HomeMy WebLinkAboutW-343025GRADY WAY WATER MAIN CROSSING PROFILE -RAINIER AVE S STA 11 +30
HARDIE AVE SW WATER MAIN CROSSING PROFILE - RAINIER AVE S STA 15+90
GENERAL WATER CONSTRUCTION NOTES
1. EXISTING WATER MAINS, HYDRANTS, AND SERVICES SHALL REMAIN OPERATIONAL THROUGHOUT
THE COURSE OF CONSTRUCTION EXCEPT WHERE WATER BYPASS SYSTEMS ARE REQUIRED. FOR
INSTALLATION OF WATER BYPASS SYSTEMS SEE TEMPORARY WATER BYPASS PLANS, SHTS
160 -163. ABANDONMENT AND /OR REMOVAL OF EXISTING MAINS SHALL TAKE PLACE ONLY
AFTER THE NEW MAIN OR WATER BYPASS SYSTEM HAS BEEN INSTALLED, TESTED, AND
APPROVED BY THE CITY OF RENTON.
2. MAIN SHUTDOWNS SHALL BE BY CITY MAINTENANCE STAFF ONLY. CUT —IN CONNECTIONS TO
EXISTING MAINS SHALL ALSO BE PERFORMED BY CITY STAFF. CONTRACTOR SHALL PROVIDE
TWO WEEK ADVANCED NOTICE TO CITY FOR SCHEDULE OF CONNECTIONS AND SHUTDOWNS.
3. EXISTING SERVICE UNES, METER SETTERS, AND METER BOXES ARE TO BE REPLACED AS PART
OF THIS PROJECT. EXISTING METERS ARE TO BE RESET WITHIN THE NEW SETTERS. COORDINATE
W /CITY OF RENTON.
4. DEFLECT JOINTS AS NECESSARY TO INSTALL WATER MAIN WITH MINIMUM COVER ALONG THE
APPROXIMATE LOCATION SHOWN. PIPE JOINTS NOT TO EXCEED 50 PERCENT OF THE MAXIMUM
JOINT DEFLECTION SPECIFIED BY THE PIPE MANUFACTURER.
5. ABANDONED EXISTING WATER MAINS SHALL BE CAPPED WITH (MJ) CAPS. PORTIONS OF THE
ABANDONED WATER MAIN MAY REQUIRE REMOVAL FOR THE CONSTRUCTION OF OTHER ROADWAY
IMPROVEMENTS.
6. EXISTING FIRE HYDRANTS SHALL BE REMOVED AND PROPERLY DISPOSED OF BY THE
CONTRACTOR AFTER INSTALLATION, TESTING, AND APPROVAL OF THE NEW HYDRANTS.
7. VERIFY LOCATION AND DEPTH OF EXISTING WATER MAINS AT ALL CONNECTION POINTS PRIOR
TO CONSTRUCTION. THE CONTRACTOR SHALL FIELD VERIFY THE OUTSIDE DIAMETER (O.D.) OF
ALL EXISTING CAST —IRON AND ASBESTOS— CEMENT PIPES, AND PROVIDE THE PROPER
LONG —BODY ADAPTERS AND TRANSITION COUPLINGS FOR THE FINAL CONNECTIONS BY CITY
FORCES. CONNECTIONS TO ALL DUCTILE IRON PIPES SHALL BE MADE WITH LONG SOLID SLEEVE
COUPUNGS (MI
B. ALL CONNECTIONS TO EXISTING WATER UNES SHALL BE MADE ONLY AFTER ALL THE NEW
WATER UNES AND APPURTENANCES HAVE SUCCESSFULLY PASSED ALL PRESSURE TESTS,
CLEANED WITH POLY —PIGS, DISINFECTED WITH CHLORINE SOLUTION, AND HAVE RECEIVED
SATISFACTORY BACTERIOLOGICAL TEST LAB REPORTS, AND ARE THOROUGHLY FLUSHED.
9. ELEVATIONS OF EXISTING CROSSING UTIUTIES ARE PARTIALLY BASED ON RECORD DRAWING
INFORMATION. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL UNDERGROUND EQUIPMENT
PRIOR TO CONSTRUCTION AND INFORM THE ENGINEER IF CONFLICT IS FOUND.
10. ALL WATER MAINS FITTINGS, AND APPURTENANCES SHALL BE INSTALLED PER CITY OF RENTON
STANDARD DETAILS INCLUDED NTH PROJECT SPECIFICATIONS.
11. WATER PIPE AND FITTINGS INDICATED ON PLANS SHALL HAVE RESTRAINED JOINTS PER
SPECIFICATIONS. SEE WATER PLANS, SHTS 132 -141 AND WATER PROFILES, SHTS 146 -159 FOR
THESE LOCATIONS.
12. PROVIDE 16 HORIZONTAL SEPARATION FROM PARALLEL SEWER UNES. WATER SHALL CROSS
OVER EXISTING SEWER WITH 18" MINIMUM VERTICAL SEPARATION. WATER SHALL CROSS ALL
OTHER UTIUTIES WITH 12" MINIMUM VERTICAL SEPARATION. CONCRETE ENCASEMENT MAY BE
NECESSARY WHERE THESE REQUIREMENTS CANNOT BE MET.
13. ALL WATER MAIN VERTICAL BENDS SHALL INCLUDE VERTICAL THRUST BLOCKING PER RENTON
PLAN 330.3. ALL WATER MAIN HORIZONTAL BENDS SHALL INCLUDE HORIZONTAL THRUST
BLOCKING PER RENTON PLAN 330.2.
0 5 10 20 40 60
HORIZONTAL SCALE IN FEET
VERT. SCALE =1 2 HORIZ. SCALE
rzCww VrznrviNw
I JLr
i JMr
i
SURVEYED. HPc
DRAWN BY SOD
KpG
All CITY OF RENTON
RAINIER AVENUES (SR 167)
DRAWING NO
156
u
S GRADY WAY TO S 2ND ST
PROJECT NO
TEDaoaass
DesicN SY. so0
79BNkmxN
@SPdJdietmAUnu
RECORD
P�eu�wo,ks Department
CHECK BY NJD
uetlgWABbIDB
Tpm,WABBVQ
DRAWINGS
DRAWINGS
WATER PROFILE
EEDAiO no.
cMSs7
�Mp
VA6Q7
APPROVED FOR CONSTRUCTION
DATE
MAR 2014
PROD MCIY. JE
w¢Ypg mn
GRADY WAY AND HARDIE AVE SW CROSSINGS
SHEET NO.
iss of aoa
NUMBER
REVISION DESCRIPTION
sv
APP.
DATE
EiLe O�UVATPFNt.Mq
DY. DATE.