0 5 10 20 40 60
SCALE IN FEET
WATER LAYOUT TABLE
STA
OFFSET LT
OFFSET RT
SIZE
42 +50
39.6'
--
12"
43 +00
40.3'
--
12"
43 +50
40.5'
--
12"
44+00
40.5'
--
12"
44+50
40.5'
--
12"
45 +00
40.5'
--
12"
WATER LEGEND
ABANDON OR REMOVE EXISTING WATER MAIN
a
w
x
°o
a
N
w
z
J
U
a
FURNISH AND INSTALL CLASS 52 DUCTILE IRON WATER PIPE. SEE WATER LAYOUT TABLE FOR STATION,
OFFSETS AND SIZE, THIS SHEET.
( FURNISH AND INSTALL GATE VALVE.
STA 43 +50.0, 40.5' LT
1 - 12" GATE VALVE, MAMJ
1D FURNISH AND INSTALL FIRE HYDRANT ASSEMBLY PER CITY OF RENTON STANDARD PLAN 310.1.
STA 43 +25.0, 52.0' LT
15 FURNISH AND INSTALL WATER SERVICE METER PER RENTON STD PLANS 320.1 - 320.3 AND CONNECT TO
EXISTING SERMCE UNE.
APPROXIMATE STA 43 +04.7, 52.4' LT APPROXIMATE STA 42 +25, 62.7' LT STA NOT PROVIDED
1 - 1" METER 1 - 1" METER FUTURE SERVICE LINE
1 - METER BOX 1 - METER BOX 1 - 1" METER
1 - METER BOX
APPROXIMATE STA 43 +79.2, 59.0' RT APPROXIMATE STA 43 +88.1, 59.0' RT
1 - 1" METER 1 - 1 1/2" METER
1 - METER BOX 1 - METER BOX
APPROXIMATE STA 43 +69.5, 605 LT APPROXIMATE STA 44 +58, 1 LT
1 - 1" METER 1 - 3/4" METER
1 - METER BOX 1 - METER BOX
33 FURNISH AND INSTALL LONG 1.5" METER CONNECTION AND REDUCE AT METER.
APPROXIMATE STA 43 +75, ADDED 4' SLEEVE
GENERAL WATER CONSTRUCTION NOTES
EXISTING WATER MAINS HYDRANTS, AND SERVICES SHALL REMAIN OPERATIONAL THROUGHOUT
THE COURSE OF CONSTRUCTION EXCEPT WHERE WATER BYPASS SYSTEMS ARE REQUIRED. FOR
INSTALLATION OF WATER BYPASS SYSTEMS SEE TEMPORARY WATER BYPASS PLANS, SHTS
160 -163. ABANDONMENT AND /OR REMOVAL OF EXISTING MAINS SHALL TAKE PLACE ONLY
AFTER THE NEW MAIN OR WATER BYPASS SYSTEM HAS BEEN INSTALLED, TESTED, AND
APPROVED BY THE CITY OF RENTON.
2. MAIN SHUTDOWNS SHALL BE BY CITY MAINTENANCE STAFF ONLY. CUT -IN CONNECTIONS TO
EXISTING MAINS SHALL ALSO BE PERFORMED BY CITY STAFF. CONTRACTOR SHALL PROVIDE
TWO WEEK ADVANCED NOTICE TO CITY FOR SCHEDULE OF CONNECTIONS AND SHUTDOWNS.
3. EXISTING SERVICE LINES, METER SETTERS, AND METER BOXES ARE TO BE REPLACED AS PART
OF THIS PROJECT. EXISTING METERS ARE TO BE RESET WITHIN THE NEW SETTERS. COORDINATE
W /CITY OF RENTON.
4. DEFLECT JOINTS AS NECESSARY TO INSTALL WATER MAIN WITH MINIMUM COVER ALONG THE
APPROXIMATE LOCATION SHOWN. PIPE JOINTS NOT TO EXCEED 50 PERCENT OF THE MAXIMUM
JOINT DEFLECTION SPECIFIED BY THE PIPE MANUFACTURER.
5. ABANDONED EXISTING WATER MAINS SHALL BE CAPPED WITH (MJ) CAPS. PORTIONS OF THE
ABANDONED WATER MAIN MAY REQUIRE REMOVAL FOR THE CONSTRUCTION OF OTHER ROADWAY
IMPROVEMENTS.
6. EXISTING FIRE HYDRANTS SHALL BE REMOVED AND PROPERLY DISPOSED OF BY THE
CONTRACTOR AFTER INSTALLATION, TESTING, AND APPROVAL OF THE NEW HYDRANTS.
