HomeMy WebLinkAboutzS-2706SetSANITARY SEWER UTILITY - GENERAL NOTES L ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON AND THE LATEST EDITION OF WSDOT /APWA STANDARDS AND SPECIFICATIONS. 2. THE HOURS OF WORK. IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30 AM. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE TRANSPORTATION DIVISION AT 277- 6222. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE. 3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON STANDARD SPECIFICATIONS - 4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 5. A PRECONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION- IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION- (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON_) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. wwpa7 -27b6 CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE- f SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION- 8. P4nNS APPROVED BY THE CITY OF RENTON, DEVELOPMENT SERVICES DIVISION, SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. t 9_ A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS- BUILT DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY LICENSED PROFESSIONAL ENGINEER OR A LICENSED PROFESSIONAL SURVEYOR. 11 BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95% OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE BACKFILL OF THE PIPE SHALL BE THE SAME AS DESCRIBED. 12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH A SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON NT STANDARDS- 1 CURRE �o ____ -_ - - -- 30.00'— — - [ 3 Z c: w CD Q w Z N L,, w Ili Q O Ld m i Q N E 13. DATUM SHALL BE CITY OF RENTON, U.S.C. AND G 14. ALL DISTURBED AREAS SHALL BE SEEDED AND MUILCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF 7,HE DEPARTMENT FOR THE PREVENTION OF OWSITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. 15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE W!TF: SECTION 7 -023(1) OF THE CURRENT STATE OF WASHINGTON STr,NDAJRD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION - THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEM ENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE PIPE BEDDING SI -LaLL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE - 16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50. 17. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 18 INCH ABOVE FINISHED GRADE- IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. _ NE - 20TH STREET _ N 89'20' 29"E 132251, .� RtM r NEW 8 ILti`i2x,2r CLEAN -OUT DETAIL 3 SHEET N 89°43' 42°E 252.42' 72,00 _ 0.00" _ 2G' PRIVATE ROAD FASEMENT FOR ACCESS_ _ AND UTILITIES 20' PAVED SIDE SEWER o DETAIL 2 SHEET C2 SIDE SEWER (TYP) INV Z`+" INV 293_Ri LOT 1 LOT 2 MIN FF 29G.6' a3 MIN FF 296,35 b 3C.0 -- �- - - -- LOT 4 ` - -tls' MIN FF 2-95.5' F _ SHARED DRIVEWAY ! (WT 4,5 ACCESS ! `a I2 PAVED ! i 20 SIDE SEWER- ! a LOT 3 MIN FF 296,3' 50.00 l 50.00` N 89 °48'2PE 252AI' SANITARY SEWER PLAN SCALE 1 =20' i ROLL 16W I L LOT 5 MIN FF 2954 MR APPROVAL !Y P `V 7 -38 By_ - DA!M BYS 'la BY #ATE LEGAL DESCRIPTION THE SOUTH'/ OF