Loading...
HomeMy WebLinkAbout03487 - Technical Information Report - Drainage � Uo � � Drainage Report FOR Van's Auto Repair Shop at 4405 NE 4th Street Renton, WA 98059 Building permit#B-080342 June, 2008 Revised January, 2009 Prepared for: (' O� Van Nguyen 8� Minh-Du Huynh �� ��� 2012 Duvall Avenue NE , Renton, WA 98059 � 4• ���0' ,�� O���1ir �ti ��� �� � :;��.:. ; / ^';��,, � . 3��389 <V �n�����;il�r" ,��1� � � -�'�10\.1L � �/ Prepared By: Jerry O'Connell, P.E. `"Y : :_� _� �(PIRES: '�� s - ��s- / S�►J ■ C �� � �" E M U I N E E i S / 9 U P 7 -- _ _ ` Lovell-Sauerland & Associates, Inc. 19400 33rd Avenue W. Suite 200 Lynnwood, Washington 98036 LSA FILE No: 5102 , 3 �'8� Van's Auto Repair Shop Drainage Review#3 Page 1 of 1 Van's Auto Repair Shop Drainage Review #3 Allen Quynn Sent: Monday,January 26, 2009 2:19 PM To: Arneta]. Henninger Cc: Ronald Straka;Allen Quynn Arnie, I have the following review comments regarding Van's Auto Repair Shop drainage report and plans dated January 2009: � 1. In sizing the media filter vault, the engineer is using a cartridge design flow rate of 15 gal/min. Based on the � design requirements in the Department of Ecology's Evaluation of Emerging Stormwater Treatment Technologies website, Contech Stormwater Solutions, Inc. Media Filtration System is to be sized assuming a design flow rate of 9 GPM per cartridge (18-in diameter, 22-in tall cartridge) using WWHM or other approved continuous runoff model. Engineer will need to confirm cartridge sizing criteria and revise drainage report accordingly. � 2. The Surface Water Utility's previous review comments requested the engineer determine if the project was I classified as a high use site and triggered enhanced water quality treatment. The be considered a high use site, � the project has to meet the following criteria: ', A commercial or industrial site that(1) has an expected average daily traffic (ADT) count equal to or greater �� than 100 vehicles per 1000 SF of gross building area; (2) is subject to petroleum storage of transfer in excess of 1500 gallons per year or(3); is subject to use, storage or maintenance of a fleet of 25 or more diesel vehicles that are over 10 tons net weight. The full definition can be found on Page 10 of the Definitions chapter in the 2005 King County Surface Water Design Manual. Number 2 above would most likely apply to this project since it is an auto repair facility that probably conducts engine oil changes. The drainage report will need to include an analysis that quantifies the amount of stored and transferred petroleum on the site in one year. If the thresholds above are exceeded, the engineer with need to provide enhanced water quality treatment per Section 6.1.5 of the manual. 3. Drawings need to clearly show the drainage pipe in the wall that is intercepting offsite drainage and bypassing around the project site. The plans must include a detail of the wall with the drain pipe. 4. Site plan shows approximately 1200 sf of driveway entrance is sloped towards NE 4th St. which means that any runoff from the area will drain to the street and bypass water quality treatment. Engineer will need to capture this area and direct it to the media filter. If grade precludes this, then the engineer will need to investigate other BMP options such as bioswale or filter strip in the planter strip along NE 4th St. Please call me if you have any questions (ext. 7247). Thanks, — � �-G � _,., --- - � _ _� _ .__ __--_. Allen — � � � ` . � tile:;,`C:�`,Documents and Settings'�,aquynn`,Local Settin�s'��Temporary Internet Files`�,Conten... 10;�27�?009 1 ' Allen Quynn From: Jerry O'Connell [JerryO@Isaengineering.com] Sent: Wednesday, January 28, 2009 9:13 AM To: Allen Quynn Subject: RE: van's auto repair-site modelling I will include a trench detail. Contech said the 9 gpm is for another product the CDS media filter system not the stormfilter system we are using. ' Jerry O'Conneil LSA Engineering Alderwood Business Campus 19217 36rd Ave. W., #106 ' Lynnwood, WA 98036 phone: (425) 775-1591 email: jerry�lsaengineering.com I From: Allen Quynn [mailto:aquynn@Rentonwa.gov] Sent: Wednesday, January 28, 2009 8:19 AM To: Jerry 0'Connell Subject: RE: van's auto repair- site modelling Jerry, The cartridge sizing is fine. Did you ever check with Contech to clarify why Ecology uses a cartridge design flow rate of 9 GPM? Also, I don't see where you have identified the trench drain. I think I see it on the plans but it's not very clear. Make sure you include a detail of the drain. Allen From: Jerry O'Connell [JerryO@Isaengineering.com] Sent: Wednesday, ]anuary 28, 2009 7:29 AM To: Allen Quynn Subject: RE: van's auto repair - site modelling Allen for your review... Based on your review comments&Contech sizing (using 7.5 gpm)we propose a 4-cartridge design. I've also added a intercept�r trench with pipe at the back of sidewalk & a slotted drain in the dwy to send the area north of the parking to the 4vq cb. ' Jerry O'Connell LSA Engineering Alderwood Business Campus 19217 36rd Ave. W., #106 Lynnwood, WA 98036 phone: (425) 775-1591 email jerryo(a�lsaenqineerin .c�com 1 � .. . From: Allen Quynn [mailto:aquynn@Rentonwa.gov] Sent: Tuesday, January 27, 2009 3:06 PM To: Jerry O'Connell Subject: RE: van's auto repair- site modelling Yes, if it can be designed in accordance with the 2005 manual which means you need to have sufficient water quality storage and minimum surface area at the design depth in the tank. Basically, you need to meet the requirements in Chapter 5, Section 6.4.2, (see Pg. 6-85, Requirement No. 10). Allen From: Jerry O'Connell [JerryO@Isaengineering.comJ Sent: Tuesday, January 27, 2009 Z:51 PM To: Allen Quynn Subject: RE: van's auto repair -site modelling lust as a thought, is dead storage in a tank acceptable in the city for basic wq treatment? (instead of using the wq cb?) Jerry O'Connell LSA Engineering Alderwood Business Campus 19217 36rd Ave. W., #106 Lynnwood, WA 98036 phone: {425) 775-1591 email: ierryo(c�lsaenqineerinq.com From: Allen Quynn [mailto:aquynn@Rentonwa.gov] Sent: Tuesday, January 27, 2009 8:12 AM To: Jerry O'Connell Subject: RE: van's auto repair - site modelling I would have to agree. Thanks, Allen Quynn, P.E. Project Manager City of Renton Surface Water Utility Engineer 425-430-7247 From: Jerry 0'Connell [JerryO@Isaengineering.com] Sent: Tuesday, January 27, 2009 8:12 AM To: Allen Quynn Subject: van's auto repair - site modelling Definition of project site. My read is that you model only the area of your property that you are developing, Jerry O'Connell LSA Engineering � Alderwood Business Campus 19217 36rd Ave. W., #106 Lynnwood, WA 98036 2 r ` � phone: (425) 775-1591 email: jerryo(c�isaenqineering.com 3 ���: i ��k� � � � Drainage Report FOR Van's Auto Repair Shop at 4405 N E 4th Street Renton, WA 98059 Building permit#B-080342 June, 2008 Revised January, 2009 Prepared for: � Van Nguyen 8� Minh-Du Huynh 2012 Duvall Avenue NE Renton, WA 98059 Prepared By: Jerry O'Connell, P.E. � � AU E N A 1 X E E R S I 9 U R V E Y O R 9 � -- _ _ � Lovell-Sauerland & Associates, Inc. 19400 33rd Avenue W. Suite 200 Lynnwood, Washington 98036 LSA FILE No: 5102 January Revision—Executive Summary This revision was prepared to acidress.the City's second review comments: The following revisions were made: 1. The disturbed area of the e.xisting site was modeled as Till Forest 2. A larger tank (200 LF of 6'diameter) was required(70 LF of 4'tank previously)for flow contro� Water qualiry treatment will be provided by media filter catch basin. 3. Using the updated KCRTS Version 6 computer model, which allows for orifice sizes less than 0.5'; a tank was able to be sized that would meet the design requirements. The previously submitted tank could not pass even using the minimum orifice size allowed by the KCRTS Version S model,primarily due to the small site and low target values. In conversations with King County, the new 2009 version of KCSWDM will allow orifice sizes less than 0.5'; which more readily allows for compliance. 