Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
zD-2206Set
C IT NGTON NELSON PLACE RAHER STORM SYSTEM RE INDEX OF DRAWINGS SHEET NO. DESCRIPTION 1 COVER SHEET 2 NELSON PL. NW /RAINIER AVE. N. - PLAN AND PROFILE 3 DETAILS I LOCATION MAP 1 =1 GENERAL NOTES: 1. Existing site improvements shown are based upon a survey by TCA Inc., dated 7/19/94 and City of Renton records. No warranty or guarantee of accuracy or completeness is either implied or expressed. Existing underground utilities and improvements have been shown on these drawings for the purpose of assisting the Contractor in locating said utilities and improvements in the field. The Contractor shall be responsible for checking actual locations in the field and checking with appropriate agencies that may have underground utilities and improvements within the project limits. The Contractor shall be solely responsible for any and all damage to underground utilities and improvements resulting from his operation. 2. All connections to new or existing concrete structures will be at manufactured knock -outs or the structure is to be core - drilled. 3. Prior to the start of construction activities, telephone (206) 277 -5570 a minimum of 24 hours in advance of required inspections. Inspection requests for the following workday must be received no later than 3:00 pm. The ONLY exception to the 24 -Hour Minimum scheduling requirement is in cases of bonafde emergencies. In cases of true emergencies (broken utilities, urgent traffic control problems, etc.) telephone 235 -2631. 4. There will be no guarantee of re- inspection on the same day for any work which is not ready at the time of the scheduled inspection. 5. Where a new pipe clears an existing or new utility by G' or less, an approved polyethylene plastic foam shall be placed as a cushion between the utilities. 6. In all cases where men, equipment, or material will in any way obstruct vision or inhibit normal traffic flow, adequate signs and flagmen will be required to protect motorists and pedestrians. In addition, the following personnel will be notified 24 hours prior to any work being performed within the street right -of -way: Street Maintenance Superintendent -- 235 -2615 Fire Department -- 235 -2642 Police Department -- 235 -2600 Engineering Division -- 235 -2631 Valley Communications Center -- 911 7. In the event difficult street crossings must be constructed in more than one continuous operation, the Engineering Division will endeavor to provide an inspector during each phase of construction so long as the Engineering Division is contacted 24 hours in advance at 235 -2631. 8. It shall be the sole responsibility of the Contractor to obtain street use and other related or required permits prior to any construction., activity on -site or in the City right -of -way. 9. The subgrodes under all areas to be paved shall be firm and unyielding, and compacted to 98% of the maximum density. (per Standard Proctor Test). Proof rolling may be required prior to paving to insure stability. 