THE NORTH 1/2 TRACT 245, C.D. HILLMAN'S LAKE WASHINGTON GARDEN OF EDEN, DIVISION NO. 4 AS PER PLAT RECORDED IN VOLUME 11 OF PLATS, PAGE 82, RECORDS OF KING COUNTY; EXCEPT THE SOUTH 15 FEET THEREOF. SITUATE IN THE CITY OF RENTON, COUNTY OF KING, STATE OF WASHINGON. ALL IN SECTION 5, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M. AQUIFER PROTECTION NOTICE THE LOTS CREATED HEREIN FALL WITHIN ZONE 2 OF RENTON'S AQUIFER PROTECTION AREA AND ARE SUBJECT TO THE REQUIREMENTS OF THE CITY OF RENTON ORDINANCE NO. 4367. THIS CITY'S SOLE SOURCE OF DRINKING WATER IS SUPPLIED FROM A SHALLOW AQUIFER UNDER THE CITY SURFACE. EXTREME CARE SHOULD BE EXERCISED WHEN HANDLING OF ANY LIQUID SUBSTANCE OTHER THAN WATER�TO PROTECT FROM CONTACT WITH THE GROUND SURFACE, IT IS THE HOMEOWNER'S RESPONSIBILITY TO PROTECT THE CITY'S DRINKING WATER. I I i EAST CORNER %µ SEC 5 T23N 1R5E WM CR CONTROL\MON 369 N 0' 32 49 E - - 163,52 EXST CONC MON� WITH _ _ 3 BRASS DISK SS MH 2 Rim EL 295.25', sw -. ]NEW INV EL 29234' JTYPE EXTRA SHALLOW C DETAIL I SHEET C2 5S EASEMENT 10' N LOT 24 i POWELI'S 1ff ADD I 9 � 9 +� u �gF F s EXST SS MH 51 INV E 291,27( +Ir; N RIME 297.80 3'- 3m - 3 a �M-I P1 r \ J 1 136.46 LF 8 PVC O M y mE — NEW SAN, S_ EWER — - - -. 3 ° O w EASEMENT a I To p m NEW SS MH I FT RIM EL 29675' o INV EL 29!,92'(08,;? z SHALLOW TYPE B (E } cn DETAIL I SHEET D IN , EL 2°2.02 'T _ Z rT I � l -- 270601 t. m T. z . -. u.I -Ij -T) us , [2° MIN COMPACTED DEPTH r_ -1. ASPHALT TRFA7ED BASE `;, D r Z e =MIN DEPTH CLASS '13' (TOP CAURSE) Z ? - IT �$ _dw_ CONCRETE rGTrD Di PTH CRUSHED Z SURFACE BASE C • URSE- Iz1- -r_LZZ� O --1. I T71i ( N cn M1iy Z(n JAMES E. HAYNES, P.E. 37234 22nd Ave So g A TYPICAL ROAD SECTION FEDERAL WAY, WA 98003 n (253) 661 -6794 $ Cam, , — 27-6- i `a z �0 J 0 9 B� r a � N z LINE 50" ALLOWABLE MAX - fr FOR CAST IP,UN PIPE \ J OR DUCiiLE !RON PIPE i UTURE c&Z 4'rc� /�.• 6 _ __ }_V E BUILDING SEVER 2". 4" STUD SERVICE MARKER PAINT UPPER TEE PITH c _..E -_E- PORTION WHITE ANS STENCIL ON SIDE mot/ I c YIj7DING "SEVER' WITH 3•" HIGH BLACK LETTERS. -e- sly[ curxEr rcc z A D q6 ' IRE WRAPPED AROUND THE STUD AND 6" SIDE S V - SEVER -.lug SEVER WAIN i Ex7ENDED TO THE TOP OF THE STUD. CONCRETE BLOCKING ANGLE I „NLESS U. HERVISE APPROVED BY THE CITY- MAKE TAP THROUGH CAST OF TEE AT MAIN OVER 25 IRON SADDLE SECURED TO SEVER MAIN WITH STAINLESS STEEL BANDS ELEVATION- WHEN CONNECTING NEW SIDE SEVERS -TO EXISTING MAIN. VITRIFIED CLAY, PLAIN AND REINFORCED CONCRETE DI PIPE AND Cl UZ PIPE SEVER MAINS ARF TO BE CORE DRILLED HO E8 OUKSNG NOTE: • LESS ❑ HERWIS S N L S S SEVER S. J, I HAVE MINI—UM 51 COVER AT PROPERTY Px-GR�`"` LINE C2 3 5 LOSS. ELEVATION, WHICHEVER IS LOWER. _ GIN _r wu s�wE_ HORIZONTAL ` SEWER MAIN STANDARD SIDE SEWER INSTALLATION TYPICAL SIDE SEWER ELEVATION 2 (SEWER MAIN TO PROPERTY LINE) CI 3/ <' SQUARES SPACE? - s -1+ AS INDICATED - HT. 1 /8" - CONCRE TC 0 C 1 , �.,- .I CLASS 3000 0 0 0 0 0 Slur -v �: -- 00 000 7 FIBER JOINT RAISE -1/2" PACKING VIDE BORDER to-• 4!5�(718) BEND 2 i 314 " CAST IRON RING AND COVER rert MATERIAL AS SPECIFIED BY TIE ENGINEER ♦_tJ 7 