MANHOLE FRAME AND COVER
SEE STD. PLAN 401
ADJUSTMENT RINGS (2- MIN.)
SEE NOTE 6
MORTAR JOINTS) (3/8- WIN.)
SEE NOTE 5
CONE (ECCENTRIC)
RUBBER GASKETED JOINTS IN
ACCORDANCE WITH ASTM C-443
STEPS - POLYPROPYLENE STEPS
SHALL BE INCLUDED
CONCRETE RISER BY PIPE INC.,
OR APPROVED EQUAL.
LADDER -POLYPROPYLENE
SHALL BE ATTACHED TO MANHOLE
MAX. PIPE SIZE - 'E'
CONCRETE SHELF
PRECAST BASE SECTION
OR CAST IN SHELF.
I NOT TO SCALE
*A# tBl Ict 4DP tEr
48" MH 480 6" MIN. 5"MIN 24" MIN. 21" 1. D,
54" WH 54" 8" MIN. 5.5" WN. 24" MIN. 24" I.D.
L 60" MH 60" 8" MIN. 6" MIN. 1 42" MIN. 1 30" I.D.
NOTES:
1. STEPS TO BE POLYPROPYLENE SAFETY STEPS.
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS ARE INSTALLED.
3. CASTING SHALL BE PER STD. PLAN 401.
4. MANHOLE SECTIONS TO BE OF REIWORCED PRECAST CONCRETE.
5. ALL JOINTS BETWEEN THE CONE, RISER RINGS, BRICKS AND CASTING SHALL BE GROUTED.
6. ADJUSTMENT OF THE CASTING TO GRADE SHALL BE ACCOMPLISHED MOTH A COMBINATION OF
ADJUSTMENT RINGS, BRICKS AND MORTAR ONLY, BRICKS SHALL BE STAGGERED TO CREATE A RUNNING
BOND OR 1/2 BOND. THE USE QE SbJMS IS ERON&MD
7. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR SURFACES, INCLUDING CHANNELING,
COATED (SEALED) WITH A HIGH SOLIDS URETHANE COATING; WASSER MC-AROSHIELD OR
APPROVED EQUAL; COLOR OF COATING SHALL BE WHITE.
8. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE WITH ASTM C-443.
9. CHANNEL HEIGHT SHALL BE A MINIIMUM OF 3/4 OF THE INSIDE DIAMETER OF THE LARGEST PIPE.
10. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK ADAPTOR, KOR-N-SEAL BOOTS OR
APPROVED EQUAL.
11. IN UNIMPROVED AREAS, MANHOLES SHALL EXTEND A MINIMUM OF 6" AND A MAX*" OF 12"
ABOVE FHSHED GRADE OR MUST HAVE A MINIMUM 2$ DIAMETER CONCRETE RINGS POURED AT GRADE.
IN PAVED AREAS, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING.
PUBLIC WORKS on. PLO - 400.1
+
+ DEPARTMENT STAPODAMO SANITARY &A ,11111404MFE
SEPTMER 2011
[- W (SEE NOTE 7)
BEDDING MATERIAL FOR
SANITARY SEWER PIPE
(SEE NOTE 5)
FOUNDATION LEVEL
LIMITS OF PIPE ZONE
1 J Oto
O.D. OF PIPE
6
BEDDING FOR SANITARY SEWER PIPE
NLDTES
1. PROVIDE UNIFORM SUPPORT UNDER BARREL.
2. HAND TAMP UNDER HAUNCHES.
3. COMPACT BEDDING MATERIAL TO 95% MAX. DENSITY EXCEPT DIRECTLY
OVER PIPE. HAND TAMP ONLY.
4. PIPE INSTALLATION SHALL BE PER SECTION 7-08 OF THE
STANDARD SPECIFICATIONS.
5. PIPE ZONE MATERIAL SHALL BE "GRAVEL BACKFILL FOR DRAINS"
AS SPECIFIED IN THE AGGREGATES SECTION OF THE STANDARD
SPECIFICATIONS OR PEA GRAVEL.
6. PIPE MUST BE ANCHORED IN SUCH A MANNER AS TO ENSURE FLOW
LINE IS MAINTAINED.
7. TRENCH WIDTH SHALL BE PER SECTION 2-09.4 OF THE
STANDARD SPECIFICATIONS.