4. A bypass system has been arided convey runoff from the undisturbed portion of the e.zisting site and offsite land Future development of the southern site would require flow control& water quality, but was not proposed under this permi� Sr VJJ^� !'l:�.9j ,,���i. fj., / � ;�/ _ Lovell-Sauerland and Associates Van's Auto Repair Drainage Report January,2009 LSA n5102 Bldg Permit kB-080342 Project Overview Project Name: Van's Auto Repair Project Site Address: 24405 NE 4'h Street Renton, WA 98059 Assessor Parcel Number: �182-1000-3902 Project Engineer: Lovell-Sauerland&Associates, Inc. 19400 33'd Avenue W., Suite 200 Lynnwood, Washington 98036 Phone: (425) 77�-1951 Project Applicant/Owner: Van Nguyen &Minh-du Huynh 2012 Duvald Ave NE Renton, WA 98059 Project Total Area: 0..535 Acres (23,301s� Disturbed site area: 0.2.5 Acres Soils Data: Alderwood(AgC) - Type C soil Modeled as Till in KCRTS I.ovell-Sauerland and Associates Van's Auto Repair ' Drainage Report January,2009 LSA#�102 Bldg Permit#B-080342 Level 1 Downstream Analysis: On June 16, 2008 a Level 1 analysis was performed on the downstream system. There are no apparent onsite storm drain facilities. The site generally sheetflows westerly and drains into NE 4`h St., where it is collected in the public catch basin near the northeast corner of the Post Office site; it then travels westerly about 500' across the Post Office Site (City project#2823) and the newly constructed Ribera-Backo Plat (City project#3111); and is discharged into a desiltation pond via a public 60"type-2 catch basin and 36" storm dra.in. It then discharges into a drainage course that is the headwaters of Maplewood Creek at a point about 600' downstream from the site. This drainage course then runs southeasterly along the perimeter of the Ribera-Backo Plat continues for about 2900' until it enters Maplewood Creek, at a point about 0.7-miles downstream from the site. There were no apparent signs of flooding, overtopping, or erosion along the existing downstream system. Flow Control & Water Quality Facility Analysis & Design Existing site hydrology: An existing conditions exhibit has been included to show the drainage patterns. The site generally drains uniformly to the northwest at a general slope of 7%toward NE 4`" Street. The site has been previously developed with a now vacant single-family house and related residential landscaping. Access was from a driveway to NE 4`�near the northwest lot corner. Due to the location of the existing water meter box, it appears the site was served by water from the main in ', NE 4th, and had a septic system in the southern portion of the lot. Adjacent land uses are as , follows: to the north-NE 4`" St. and a Safeway in a retail shopping area; to the east-a vacant wooded lot; to the south-the Ridgeview Court residential Plat; to the west-a main Post Office. Developed site hydrology: The site will be developed with a 3,OOOsf auto repair building, 10 paved parking spaces and a 26' wide access lane. The water quality runoff from these pollution generating impervious surfaces will be collected and treated in the proposed media filter catch basin near the northwest of the parking lot. A flow restrictor w�ill control the developed release rate to the required target levels and release into a new catch basin placed within the existing NE 4�'public storm drain. The developed site map has been included in this report. Flow control svstem: KCRTS design calculations have been included to show the facility required to match the level2 criteria, which requires developed runoff to be released not to exceed the existing 2-yr and 10-yr levels, as well as sizing the facility to have developed release match flow durations between 50% of the existing 2-year and the 50-year values. The 0.25-acres of disturbed site area was modeled as till forest. The runoff from the remaining undisturbed portion of the site will be collected in a grass-lined swale & underground conveyance system, and then discharged into the NE 4�' storm system. This bypass system will reduce the amount of runoff currently going onto offsite properties. Flow control &water quality systems will be designed under a separate permit at the time of any future development for the remaining undisturbed site. Lovell-Sauerland and Associates Van's Auto Repair ' Drainage Report January,2009 LSA#5102 Bldg Permit#B-080342 Water quality system: A perlite media filter catch basin was proposed to provide runoff treatment. Please refer to the attached drainage calculations. ESC Analysis and design A temporary erosion control plan has been prepared as part of the Civil Engineering plans. It shows the BMPs that are proposed in order to prevent silty water from leaving the site. BMPs such as a temporary construction entrance, silt fencing, and rock check dams will be constructed, monitored, and revised as needed to prevent disturbance of the adjacent properties. __ _ __ __ - ' ��__i _; I, il _ ; Lovell-Sauertand and Associates Van's Auto Repair , Drainage Report Januarv,2009 LSA#5102 Bldg Permit#B-080342 Appendix � _ __ � LOVELL-SAUERLAIVD&ASSOCIATES,L'V"C. 19400 33'd W.,Suite 200 Lynnwood, WA 98036 ' � _ 1 i tX. l..C.� �'"'�' ♦-TEL.U6LE TOP a02.98 �� � iNV J93.9B-10'S � EX. M.H. " •'�2'E �� = TOP IOSl1 ,' ��2'w �� � _ �Nv 379.Jt-i!'E . •N .w(�1�7�11-76'N Np0 70'S7L-2s'HOPE B�R w/CAP NO' \ '217J8'OY PppF. Oa "S.�o'��,— ; `. i i '. N.E. 47H ST �������� � ' --.'—` �----�� (Posno�wrH� � �.�� �ix� o ` � 6'raS--- � ! n I � � YI v �_ AB4N�ONED s'�� � ; ,P " � Ex.��BEpu K -�-- e 1.��sEx�c c�u —i*Ti � ��� � �� . �'^.�.w(7.�.1(/'a'-2so� ERTRUCE7Z0iac cur�6 � � ' ':t�t!'-� Fi: ... ��- --�-5b.yti.0r , � � . ,.. T— A�ar+"� — -• -e- ' , ,. _ ;;- , _n_--- ,d wRve,Eo) >406.55-2�3j'RT ' '.0 "Y e� _ ' � �x.�_5������� �� Fc _ ' ,l, , il$ T TE r9u: J � i � NAI�IN , sY� 1�4`;�} �� �„o- " e�ev- +os.sr � - �---- - �� GQ� � � V ♦ 'IM.95 y:`� '��� � � ; � ; � , ,I __.,� aY� .�,��_ �(1��/(', 4�� -r` 6, , ; ; �£MAY ?( � , � � ' n � �� .�e�'!� � i� � r� � ' �� �, . �� �1�.v�'ps� � � �' i 'I Zo0' Tf�►� P�-�PKss � g � k� 'i' � �� � �`�:I� j�. ' � �`�� � ,I � � � �. ;; � � � I _----.,. . � � � � � FN' 1�'w OG ' 1 . 'y� FFCP.�WE ''�I I I � �`� �, 1`1 � n i� � i i' I �'.I ,'� .q '' I ; . CTR.OF RKY��! � 1 � i 6.6 II �f I� � I « 23S �1��pe' , FROP.LINE � _I �, r ; � r .� y � � �,�'p�¢' �� •I f I •- I' i � i ��� I ��o� '� Ix 407.Op � 1 1�s�� .' 'a 0 9 .� I 'A I .' R/' � t � 0 q � � H ,�, $� i'C 45 � 7 1 � 0 � �1 9 6M1 �' �Y � C � �� fG i ' SQ 40 J�0� c6r� I � �' G q �' ' _ " ��. i ! ; � ' _ ' _ 'p�""_ ' _ ____' ��4 . � �' "_ '__'�'_'_""_____' i i � 15''.Ni.RE55,EGRE55 I �`�.� �Nd' pE , t unutt ESuT. � �'L V ZEC.N6. 72�02�:1068 I � � � � � — � 2t19.17-29.YRT _J � � . � ' t `---- _ `�, ,� -. .�, ,. , I '�WE'h'�!2.'Nt/2 Nl/2. j( I � �� �V�li�.NMi:'a.NWI/� n ` � �y P�S :' k � ' � � - �. k �i k :�� ,�� �� I � s .., s���� � � I �� = � s ,� #���� u� ,� �_ �,{ a !�� �� �� ' ' �, ' "rbTl��- $1 T E ' � i '�1 , � � � I'I I I , � � n N p,; � , , _ Q . s'� �iiv� . N 'X .I j �1� cT-t � ,:�' ,� � ' � � '��1 �7 `V�� � �K � � � INE M�/2.M'/2/M11;2 � , O.��C ��.VWI�{.I.A' � I, � \ ``�\` �� 3 x 'p�'�,�J I — � ���'�, � iwz w/GP no'D I��I � � _%. A�.N. � .HL'ON PROP CCF. � _. -� �rEc z/oaj ' I , � rcw.iois � � - ` ',hJ�OC 0�f8"JJ'-5 FN^. I.}'W C� �R yps � �NOT SURVE`!0; O aROP. JNE � .�y , !,�+ / r � �, �i',' '�E8'C6'�'�w 8C 88' . " " " " - � kl , I � � �i �I ��. � 5 �.iNE vti2.E�!�. � T 3 "_ _.,._. '�I�I /i � �Fn= C 25_s��-MG`J� ' t. �:h.,� . i - Y���� � N S l T� ' O � � � �..._�.--�' . ��}h � - ' -�,✓•-,_, .'^a M � �_- -=/ ���- _ � , ,� � r �'�-'�--,,,�'�� _ '�� "�1, � �'=�� � "��. . � �,..���,� ■ � y T _ , ._-- f _.J'y,_�:�^ � ,, '� _ . � ..� ; -.,_ -- __ �,. � -(�-, -`��z .�c_:�^�,,�: r Y�y/ � . ..._., - ��' J�.,"' '� __ fii7 f�, � .>` i p ---. � - - � i l ._.a...s.., t� M .7..¢'; - .��'�.-i `-'- - '/-: -�- _ i m �I�l.... � ._.� _.. -- � � ,�;� •--'`. 'e� .,.- �. "�. .�.-.-�vr`�:-y°- `..�' � �{— ���� ... � . ,�,.,,_m��. — ( 0 I �— .. _ - � L,ri---��oo: r�"°` .; _w. _ �'6�-�+ �o :;;i^�-° �'~' u - _ �^_ ,. � �a, � f ,.......r�4-r�-7 . �`'� . 1�' � �- w'� �A . .. ., ;� .li� � �- r� i^"�'=,.•�.-e^��'��-�-�'_'__��� ,,c' � � L ��� _-o�. _ � �'� � � ���'; k. m � . .: _ - . �3 r"�• «?w..;,�..�,,_... ,,._,., i, � ,,.$ �.,.� ��� �...-.°'� 'J�'_ _ �'^r.,t` �.. � .� v�. �..,._ . ___ .,� .�f� �+ �' j _ _ / _ ��--- _ sr /` --� /y 4 �, ��'•.\ m�_ .�}__ _� •� k., ��''� �y . �. _ , _ ��,,�. l _1�.., �M1.y - �,�' \`,� -� ---" � � " "��.�.��o� �.,� � — f: „/ m.�`� { I _ � � �'�.':��,. �"`-„""� �� �'� �. -�`-�-�-� - = ��� � . ��_ `_ . � , _.. ^r,��'t ^„ _ 'r. � :{� .�,'�.a._:.. - : v '�i._.. f. � .h� �" ` a ��� � `^ � - , 3 , ; ��"[ 8�. . . � � '.' � i �� �,:G��a�' .",��.fi..�..����0 _ i.'._ �� tl . i"4� �'j + -� �-�-- '?rp., � � � ,fy.e '� '�y.`.,.,� � . � �.,...-^'i•� ,._ p {-r �� � . . � �..�" . " � -�-3 __ � � � � a� �)�� � m �„�,,•�^'"��/` �.W...�..., � . «, c _`� �` �__� i �. " ` � � „ • � � �..., �.. _ � ,. � _ � � �� . .� �. ,...,.....,,,....�o r. .:._ -�, _ ` V —_ . _ , ���' � M� ��� ' `y • Witr� ,- m�. .. . ,--c� `` i ��L i '�' �: .�./� �,b1 '�_ .....�,.� ' q d 94� � tj � ��•• y►-. � _; ` —�. 