J d I 1 ( I wwP -27- 2706 - _ PLUG TO BE SEALED ? - IY. SAME MANNER. AS MAIN SEWER JOINTS. _ __ __ _ ___ --1 3 6 INCH OR 8 INCH CLEAN -OUT Ci Z 11.1 J Z 01 a k;s e cr 0-1 � ;.yS~ =="• -v70 PROP0 ED NEW 8' CLEAN -OUT i !LOT ,,,jiiJt ScwEk 4 +50 4 }00 3+50 �EXST GRADE 5 180,75 LF C900 `LOT 3 SIDE SEWED EL 2.93,25 — LOT Z SIDE SEWER t EL 293.35 .3+00 INV 292.44 - -+ - Z +50 - 2 4' r 6 FRAME AND LOCKING LI PER DRAYANG BR29, ADJUSTING RINGS OR BLOCKS AS REQUIRED. . J C TO 12-.. PRECAST VALVE / CHAMBER CONE ADAPTOR COLLAR R.C.P. OR EQUAL —� RUBBER CASKS. \ �\. - \ � 3t- wIn To .e" unx. >> e NOTES SANITARY SHALLOW MANHOLE TYPE B / 1. STEPS TO BE 3/4•• 0 DEFORMED BAR GALVANIZED SAFTEY STEPS OR EQUAL 2. STEPS ARE IH BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED 3. CASTING TO BE OLYMPIC FOUNDRY MH30 WITH MH30 D/T OR EQUAL. PER DWG. BR29 - POURED IN PLACE BASE 4 MANHOLE SECTIONS TO AE OF REINFORCED PRECAST CONCRETE 5- OPENING SHOULD BE ON DOWNSTREAM SIDE. 6. ALL JOINTS SHALL BE GROUTED 7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SANITARY EXTRA SHALLOW MANHOLE TYPE C SURFACES, INCLUDING CHANNELING, COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING: WASSER MC- CONSEAL OR APPROVED EQUAL COLOR OF COATING SHALL BE WHITE. r/I = SANITARY MANHOLE DETAILS LI RIM EL 295.25 I INV EL 291,27 +zao NEW SS M142- 1 EXTRA SHALLOW 1 TYPE G Yr-` �! �r LOT 4 � m SIDE SEWER „ate � .,� EL 292.40 1 +00 O +50.00 O +00 O -20.00 E� �a q 1 Sf.50 �C900 -0 `. -INV 7_ LOT 5 INV SIDE SEWER i t EL 29235 2 +00 - 1+50 SANITARY SEWER pR�E�LE �- I "`=Z0.0' HORIZ- SCALc. I " =2.0' VERT i ROLL 157 T` .T 3 81 [s1 Z J c 300 I I +29�v ANEW SS MN I L SHALLOW TYPE B RIM EL ?_96-15 I 1 + 29y i'! I O g � M B 1 iI 9 ti Z L UP m ^' F � m f �o N,p �m 3a m Q n f (Ii aF 71 0 Tj a� o� O• ^n47 L T� °t B3 8 LF 8" PvC +292 \ I NV 291.92 D ?920Z 4 EX5T 55 NH 51 z T s 270602 INV EL 291,27 +zao > Fri tea_ � m -+ + „ate � .,� � • I 1 +00 O +50.00 O +00 O -20.00 E� �a q 1 co C!) �7 -t , ` -0 `. i Pm -AMOVAL gy P. Lv..,BEZ r �� 5F -7 JAMES E. HAYNES, P.E. 37234 22nd Ave So f°°— FEDERAL WAY, WA 98003 � g Q (253) 061 -6794 € C�D; -7­6--'z o° y N o � O i I % Iv O SANITARY SEWER UTILITY - GENERAL NOTES 1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON AND THE LATEST EDITION OF WSDOT /APWA STANDARDS AND SPECIFICATIONS. 2. THE HOURS OF WORK IN THE STREET RIGHT -OF -WAY SHALL BE LIMITED TO 8:30 A.M. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE TRANSPORTATION DIVISION AT 277- 6222. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE TRANSPORTATION DIVISION 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE. 3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON STANDARD SPECIFICATIONS, 4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 5. A PRECONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE CITY INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. >riisT 6. CONTRACTOR IS.SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. 7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION. 8. PLANS APPROVED BY THE CITY OF RENTON, DEVELOPMENT SERVICES DIVISION, SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. 9. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS- BUILT DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR A LICENSED PROFESSIONAL SURVEYOR. 11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95% OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH FIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE BACKFILL OF THE PIPE SHALL BE THE SAME AS DESCRIBED. 12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH A SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON NT STANDARDS. CURRE OD L 30.00' - - - I E I z OD OD N IJ-1 N Q w Z N tit W `n ® o _ -- -.W._ I m I ED N wwp -17 -?706 13. DATUM SHALL BE CITY OF RENTON, U.S.C. AND G.S. 14, ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. 15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH SECTION 7- 02.3(1) OF THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE. 16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50. 17. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 18 INCH ABOVE FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. _ NE . 20TH STREET N 89° 20' 2.9 "E 1322.57' RIM 23S.R NEW 8'/ INY 293.2^ CLEAN -OUT DETAIL 3 SHEET C ?_G' PRIVATE ROAD ASEME_NT_ FOR_AC_CESS_ _ AND UTILITIES ZO' PAVED `� s y cV SIDE SEWER -* ' e DETAIL 2 SHEET C2 SIDE SEWER (TYP) INV �Ab INV 294.00 180.-75 LF S' -- -- -`�'_ _ MI OT 455' I� SHARED DRIVEWAY I �l �\ (LOT 4,5 ACCESS) I> SEWER Al2' PA`�/ED INV �° t Zo SIDE SEWER 293.70 'VFW UW292 6Z �� I . N 89°4342 E 79.49' LOT I LOT 2 LOT 3 1�.�.�:�� -�f (, / MIN FF 296.35 � MIN FF 296,3 A MIN FF 29F.6 �- - m zb INV ?2.57 OM 9N co0 _ O o ° - LOT 5 zo MIN FF 295,4' 73.82 1 50,00 1 50.00 �; 78,59 N 89 °48'21 "E 252A1' SANITARY SEWER PLAN SCALE 1 " =20' mecaummom MR APPROVAL Pt�M ar � 7 -98 BY- Qa tit B �AIE BY _ - -� LEGAL DESCRIPTION THE SOUTH '/2 OF THE NORTH' /: TRACT 245, C.D. HILLMAN'S LAKE WASHINGTON GARDEN OF EDEN, DIVISION NO. 4 AS PER PLAT RECORDED IN VOLUME II OF PLATS, PAGE 82, RECORDS OF KING COUNTY; EXCEPT THE SOUTH 15 FEET THEREOF. SITUATE IN THE CITY OF RENTON, COUNTY OF KING, STATE OF WASHINGON. ALL IN SECTION 5, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M. AQUIFER PROTECTION NOTICE THE LOTS CREATED HEREIN FALL WITHIN ZONE 2 OF RENTON'S AQUIFER PROTECTION AREA AND ARE SUBJECT TO THE REQUIREMENTS OF THE CITY OF RENTON ORDINANCE NO. 4367. THIS CITY'S SOLE SOURCE OF DRINKING WATER IS SUPPLIED FROM A SHALLOW AQUIFER UNDER THE CITY SURFACE. EXTREME CARE SHOULD BE EXERCISED WHEN HANDLING OF ANY LIQUID SUBSTANCE OTHER THAN WATER TO PROTECT FROM CONTACT WITH THE GROUND SURFACE, IT IS THEE, HOMEOWNER'S RESPONSIBILITY TO PROTECT THE CITY'S DRINKING WATER EAST I ' C O N ER SEC 5 T23N R5E WM CR CONTROL ON 3G9 E N 0'32' 49'E -- < 183.52' EXST CONC MO WITH _ 3 BRASS DISK NEW SS M!' 2 RIM EL 295.25' jt4V El- 29Z•44 VN) INV EL 292.34'(OUT) EXTRA SHALLOW TYPE C DETAIL I SHEET C2 -S5 EASEMENT (v LOT 24 POWELL S I5T ADD Sm 2706 03 a i I w a t O z I z u1 r w V) e w a � Z 0 ml 4 1 13 R"OLL 159 EXST I SS MH 51 INV E 291.27(i-, RIM E 297.80 136.48 LF 8 PVC - -` S =00047 NEW