PUBLIC WORKS P1101% imam"66 M. PUN - 4"
DEPARTMENT FOR SANITAMtY SEARS OCTOBER 2012
t�LAM CRE�C PUD
A PORTION OF K 1/4 IN 1/4 lECTI011 10 Toftw�wr 23 IL �uwoE 5 E09
TE Yo W TON
NOM MD DUALS LUA v 06 067 I a
BOLTHOLES - 3 PLCS
EQUALLY SPACED 120*
APART ON 23 1/16' (586mm)
TITA R.C. (-wF nF-TAIL)
RENTON'
SEWER
COVER & FRAME
PLAN VIEW
25' DIA,
E635mml
3/4' 5mml
El9mml
8 3/4' t 2 1/2'
1222mml 164mml
TYP
COVER SECTION VIEW
26 1/2' DIA
1673mml
25 1/4' DIA
[641mml 1 1/16'
F1/4' (E +) DIA (27mm1
NEOPRENE GASKET
61
1152mml
23 3/8' -DIA CL OPEN
116MMI 1594mml
27 5/16' DIA
1694mml
34 1/8' DIA
COVER BOTTOM VIEW
(3) BLT SOC, (ALLEN HEAD)
5/8'-11 X 1.5 SS
RUBBER WASHER
1/4* 1 1/16'
[27mml
E3ml
ER3mml
"SKET GROOVE DETAIL
U5b /M"j NOTES:
FRAC SECTION VlEW 1. ALL COVERS SHALL BE LOCKING LID PER EAST
JORDAN IRON WORKS INC. No. 371701 OR EQUAL.
2. USE FRAME AND COVER FOR STORM (SPECIFY
"DRAIN" ON COVER). SANITARY (SPECIFY
"SEWER"), OR WATER (SPECIFY Itt WATER").
+
PUBJIC WORKS LR 9M. PLAN - 401
+ DEPARTMENT KAAIK AA4D
DECEMBER 2008
12 h"
14"
2
RECESSED
LIFT POCKET
%" - 11 N,C. SOCKET HD
SCREW 1 A4" LONG
(BRONZE OR S.S.)
X" x 2" RAISED PADS
11M» At
12
14"
CAST IRON RING AND COVER
2" A.C.
I _L
6" CONCRETE
CLASS 3000
45- (1 /8) BEND
45- (1/8) BEND
"&Iwiffi
SAND OR
EXPANDABLE
FOAM
WATER TIGHT
PLUG
PIPE MATERIAL AS SPECIFIED
BY THE ENGINEER
NOTES:
1. 8` AND 6" CLEANOUTS ON SEWER MAINS SHALL BE EAST JORDAN IRON WORKS, INC.
No. 3698 OR EQUAL. CLEAN OUT SHALL BE A WATER TIGHT ASSEMBLY.
2. IN UNIMPROVED AREAS, POUR A l' -O" THICK, 2"-0" SQUARE
CONCRETE, CLASS 3000, PAD AROUND THE RING AND COVER.
PUBLIC WORKS IB OR 6 INCH CL iT M. PEM - 408.1
DEPARTMENT FOR SAMITAItY SL"ARM SEPTE R 2011
HORIZONTAL
6" SIDE OUTLET TEE
SEWER
6" MIN, MAIN SEWER MAIN
CONCRETE BLOCKING ANGLE TYPICAL 511)E S&W.R ELEvA-nON
QE TEE AT MAIN OVER 25
ELEVAIM
NOTE:
UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEVER SHALL HAVE
A MINIMUM 2.5' COVER AT PROPERTY LINE OR 3-5' LOWER
THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER.
'y STA QAR0 Sam swv*un MD. PLAN - 4".1
+
PUBLIC WORKS WMTAAJLATS"
DEPARTMENT
R NL%M TO KTY Lum) JANUARY 2013
A
m
SEA! W-TH AR 4000 OR APPROVED
EOVAL AND DRY SAND AFTER
PATCHiNG
PATCHED AREA
PLAN
NTS
A
DEPTH OF CLASS *8"
ASPHALT TO BE 2" BELOW
BOTTOM OF THE UPPER
ADJUSTMENT RING OR A
MINIMUM OF 8** WHICHVER
IS GREATER.