10. The Contractor shall adjust all existing and new manhole rims, drainage structure lids, valve boxes, and utility access structures to finish grade within areas affected by the proposed improvements. 11. All pavement, walk and curb removals shall be vertical saw cut at the boundaries of removal area. Removals shall be included in the total contract price. Contractor shall restore or replace all pavement, walks, curbs, driveways, walls, rockeries, landscaping including lawn, fences, utilities, meters, vaults, mailboxes and signs, or related items damaged by construction to original or better condition. 12. All street closures, partial or full, shall be approved by Public Works 24 hours in advance. 13. Th e hours of work in street right -of -way shall be limited to 7:00 am to 5:00 pm on weekdays only unless otherwise approved in writing by Public Works at 235 -2635. Truck hauling on City of Renton arterial streets shall be limited to 8:30am to 3:30P, . 14. Prior to any utility service interruptions to an individual residence, a minimum of 24 -hour written notice shall be given to the resident and the City of Renton. Contractor shall make all efforts to restore service within a reasonable time period. 15. Any work within the street right -of -way requires a separate permit and bond, and work must be performed by a licensed, bonded Contractor. S v R D E S I G N C 0 M P A N Y • Civil Engineering • Planning • Landscape Architecture • 911 Western Avenue • Suite 302 • Seattle, WA 98104 • Phone 206.223.0326 • CITY OF RENTON STORM WATER DRAINAGE NOTES: (The following notes are required by the City of Renton to appear on these plans. some notes may not apply to this project) 1. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRECONSTRUCTION MEETING MUST BE HELD WITH THE CITY OF RENTON DEPARTMENT OF PUBLIC WORKS DESIGN ENGINEER. 2. All construction shall be in accordance with the "1994 Standard Specifications for Road, Bridge and Municipal Construction prepared by WSDOT /APWA, as amended by the City of Renton Department of Public Works, and the City of Renton Public Works Department Standard Details manual dated 2/1/91. 3. The storm drainage system shall be constructed according to the approved plans which are on file in the Department of Public Works. Any deviation from the approved plans will require written approval from the City of Renton Department of Public Works, Design Engineer or Storm Water Utility. 4. A copy of these approved plans must be on the job site whenever construction is in progress. 5. Datum shall be U.S.G.S. unless otherwise approved by City of Renton Department of Public Works. Reference benchmark and elevation are noted on the plans. 6. All sedimentation/erosioni facilities must be in e, ration prior to clearing and building construction, and they must be satisfactorily maintained until construction is completed and the potentiel for on -site erosion ha =U.,,,; 7. All retention /detention facilities must be installed and in operation prior to or in conjunction with .all co4jt9/ctioh' activity unless otherwise approved by the Department of Public Works, Storm Water Utility. 