SAN. SEWER - - EASEMENT I I NEW SS MH I RIM EL 29675' INV EL 291.92' (OUT) SHALLOW TYPE B �54'0) DETAIL I SHEET 2 INV EL 292.02 Ln 0 z r i S s a T M 0 N y 3" r 3m 3 n o� �P z n 3 i ®// 3 o LJ �N z� T� o a TYPICAL ROAD SECTION NO SCALE S-27046-? C Imo, JAMES E. HAYNES, P.E. 37234 22nd Ave So FEDERAL WAY, WA 98003 (253) 661 -6794 D D Z n D C ETi m Cr) D z -r- 00 zZ --I ° m N cn �m > _`= N 00 o� o 0 o\ Z" MIN COMPACTED DEPTH ASPHALT TRFATED BASE , 2" ,MIN DEPTH CLASS 3� (TOP COURSE �SPHAI.T CONCRETE (_ 6 "Mrnl COMPACTE=D DEPTH CRU5HED ' SURFACE BASE C vRSE -tzll� �z t 2% a TYPICAL ROAD SECTION NO SCALE S-27046-? C Imo, JAMES E. HAYNES, P.E. 37234 22nd Ave So FEDERAL WAY, WA 98003 (253) 661 -6794 D D Z n D C ETi m Cr) D z -r- 00 zZ --I ° m N cn �m > _`= N 00 o� o 0 o\ 60" ALLOWABLE MAX. EUR CAST IRON PIPE OR DUCTILE IRON PIPE, - cacrc BLOC V.Ir+G H,t - / l /N ZS 6- sloe I-11 TEE 6" NIN SEWER MAIN CONCRETE BLOCKING ANGLE OF TEE AT MAIN OVER 25 ELEVATION Ova ��p'F'CRLSL GO�___z% wu sLOPT HORIZONTAL ` SEWER MAIN TYPICAL SIDE SEWER ELEVATION 3/4" SQUARES SPACED - 3/4" AS INDICATED - HT. 1/8" EI T O❑)❑ RAISE -1/2" VIDE BORDER STANDARD SIDE SEWER INSTALLAF!ON 2 (SEWER MAIN TO PROPERTY LINE) CI CONCRETE I, °•• CLASS 3000 12" B FIBER JOINT PACKING 45 (I /e) BEND 0 m CAST IRON RING AND COVER —L MATERIAL AS SPECIFIED BY THE ENGINEER PLUG TO BE SEALED r -. -- IN SAME MANNER AS — MAIN SEWER JOINTS. 7 CD 3 6 INCH OR 8 INCH CLEAN -OUT �) CI Z Z I n ::1 0 RIM EL 2195.80 I $.p, O PROPOSED EXST GRADE GRAD[ I NE4.f 8:T - CLAN -OUT INV 293.2.0 Ift 1.11 44 414 S = 0.Oa43 4 +50 4+00 j LOT 1 \ 145IbE SEWER ,� EL /180,75 LF C900 LOT 3 SIDE SEWER ¢ ELr 293.18 — LO-T 2 SIDE SEWER qL EL a%=55 293.46 ,3+00 k j 4a, INV 292.44 +50 I ADJUSTING RINGS OR BLOCKS AS REQUIRED. 1 24' % 6' FRAME AND LOCKING L PER DRAWING BR29. -" " NIN. TO I2•• MX. PRECAST VALVE ``•,; CHAMBER CONE ADAPTOR COLLAR R.C.P. OR EQUAL B _ OR 12' I6° • RUBBER GASKET PIPE' ]I" NIN. TO 5" .D —L p • G ' NOTES: SANITARY SHALLOW MANHOLE TYPE B I. STEPS TO BE 3/4' 0 DEFORMED BAR GALVANIZED SAFTEY STEPS OR EQUAL •o•. 2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED 3. CASTING TO BE OLYMPIC FOUNDRY MH30 WITH MH30 O/T OR EQUAL. PER DWG. BR29 POURED IN PIKE BASE 4. MANHOLE SECTIONS TO AE OF REINFORCED PRECAST CONCRETE 5. OPENING SHOULD BE ON DOWNSTREAM SIDE. 6. ALL JOINTS SHALL BE GROUTED 1. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SANITARY EXTRA SHALLOW MANHOLE TYPE C SURFACES, INCLUDING CHANNELING, COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC- CONSEAL OR APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE. SANITARY MANHOLE DETAILS GI RIM EL 295,25 I NEW SS MH 2 I EXTRA SHALLOW I r TYPE C, LOT 4 i SIDE SEWER IL EL 292.40 I 81.50 LF 8° C900 5- •OQ3y e INV 292.34 Z +00 LOT 5 —y SIDE SEWER ELF a.9z.a3 2 SANITARY SEWER PROFILE SCALE; I "= 2.0.0' HORIZ• i " =2.0 VERT. M4 , MW Lm N_ O z Jill" a � Z Z m Lp In h I Fri D ' S Z J CL 1� O.. �I 1-300 TPROPERTY LINE o �a o• -o' nIN. 6-0•• FUTURE 6" BUILDING SEWER FIFE I _ _ _ __ _ BUILDING SEWER _ _— — a oe �2 "x 4" STUD SERVICE MARKER PAINT UPPER I " SIDE