Af
V-4
MORTAR i O,INT(S) (3/8" M N SEE AUoiUSTMENT RING (1„ 1414.) OR
NOTE 3 AND SPECIAL PROVISO BRICKS. SEE NOTE 4
S C _7 ON A --A
. ... ......... .. . ..
N.QTEJ
1, REMOVE PAVEMENT AND BASE MATERIALS FOR A DISTANCE 3 ALL JONYS WTWMN THE COME, ADJUSTIMENT WNW,
WHICH IS EQUAL TO THE 0"415TER OF THE FRAME PLUS FOUR 8110ICKS AND FOAM SHALL BE GPKXffW
FEET. ADJUST CASTING FPAW TO PAVEMENT SURFACE
US040 RISER RWW OR CONCRETE BLOCKS PER STO. PLAN 4 A"JSTMEW OF THE FK#AiE TO OR40E SHALL ME
400.1. ACrA*AlLN**D VM A COMIMATION OF ADANTWNT
RINW, &MO AND MORTM Y. BNOM SHALL ME
2. REPLACE EXCAVATED MATERIAL WITH A MINkUM OF 8* OF STAGOOM TO COWATE A RLMOIG BOND OR 112 MOND TW
CLASS 'SASPHALT OR TO A DIED THAT IS 2* BELOW THE mm. n.
BOTTOM OF THE U~ ADJUSTMENT RING WHICHEVER IS
GREATER OR AS APPWVED BY THE ENGINEER.
SM. MM - 4W4
I VPPICAL UTUar" ............. . .... . ..
PUBLIC WORKS
DEPARTMENT
�►
OK
SMUMY SEWO MOTU
l. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE NTH THE STANDARDS AND SPECIFICATIONS
OF THE CITY OF RENTON PLANMNG/MDlNG/P0BlJC WORKS DEPARTMENT AND THE LATEST EDITION OF
THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF
RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE
KEPT ON SITE AT ALL TKS DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON WEKDAYS
UNLESS OTHERWISE APPROVED IN WRlTlNG BY THE PLANNlNG/8ULDING/PL8JC WORKS DEPARTMENT. AN
APPROVED TRAFFIC CONW PLAN MUST BE OBTAINED PRIOR TO BEONNING ANY WORK WITHIN PUBLIC
RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILlTIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S
RE90MUTY TO VERIFY THE W AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR
DISTURBANCE.
4. A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING
NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSOUTY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WALL BE ACCMUSHM BY A REPRESENTATIVE
OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RET04MUTY TO NOTIFY THE PUBLIC
WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSELE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION
AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND MY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE
OVER ALL OTHER PLANS.
8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN
PROGRESS.
9. THE CONTRACTOR SHALL PROINVIDE THE CITY OF RENTON NTH AN AS -BUILT DRAWING OF THE SANITARY
SEAR SYSTEM, WHICH HAS BEEN STAMPED AND SOO BY A LICENSED PROFESSIONAL ENGINEER OR
LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL. BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS NTH A LOOSE AVERAGE
DEPTH OF 6 WKS, MAA" DEPTH OF 8 WKS, THOROUGHLY TAMPING EACH LAYER TO 95
PERCENT OF MAW" DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON
EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER
PIPE SHALL BE THE SAME AS DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED NTH CRUSHED ROCK AND MEDiANICALLY COMPACTED LWLESS OTHERWISE APPROVED.
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR
HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE
APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE BENCHMARK AND
ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON-SITE EROSION AFTER THE COMPLETION
OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE NTH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLAM"/WUWMA*JC WOWS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA
STANDARDS AND SPECFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON
STANDARD PLANS & SPECIFICATIONS. THIS SHALL NCLUDE NECESSARY LEVELING OF THE TRENCH
BOTTOM OR THE TOP OF THE FOLINDATION MATERIAL, AS HELL AS PLACEMENT AND COMPACTION OF
REQUIRED BEDDING MATERIAL, TO LWORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WALL BE
SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6 INCHES
ABOVE AND BELOW THE PIPE.
15. SANITARY SEVER PIPE SHALL BE POLYMNYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35,
OR DUCTILE IRON WM 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER UTILITY.
16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MUMUM 6 INCHES AND MAX" 12 INCHES ABOVE
FINISHED GRADE OR MUST HAVE MNM 2DWETER CONCRETE RING POURED AT GRADE.IN PAVED
AREA, COWER MUST SLOPE IN ALL DIRECTIONS TO MATCH PANG.