8. Grass seed may by applied by hydroseeding. The grass seed mixture, other than City of Renton. - poproved standard mixes, shall be submitted by a Landscape Architect and approved by the Department of Public Works, Storm Water utility. 9. All pipe and appurtenances shall be laid on a properly prepared foundation in accordance with Section 7- 02.3(1) of the current WSDOT Standard Specifications for Road and Bridge Construction. This shall include necessary.. leveling of the trench bottom or the top of the foundation material as well as placement and compaction of required bedding material to uniform grade so that the entire length of the pipe will be supported on a uniformly dense unyielding base. All pipe bedding shall . the Class "C", with the exception of PVC pipe. All trench b shall be compacted to minimum 98% for pavement and structural fill and 95% otherwise, per ASTM D155 - bFIROVI Pea gravel bedding shall be 6" over and under PVC pipe. AY 10. Galvanized steel pipe and aluminized steel pipe for all drainage facilities shall have asphalt treatment #1 better inside and outside. /1.,� 11. Structures shall not be permitted within 10 feet of the spring line of any storm drainage pipe, or 15 feet fryfp, the,0 . -/ `� /DA'T'E top of any channel bank. t3Y 12. All catch basin grates shall be depressed 0.10 feet below pavement level. $,,,,. a Wat r Ut lit 13. Open cut road crossings thru existing public right -of -way will not be allowed unless specifically approved by City f Y of Renton Department of Public Works, Design Engineer. 14. Rock for erosion protection of roadside ditches, where required, shall be of sound quarry rock placed to a depth of 1 foot and must meet the following specifications: e- 8"/40 % -70% passing; 2 " -4" rock /30 % -40% passing; and -2" rock /10 % -20% passing. 15. All building downspout and footing drains shall be connected to the storm drainage system, unless approved by the Department of Public Works, Design Engineer or Storm Water Utility. An accurately dimensioned Certified as built drawing of this drainage system will be submitted to the City of Renton upon completion. 16. Issuance of the Building or Construction Permit *by the City of Renton does not relieve the Owner of the continuing legal obligation and /or liability connected with storm surface water disposition. Further, the City of Renton does not accept any obligation for the proper functioning and maintenance of the system provided during construction. 