Loading...
HomeMy WebLinkAboutW-343026EXISTING SURFACE ELEVATION ............. ............................:.. EX. 12° STORM DRAIN. IE UNK AVE S JOINTS SW 7TH WATER MAIN CROSSING PROFILE - RAINIER AVE S STA 22+40 CONNECTION TO RAINIER AVE S, TO EAST SIDE OF ................. .AVE . S, . SEE SHT 149 ..................... JOINTS .............................................. ..............................: 1� STIX2M DRAIN EX. TELE. COSM. & POWER, INV. UNK. IE 30.8 CONTE. TO VERIFY LOCATION & DEPTH ...................... ............................... : .EX�: �GA5;.. fNU: �liNK :......... ..............................: CONTR. TO VERIFY LOCATION & DEPTH E%. WATER ;TO BE REMOVED CONTR. TO:VERIFY LOCATION & DEPTH . ............................... ............: ............................... GROUND POWER, INV. UNK. VERIFY LOCATION & DEPTH ......... ............................... r ........... .... ... .... . .... ............................... EXISTING SURFACE ELEVATION : RESTRAINED JOINTS H RAINIER AVE S STA NOT PROVIDED CONNECTION TO S 4TH PL ........... ..............................: S STA 34 +210 UNK LF 12" DI WATER PIPE TO WEST SIDE OF RAINIER AVE S. SEE SHT 152 GENERAL WATER CONSTRUCTION NOTES 1. EXISTING WATER MAINS, HYDRANTS, AND SERVICES SHALL REMAIN OPERATIONAL THROUGHOUT THE COURSE OF CONSTRUCTION EXCEPT WHERE WATER BYPASS SYSTEMS ARE REWIRED. FOR INSTALLATION OF WATER BYPASS SYSTEMS SEE TEMPORARY WATER BYPASS PLANS, SHTS 160 -163. ABANDONMENT AND /OR REMOVAL OF EXISTING MAINS SHALL TAKE PLACE ONLY AFTER THE NEW MAIN OR WATER BYPASS SYSTEM HAS BEEN INSTALLED, TESTED, AND APPROVED BY THE CITY OF RENTON. 2. MAIN SHUTDOWNS SHALL BE BY CITY MAINTENANCE STAFF ONLY. CUT —IN CONNECTIONS TO EXISTING MAINS SHALL ALSO BE PERFORMED BY CITY STAFF. CONTRACTOR SHALL PROVIDE TWO WEEK ADVANCED NOTICE TO CITY FOR SCHEDULE OF CONNECTIONS AND SHUTDOWNS. 3. EXISTING SERVICE UNES, METER SETTERS, AND METER BOXES ARE TO BE REPLACED AS PART OF THIS PROJECT. EXISTING METERS ARE TO BE RESET WITHIN THE NEW SETTERS. COORDINATE W /CITY OF RENTON. 4. DEFLECT JOINTS AS NECESSARY TO INSTALL WATER MAIN WITH MINIMUM COVER ALONG THE APPROXIMATE LOCATION SHOWN. PIPE JOINTS NOT TO EXCEED 50 PERCENT OF THE MAXIMUM JOINT DEFLECTION SPECIFIED BY THE PIPE MANUFACTURER. 5. ABANDONED EXISTING WATER MAINS SHALL BE CAPPED WITH (MJ) CAPS. PORTIONS OF THE ABANDONED WATER MAIN MAY REQUIRE REMOVAL FOR THE CONSTRUCTION OF OTHER ROADWAY IMPROVEMENTS. 6. EXISTING FIRE HYDRANTS SHALL BE REMOVED AND PROPERLY DISPOSED OF BY THE CONTRACTOR AFTER INSTALLATION, TESTING, AND APPROVAL OF THE NEW HYDRANTS. 