1,.. _....,,., �r - ��, B I� •� � ^'� �-�� `� �oi -�- ��� ,- \r� I, , � . �. _ ��� :.��� �--%`��.� ��ll� �°�� "� � �_ _ ��, �. �� i �� L,_,,.. � -�;: , ( � � �.� �. � �«- ..... ���,� �S� ��� �,,,j��� '�, � � ', �' � �`, � ) �i� ,� � ' ,���f ��- s,- '� � m���`�� + � _ a� '� / �� ��,; �^d`o � } >- - � ti J '' _ � `'� � 1�� _ � �� �`�� J f/t'. ���'��� �`' l �-- r�� ..�.... _ .M.�=- ' �� ",� '�` ' ��'`r � •i�lf�> `� ) %,��/�°� �� `}� �; �; +4 i ��,,��,,.�/��ry�- � � , .. � - � � •-:/ ' ,y�'�. ��� / �� � 1� .i.,,� �.�I" �� .,�\ - ��� �� � � �� .� �_, �.,,.4,-T �.i,�....a�¢'�������t�' � �� �` � `".�'.._, � ��, l i �.�� ( ��� - -__ l ° ;;'a� , f�) s- '-� �. o;)�, , ,,, ��,`'f �� �� r� �;.;..�.�...,.,._.._..�...�;� �'i � � �r:.: �' 7' / � - � �� / � � �-�t"' •� � _ o'„ ��d.- � ! `4`.._._ a T _ _ J� � �_� .1�_ ;r'E'"1'.�` ��;�r r ,✓°y �� �C i -S ✓ \�,f� � '���( M:� - __ �k _`° (�: ', ," _ �� �� � ;�- � ' � � � �r" `�a 'I ,' ... °' ,�"' � �i � _ ca t 1 i ,��� � �, � _� h _ ' �� � � �� � Pa � ('� '_'�� �W��f � �."e m '`'� `��`1''"; , %''r ,.,� __ ,� �, 0�__". ��.J..;4.�* �_�� �� � .� '� ��'+-.. �.__,• `R' �� ,'« 1 / 9 �; � `n s'� 1 -, � � �^ � � ���^^�. ��� �� � � ..�, r �.r�C ���,.F�'""�y � � !IJ \ \, �� ��C,�� ^-N i ? � . la _.� ....,y, .,M'TM �'.. -,aC..-.«.... { ...�...w 1,.�� �.e� ! ✓V( //�,,,'� 1 <� / I J � w�'. � N"�"' t� b 7 W�+'""1 i „'�"'" . �' ....qt ""`...,..,.......,._ f.. � ` .. -�� f�J v'�,! �y}� ,/��� � / - ro �, �� � ......?�� .Tc. �wk-.......�7 � �'/'� [...,, . �.,...4� . �.���� . m� � :�r� !� ��.� � �� � �� ��� .. � ...�� ...J,""�. �������..� �� . _. � ' } ^ . ... N �w.'i ^ �'��,�SQ`�-� '"'��rr� ` \+ ` f�/ •,� r' !�j/( _� A� ` �w� ''�"" � �,,,,_...���,...��_ � ��,...»..� ���� f �~ ......w r '� .����� ��� r .M1� '��I �� ���P�.,1. `� , � � �.��. ■ � ..-� ���..,.,�N 1-�. {. � . f 11� y .. . �: �__..._ �� .. . ,w..�...,...�..-.�..,.. ...... � � ,. 1' � .� e � �.m..,...,..�.......��'y�d _ _, / o ���y .�` .. 1!I4 /..iol ( (�\ , �.��.1r'� b _],� � _ .,.��ri.�.�_�..�. ..-..:� .� •� �� �, 5 _ ��� � . o� �,., ..._..�, . � r_ t� � a ao \` 7 i�,, � � •� "r"� � _e�� ( � �G _.<.__.`x..- -�� i � t�� � 'w ��� '-�- �, _ �� 7� �- ` ��1 � V B � � z �- � lY � '�,� �,�" �'" ; ���; ,,� � � -� ;���( �� T _ � ' W�,1..9 ��--��� 1—� _� '�� ��.�� � � ���� � �t �l � ¢1� �d -c pr� �� m �! ��6 '� 1 f '?�..( a�.. ,--� � .. f� �-- � ..`��,.,..�...� .,.�p r�,c I� 1:,,� �� �� �..�� "4) � �O/ ��� �l. I �� �� 7C P\� �i p S ^ �4 ` !��� � �1` ��\i. yd pp n. ..,..,.lrv.-m ��. 6 � /� I I _ - b / '� _.]�, � r.....F,.F � _ .,'A dA' '��.. / - I -) i I� L� ' ._....�a. y /i ,..�.,�,..�. , ���„ � �� f��� Ml� �( �~� � _ �-. ,' y rY•� f` ���'�� ' _�f >/ — �....�;F� ,..�.... _" . � „� ��(��,�' � � 1' ��f, / •�� f,�{ .� � , . � Y ys..» {^ -��) •�� � . 3� . ,�� i _ �I ..� '"`��. i 'h �� ' � .*r^ �// � i ��"�� � S „4 , � !S �...,. ,. i-_�'m,� ���..- � � �;�.., i � / �O ' �. �ry X , y,' • l � )�:%• ,C'f ;\ � — ,� � L _J. + \' �-�...,.... t....� i ! � •, -o �'_" _' / �...._ r . �� % ���.����� Q`Y`+ ���� � l+.' ��� } i4 �� .. a.......f �� }.� .� �.��. � S .e..�, . �( �/----F� '��'? �° �'�� � � � /r'" ' �))� �j� - �� C ,.���C � __ ' � - �. - - . . `> �, � -=_ _Mo1a � '''1"'-`'�' ' r "- 1�� V� ���^�� - _ �; '_ ? � _ � ...- .. I�"^�.,� T . ��,qN - - � �w r� �� c� _ __ � ,�� '�.� ....�.._ _ _ � ' f � �, � � ,W{ - --�� �.........,'�j,�+�v,'�.te��'�°'`• ) { ` �C` f\�°-���` �"'.,«.F i �/ �n�" _� l�i,., r �� . s � � i' h�-`..��. .;t�S ) ., ......s � �- �� ��� ,_ .cc , ) 0 /- � �@7j O . �,I _ o � 1 �fI ��L^_ -_ �/�� nm ( Ill 1.,\� 1 � '�.� �wr]� f R7 :V " �``� � �� O t _L�r. 1 ������ _ *` i �,� 1 � � ��� � � �' ������ �;K..�'� �` � � � � � ,,.�.,,,..., , _ .. � _ � , �-., ; � � . ,� ,� f^��'' ' �, 4 --�- ' + , __ �. ,� ; _ , � �� ��� ' ) � � ��`� , � � � � ;��� ..�M_ � � � J�' ` f , x I�� ' � l 1 � � t" _ � I � , _ , � , �` -� / � � � >>; i �.. �i l. �^�,�! —'�� � _ % �� ��� ��' ��'-,,�i �� �a .��.�, � ...... ��� � - �� -- d 2 _ . \� .-e �`. . t � % �(- ' 1 ' -'L'� ' -� � - � � � _ �{ �,_.....-'" � : 'J f ' .'..., � � '. �� �.�- � •�� ��_ � s t`/ J,� ,� / �11�� � �'^�yl .�. �-4� � " ^ �. . > � � y. �k' ',.. /r � � ,� � � � \ �W �4 { �� ,� °ti..�. • �+ : �, _ .. , , ' ' � �.. +�� � � �-- . -. - - __�-- : ..... .. _- :e - _ , �i:� �� � � �) ��� �.. ,;�� , • - , E �" � ��"� � � ,>,r- . � ' �.: �� � �1--- •f, � �.. � �, �� �W � �� j\ �^ .;- 1 .. �j .._.�_r.. '//I��� ..c�^�-1 ' ' ���,'r> , .,, (�� � �:, , � m% � ;`_��r'� � �� ��� � ;�_,.,��..k.�...::'.. ' • •,i�� .....� � .... .... -.�.r+�,'_ � _ ,�+�-- I � � � j �� , � � _ _ nE.�_..,.�� 1� ,� ,� _ _ � � � -��`' _ �"'M��: '' ; ' ri `' �� ��� ,1.�= �� � �` -- � �� .� , � � � � . �. � � ��..�_ �.� `:"�, •� � �.;,��• � L• .A � , � , ,/�`�� � �� ��' � . !`� --� �'4 q� � � (`-'�� 1�, z � ��� ��c��,��_.__ ��� �:.�.�t ark A��� E______._ ',�� � ��� 4� � . a . ..... . `., � � � [ ' ��� � '_ ` � � � . � �`�1 � ( �r' � �l' `' ' �,, ��� ,�- �l<<� ' � \ ����( g� ��.' .� :� - T�' . .� �� / ; f " - :� -�.� � � ; . �, , ` . � . �. /��`���Z� j ^ . . . � 1` � _ ' y .• . .__._..�� � ,�� „��� � � - � � �jj�� y l .�. , �.-6 � . �-�-r.�:.--- � � � r ... _ c� � ��J ^- ,,j= "� -_ _�\���-- ° ��r ;i �� � � �� - °s ��,,!�' Z � �<_—�_c . � �_ -!- � .. . ' _ _ . � �. �� ,:�� ,� � �� � - r �; .,,,i„o° �` ...� -- _ � _ - ' '�_�... .. • --� �y" C � .� ,� �,i , � �_. z / _ ' . . 'I � . � � ��� �- �, - _.��_. _ �l r , ..-.. ... . . . ; � > � �--� ` � � .i��. o - ;,�J��(�.. �° , �c= �; .',�� � i • - �-�: = O p..--� � . KING ,COUNTY SOIL SURVEY SOIL LEGEND 1973 1952 MAP � SYMBOIS SYMBOLS MAP UNIT NAME � Aa,Ac,Ee AqB Alderwood gravelly sandy loam, 0-6o slopes �' Ab,Ae AgC Alderwood gravelly sandy loam, 6 15o slopes � Ad AqD Alderwood gravelly sandy loam, 15 30o slopes � Rh AkF Alderwood and Kitsap soils, very steep Aa,Ac AmB Arents, Alderwood material, 0-6% slopes Ab,Ae AmC Arents, Alderwood material, 6-15o slopes Eh,Ek An Arents, Everett material Cc,Cf BeC Beausite gravelly sandy loam, 6 15$ slopes Cd,Ce BeD Beausite gravelly sandy loam, 15-30% slopes Cd,Rk BeF Beausite gravelly sandy loam 40-75� slopes '� Nc,Bf Bh Bellingham silt loam � Pk Br Brisco� silt loam Bg,Bh Bu Buckley silt loam Cg Cb Coastal beaches i Pd Ea Earlmont silt loam I Ea Ed Edgewick fine sandy loam Ba,Eh,Se,Sg EvB Everett gravelly sandy loam,0-5a slopes Ek,Ba,Sh EvC Everett gravelly sandy loam, 5-15� slopes Eg,Bd,Bd EvD Everett gravelly sandy loam, 15 30o slopes EwC Everett-Aldenaood gravelly sandy loam, 6 15� slones Gravel Pit G.P. Gravel Pit La InA Indianola loam fine sandy, 0 4$ slopes Ic TnC Indianola loamy fine sand, 4-15o slopes ' � Ib InD Indianola loamy fine sand, 15-30o slopes Kb KpB Kitsap silt loam, 2-8$ slopes Kb KpC Kitsap silt loam, 8-15� slopes � Ka KpD Kitsap silt loam, 15-30$ slopes i Kc,Kd KsC Klaus gravelly loamy sand, 6-15� slopes ! Af Ma Mixed alluvial land I� Ef,Be,Sf NeC Dieilton very gravelly loamy sand, 2-15o slopes I ;--� Pk Ng Newberg silt loam Na Nk Nooksack silt loam Nb No Norma+ sandy loam ' 3.2.2 KCRTS/RUNOFF FILES 1�4ETHOD—GENERATING TI.�1E SERIES ���� �TABLE 3.2.2.B EQC�IVALENC� 6ET1�'EE?\SCS SOIL TYPES t�ND KCRT�S��SOIL T�'PES � �� � SCS Soil Type SCS KCRTS Soil Notes Hydrologic Group ' Soil Group � Alderwood (AgB gC AgD) C Tiil � , Arents, Alderwoo aterial (AmB, AmC) C Till - Arents, Everett Material (An) B Outwash 1 Beausite (BeC, BeD, BeF) C Till 2 , Bellingham (Bh) D Till 3 Briscot(Br) D Till 3 Buckley(Bu) D Till 4 Earlmont(Ea) D Till 3 ' Edgewick(Ed) C Till 3 Everett(EvB, EvC, EvD, EwC) A/B Outwash 1 Indianola (InC, InA, InD) A Outwash 1 Kitsap (KpB, KpC, KpD) C Till Klaus (KsC) C Outwash 1 Neilton (NeC) A Outwash 1 Newberg (Ng) B Till 3 Nooksack(Nk) C Till 3 Norma (No) D Till 3 - Orcas (Or) . . D Wetland Oridia (Os) ' D Till 3 � Ovall (OvC, OvD, OvF) C Till 2 Pilchuck(Pc) C Till 3 Puget(Pu) D Till 3 Puyallup(Py) B Till 3 Ragnar(RaC, RaD, RaC, RaE) B Outwash 1 Renton (Re) D Till 3 Salal (Sa) C Till 3 Sammamish (Sh) D Till 3 Seattle (Sk) D Wetland Shalcar(Sm) D Till 3 Si (Sn) C Till 3 Snohomish (So, Sr) D Till 3 Sultan (Su) C Till 3 Tukwila (Tu) D Till 3 Woodinville (Wo) D Till 3 Notes: 1. Where outwash soils are saturated or underlain at shallow depth (<5 feet)by glacial till,they should be treated as till soils. 2. These are bedrock soils, but calibration of HSPF by King County DNRP shows bedrock soils to have similar hydrologic response to till soils. 3. These are alluvial soils, some of which are underlain by glacial till or have a seasonally high water table. In the absence of detailed study,these soils should be treated as till soils. 