C t),
CALL 48 HOURS
BEFORE YOU DIG
DIAL 811
00
C)
>
PROPERTY LINE
z
1
3
30-0**
o
FUTURE
6" BUILDING SEWER PIPE
BUILDING SEWER
PAINTED
,TEE VATH 6" SIDE OUTLET
2"x 4" STUD MARKING POST
6")(6"X6" WYE WHITE VlATlH THE WORD "SEWER" STENCILED
SURFACE CLEANOUT WITH IN 3" HIGH BLACK LETTERS AND #6 WIRE
cr CAST IRON MG & COVER
(EAST JORDAN VtON WORKS WRAPPED AROUND THE STUD AND
EXTENDED TO THE TOP OF THE STUD.
2975 OR APPROVED EQUAL,
CL SPECIFY "SEWER" ON LID,
SEE STD. PLAN 403.1 FOR
6" SIDE SEVER AND BUILDING SEWER
INSTALLATION)
ACCEPTABLE PROCEDURES FOR SIDE SEWER CONWC'RONS TO MAIN
LINES ARE AS FOLLOWS:
A. \ATRInED CLAY MAIN - CUT IN A NEW SECTION OF SEVER MAIN WITH
A NEW TEE USING FLEXIBLE COUPL04GS
(FERNCO OR APPROVED EQUAL).
B. CONCRETE MAIN - CUT IN A NEW SECTION OF SEWER MAIN VATH
A NEW TEE USING FLEXIBLE COUPLINGS
(FERNCO OR APPROVED EQUAL),
C. PVC MAIN - CORE -DRILLED MATH A ROMAC SADDLE (OR APPROVED
EQUAL) OR CUT IN A NEW TEE USING RIM COUPLINGS.
D. DUCTILE IRON MAIN - CORE -DRILLED WITH A ROMAC SADDLE (OR
APPROVED EQUAL)
E. MANHOLE CONNECTION - ALL CONNECTIONS TO MANHOLES SHALL BE
AT MANUFACTURED KNOCK -OUTS OR THE
STRUCTURE SHALL BE CORE -DRI -LED.
60" ALLOWABLE MAX.
FOR CAST IRON PIPE
OR DUCTILE IRON PIPE.
1: 3:5 MIX
CONCRETE
BLOCKING ,�� 25
'�, ��,P '. '�'`'
2% IN SLOE
HORIZONTAL
6" SIDE OUTLET TEE
SEWER
6" MIN, MAIN SEWER MAIN
CONCRETE BLOCKING ANGLE TYPICAL 511)E S&W.R ELEvA-nON
QE TEE AT MAIN OVER 25
ELEVAIM
NOTE:
UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEVER SHALL HAVE
A MINIMUM 2.5' COVER AT PROPERTY LINE OR 3-5' LOWER
THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER.
'y STA QAR0 Sam swv*un MD. PLAN - 4".1
+
PUBLIC WORKS WMTAAJLATS"
DEPARTMENT
R NL%M TO KTY Lum) JANUARY 2013
A
m
SEA! W-TH AR 4000 OR APPROVED
EOVAL AND DRY SAND AFTER
PATCHiNG
PATCHED AREA
PLAN
NTS
A
DEPTH OF CLASS *8"
ASPHALT TO BE 2" BELOW
BOTTOM OF THE UPPER
ADJUSTMENT RING OR A
MINIMUM OF 8** WHICHVER
IS GREATER.
Af
V-4
MORTAR i O,INT(S) (3/8" M N SEE AUoiUSTMENT RING (1„ 1414.) OR
NOTE 3 AND SPECIAL PROVISO BRICKS. SEE NOTE 4
S C _7 ON A --A
. ... ......... .. . ..