17. The Contractor shall be responsible for providing adequate safeguards, safety devices, protective equipment, flaggers, and any other needed actions to protect the life, health and safety of the public, and to protect property in connection with the performance of work covered by the contract. Any work within the traveled right -of -way that may interrupt normal traffic flow shall require an approved traffic control plan by the Traffic Engineering Division of the Department of Public Works. All sections of the WSDOT Standard Specifications Sec. 1- 07.23, Traffic Control, shall apply. Contractor shall prepare and file a Traffic Control Plan with the City of Renton, in 2 accordance with City requirements. An approved Traffic Control Plan shall be on file with the City prior to starting 0 work. J&2 18. Special drainage measures will be required if the project location is within the aquifer protection area. AR T CALL 48 HOURS BEFORE YOU DIG 1 -800 -424 -5555 RECOMMENDED FOR APPROVAL PLAN REVIEW �. SURFACEW ER UTILITY DATE TRANSPORTATION DATE REVI ft FOR COMP NC_ E TO CITY'S STANDARDS L�a /4' 5 18 5S RLITY KSTEMS MANAGER DATE MAIN ENANCE SERVI ES ANAGER ids DATE S• /Fs- gs &TRANSPORTATION SYSTEMS MANAGER DATE SHEET 1 OF 3 Vl Hi 0 m U, 7O, z� N r i g� '0 19 18 17 16 15 14 13 12 11 10 9 8 7 6 MI RO OX 6 7 8 9 10 11 12 13 14 15 16 17 18 19 SE SECTION 18 TOWNSHIP 23 RANGE 5 E 20 0 10 20 40 EMSTING LEGEND �T7SCALE: 1" = 20' LD ADJUST SD. ALIGNMENT TO STA. 9 +85.73 RAINER AVE. DID DAMAGING EXISTING BRICK N. W. 3RD PLACE \11TARY SEWER MANHOLE CENTERLINE OF ROW REMOVE EX. INLET STA. 10 +00 RAINER AVE. = STA. 11 +47.7, 32'RT STA. 20 +00 N.W. 3RD PLACE INSTALL TYPE I CB & 8" SD TO MANHOLE FIELD VERIFY LOCATION +00 w 10 +00� 11+00 - _ 12 +00 CONC. SD oZ POT Hbt�-ED LOCATION OF EXIST 'E C. CONDUIT oZ ✓ 2 CB #1 3 3 TYP 3 CB #51 SEE NOTE 8 \ RAINIER AVE. N 3 (16, E3 -2) CB #10 3 39LF „ -1SL9 T�-LE 12 SD . -\ -- -- -- -- 1- D EASEMENT 2Q ° _ r-.. PROPOSED LEGEND TYPE 1 #7 STA'. +27'.332, T.... ... .. REPLACE RIM = 5 . 4 EX. 6" CONC. 51.1:4 IE 12" (SE) 49. 0 128th F CONC. 2.947 TT 50 .... .. - _ �_ 1 ExlsT. 6'_conlc- CB TYPE I #6 ^� NO? FOUND 45 STA 8 +21, 30.2'RT �: RIM =. 53.73 .............. �.. REPLACE EX. CB 50.20 NEW I.E. 12" (S) 513-7-, 5 ° EX. I.E. 6" CONC. (W) = 51.33 2 - 6 "CONDUITS �2 3 "CONDUITS TYPE II CATCH BASIN I PLUG TYPE I CATCH BASIN 18 "SD STORM PIPE BASIN PROTECTION /5 _ _ 35 40 CATCH STA. MATCHLIINE STA. NOTE 4 it for any purpose. 18 +50 CALL 48 HOURS RIM. -4-20'+ 51.25 U CB #3 JI BEFORE YOU DIG EX. IE. 10" CONC. (NW) =380N. NW IE =35 39 30 S E =41.76 19511; 32 s'Rr I � � 1 -800-424 -5555 I 0 .. I + Q - RIM . _ .. .... ... I DR i - DI "c" orR �� � ., , B TYPE II 54" #3 - z �;TORM _-Ni palra'EC MARK = 2' -6 "DIA, 5' DEEP, CONC. '14�63n�T 6) RAINIER .- S T - C " AVE N FOUR CONC PANEL STA. ��-.- - 19 +09.9, 5.7'R RIM = -54-3 - 51.86 r MATCHLINE STA. EASEMENT RECORDED #9508280393 EX. I.E. 12 CLAY CB TYPE TI 54 5 `I A° 18 +50 8) POWER CONDUITS 24 "WIDE -(N) - F 41.81 FIELD VERIFY TOP =28 ", BOTTOM =52° BELOW GROUND ( ) _ - 4&.4$- 46.33 STA. 9 +40, 30-Rfi 31.7'RT -- NEW IE 12' E �� 41.76. . . 