4. Buckley soils are formed on the low-permeability Osceola mudflow. Hydrologic response is �. assumed to be similar to that of till soils. � 2�05 Surface Water Design Manual 1/24;2005 3-25 SECTION 3.2 RIJNOFF CONiPUT.ATION AND ANALYSIS 1�4ETHODS FIGURE 3.2.2.A RAINFALL REGIONS AND REGIONAL SCALE FACTORS ST 1.0/ ST 1.0 LA 0.8 LA 0.9 � 1.0 LA 1.2 ST �.� �`� �: � , SNOXOMISH CDUNTY ('i11[C � Q �- � � KING�COUNTY ��; ";. Z x�si-� ����' ♦ . r q � M �" f• _ � ---`�y�?"�� ;. , �,� �� '�'�� + � ��'`�, x 6� ��n, �` � `� �Q �� „_ _ , ._. �' � E' r' ,� .�� . ?•� � , ,�° s `3 '� ��i [ .. x ,`�yFtf �R�t'�° . . ---. ..g � i.a � ,6� ..�+v' t i� g . . t� �N "r # 3. -' � ifiE� ND� . . . . �. ` � ���� �. . ' + ` t - � �x- � y j ��' '� (� �y � a , � ,� � �'— , ��a'� �� ,�� a { ti � .a �`T'J , � � .tl6a+a t' � ., �. ��a �s _=�r�t. � j'r I ,"�- � C1 . - ' � �,Y .-i�w� � ;. y � ^ • '-� � �c, s�ar� _ � ; � . ��� , � £LEE1�lE ���� � ' ' � a �'e i^ . • .:q t r-- .. Bc� � .� . ,: ;wE a . ram f u� s a _. . :�=�. s- i � _� � �� . � - � ` � ,"E�� � - �"'` � .� ��Y ��� `_ � � ,�� - ,.�, _��,` �'� , r-� , e' - i �� . M ppEsi ��SNOOUALMtE � E,--i I . � ^1.� �G �� ? yF h �O�r 11�� POfR t'�t 5 � ! i t ,.�. �a ` ,�„ v r_"• _ � .� ? �� �� . ( � o � � �; ,v } ; ' �` p `----�' �- +�i.`'� FW���� �' �� `' 4`Y � �.- 1- � ,, � , 4v�K f�1�. .�,z � ,,� . IEPrtsTW . . _ € $ - .�� �� 4��; ; Q LANDSBURG i � } `,}' � Y��Iwn _ � GRa'E . �_ AYn� - <_. -` . N �'. ' �� Ya � � . .. _ c'3' ���g � . a � .. � r f �-`'��'� � z � `—� g� �.���,. KBa�� o � ��«�� , , Q 1 � � � �� � � , r �� ; _ � �.� �j�- � � � ,f '''*. _ ' � � 1 _'� $�* e . ���!`� � �`� � ou„ ` i � � �`Y � f` � r-5- . ST 1.1 � ��� � ' ` ' ' �. �,�_� t _ �. � ��`.�~ ���' � 6 1`d � �.N IL/fF?v PIEqCE COUMTY �� � ST 1.0 �� , Hw�u� Rainfall Regions and �, 0 8� '' � J �� Regional Scale Factors �A o.9 � LA 1.0 �A 1'2 �� Incorporated Areap .� River/LakeO Major Roadp � ' 1/24/2005 2005 Surface Water Design Manual 3-22 t ��i. — ( ` _... _ . -_`' � . __. _ __ . _ __— '_�`j'`� L , i\ ��.'�;�3��� •.• � Ta EF r I ��..� � � I 7 !� _ _ _. 1 1 T� _ _"�"� �; ��� '� "' \Ka I� a° . �;�; I� �� 1 `� F t � ` �� ...... ..... ... _- � j :�- � ,�� �_ r �, .;,�"�� �� . '�° I � � \ �� b � �Re� .�1 � Sh� ,: � - : . � - � � �- ,� � .� . . � ; � �. � � � ��;- RBeach; � � � ��, � Ke��— ���xd •, � ; �s 3A � � 35 � 36� -_-. � � ��-"-� ��, �e F n��� �#.. � � � � 1i�:�.� I \ I e�� _ �'�q�" Eh� �' � � Ae \ �if` � , I � _ r. ��-; : � � - �j' 1"� I '� �� � � , �� : �-�� Y E , _ , �.--- _ - _ _ `_' y-���.. \ , � �� t �� �9,� ' ' �"" A na} `�` j � y ��I I�� ---------` e.� ii,�..� � �. . o t��, r � �i ��� �� �y ��.�� � �� .�'��� '� ���� {� � �Ek 1�� 3 � �Xd ' � � .��Ge � il J,'"` o �' 1, �\f ��•��L o � •�' • ,,_'~ � } +� ,,.,.A" ``\�b�'' x-. a�Ek,� . . . . � • U-at�a�� I�.h 1��" � � aWfa �� - J� I+b ^+���@ ��:.� �.•�'�•a�n--� . �e'.. _ �^ ��"r����� — c, ,��`�`- �h.. -- `�`-��'Ot'Y_ER �''�� ,_ 'y�c' �rw oal FieId • ' � _. �-Aey • .�� ���a� "'°Pa- � l Pd � c�', E� . A�` Coal � �`�, oot �P I3 n a � � r �� .�! . � � �r, y�� I �+4c-�1 �~ � � �'':- ---\ � _, e. \ - II 11 �a�� �` � �yil:I'^F'�,�� Pd!\a' � �� �J � i p: +Ad�.��✓' • t� Ib .°� �,`r 'Ca.� I ` `� � `� ��� •.:r. I� ���C.` ,y� A��a���,�����7': �1� Pi+ _-{�PI�. $� I :r� \ .� � j `. ���jthib � -U .s. � � ..I,."t �_-" . Cb � �V , Ad�, � r !+a� x,� ,od r �_'�I� e . ta �9 I �t� (�, `�\ 11 '�:U�t��i,�j 3td V ': 1, ^�t rT,`"a �'il��i "� � ,r �. _ r �' A8.� � ` \� , �� � � .,,�_ �, �f - . ,:�y� � �-� {. � . Pe �_ �-i� �I , ,� . n '/ o } _. � _ � � � �, � �' � t` 6�...�._, � � � ', ��/�, ,�� "'.�P � -:�- � Ek �C I p �C{ ��`��� i �' ",7i��� ��t ��I ,. a r� . Eh'. j; Nb . � .�! ' �� ��f�`� '�:-�!���,1`�'�' �:�\ j.:U � #"'" ��"�_ EH .� •r �. - - -Qe� - M��� . :-'� : I, .� � � � � ��e � '�`�� �_� (� �t �=�J� i ,j[+,�� 14 .`��e — � \ � en�4�3��''S�� e f �- ° a Q' � S�' s 1 p �. ` � � �°A F ��.C k :. 3 ���� � � 9.�� ` � ��_ � e .. � � g ��. � 1 � � � ^ ��-K � 3�'�f �� �� '1� '` Prr' ��SF I� ���,4 '"�.��\1 e����3_E ;� f{h � 'n 1 )��y . J� �� �'' ��' . I v i ' '�!: ` '.� t ` � �� :. ��� � �. ., � � Gt _ � � n -,- ��.� . 'E ],� � Ek *. C N � �._ .��: � '�m.P �U ,..r � � c ��� y G � er �F �� �--�� n. +� , � �� r- a - �� 'CLU D\ P8 � -_ �= �, 1 S' � } P �rk.� � � �- � � � �a.� e 1 ��\ 'r�,� �m ��.�1 �� .. _L� f �. -, t`,c �� ��^�� � �_ Pg�L � � � �,E� �'�, � ,t� , ', �R Rh � � � , f J , � �� � � � �_24� :� 1 �y � �,o�� � t y-=''� �����e;c,� an�;1-� � ��— Pg , 1 Ek ,; , � �i� .ti• ���� �" �`� :.5�•:� �'�� 1;_-Ge, t�`, � �`�,.; ��� P�� r '.'�' '•v- ��`� _:"� Ad Rh ..J-s •'�c �Ro�, ;'`M�P�,- � •P^ ��.c�,,,�� ti,��20 21 ��y 22�.�� . � �. �/2 pt � ' .� ' � ��� ' ac � ti � :� 3 '� p '. Wa ar ,� __�_:: R9 �'f i,. � �,�c�'� _ ; L ��G ������.•. ha� �. � f'O�.yE.R PC� `� � Pf �� �'.�P�_�✓�f• � -�R�\_ �-E ,� s � TM� . • - -;,� � w� �' R Frc , �� ce• � � ��d � Ad �_� 1, 9 Fj 4 �KE �• :�.. �; , _ _ i . _. ,� Rh � - � Rd `7 � .� Ptl S' ���� I j��� �I -... .. �v . Ci�� `����-� ! - s, ' Wa �� pk ' _ _`- � ' � � i� ' _ ' � \T4� �-�LS J .� � ,} � � - � (P; P I ' � � � � - . - , � r��{� ( _,z�,� ''�,� d . � ��! �f�"Y A'� ,, ! ��?',`o j � � _ ,� �a � Ad . �� � . =�;f S�� `i n Pg' 5 �� 2 __. � Ae 28 "a� ' \� 7 � I � } dfI � � \,���' s 26 ° � 25 �Gb. I , ���I: � Sn -' - �Pq �. � � h�e �a �Rh P I:S%�� 1 . l �. \� . '. � ... _. � I"t,,r/' I �P�+ ., _ ' Ic� _ �.CB . _ � �tw ��f hSd � A n � k "��'�^" na Md / � � � p9 u��•�pk� e � � Z '�x� �r� � �.:,�� � �' - �<.• --;F r ,4 '} . 4t •��'� a . Y� - `'� � Pd v ) �} ; _�" - "xw �� . .. . � ��� . 'E Jl aa -5 ;`�- ) _�� Pa I F� -- 2 ,r .� 3 /� . ,{; _ - 'y ; ,� ��� � Sn 1 � �y � '� �5 �`. o'� ��� �� ' '+ ' •� � Ad• I �• ��� u I kb �/ � � 34��� -�� s - �' , �x --�36� �` � iW, __ �Pd � ''� .�-.__ � ��-�-� ,� � i � w , o � 2: .-- � �. „ h• x =Ek .a ' � � , / '�� ySd Nb•u • n• kAd Iw' �b A �„_-� � �� , . �' ��, � �° � 1 Pf � . . . �, � ,�_ � � ' � •(l � - ,�•. ; '�. q�- M7,u,td-> '�P9 Fk VI��1 � � � ��l,`th Ad 5., pRd ' Re` j . �, ^'S�'�SS' `""� 'g� ,� Pd.'� ...._. ,4a• �� Q' �. 3 � 'Czj O�' y � � Pd i'-� �? Ae Nb � " �� � a -- __ ��'� �Pttnther , + Pd ` '� � '�' _ ry' Gb ke y� "� ` ' _ . � s� r �. �� � _ Pf 0'$ _�� r, � ',' -- • . .. . . r s _ C 4 ' .� :Pk S � Sn �e ; nEF g Ikle� e Rd , r i � Ca tb "'": _ _ ,� � P 1 Ek� _ � �-f— � R� ! oh Sn k �� Ad } '�{� i� Ae � � p�' : � � �'�IZ � '.i � A' c� � }- � Ad ,t�_' ; Pdl l )�t ,, 1 ` � •i X�� a� `�Nb • o � Ca-� � I L�. (I , � g� ' U 9 � ..�.l 1 == j l 12 A� ,? l�'e,, i i .� �E 1 qe� ` :� '� �5f �Eli ' � ,�U. �I 4Va /�'`, � , �d Pe � d/, � . Ae � � � b, Ae �, � � ' � � � : `` Pdl � r A �� _� ��qd t- � o+� Rd �l� � fJo _ / � r- • ` j f; _� ;,I�' � . .l� �A. Ca _ .e Pk ' 1 � 'W Sn ad • � � --� ''.4d`� J .._ R .•j _ ���Sk Pe Pd �0 ,�1� � I ' Gb ' � Kb 1N � I �' + �� d s,, � Pk ' �: ' 13�\ Pf:• 'Pk 1 .� ;_ '�`', e '� 1 f/:�� �y�p:� J k ---'` '� I `� }� .= 1� 16 ;; aQ � , a�i � Sri�d -� 4 � Ad � r �'�h .�Bt � 3 � � b \ r'� �, ��' _� � � �Ab Ca� :,;ttir,,;� x� ! �� � , . ` ' . � < Pf � � y t r r b � Nb Nb � � V a Nb =_- � ; � . . . .. . � 'F(��. � Pk� � I .' � �._ . .- � . . . e fi_ Pt��"'� Pm .' e. . � � .E T H1uf ;I Bf . CIaY.�Gr _�:�lp • . .. , ` �*^,:r _� Pk �n. �� - Ty a �Lakt, �pj � � Ca �a bAd.:l' `� r ' !.7y��.'�fl� x ���.\; • 20 K 21Md �'Bfl,, aNb �. •� : �� . . �' � ?� €1 E] �� � •;�,�� .. .- . - " Nb Re .� �' �� 'e,�e5a � \ 2 ' � .. Pk, P�e� i `��E .�"��' � = �\. . � �� l.A , :��� 3 =� 24 ,�� ` • � • ' iar�02� � tX. C.B. wv aas.oe-�o's � ����� �EX. M.H. �� wv un��..�z'w rov+os.a� � y�� � NV J79.31-ta'E � � NV 379.21�1E'W pp���� .--_ W/CAP NOb �``� _ ���-S11-21�MDGE '�)�l��sa '2T3Jl�ON PROP. . N (N47ED 2/00 �` p����� a 0 I` � I � � •- e•r.e - ,� • ,``� �• � AC BERN ��� • � � 7.SbCAC PNI �� � � �� �� . / • .1J(�II-2{OJ T T T T T �T J T ____� ��� � �� �0:3t'-�—a-�.�-�'__ "e__—A�D1N0'f A1RYE1Ep) / ii � i �ii r�r -�ye�j'����' R'yy`�^_Y — � %�-I . i '' /� . i`� � I . k "' VI)fatli� � t I � . : I I � � ' EIEY�109.9 ; � i � I � i I ' 7FFICE __ }� I � � _ ��x �E-IIWU CONC.� � � I DRI�EWAY � �y� '� � � � � I I C7R.OF �i� � �4 j � PROP.UNE f I �j i � t � �+a�.s•w a 1 � ,' i vaav.u� . � � 1• ! �,' � � , � , ! ' I I ' ' � f , ;'� , � ; � -----y--------- � � � Y; � t ,i I ' 'o�'° '' ��7%�� � � �� �� ;�� � � �� � , _ � � �, � ; ; � ; 1; , --^• Z �%� ; ; �1 �j I; ' ; ��e' "- " � � ; I � � `.' ;� � % � �� lt��! { ' I 1 I ' � ' r ;��; i � � � r ; � � � � ' -� ----- . . . . ' '� � ' I , � ; ; m t I ' ; •r�r.j-�„�; , � ; ` VrK '1 1 I 4'�r��`y I � ; �p�o� � .. � ' 1 y 6�p�•j, (^�I f � �/��}� � �9'•' O • �1 V �OZ'9 � i�� j t�:`�� i � '� ��t�G�10 1 1, ,�q 0 �st—S � � � S P p \X ;�G' � /�I � �y �`K�0, O I L�r � � ��t dd 25'INCRE55.EfYtE$S s I j/ a.r; �6� 4 k U11Un'E511T. � � � � REC.HO.72102/0068 �� � �� 1 ij � � \ � `�� � i � ' , ``� I � \ � �\ • �, � J��� ��� � E������ � 1 ;I{7/�, 4.NWI/! � � i � ,1� i � i •�i � W 1 � ' ,� �n � � i 'i g i � a �'° ' ' � ' ' ���'� � .