7. VERIFY LOCATION AND DEPTH OF EXISTING WATER MAINS AT ALL CONNECTION POINTS PRIOR TO CONSTRUCTION. THE CONTRACTOR SHALL FIELD VERIFY THE OUTSIDE DIAMETER (O.D.) OF ALL EXISTING CAST —IRON AND ASBESTOS— CEMENT PIPES, AND PROVIDE THE PROPER LONG —BODY ADAPTERS AND TRANSITION COUPLINGS FOR THE FINAL CONNECTIONS BY CITY FORCES. CONNECTIONS TO ALL DUCTILE IRON PIPES SHALL BE MADE WITH LONG SOLID SLEEVE COUPLINGS (MJ). 8. ALL CONNECTIONS TO EXISTING WATER ONES SHALL BE MADE ONLY AFTER ALL THE NEW WATER ONES AND APPURTENANCES HAVE SUCCESSFULLY PASSED ALL PRESSURE TESTS, CLEANED WITH POLY —PIGS, DISINFECTED WITH CHLORINE SOLUTION, AND HAVE RECEIVED SATISFACTORY BACTERIOLOGICAL TEST LAB REPORTS, AND ARE THOROUGHLY FLUSHED. 9. ELEVATIONS OF EXISTING CROSSING UTIUTIES ARE PARTIALLY BASED ON RECORD DRAWING INFORMATION. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL UNDERGROUND EQUIPMENT PRIOR TO CONSTRUCTION AND INFORM THE ENGINEER IF CONFLICT IS FOUND. 10. ALL WATER MAINS, FITTINGS, AND APPURTENANCES SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAILS INCLUDED NTH PROJECT SPECIFICATIONS. 11. WATER PIPE AND FITTINGS INDICATED ON PLANS SHALL HAVE RESTRAINED JOINTS PER SPECIFICATIONS. SEE WATER PLANS, SHTS 132 -141 AND WATER PROFILES, SHTS 146 -159 FOR THESE LOCATIONS. 12. PROVIDE 10' HORIZONTAL SEPARATION FROM PARALLEL SEWER LINES. WATER SHALL CROSS OVER EXISTING SEWER WITH 1B* MINIMUM VERTICAL SEPARATION. WATER SHALL CROSS ALL OTHER UTIUTIES WITH 12' MINIMUM VERTICAL SEPARATION. CONCRETE ENCASEMENT MAY BE NECESSARY WHERE THESE REQUIREMENTS CANNOT BE MET. 13. ALL WATER MAIN VERTICAL BENDS SHALL INCLUDE VERTICAL THRUST BLOCKING PER RENTON PLAN 330.3. ALL WATER MAIN HORIZONTAL BENDS SHALL INCLUDE HORIZONTAL THRUST BLOCKING PER RENTON PLAN 330.2. S 4TH PL WATER CONNECTION - RAINIER AVE S STA 34 +20 STA 28 +60 WATER CONNECTION 0 5 10 20 40 60 HORIZONTAL SCALE IN FEET VERT. SCALE =1 2 HORIZ. SCALE RECORD DRAWINGS I JLF I JAF 13/2014 1 1 Or RVFYFD. KPc DRAWN BY SOD DESIGN BY SOD CHECK BY NJD PROJ MCIY. JF FlLE. 0655GWATPFN1.Mq KpG ?MlhkI eN 75PtJMmmAUnu RECORD Batlb,W1BB14B TpYIq WAS DRAWINGS 2014W V46Q7 DRAWINGS w¢Ypg mn All CITY OF RENTON "N P�eu�wo,ks DaPaamam APPaoveo FOR comsTaucTiom BY. DATE. RAINIER AVENUES (SR 167) S GRADY WAY TO S 2ND ST WATER PROFILE SW 7TH ST AND STA 28 +60 CROSSINGS DeAwwc NC. PROJECT NO FEDADIJD. DATE SHEET NO. 157 TEDaoaas -0M0 8) MAR 2014 iss of aoa NUMBER REVISION DEBGRIPTION BY APP. DATE