OUTLET -' 7SIDESEWER PORTION WHITE ANS STENCIL ON SIDE WARDING 'SEWER' WITH 3" HIGH BLACK LETTERS. mQ zj 6" AND BUILDING SEWER w of AND U6 WIRE WRAPPED AROUND THE STUD AND EXTENDED TO THE TOP OF THE STUD. a UNLESS OTHERWISE APPROVED DV THE CITY, MAKE YAP THROUGH CAST NN 0 IRON SADDLE SECURED TO SEWER MAIN WITH STAINLESS STEEL BANDS t RIM EL 6._75 WHEN CONNECTING NEW SIDE SEWERS -TD EXISTING MAIN. VITRIFIED CLAY, PLAiN AND REINFORCED CONCRETE, DI PIPE AND CI D m 0 PIPE SEWER MAINS ARE TO BE CORE DRILLED NOTE. UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEVEP. SHALL HAVE A MINIMUM 5' COVER AT PROPERTY LINE OR 3-5' LOWER THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER. 3/4" SQUARES SPACED - 3/4" AS INDICATED - HT. 1/8" EI T O❑)❑ RAISE -1/2" VIDE BORDER STANDARD SIDE SEWER INSTALLAF!ON 2 (SEWER MAIN TO PROPERTY LINE) CI CONCRETE I, °•• CLASS 3000 12" B FIBER JOINT PACKING 45 (I /e) BEND 0 m CAST IRON RING AND COVER —L MATERIAL AS SPECIFIED BY THE ENGINEER PLUG TO BE SEALED r -. -- IN SAME MANNER AS — MAIN SEWER JOINTS. 7 CD 3 6 INCH OR 8 INCH CLEAN -OUT �) CI Z Z I n ::1 0 RIM EL 2195.80 I $.p, O PROPOSED EXST GRADE GRAD[ I NE4.f 8:T - CLAN -OUT INV 293.2.0 Ift 1.11 44 414 S = 0.Oa43 4 +50 4+00 j LOT 1 \ 145IbE SEWER ,� EL /180,75 LF C900 LOT 3 SIDE SEWER ¢ ELr 293.18 — LO-T 2 SIDE SEWER qL EL a%=55 293.46 ,3+00 k j 4a, INV 292.44 +50 I ADJUSTING RINGS OR BLOCKS AS REQUIRED. 1 24' % 6' FRAME AND LOCKING L PER DRAWING BR29. -" " NIN. TO I2•• MX. PRECAST VALVE ``•,; CHAMBER CONE ADAPTOR COLLAR R.C.P. OR EQUAL B _ OR 12' I6° • RUBBER GASKET PIPE' ]I" NIN. TO 5" .D —L p • G ' NOTES: SANITARY SHALLOW MANHOLE TYPE B I. STEPS TO BE 3/4' 0 DEFORMED BAR GALVANIZED SAFTEY STEPS OR EQUAL •o•. 2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED 3. CASTING TO BE OLYMPIC FOUNDRY MH30 WITH MH30 O/T OR EQUAL. PER DWG. BR29 POURED IN PIKE BASE 4. MANHOLE SECTIONS TO AE OF REINFORCED PRECAST CONCRETE 5. OPENING SHOULD BE ON DOWNSTREAM SIDE. 6. ALL JOINTS SHALL BE GROUTED 1. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SANITARY EXTRA SHALLOW MANHOLE TYPE C SURFACES, INCLUDING CHANNELING, COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC- CONSEAL OR APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE. SANITARY MANHOLE DETAILS GI RIM EL 295,25 I NEW SS MH 2 I EXTRA SHALLOW I r TYPE C, LOT 4 i SIDE SEWER IL EL 292.40 I 81.50 LF 8° C900 5- •OQ3y e INV 292.34 Z +00 LOT 5 —y SIDE SEWER ELF a.9z.a3 2 SANITARY SEWER PROFILE SCALE; I "= 2.0.0' HORIZ• i " =2.0 VERT. M4 , MW Lm N_ O z Jill" a � Z Z m Lp In h I Fri D ' S Z J CL 1� O.. �I 1-300 INV EL 291,27 o �a I 3GO +z90 a oe � mQ zj oo N +29� NEW SS MH1 ( SHALLOW TYPE B (540) NN 0 �> t RIM EL 6._75 o I .294 D m 0 5=0.0047 L 136,48 LF 8' PVC +292 i Ci > r _ 0 -20.00 B INV 291.92 EXST SS NH 51 / INV 29� z 1 +50 r c INV EL 291,27 D +z90 :U -< C/) m = D m 0 +- 1 +00 + 0+50.00 0 +00 r _ 0 -20.00 B I- co O ti m z FM APPROVAL Qo N My / LwnBE27- 1 � 7 JAMES E. HAYNES, P.E. y 37234 22nd Ave So °- _..__,.,..._.,._._.__ FEDERAL WAY, WA 98003 , P z (253) 661 -6794 N a N 2-13 ; S- z�Q6o-� C�/J; S a7o6o z r c