` _ ; ,, ; ; fC,�'� 1� �' � - � �"'-«[,�.� � ; � , , , , I � � � . , � a ; -� . � � � � ¢ •� "� "�" ' �' ,'` c� � �� ar'_ c�i � � �� ,�,.� I ��'� � � � o �� ' o �.�,�c�n.�n M,n. ' � N NE1/4.MYII�.NWI/4 i ` ' I � � .�R N �eN+w/c�r Nob �� ��`, O '�oasa'aa vaar.coa. � � D(. M.H. � cv�s,m z/oe� {� � . Tov ao.,s � �c tatv ar � rrv�oo.00(e- 3 vRov.uf � MoT suR� � n aene•; w eo.ee' -- - -- � � � I s uNe rn/2 e�/2 Mc.ars I tn cm.av Pocr (P '" aaor �� __ ' aF No e.�w a o' -' --- / `/ PROP.LNE �i��` ` _PROP_lN I� �P � �� 13_'_"_ " I 18'PEOES7ItlAN \�j.� 1( � � 'I ` `- _='_""__' ' �3{2 N/�CORTES ALE NE ACCESS t �� � �»v.� � , , --------- �_ umin�T. 15 3 ; ' - -- •� I . 's ' �����z' �� � _ _�1_ a p F� IDGEVIEW COURT � I ' � V�OL 235, P GS. 75 —� � � I � � ♦ Drainage Calculations NE 4t" Auto Repair Flow Control— Detention Sizing Flow Control Standard: Flow Conservation Land Use: Historic Site Conditions (forested) Redevelopment Project? NO - (ez. impervious area=24.5%<35% threshald) Predeveloped Condition Land Use—Forested Condition � . --Ar�a____._ _ � �, T�11 �ares# 0,25 acres'�' Tiil P�stureli O.UO acres'' Ti#I �Eass 0.0�1 acres' �uiwash Forest fl.Dtl acr�� O�twash Pastu�e' D,U� acr�s Outavash Gr�ss; �1.�� a�xes: We#tand': Q.�O ��res' Impervious Q,�O at�es'; �Tatal-�_� __� �.25 ��es' Scale F��t�r: �.t10 Nourt�t_ Re�uced ���� Time Series: predev�s� 33 Com�ute Ti€ne Serias Modi#y User lnput __�._._�� ..� _» Fle fior�computed'Rme �eries [.TS�] ��__.___ _�. �,._�_.��� Flow Frequency Analysis Time Series File:predev-st.tsf Project Location:Sea-Tac ---Annual Peak Flow Rates--- -----Flow Frequency Analysis------- Flow Rate Rank Time of Peak - - Peaks - - Rank Return Prob � (CFS) (CFS) Period 0.016 2 2/09/01 18:00 0.020 1 100.00 0. 990 I 0.004 7 1/06/02 3:00 0. 016 2 25.00 0. 960 0.012 4 2/28/03 3:00 0. 012 3 10.00 0. 900 ' 0.001 8 3/24/04 21:00 0. 012 4 5.00 0. 800 I 0.007 6 1/05/05 9:00 0. 010 5 3.00 0. 667 , 0.012 3 1/18/06 20:00 0.007 6 2.00 0.500 �� 0.010 5 11/24/06 4:00 0.004 7 1.30 0.231 0.020 1 1/09/08 9:00 0.001 8 1.10 0.091 , Comouted Peaks 0.019 50.00 0. 980 �i 5102-calcs-tank.doc II ' . Developed Condition � « � , 11res._..._._.__.._. ._ � Till �'orest; Q.OQ acres; a 3 _ � Till Pasture� Q.O� acres; __ TI{ Grass 0.06 �ares';: Uutwash �arest 0.0� acres; Oula�rash Pasture O.O�I acres! flutwash �rass: D.00 acres �letland 4.00 a�es Impervious: 0.1 J acres' �-Tatal�-���.� � � � ; 0.25 acres'' ___.._ .. .--_---�.._, Scsle �actvr : 1.�I� Hourty Redt�c�d Time Ser�es: dev�st » Compute Tim� Se�es M�ndi#y User Input ______�__._ _._.�.__ __�_r_��_.__. �___._�__._.._..__---___ .___..�.._ � � ,, __ �____ F!e for cort�puted Tirr�e Se�ies t.TSFj Flow Frequency Analysis Time Series File:dev-st.tsf Project Location:Sea-Tac ---Annual Peak Flow Rates--- -----Flow Frequency Analysis------- Flow Rate Rank Time of Peak - - Peaks - - Rank Return Prob (CFS) {CFS) Period 0.052 6 2/09/O1 2:00 0. 102 1 100.00 0.990 ' 0.044 8 1/05/02 16:00 0.071 2 25.00 0.960 0.061 3 2/27/03 7:00 0. 061 3 10.00 0.900 0.049 7 8/26/04 2:00 0. 058 4 5.00 0.800 ' 0.058 4 10/28/04 16:00 0.055 5 3.00 0. 667 � 0.055 5 1/18/06 16:00 0.052 6 2.00 0.500 'i 0.071 2 10/26/06 0: 00 0.049 7 1. 30 0.231 '� 0.102 1 1/09/08 6: 00 0.044 8 1. 10 0.091 �I Computed Peaks 0.092 50.00 0. 980 �i ' 5102-calcs-tank.doc Target duration curve N O G '.3r.y--;,.,,,' --�•\� p _� . �.�_,_' _� O O ?.}--. O O - -- - N � 'i U ' � o `o a L M �� 0 �1 O O O O __�_ "�' O O C O O O ,O ; 'r:� ;'J : 1fj 1 , , 'v , ,L ProGabi6ty Excee�erca 2-yr & 10-yr Peak Comparison F�um PeroC � '0 2J 5G iDG • pr���-S,�Fk< ,,_. ._. " �i � ��/�/"D V1� • � ,T, Zy�-r ��•`I � . tn �� F' • LL U • ♦ m 1 � ic z � . O � c� _ c 1L':"� �----+-r--r- . 2 5 ?u �_ ?A d0 50 6� '0 3n 90 25 � 99 GUm:l26ve Proi,2D:�ity. t •� I�/ � , ' S102-calcs-tank.doc Duration Comparison N O � { ....�._. ,� P. � � ;argk-<_t.�ur • �` 0 o �� � o i� �- o � �JS �O ' - N O �LL V ^; �� 0rn Q �' o � q O � L M 0 �. O O q �y " "} � o � ;______.______.___�. __._..___.ir, 0 . ,; 0 � -- - �____._--_...., _ a a . �.� 0 o '� �1. 10-� , 'r � 1� � . � 1�_` iG '` Protfabifity�ceederie Duration Comparison Anaylsis Base File: predev-st.tsf New File: rdout-st.tsf Cutoff Units: Discharge in CFS -----Fraction of Time----- ---------Check of Tolerance------- Cutoff Base New �Change Probability Base New %Change 0.003 I 0. 10E-01 0.78E-02 -22.7 � O. 10E-01 0.003 0.003 -13.1 0.004 � 0.73E-02 0.75E-02 2.9 I 0.73E-02 0.004 0.004 2 . 6 a.004 I 0. 65E-02 0. 62E-03 -90.5 � 0.65E-02 0.004 0.004 -7 .0 0.005 I 0.59E-02 0.59E-03 -90.1 ( 0.59E-02 0.005 0.004 -14.9 0.005 I 0.54E-02 0.57E-03 -89.5 � 0.54E-02 0.005 0.004 -21.6 0.005 ( 0.45E-02 0.55E-03 -87.8 I 0.45E-02 0.005 0.004 -27.3 0.006 I 0. 41E-02 0.54E-03 -87.0 � 0.41E-02 0.006 0.004 -32 .3 0.006 I 0.38E-02 0 .52E-03 -86. 1 � 0.38E-02 0.006 0.004 -36. 6 0.007 � 0.34E-02 0.52E-03 -84.5 I 0.34E-02 0.007 0.004 -40.4 0.007 I 0.29E-02 0.52E-03 -81.8 � 0.29E-02 0.007 0.004 -43.7 0.008 I 0.27E-02 0.49E-03 -81. 6 � 0.27E-02 0.008 0.004 -46.7 0.008 I 0.24E-02 0.47E-03 -80.4 I 0.24E-02 0.008 0.004 -49. 4 0.008 I 0.22E-02 0.42E-03 -81.0 � 0.22E-02 0.008 0.004 -51. 9 0.009 I 0. 17E-02 0.39E-03 -77 . 4 � 0.17E-02 0.009 0.004 -54.1 0.009 � 0. 15E-02 0.33E-03 -78 .0 � 0.15E-02 0.009 0.004 -56. 1 0.010 � 0. 14E-02 0.29E-03 -78.3 I 0.14E-02 0.010 0.004 -58 .0 0.010 I 0. 99E-03 0.24E-03 -75 .4 � 0.99E-03 0.010 0.004 -59.7 0.010 I 0.83E-03 0.21E-03 -74 .5 � 0.83E-03 0.010 0.004 -61.2 0.011 � 0.72E-03 0. 18E-03 -75.0 I 0.72E-03 0.011 0.004 -62.7 0.011 � 0. 64E-03 0. 18E-03 -71.8 I 0.64E-03 0.011 0.004 -62.7 0.012 � 0. 38E-03 0. 13E-03 -65.2 I 0.38E-03 0.012 0.009 -23.4 0.012 I 0.33E-03 0 . 98E-04 -70.0 I 0.33E-03 0. 012 0.009 -21 . 9 ' S102-calcs-tank.doc 0.012 � 0.29E-03 0.82E-04 -72.2 I 0.29E-03 0. 012 0.010 -22.7 ; - 0.013 I 0.28E-03 0.82E-04 -70.6 � 0.28E-03 0. 013 0.010 -24.5 0.013 � 0.21E-03 0.82E-04 -61.5 I 0.21E-03 0.013 0.010 -21.5 ' 0.014 � 0.18E-03 0.65E-04 -63. 6 � 0.18E-03 0.014 0.011 -17 . 8 0.014 � 0. 15E-03 0.65E-04 -55. 6 � 0.15E-03 0.014 0.011 -19.3 , 0.014 I 0. 15E-03 0.33E-04 -77.8 � 0. 15E-03 0.014 0.011 -21. 6 0.015 ( 0. 82E-04 0.33E-04 -60.0 I 0. 82E-04 0.015 0.013 -10.1 0.015 � 0. 65E-04 O.00E+00 -100.0 � 0. 65E-04 0.015 0.014 -6.1 0.016 I 0. 16E-04 O.00E+00 -100.0 I 0. 16E-04 0. 016 0.015 -3.7 0.016 I 0. 16E-04 O.00E+00 -100.0 � 0. 16E-04 0.016 0.015 -6.2 Maximum positive excursion = 0.000 cfs ( 3.3%) occurring at 0.004 cfs on the Base Data:predev-st.tsf and at 0.004 cfs on the New Data:rdout-st.tsf Maximum negative excursion = 0.007 cfs (-63.1�) occurring at 0.011 cfs on the Base Data:predev-st.tsf and at 0.004 cfs on the New Data:rdout-st.tsf Retention/Detention Facility Type of Facility: Detention Tank Tank Diameter: 6. 00 ft Tank Length: 200.00 ft Effective Storage Depth: 4.22 ft Stage 0 Elevation: 0.00 ft ' Storage Volume: 4250, cu. ft Riser Head: 4.22 ft Riser Diameter: 12.00 inches Number of orifices: 2 Full Head Pipe Orifice # Height Diameter Discharge Diameter (ft) (in) (CFS) (in) 1 0.00 0.28 0.004 2 3.70 0.75 0.011 4.0 Top Notch Weir: None Outflow Rating Curve: None , Stage Elevation Storage Discharge Percolation ' {ft) (ft) (cu. ft) (ac-ft) {cfs) (cfs) I 0.00 0.00 0. 0.000 0.000 0.00 ��� _ , 0.01 0.01 11. 0.000 0.000 0.00 I 0.02 0.02 22. 0.001 0.000 0.00 0. 12 0.12 133. 0.003 0.001 0.00 0.22 0.22 245. 0.006 0.001 0. 00 0.32 0.32 359. 0.008 0.001 0.00 0. 42 0.42 474. 0. 011 0.001 0.00 0.52 0.52 590. 0. 014 0.002 0.00 0. 62 0.62 707. 0. 016 0.002 0.00 0.72 0.72 825. 0. 019 0.002 0.00 0.82 0.82 944. 0. 022 0.002 0.00 0. 92 0. 92 1063. 0.024 0.002 0.00 1.02 1 . 02 1183 . O. G27 0.002 �. 00 ' 5102-calcs-tank.doc 1. 12 1.12 1303. 0.030 0.002 0. 00 1.22 1.22 1423. 0.033 0.002 0. 00 1.32 1.32 1543. 0. 035 0.002 0.00 1. 42 1.42 1662. 0.038 0.003 0.00 1. 52 1.52 1782. 0.041 0.003 0.00 1. 62 1.62 1901. 0. 044 0.003 0.00 1.72 1.72 2020. 0. 046 0.003 0.00 1.82 1.82 2138. 0.049 0.003 0. 00 1. 92 1.92 2255. 0.052 0.003 0. 00 2. 02 2.02 2371. 0.054 0.003 0.00 2. 12 2.12 2486. 0.�57 0.003 0.00 2.22 2.22 2600. 0.060 0.003 0.00 2. 32 2.32 2712. 0.062 0.003 0.00 2.42 2.42 2823. 0.065 0.003 0.00 2.52 2.52 2932. 0.067 0.003 0.00 2. 62 2.62 3039. 0.070 0.003 0.00 2.72 2.72 3145. 0.072 0.004 0.00 2.82 2.82 3247. 0.075 0.004 0.00 2. 92 2. 92 3347. 0.077 0.004 0. 00 3.02 3.02 3445. 0.079 0.004 0. 00 3. 12 3.12 3539. 0.081 0.004 0.00 3.22 3.22 3631. 0.083 0.004 0.00 3. 32 3.32 3718. 0. 085 0.004 0.00 3. 42 3.42 3802. 0. 087 0.004 0.00 3. 52 3.52 3881. 