2 - 6 4 "GREY CONDUITS, 3- 2'CONDUITS NEW E.. 18 ". (S). = . f REPLACE .EX..CB- , GRATED. LID IN .CURB. LINE - 2Q...... g) EASEMENT RECORDED RIM = 52.16 INLET CB TYPE: 11 54" # No. Stlob5oso3 (MATCH IE. :OF EXIST. :OF STA. 11 +4 . z.z'RT: STA. 11 +:60 30.2'RT 12" S6A� EX. I.E. 6" CONC. (NW) = 48.71 GRAT 48.00 ) 12" (N) =41.90 m. O CB: TYPE I 10 I b" cork. (s) = o REPLACE: EX. CB CONC 2 CONC 2 \9 EX. I.E. 8" CONC. E = 48.81 # EXIST GRADE { y EX. I.E. 8" CONC. (SW) = 48.96 STA. 11 +21, 30.0'RT RIM = 7.74: OJ ED TO "' EX E 8 PV 40 92 4 C S4N NEW' LE. 12" (S) - �0 46:52 RIM 48.41 ( ) P ieau NEW I.E. 12" (N) _ �8@ 46.65 EXIST GRADE NEW IE. 12" (N) = 43=x4 42.85 EX. I.E. 6" CONC. (E) = 45.57 CB TYPE I #8R ` aL,�"'„zm's� _ PROJECTED TO CE " j S) = 2.8 EX. LE. 18" CONC. = 35.37 STA. 19 +42 11.6' LT EXPIMS W11 -11 NEW OE. 12 4 0 _ CB _------ :_ -_ -- - N IE 8 = 46 NEW IE _ �57`s3 9 = 05060. - 30..5LE NEW " (W 48 _ RREI�PLACE - ... ) NEW I.E. :12" (S) = :4-76 NEW IE. 12" N) 42:4 42.18 50 E _ _ Ex s:T 12„ . / 47.85 2.9012 1 D 1 g ". N.W 5.3 2 - _ _ corv_c C, ASBUILT DRAWING - _ 11.1 LF .8 "STEEL - - ®$% - - - -:- - - - - -- @ 0 _ 0 7?ti .54 %� q0 6' �Oo1 6 NOVEMBER 17, - - - - - _ - - 3.67%& .... ..1995W ems not l m r ere.unch .ar ..... ..... .... - -. ___ :. ..�c� � ere completed Drt 2 45 a ked w ange -188- LF 12" - _ - - - - - ' Z . NEW 18 "(S) w not checked. �3 -6 "CONDUITS 181.9 ASD, @ 8t - - - - -- o 2 -3 "CONDUITS CONIC 2.02% zQ - - 2 EX. 12 Q DATE: March 12, 1995 ..:.... ©. 39L..12 "GONG AT 45BATR OF MIS o� ®1,5 % liaunlSglv&nSSOCIaTESINC DUCT BANK: c-��NOT FOUND 19 +00 40 47:65.. fl...... - ... NOT .FOUND .. . I .... - z. o s2 "a ST (N) Q 176141 BE 3 � O IN_ EXISTING - - PO BOX 516 3 "CONDUIT - - RAINIER : AVE 11 0 � CB : TYPE I #9: MONROE, WA. 98272 -0516 47.00 Y b CONC. PANEL A2 � � _ _ _ C STA 9 +39 :0 6' EX. 8'CVP Phone: (360)794-7811 M o� m 45 50.: - TL 5O S5 LOWERED - 0 RIM . 10150.65RT CAPPED 35 45.... ........ Z .U. G P BELOW PIPE �.. - -.- NEW l E. 12" (N) - -47.@6-47.48 T . 0 BE 10 ±00 NEW I.E. 12" W = x+6-46 -47.45 fly ° oo Pv° (IOU n CB TYPE :1 ( ) 206 of ® o' x ~ 11 +32 32.0'RT 11 +60 INSTALLED ON OLD CONC. BASE. a J �� '�� RIM =48.52 NEW CONC. POURED TO SET CB 40 �� Q.......w - o a Q �'Lq a r : 26.5:.....1..1- - :..... NEW. IE. 8 ". (NE)= 46:54..... '.NO CATCH wn 40 45 45 w _<L1 oc : -2-i- L:F 18 ,,1 1 NOee. : : VON S, . 97. EMSIING C b 18 SD w `a 8" CONC THIS DRAWING HAS BEEN REVISED PER CONSTRUCT /ON RECORDS ?/23/96 fi 5 WAy LF C t Nh% th" ,to f n �t� -� ryr -gam 2 39% - CONC. - - �` : : : This record droNrrng has been. prepared, based upon Information Iumrshed -y the ontrac or r e rs r rmo. ro D' @-i 1 is believed to be :reliable, SvR Design Company cannot be assured of its accuracy, and thus ca�nat be responsib /e For 35 EXISTING_ BRICK. GB _ .. _ _ . _ .. _ : TYPE II 54' _ NOTE 3 - -� _ _ 35 40 1 .g2�. I- _ : 40 ..the- aecurocy of fhls record drawing or for any error or omrssions which -may hove been incorporated into it os a resu /t &CONC. LIJ : Those:re/ying on this record document ore cdvlsed to obtain Independent field verification of its accuracy be`ore applying STA. NOTE 4 it for any purpose. d CALL 48 HOURS RIM. -4-20'+ 51.25 CB #1 CB #3 EX: CB (16, E2 -z) BEFORE YOU DIG EX. IE. 10" CONC. (NW) =380N. NW IE =35 39 30 S E =41.76 19511; 32 s'Rr s c c N r D E N O M P A 1 -800-424 -5555 30 E.X.. !E. 18" CONC, .