N.QTEJ
1, REMOVE PAVEMENT AND BASE MATERIALS FOR A DISTANCE 3 ALL JONYS WTWMN THE COME, ADJUSTIMENT WNW,
WHICH IS EQUAL TO THE 0"415TER OF THE FRAME PLUS FOUR 8110ICKS AND FOAM SHALL BE GPKXffW
FEET. ADJUST CASTING FPAW TO PAVEMENT SURFACE
US040 RISER RWW OR CONCRETE BLOCKS PER STO. PLAN 4 A"JSTMEW OF THE FK#AiE TO OR40E SHALL ME
400.1. ACrA*AlLN**D VM A COMIMATION OF ADANTWNT
RINW, &MO AND MORTM Y. BNOM SHALL ME
2. REPLACE EXCAVATED MATERIAL WITH A MINkUM OF 8* OF STAGOOM TO COWATE A RLMOIG BOND OR 112 MOND TW
CLASS 'SASPHALT OR TO A DIED THAT IS 2* BELOW THE mm. n.
BOTTOM OF THE U~ ADJUSTMENT RING WHICHEVER IS
GREATER OR AS APPWVED BY THE ENGINEER.
SM. MM - 4W4
I VPPICAL UTUar" ............. . .... . ..
PUBLIC WORKS
DEPARTMENT
�►
OK
SMUMY SEWO MOTU
l. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE NTH THE STANDARDS AND SPECIFICATIONS
OF THE CITY OF RENTON PLANMNG/MDlNG/P0BlJC WORKS DEPARTMENT AND THE LATEST EDITION OF
THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF
RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE
KEPT ON SITE AT ALL TKS DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON WEKDAYS
UNLESS OTHERWISE APPROVED IN WRlTlNG BY THE PLANNlNG/8ULDING/PL8JC WORKS DEPARTMENT. AN
APPROVED TRAFFIC CONW PLAN MUST BE OBTAINED PRIOR TO BEONNING ANY WORK WITHIN PUBLIC
RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILlTIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S
RE90MUTY TO VERIFY THE W AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR
DISTURBANCE.
4. A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING
NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSOUTY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WALL BE ACCMUSHM BY A REPRESENTATIVE
OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RET04MUTY TO NOTIFY THE PUBLIC
WORKS INSPECTOR 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION.
5. CONTRACTOR IS SOLELY RESPONSELE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION
AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE.
6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND MY OTHER
RELATED PERMITS PRIOR TO ANY CONSTRUCTION.
7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE
OVER ALL OTHER PLANS.
8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN
PROGRESS.
9. THE CONTRACTOR SHALL PROINVIDE THE CITY OF RENTON NTH AN AS -BUILT DRAWING OF THE SANITARY
SEAR SYSTEM, WHICH HAS BEEN STAMPED AND SOO BY A LICENSED PROFESSIONAL ENGINEER OR
LICENSED PROFESSIONAL SURVEYOR.
10. BACKFILL SHALL. BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS NTH A LOOSE AVERAGE
DEPTH OF 6 WKS, MAA" DEPTH OF 8 WKS, THOROUGHLY TAMPING EACH LAYER TO 95
PERCENT OF MAW" DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON
EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER
PIPE SHALL BE THE SAME AS DESCRIBED.
11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE
BACKFILLED NTH CRUSHED ROCK AND MEDiANICALLY COMPACTED LWLESS OTHERWISE APPROVED.
12. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR
HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE
APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE BENCHMARK AND
ELEVATIONS ARE NOTED ON THE PLANS.
13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE
SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON-SITE EROSION AFTER THE COMPLETION
OF CONSTRUCTION.
14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN
ACCORDANCE NTH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLAM"/WUWMA*JC WOWS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA
STANDARDS AND SPECFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON
STANDARD PLANS & SPECIFICATIONS. THIS SHALL NCLUDE NECESSARY LEVELING OF THE TRENCH
BOTTOM OR THE TOP OF THE FOLINDATION MATERIAL, AS HELL AS PLACEMENT AND COMPACTION OF
REQUIRED BEDDING MATERIAL, TO LWORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WALL BE
SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6 INCHES
ABOVE AND BELOW THE PIPE.
15. SANITARY SEVER PIPE SHALL BE POLYMNYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35,
OR DUCTILE IRON WM 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER UTILITY.
16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MUMUM 6 INCHES AND MAX" 12 INCHES ABOVE
FINISHED GRADE OR MUST HAVE MNM 2DWETER CONCRETE RING POURED AT GRADE.IN PAVED
AREA, COWER MUST SLOPE IN ALL DIRECTIONS TO MATCH PANG.
C t),
CALL 48 HOURS
BEFORE YOU DIG
DIAL 811
00
C)
>