0. 089 0.004 0.00 3. 62 3. 62 3956. 0.091 0.004 0. 00 3.70 3.70 4012. 0.092 0.004 0. 00 3.71 3.71 4018. 0.092 0.004 0.00 I 3.72 3.72 4025. 0.092 0.005 0.00 i, 3.73 3.73 4032. 0.093 0.006 0.00 I 3.74 3.74 4038. 0.093 0.007 0.00 '� 3. 75 3.75 4045. 0.093 0.008 0.00 3.76 3.76 4051. 0.093 0.008 0.00 3. 86 3.86 4112. 0.094 0.010 0.00 3. 96 3.96 4165. 0.096 0.012 0.00 4. 06 4.06 4209. 0.097 0.014 0.00 4. 16 4.16 4240. 0.097 0.015 0. 00 4.22 4.22 4250. 0.098 0.015 0.00 4. 32 4.32 4250. 0. 098 0.324 0.00 4. 42 4.42 4250. 0. 098 0.889 0.00 4. 52 4.52 4250. 0 . 098 1. 620 0.00 4. 62 4.62 4250. 0. 098 2.410 0.00 4.72 4.72 4250. 0.098 2.690 0. 00 4.82 4.$2 4250. 0.098 2. 950 0.00 4. 92 4. 92 4250. 0.098 3.190 0.00 5.02 5.02 4250. 0.098 3.410 0.00 5. 12 5.12 4250. 0.098 3.610 0.00 5.22 5.22 4250. 0.098 3.810 0.00 5.32 5.32 4250. 0.098 3.990 0.00 5.42 5.42 4250. 0.098 4.170 0.00 5.52 5.52 4250. �.098 4.340 0.00 5. 62 5.62 4250. 0.098 4.500 0. 00 5.72 5.72 4250. 0.098 4. 660 0. 00 5. 82 5.82 4250. 0. 098 4 . 810 0.00 ' 5102-calcs-tank.doc 5. 92 5.92 4250. 0. 098 4. 960 0.00 i 6.02 6.02 4250. 0. 098 5.100 0.00 6. 12 6.12 4250. 0. 098 5.240 0.00 6.22 6.22 4250. 0.098 5.380 0.00 Hyd Inflow Outflow Peak Storage Target Calc Stage Elev (Cu-Ft) (Ac-Ft) 1 0.05 0.02 O.Q1 3. 94 3. 94 4151. 0.095 2 0.10 ******* 0.01 3. 94 3. 94 4153. 0.095 3 0.06 ******* 0.00 3.59 3.59 3930. 0.090 4 0.05 ******* 0.00 2.96 2. 96 3391. 0.078 5 0.06 ******* 0.00 2.24 2.24 2621. 0.060 6 0.04 ******* 0.00 2.08 2.08 2439. 0.056 7 0.03 ******* 0.00 1. 97 1. 97 2313. 0.053 8 0.05 ******* 0.00 1.34 1.34 1561. 0.036 ---------------------------------- Route Time Series through Facility Inflow Time Series File:dev-st.tsf Outflow Time Series File:rdout-st Inflow/Outflow Analysis Peak Inflow Discharge: 0.102 CFS at 6:00 on Jan 9 in Year 8 Peak Outflow Discharge: 0.015 CFS at 20:00 on Feb 9 in Year 1 Peak Reservoir Stage: 4.18 Ft Peak Reservoir Elev: 4.18 Ft Peak Reservoir Storage: 4244. Cu-Ft . 0.097 Ac-Ft Flow Frequency Analysis Time Series File:rdout-st.tsf Project Location:Sea-Tac ---Annual Peak Flow Rates--- -----Flow Frequency Analysis------- Flow Rate Rank Time of Peak - - Peaks - - Rank Return Prob (CFS) (CFS) (ft) Period 0.015 1 2/09/Ol 20:00 0.015 4. 18 1 100.00 0.990 0.003 6 1/07/02 4:00 0.012 3. 94 2 25.00 0. 960 0.010 3 3/06/03 22:00 0.010 3.86 3 10.00 0. 900 0.003 8 8/26/04 8:00 0.004 2. 97 4 5.00 0.800 0.003 7 1/08/05 6:00 0.003 2.28 5 3.00 0. 667 0.003 5 1/19/06 7:00 0. 003 2.09 6 2.00 0.500 0.004 4 11/24{06 12:00 0.003 2.04 7 1.30 0.231 0.012 2 1/09/08 16:00 0.003 1.37 8 1. 10 0.091 Computed Peaks 0.014 4.05 50.00 0. 980 F1ow Duration from Time Series File:rdout-st.tsf Cutoff Count Frequency CDF Exceedence Probability C FS °s a o 0.000 78 0.127 0.127 99.873 0. 999E+00 0.001 30993 50.543 50.670 49.330 0. 493E+00 0.001 2574 4.198 54.868 45.132 0.451E+00 0.001 13366 21.797 76.665 23.335 0.233E+00 0.002 1082 1 .70'S 78 .430 21 . 570 C.216E+00 ' 5102-caics-tank.doc Water Quality Calculation Design Flow Method with 15-minute developed peak flow � � __A,rea ._ __.. � T#! Forest'; t1.Ufl acres! Tilt Pasture`: tl.atl a+:res; Tlt! �r�ss" �1.06 �crss' ;, Out�i�sh Fo�es� t�.fltl a�esf �� Outv�rash Rastur�I �.OU a+�res Qutarash Grass' �.QU a�tes; We�ia�di t1.Ofl ac�es', Impe�+riou� �.19 acres ; . __ _ __ _ ; � � . Tc�tal __ � 3 _ /,� Q.25 acres' r ��< , ' � ,: .._._. Scale Fact+�r: 1.00 l 5-Min Reduced Edit Flovr P�ths _ Tir�ne Scri�s: dev-s#-15 ?> �. ; Compute Timc Se�ies 7 ' .;�.� _ �~- � , , Moclily Us�er Input � _ __ __ _ . ___ . _ _, � I� , = File fnr compui�d Time Series [.T�F] ; , _ , s�K .J�� ', Flow Fre uenc Anal sis y\,,,, ��Js ��� U� �, q Y Y � � �,J'�� Time Series File:dev-st-l5.tsf Project Location:Sea-Tac ---Annual Peak Flow Rates--- -----Flow Frequency Analysis------- Flow Rate Rank Time of Peak - - Peaks - - Rank Return Prob (CFS) (CFS) Period ' 0.090 6 8/27/Ol 18:00 0.255 1 100.00 0. 990 ' 0. 063 8 9/17/02 17:45 0. 184 2 25.00 0. 960 '�, 0. 184 2 12/08/02 17: 15 0. 124 3 10.00 0. 900 '� 0.073 7 8/23/04 14:30 0. 105 4 5.00 0.800 I, 0.099 5 10/28/04 16:00 0.099 5 3.00 0. 667 ��I i 0.105 4 10/27/05 10:45 0.090 6 2.00 0.500 i '�, 0. 124 3 10/25/06 22: 45 0.073 7 1.30 0.231 0.255 1 1/09/08 6: 30 0.063 8 1.10 0. 091 Computed Peaks 0.231 50.00 0. 980 - Treatment flow = 60� of developed 2-yr = 0.6 x 0.090 = 0.054cfs No. of cartridges at 0.0334cfs/ea= 0.540/0.0334=1.62 (use 2 cartridges) ' S102-calcs-tank.doc � 5.3.4 CONTROL STRUCTURES—DESIGN CRITERIA FIGURE 5.3.4.A FLOW RESTRICTOR(TEE) This.._f gure_.has.._beep changed to.inelude � the screen detail. ��� f�na s sow cwer �. ���P��� �wA�ad"�it�1kIKN`�bekk�y botts R dwya 2-Q2'2.2-�u:i P mh ua�de� T 8`r�t. �errsgtN 16"ma�cT �" e r vettk�l�' �� � 6�min. ��ry in�t � dasi V4f$. v ' ������� ebow rast�aeta,�de�s� hsndtzdds.st a ' ELBOW FtESTRlCTQR DETAIL ��'�a t�f�Kc� NTS �,s:t� �a.�-�s ��n, �md,. � «.�,+,�. � �. � .��.,ss � impt anct ciGvs�ort � shsar gate wwithn conua ��� E tod!or deat�x,U[irairt �y i2` �rod be�[t as rt�qturetl or verYltxi alIgnment w�h Goverl sEe K�tS �esfsicWr�"t�atn,., .E �� da+g.2-02g vr#�oaf�ce dem�ter as vr S�ed��naedeC if iu 1 Y r� tw sa;�c���d onN1 ` SE�TIt3N A-A t;�mn,ar� NTS � - 1St�METRIG , NTS �� � �, �� � �,��a;a�n�„ SMALL C?RIFICE m�-�,� SCREEN [�ETA1L � xr�s: N'fS _ L fJse a rnim�num o�a `6iameter>.ype 2 � ca�tr t�asin. �. o�n�cca� ,on.v ,��o4n. f � A a. �+et���: r� . � � rx�n-�vvarE�a aans v�+�.ea• f arE Gatvert¢sd p�e p�ts�ta�r��ph� �� � � � I �—.. � st� #reafar�s t. �� I[] � 4. Fr�ins and 1�1Ar or a�,r aN�+t sc: � � ��e' J As Clear+out s,�is rs�frtan top ry B.C�irnb-doKm spsce�ttear W nset atW °�� 1\ T mitt:�e ntata 7 � ��5yts�1o�aUnw at.�cess deanout�b�. �� �/ tn t�nita or vsilts when C. Frame ia deaz of arra. , ��,.- sump�s fi��with tiratee 5, lf inefei�e#pape eonneets to�m�tst cor;crete pipet an�fet D'R�h�Itaye arn�t O,D.eR�to canuEte P�[.D.less}'. e. �o����s•x.a�a�,����mca�e�,�. PLAN VIEW ���,s�-ts��'�} NTS �: �«�e���cs>�s�an w�taa��,��s�. a u�ate ad�aonat�svngs in strt,dures�1 a�acc�a m tartks artd v�w af�oar atx:ass�tx+lc�t t�in fs t€�d wi�watar, 9, Pmv�trtesdr ea�prot¢c6on fir bottio€rt atiEca�I�s fltrt}'d�.Oa��ttWaDla �cage ta rtse�acfb�attachad bdt-an tt�nded�.Caqe b be mat�wqh}tttesh scrsea in afumtnum ar s�iNess ateel. ���� 5 Surface Water Design i�lanual 11/O1/2006 5-39 1 � �� �� l V July 25, 2008 Earth Solutions NW LLC ES-1311 •Geotechnical Engineering •Construction Monitoring • Environmental Sciences Mr. Robert Champion, AIA 3802 - Cofby Avenue Everett, Washington 98201 Subject: Geotechnical Recommendations Proposed Auto Re�air Building 4405 - Northeast 4 Street Renton, Washington Reference: Structural Engineering Plans Prepared by Swenson Say Faget Dated May 14, 2008 Dear Mr. Champion: In accordance with your request, Earth Solutions NW, LLC (ESNV1� has prepared this letter providing geotechnical recommendations for the subject site. We reviewed the following documents andlor resources: • King County iMAP online GIS resource; • Composite Geologic Map of King County, Booth et al, 2006, and; • King County Soil Conservation Survey (SCS). Proiect Description The subject site consists of a single, rectangular tax parcel with an area of approximately 0.5 acres, which is located near the southwestern corner between Northeast 4th Street and 136rn Avenue Southeast in Renton, Washington. The site is bordered to the north by Northeast 4tn Street, to the south by a residential development, to the east by a vacant parcel and to the west by a retail development. The property is currently developed with a vacant single-family residential structure and associated improvements and is otherwise forested. Site topography is relatively level, with elevations ranging from between appraximately 405 to 410 feet. We understand the site will be redeveloped with an automobile service facility and associated improvements. The service bay portion of the structure will be one-story in height and will utilize conventional foundations and either concrete masonry unit (CMU) or wood framing. A second story space will be constructed in the northern portion of the building. Slab-on-grade floors will be utilized across the structure. We anticipate minimal grading will be required to achieve design elevations, generally less than five feet. , 2881 1�2nd.A�-enue NF• Redmond,bVA 98052 • �-125i 28-3-3300• FAX(425) 284-2855 •Toll Free i8661 336-8710 ('� S��2�) Mr. Robert Champion, AIA ES-1311 � July 25, 2008 Page 2 If the above design estimates are incorrect or change, ESNW should be contacted to review the recommendations in this report. ESNW should review