(N) - .. RIM . _ .. .... ... .. DR EX. IE. 6" CONC. (E) 41.70 NOTES: U 4) ENCOUNTERED 2" TO 5" DIA. COBBLES EX E 12' CONIC. (r rr ; = ds.6 rI +P cg.22 911 tern Avenue: Western oNTmans FROM oM RENTON JDR NEW IE. 18" SE = :3-7-.W 37.72 ( ) 3) PEATY SOILS, WET AROUND CB #3, 2' TO 10' BELOW GROUND, X 8" ,S`:yl = E_ !,8" CC1,C. (S) - 41:12 Suite 302 Z - REMOVED 2 TO 4 FEET BELOW PIPE - 30'+ WIDE TRENDING WEST UP NW' 3RD PL _x, - - "dEVv IE. i8" (Il) _ =a-2" 41.25 - Seattle, WA 98104 1 AS -BUILT FROM SURVEY JDR %F0-410 -?206 : PLACED 2" TO 4" QUARRY SPALLS SEVERE SLUFFING AND PAVEMENT LOSS _ Phone 206.223.0326. ND. REVISION BY 18 17 16 15 14 12 11 1 • 8 , A mig '•C! R14 1 V1 o� 40 r �ro z N Z Q, A I ®! ! I A I I 1 !Y ! ! 1 1 i Al I 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 i 10" HIGH CONC. RETAINING WALL SSMH 56 _ `l RIM = 5,199 ` ' z I I.E. 8" PVC (N,S) = 48.59 41e '.Ji P ` 55 6" MAPLE I H3`: I ( I 30" DIA. BRICK CB RIM = 53.73 I.E. 6" CONC. (W) = 51.33 I.E. 6" CONC. (S) 50.73 TYPE I CB GRATE = 54.54 I.E ASPHALT . 8" PVC (N,S,W) = 52.34 I v I.E. 6° CONIC. (E) = 52.34 4" VERT. CURB t 8" EXTRUDED CURB` O�PS, S SANITARY SEWER 1' HIGH RETAINING WALL E CLEAN OUT I 3 C. 'J�i MERIDAIN PER WASHINGTON STATE DEPARTMENT OF TRANSPORTATION R.O.W. PLANS 2.0' X 0.7' METAL CB FOR S.R. 167 DATED 1 -14 -94 I I 's RIM = 52.24 TYPE I CB I; I.E. 6" CONIC. (S) 51.14 GRATE = 50750 I I.E. 6" PVC (NE) = 49.50 I I f Fl t II I GRAPHIC SCALE cRn� CBSO.7a 20 0 10 20 40 I.E. 8" CMP (SW) = 49.55 ROUND I TYPE II CB 1 inch = 20 ft RIM = 51.1. 17 I GRATE = 52.76 I.E. 12 TERACOTTA (N) = 41.27 I.E. 6" CONIC. (N) = 47.76 I.E. 6° CONC. (N) = 46.17 I 81, MAPLE 5y I.E. 6" CONC. (NW) = 48.71 ' 1 2" CONIC. (NW) = 46.67 I I -- t I.E. 8" CONC. (E) = 48.81 I.E. 8" CMP (SW) = 46.22 ! I.E. B" CONC. (SW) = 48.96 I.E. 8" CMP (NE) = 48.02 w I I.E. 12" CONIC- (5) = 47.66 I.E. 12" CONIC. (S) = 41.12 DATUM: CITY OF RENTON I ~ BENCHMARK: RAILROAD SPIKE 1' HIGH IN WEST FACE - ----------------- --------- - - - - -- - CENTERLINE RAINIER AVE. OF POWER POLE ® S.E. CORNER OF INTERSECTION OF TYPE It CB ¢ I'r // p = 10'50'00" 95 NELSON PLACE N.W. & HARDIE AVE. N.W. RIM = 50. I.E. 8" CMP (NE) = 46.35 y° .'' R - 5730.00' I.E. 8" CMP (S) = 46.30 ,� /'/ L 1083.41' �+ 1" VERT. CURB I 1 °- 1' WIDE THICKENED EDGE CURB t 5`E - ) 4" VE;EC URB - I CABLE VISION VAULT i S 1 $ { 1fl 89'4'30a E O (F) SSMH I�1 CABLE N PAINT DMARK I � RIM = 57.18 I : ird 'PLACE I I 5 I.E. 8" PVC (N,S) = 42.48 6" CONC. VERT. r 41 'I i ) � !` 1' i sl, f ' `l it' WA MANHOLE � I a`L SFORM(DRAJN PAINT MA- 1 Ji CURB (TYPICAL)) ry6 j �E� j I i; j tis 1O 0° 5 1 -'G p I j POWER VAULT CO-(JC. LK J �y F I ((TYPICAL) � / J J il R cOVC O,` I ^ Pl ROUND BRICK CB RIM = 66.24 RRIGATION I.E. - CONIC. (NW) RIGHT -OF -WAY (TYPICAL) j I I = 6329 VALVE 1(TYP) I.E. 12" CONIC. (N) = 63.29 3 ; w / j I.E. 12 CNO. (E) = 61.39 ( USINESS E I.E. 72" CO ONC.