYPE III LIGHT DISTRIBUTION
(1) NUMBER TO BE AFFIXED TO POLE IN ACCORDANCE WITH CITY OF RENTON STANDARD DETAlL.
ROLL 161
SERVICE CABINET (I.D. R0. 00�
BREP:KF_R AND CONTACTOR SCHEDULE
CIRCUIT
N0.
MAIN BREAKER
AMPS
BRANCH BREAKER
AMPS
COPJTACTOR
AMPS
REMARKS
MAIN
100
–
–
120 240 VOLT
1 ILEUM
–
20
30
240 VOLT
2 N0. 10 (ILEUM)
1 GREEN N0. 8 (GND)
1 -1 /2" PVC
WIRE NOTES
�4
PULL STRING
(FUTURE LIGHTING}
2" PVC
RUN
CONDUCTORS
CONDUIT
FINdL CORREG ?ED PLAN
_.RD !Z
iHiS DRAWING rix- �?E�iV PREPARED
-1,
BASED ON fNFlNiFhti °,� *, ^OMPILED
�G�;•'..
_
FROM rHE COQ ,� �7R AND
-`
- ,�
OTHERS
ev /7`1,x'
� 1
`�. rA!>Q
,n7F //— /1_-99_
�:.,�riHES. iQVOO
///i2/49
2 N0. 10 (ILEUM)
1 GREEN N0. 8 (GND)
1 -1 /2" PVC
WIRE NOTES
RUN
CONDUCTORS
CONDUIT
3 N0. 2 (POWER)
1 GREEN N0. 8 (GND)
2" PVC
2 N0. 10 (ILEUM}
1 GREEN N0. 8 (GND)
2" PVC
2 N0. 10 (ILEUM)
1 GREEN N0. 8 (GND)
1 -1 /2" PVC
�4
PULL STRING
(FUTURE LIGHTING}
2" PVC
NOTE: LATERAL CONDUITS SHALL BE PVC SCH. 40.
STREET CROSSINGS SHALL BE PVC SCH. 80.
��_ ��
�� � �
s
LEGEND
® LIGHTING CE3NTACTOR CABINET
�� --�'S- COMBINATION FOUNDATION WITH LUMINAIRE
� ,y�.(� AND TYPE 1 JUNCTION SOX
C����--1J CONI611VAlIVIV FGUiJ DATiON LVITH ! UMINAIRE
AND TYPE 2 JUNCTION BOX
® TYPE 1 JUNCTION BOX
- - - - - -- CONDUIT
O CONSTRUCTION NOTE
WIRE NOTE
CO, T— z7� /oz �8-t': T— �..2�6/a3 :Cd►r1NED DEC 10199 q� /os