7. VERIFY LOCATION AND DEPTH OF EXISTING WATER MAINS AT ALL CONNECTION POINTS PRIOR
TO CONSTRUCTION. THE CONTRACTOR SHALL FIELD VERIFY THE OUTSIDE DIAMETER (O.D.) OF
ALL EXISTING CAST -IRON AND ASBESTOS - CEMENT PIPES, AND PROVIDE THE PROPER
LONG -BODY ADAPTERS AND TRANSITION COUPLINGS FOR THE FINAL CONNECTIONS BY CITY
FORCES. CONNECTIONS TO ALL DUCTILE IRON PIPES SHALL BE MADE WITH LONG SOLID SLEEVE
COUPLINGS (MJ).
8. ALL CONNECTIONS TO EXISTING WATER ONES SHALL BE MADE ONLY AFTER ALL THE NEW
WATER ONES AND APPURTENANCES HAVE SUCCESSFULLY PASSED ALL PRESSURE TESTS,
CLEANED WITH POLY -PIGS, DISINFECTED WITH CHLORINE SOLUTION, AND HAVE RECEIVED
SATISFACTORY BACTERIOLOGICAL TEST LAB REPORTS, AND ARE THOROUGHLY FLUSHED.
9. ELEVATIONS OF EXISTING CROSSING UTILITIES ARE PARTIALLY BASED ON RECORD DRAWING
INFORMATION. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL UNDERGROUND EQUIPMENT
PRIOR TO CONSTRUCTION AND INFORM THE ENGINEER IF CONFLICT IS FOUND.
10. ALL WATER MAINS, FITTINGS, AND APPURTENANCES SHALL BE INSTALLED PER CITY OF RENTON
STANDARD DETAILS INCLUDED WITH PROJECT SPECIFICATIONS.
11. WATER PIPE AND FITTINGS INDICATED ON PLANS SHALL HAVE RESTRAINED JOINTS PER
SPECIFICATIONS SEE WATER PLANS, SHTS 132 -141 AND WATER PROFILES, SHTS 146 -159 FOR
THESE LOCATIONS.
12. PROVIDE 10' HORIZONTAL SEPARATION FROM PARALLEL SEWER ONES. WATER SHALL CROSS
OVER EXISTING SEWER WITH 18" MINIMUM VERTICAL SEPARATION. WATER SHALL CROSS ALL
OTHER UTILITIES WITH 12" MINIMUM VERTICAL SEPARATION. CONCRETE ENCASEMENT MAY BE
NECESSARY WHERE THESE REQUIREMENTS CANNOT BE MET.
13. ALL WATER MAIN VERTICAL BENDS SHALL INCLUDE VERTICAL THRUST BLOCKING PER RENTON
PLAN 330.3. ALL WATER MAIN HORIZONTAL BENDS SHALL INCLUDE HORIZONTAL THRUST
BLOCKING PER RENTON PLAN 330.2.
SHEETS
CATEGORY
SHEET
RIGHT OF WAY PLANS
15
EXISTING CONDITIONS
63
SITE PREPARATION & TESC PLAN
77
ALIGNMENT PLAN
89
ALIGNMENT PROFILE
101
DRAINAGE PLAN
112
DRAINAGE PROFILE
123
WATER PLAN
-
WATER PROFILE
154
JOINT UTILITY TRENCH PLAN
172
JOINT UTILITY TRENCH PROFILES
188
PROPERTY RESTORATION PLANS
203
CHANNEUZATION & SIGNING PLAN
225
ILLUMINATION PLANS
236
IRRIGATION PLAN
290
LANDSCAPE PLAN
302
rzCwrzU UKARINU3
aLr
UPT
I
SURVEYED. HPc
DRAWN BY So0 /KH
DESIGN DV. soDrKH
CHECK BY dLE
PFE MCIY. M
EiLe a�rnvem�.aa
?I RECORD
79BWbrueN 25IQJdiaamArmm
Batlb,WABM4B Tmim,WA9BVQ DRAWINGS
INCA VA�1� DRAWINGS
Aw. mn
b6
All
CITY OF RENTON
"N P�eu�wo,ks DaPaamam
APPROVED FOR CONSTRUCTION
BY DATE
RAINIER AVENUES (SR 167)
S GRADY WAY TO S 2ND ST
WATERPLAN
STA 42 +00 TO STA 45 +00
DRAWING NC. 140
PROJECT NO TEDaoaao
EEDAiD no. cMO s7
DATE MAR 2014
SHEET NO. iao OF aoa
NUMBER
REVISION DescawnoN
Dv
APP.
DATE