((Wj = 61.39 z ¢ f'f 1 (SIGN P ) l0 I.E. 6" CONC. SW = 62.54 O I I.E. 12" CMP (S) = 61.54 f 31 ,, 0 S 9J\� CONIC. � I S�O�{ �,�� ti.../ I I I CURB 18 M� PLE ,. CB C5 ¢ I ¢� NI I pRF'P 3r I/ y I.E.A6" D.1.4(SW) = 47.95 O rf PQZ�l ✓' �i Off O =c' j I '� <I X18 "MAPILEr� I' I tml SIZE OF ENDS OF CONIC. 1 PIPE ARE DIFFERENT BUT IT APPEARS TO CONNECT CB 157 i I l l GRATE = 48.00 4 LryLP I.E. 6" CONC. (S) = 46.90 A = 2737'00" r 2 R = 390.92' `°�FiApLE 1 L = 188.42 _ ) i 9.19 (F) f% Ir LPl TYPE II CB GRATE = I.E. B" PVC (S (sw) = . I .. ao. "� = 35 .75 . �y I.E. 6" CONC. (NW) = 44.67 GRATE CB , B / ;\ 'D�• I I.E. 12" CONC. (N) = 42.42 I.E. 8" CMP (W) = 47.05 `'' / i 9 r�L I.E. 6" CONC. (E) = 45.57 I.E. 12" CMP (N) = 47.00 / 1 f�• 7 I Qe I.E. 18" CONC. (SE) = 35.37 54" DIA. BRICK CB / / s RIM -'.51 .20 I.E. 1 CONC. (NW) = 40.45 O I.E. 18" CONC. (N) = 38.50 I.E. 6" CONC. (E) = 41.70 I.E. 18" CONC. (SE) = 37.50 t 21 20 19 18 17 16 15 14 18 12 11 10 9 8 7 6 CONC. CURB SURROUNDING TRAFFIC ISLAND el / I` ' I / CJ 2" VEP/T. CURB RT . CURB / TYPE I CB WITH OIL /WATER SEPERATOR SSMH q GRATE = 45.69 _ RIM = 43.27 i I.E. B" PVC = 43.74 o- I.E. 8" PVC (NS) = 38.87 EXPI S NOTES 1) ALL UNDERGROUND UTILITY CONNECTIONS SHOWN ARE ESTIMATED FROM OBSERVATIONS MADE AT POINTS OF ACCESS (MANHOLES, CATCH BASINS) ONLY. USE AS APPROXIMATE GUIDUNE ONLY. 2) RIGHT -OF -WAYS AND CENTERLINES SHOWN ARE BASED ON RECOVERED STREET MONUMENTATION, CITY & COUNTY RECORDS AND UNRECORDED MAPPING PREPARED BY H.W. RUTHERFORD, ENGINEER ON FEB 11, 1952. 1Q APPROXIMATE LOCATION, OTHER END NOT FOUND Q APPROXIMATELY 392 L.F. 8° PVC ® 0.92% TO OFFSITE MANHOLE TO SOUTH. O APPROXIMATELY 130 L.F. 8" PVC ® 4.609" TO OFFSITE STORM DRAIN CATCH BASIN TO SOUTH. NOTE TO SVR ENGINEER: THE T.C.A., INC LOGO & TITLE BLOCK /BORDER COMBINATION MAY BE REMOVED BY ERASING OR TURNING OFF LAYER "TCA- BORDER ". OTHER LAYER NAMING IS ALPHA BASED AND IS SELF EXPLANITORY - IF YOU HAVE QUESTIONS PLEASE CALL LEGEND FIRE HYDRANT IRRIGATION VALVE FIRE DEPARTMENT CONNECT ® WATER METER D4 WATER VALVE O STORM DRAIN MAN HOLE ❑ STORM DRAIN CATCH BASIN O SANITARY SEWER MANHOLE o SANITARY SEWER CLEANOUT PAD MOUNTED TRANSFORMER 10 SIGNAL VAULT © ELECTRIC VAULT VAULT (UNDETERMINED UTILITY) © POWER TRANSFORMER ON CONC. PAD -{ STREET LIGHT j( YARD LIGHT ■ ELEC. STUBOUT BOX TELEPHONE RISER ID GAS VALVE O GAS METER a SIGN • -� -- GAURD POST FENCE AS NOTED 4n.2 DECIDUOUS TREE - G - GAS PAINT MARK - E - ELECTRIC PAINT MARK -TV- CABLE TELEVISION PAINT MARK -SD- STORM DRAIN PAINT MARK + 50.57 SPOT ELEVATION AT FLOW LINE (F) FLOW LINE OF GUTTER (TYR) TOP OF CURB IS 6" HIGHER UNLESS OTHERWISE NOTED (A) ASPHALT ELEVATION AT FACE OF TRAFFIC ISLAND Rm2206 V 9 V/1 a O ro � ro B C" w t8 C Z' l® ti I A' ! MI RO OX 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 --wR i