the final design to confirm that our geotechnical recommendations have been incorporated into the final design. Subsurface Conditions Three hand-auger test pits were excavated across accessible portions of the site to characterize the subsurface conditions which may impact site designs. Please see the soil logs attached to this letter for a more detailed description of the site soil and groundwater conditions observed at our boring locations. In general, underlying a thin topsoil and fill layer, firm native soils were encountered. The native soils consisted primarily of inedium dense to dense silty sand with gravel extending to the maximum exploration depth of three and one-half feet below existing grades where refusal was encountered. Geologic Setting Based on our review of the referenced geologic map, the site is underlain by glacial till deposits (Qvt). The referenced SCS resource indicates the site is underlain by Alderwood series (AgB) glacial till soils. The soil conditions encountered at our test sites generally correlate with the published geologic map resources. The native soils encountered at the test sites were consistent with glacial till deposits. Groundwater Groundwater was not observed at our test pit locations during our fieldwork (July 2008). It should be noted that groundwater seepage rates and elevations fluctuate depending on many factors, including precipitation duration and intensity, the time of year, and soil conditions. In general, groundwater seepage rates and levels are generally higher during the wetter, winter months. Site Preparation and Earthwork The primary geotechnical considerations during the proposed site preparation and earthwork activities will involve structural fill placement and compaction, site drainage and erosion control. In-situ Soils From a geotechnical standpoint, the native soils encountered at our test sites are generally suitable for use as structural fill. The moisture sensitivity of the native soils can be generally characterized as moderate to high. Because the native soils are moderately to highly sensitive to moisture, successful use of the on-site soils will largely be dictated by the moisture content of the soils at the time of placement and compaction. Soils encountered during site excavations that are excessively over the optimum moisture content may require moisture conditioning prior to placement and compaction. Conversely, if the native soils are found to be dry at the time of placement, moisture conditioning through the application of water may be necessary prior to compacting the soil. , Earth Solutions NW,LLC 1 Mr. Robert Champion, AIA ES-1311 � July 25, 2008 Page 3 If the on-site soils cannot be successfully compacted, the use of an imported soil may be necessary. Imported soil intended for use as structural fill should consist of a well graded granular soil with a maximum aggregate grain size of six inches, and a moisture content that is at or near the optimum level. During wet weather conditions, imported soil intended for use as structural fill should consist of a well graded granular soil with a fines content of five percent or less defined as the percent passing the #200 sieve, based on the minus three-quarter inch fraction. Structural Fill Placement In general, areas to receive structural fill should be sufficiently stripped of organic matter and other deleterious material. The project geotechnical engineer should observe cleared and stripped areas of the site prior to structural fill placement. Structural fill is defined as compacted soil placed in foundation, slab-on-grade, and roadway areas. Fills placed to construct permanent slopes and throughout retaining wall and utility trench backfill areas are also considered structural fill. Soils placed in structural areas should be compacted to a relative compaction of 90 percent, in general accordance with the maximum dry density as determined by the Modified Proctor Method (ASTM D-1557) and placed in maximum 12 inch lifts. In pavement areas, the upper 12 inches of the structural fill should be compacted to a relative compaction of at least 95 percent and be in stable, non-yielding condition. Excavations and Slopes The Federal Occupation Safety and Health Administration (OSHA) and the Washington Industrial Safety and Health Ace (WISHA) provide soil classification in terms of minimum temporary slope inclinations. Based on the soil conditions observed at our test sites, the weathered native soils and fill encountered in the upper approximately one to two feet would be classified as Type C soils by OSHA. Type C soils should be sloped no steeper than 1.5H:1V (Horizontal:Vertical). The dense glacial soils encountered below about two feet would be � characterized as Types A and B by OSHA, and should be sloped no steeper than 0.75H:1 V and 1 H:1 V, respectively. ESNW should observe temporary slopes to provide supplemental , recommendations, as necessary. Permanent slopes should be sloped no steeper than 2H:1V. Permanent slopes should be mulched or vegetated with appropriate species of plants to reduce the potential for surface , erosion. The project geotechnical engineer should observe temporary and permanent slopes to ' verify that the inclination is appropriate, and to provide additional grading recommendations, as necessary. ' Earth Solutions NW,LLC I I , Mr. Robert Champion, AIA ES-1311 July 25, 2008 Page 4 Utilitv Trench Backfill In our opinion, the soils observed at the test sites are generally suitable for support of utilities. Organic or highly compressible soils encountered in the trench excavations should not be used for supporting utilities. In general, the native soils anticipated to be exposed during grading should be suitable for use as structural backfill in the utility trench excavations, provided the soil is at or near the optimum moisture content at the time of placement and compaction and fines contents are within acceptable limits to maintain stability. Moisture conditioning of the soils may be necessary at some locations prior to use as structural fill. Utility trench backfill should be placed and compacted to the specifications of structural fill provided in this report, or to the appticable specifications of the City of Renton, as appropriate. Foundations In our opinion, the proposed building can be supported on conventional spread and continuous footings bearing on competent, undisturbed native soils or structural fill. Assuming the building will be supported as described above, the following parameters should be used for design of the new foundations: ■ Allowable Soil Bearing Capacity 2,000 psf ■ Passive Resistance 300 pcf (equivalent fluid) ■ Coefficient of Friction 0.30 ■ IBC Site Class Site Class C (Table 1613.5.2, 2006 IBC) ■ Liquefaction Susceptibility Low A one-third increase in the allowable soil bearing capacity can be assumed for short-term wind and seismic loading conditions. Competent soils suitable for support of foundations are anticipated to be encountered at depths of approximately one to finro feet below existing grades. Where loose or unsuitable soils are encountered at the foundation subgrade elevation, the soil should be recompacted or replaced with a suitable structural fill soil, as appropriate. Slab-On-Grade Floors Slab-on-grade floors for the proposed building should be supported on a firm and unyielding subgrade consisting of competent native soil or structural fill. Unstable or yielding areas of the subgrade should be recompacted or overexcavated and replaced with suitable structural fill prior to construction of the slab. A capillary break consisting of a minimum of four inches of free draining crushed rock or gravel should be placed below the slab. The free draining material should have a fines content of five percent or less (percent passing the #200 sieve, based on the minus three-quarter inch fraction). In areas where slab moisture is undesirable, installation of a vapor barrier below the slab should be considered. If a vapor barrier is used it should consist of a material specifically designed for that use and should be installed in accordance with the manufacturers specifications. ' Earth Solutions NW,LLC . , Mr. Robert Champion, AIA ES-1311 July 25, 2008 Page 5 Retaininp Walls If retaining wall will be utilized at this site, they should be designed to resist earth pressures and any applicable surcharge loads. For design, the following parameters can be assumed for retaining wall design: • Active Earth Pressure (Yielding Wall) 35 pcf(equivalent fluid) • At-Rest Earth Pressure (Restrained Wall) 55 pcf • Traffic Surcharge (Passenger Vehicles) 70 psf(rectangular distribution) • Passive Resistance 300 pcf(equivalent fluid) • Coefficient of Friction 0.30 Additional surcharge loading from foundations, sloped backfill, or other loading should be included in the retaining wall design. Drainage should be provided behind retaining walls such that hydrostatic pressures do not develop. If drainage is not provided, hydrostatic pressures should be included in the wall design. ESNW should review retaining wall designs to verify the recommendations earth pressure values and drainage have been incorporated into design, and to provide additional recommendations, as necessary. Retaining walls should be backfilled with free draining material that extends along the height of the wall, and a distance of at least eighteen inches behind the wall. The upper one foot of the wall backfill can consist of a less permeable (surFace seal) soil, if desired. A rigid, perforated ' drain pipe should be placed along the base of the wall, and connected to an approved discharge location. Drainaqe ; , No groundwater seepage or indications of the seasonal groundwater table were observed at j the time of our �eldwork (July 2008). However, perched groundwater commonly travels along ' the shallow contact befinreen the weathered and unweathered soil horizon within glacial till deposits. As such, groundwater seepage could be encountered in deeper site excavations, i particularly during the wetter winter months. Temporary measures to control groundwater seepage and surface water runoff during construction would likely involve interceptor trenches I and sumps, as necessary. In our opinion, perimeter drains should be installed at or below the invert of the building i _ footings. � , Earth Solutions NW,LLC Mr. Robert Champion, AIA ES-1311 July 25, 2008 Page 6 Seismic Considerations The 2006 International Building Code specifies several soil profiles that are used as a basis for seismic design of structures. As previously mentioned, based on the soil conditions observed at the test sites, Site Class C, from table 1613.5.2, should be used for design. In our opinion, liquefaction susceptibility at this site is low. The relative density of the site soils and the absence of a relatively shallow groundwater table is the primary basis for this designation. LIMITATIONS The recommendations and conclusions provided in this letter are professional opinions ! consistent with the level of care and skill that is typical of other members in the profession currently practicing under similar conditions in this area. A warranty is not expressed or implied. Variations in the soil and groundwater conditions encountered at the test sites may exist, and may not become evident until construction. ESNW should reevaluate the conclusions in this geotechnical engineering study if variations are encountered. We trust this letter meets your current needs. If you have any questions, or require additional information, pleas call. Sincerely, ��' �Ati��e �� ��WAS�,�lN �C EARTH SOLUTIONS NW, LLC �y�� 4� `'� � �� 7• �' '�ci�� � �l'i`��5� r , S10NAL�U J�� i � EXi'{RES �L� ��29,J� �� .....�....., \ tt S. ' , L. . Kyle R. Campbell, P.E. �J�S nior o�ect gist Principal �,/ Attachments:Site Plan Soil Logs , Earth Solutions NW,LLC iMAP ¢ ��� F ��{���� � ������� , ;� r , ,� r � � � �.��.�� _ _ _ , _ �_ �_ . . _�.� _ _ _ - � 1 � _ �'�� f r i �( � ' rrf , 1 �I =_ �f I�I NA�� �'' �� � �� ; � ; � �` �, � � '`55 1 5782lDOG39 5�� � �i ,� Rento n �t �'� �,$�,�.,, t '�� '��� �q'� r� � �F�- �� + � �,�`�� � 1 '' � 5i£i1 i fJ'�33? � H�1-1 �'�� � �,� � � �� �`�- � -.._ �-y-� ��f , � � 1312�tk17 30 j �7317i�JDi�(1 T3i�i�01fi0 3121�0�� -���1 . . . . .. ... . � . . f�£ � � .. . . . ... .. .. __ \. I3i21�37D fz _ }� — ''�,.�1 ���� 73�27��4Q 5 5 t-, T�t21�:�4 y Y312iL�i1f1 � �372�G[J'.T�J i ���' '� 7��27d1f1}8� � 4_ �� � � �. �— �'#i2i�0iQd f f S Y"�'' �� ``�`1 ` ��� _ - �j���j _i' �������� �� 5 I - j1Y" -. .i,lt_I � .. :�1-rs��,na c,�R�y � � 4 85ft �, Tha information induded on�this map has been wmpifed by King Courtty staff hom a variety of sources and is subjec:t to change wifhout nodce.Kmg �' � Counry makes no representations or warranties,express or implied.as to accuracy,comple[eness,timeliness.or rights to the use of such information. I, � This document is not intended fw use as a survey product.King County shall rtot be liable for any general,spedal,indired,incidental,a corasequential s � M i damages incN�ng,but not limited to,lost reve�ues or lost profits resutting from 4he use or misuse of the infom�ation contained on this map.My sale of � K�ng��u,sty � ttus map a informadon on this map is prohibited except by written permisswn of IGrg County. '�, , Date:712512008 Source:King Cou�ty iMAP-Property Infortnation(httpJAvww.metrokc.gov/GISliMAP) 'I JOB NO. )311 CLIENT �o�r�- Ch�.-� �d� TEST PIT NO. DATE `?� I'1 IO$ BY S(S ELEVATION fi W� C�� (-�f�1— �, CONTRACTOR SHEET 1 of 1 � � � � -� � SURFACE CONDITIONS �� �Q �, a�, c�� �;a.w,5les � gtav�\ �� a� � � v�°i 'c a°i -°�a � v•� � c°� NOTE: DEPTH OF TOPSOIL& SOD Sy� �C'o�rL S_�� _S�}�l�_�s1_��J�✓e��_rv����s.��_�PnS P_� In01 ST_'— �� 0 � — ------------------------- 2 co S P� --- ------ -------------------------------- 2'S 3 e Sa�\ m.� � ;\\ ------------------------------------------- 4 ------------------------------------------- 5 ------------------------------------------- 6 ------------------------------------------- ------------------------------------------- 8 ------------------------------------------- ------------------------------------------- 0 : II ------------------------------------------- ------------------------------------------- ------------------------------------------- 3 ------------------------------------------- 4 ------------------------------------------- 5 ------------------------------------------- 6 ------------------------------------------- 7 -------------------------------------------- 8 ------------------------------------------- ---------------------------- ------------- 0 Test Pit terminated at Z`S feet below existing grade. (� Groundwater(table/seepage)encountered at feetduring excava6on. Earth Solutions NW��c ' i JOB NO. /3� � CLIENT ���� e.�a,�.��Rp� TEST PiT NO. DATE -]� ��l D g BY �4� ELEVATION �' t-{f O� N� - � CONTRACTOR SHEET � of I �, � u� � �� � SURFACE CONDITIONS E E E n N nY V -°�a ��SS � �S'a�►'t�j��5 �1 v�i c uWi -a � v•� � c°� NOTE: DEPTH OF TOPSOIL& SOD� S(1� 'row� s;?-�_��N��v_�-fL��f`ay c\�_�e ��.�1'L Q���,J�o1 Si O 1 -- - --------- --------------------------------- 2 c 5 P� ------------------------------------------- 3,c� 3 ! -2--�\_ o�__��se _ ��\-S��-�--------------- _ ' 4 ------------------------------------------- 5 '� ------------------------------------------- 6 _ ------------------------------------------- " ------------------------------------------- � ------------------------------------------- , p i ------------------------------------------- - 3 ------------------------------------------- ------------------------------------------- 5 6 , ------------------------------------------- 7 -------------------------------------------- 8 ------------------------------------------- 9 ------------------------------------------- 0 Test Pit terminated at 3 feet below existing grade. ( I�O Groundwater(table 1 seepage)encountered at feet during excavation. Earth Solutions NWuc ' . � , - JOB NO. J3� 1 CLIENT ����-�- C�a �a� TEST PIT NO. DATE � J'� {� $ BY ��� ELEVATION 'f' �-/'C`? S � }�/�- �j CONTRACTOR SHEET � of � �, �, u� � � � SURFACE CONDITIONS �E E n. o �� � o �CZt�'2� Su��e. ,r v�0i c vf°i v � �°' � � NOTE: DEPTH OF TOPSOIL& SOD� � sM 3rou9v� s_,l _���_UL+ ���1� ��+,�'''-�'�'_ '�11 ---- C�,5 � S,� 8 w � S ;�-h c e � vr�D t � � ------- -------------------------------- ,� c���5 2 ------------------------------------------- 3 � ---- ------ ----- ----� --------------- 3 , � 4 �,,�. � ;c` S�,C- ------------------------------------------- 5 ------------------------------------------- 6 ------------------------------------------- 7 ------------------------------------------- 8 ------------------------------------------- ------------------------------------------- 0 ------------------------------------------ ------------------------------------------- ------------------------------------------- ------------------------------------------- 5 ! ------------------------------------------- ------------------------------------------- 7 -------------------------------------------- ' 8 ------------------------------------------- 0 Test Pit terminated at 3 `� feet below existing g�ade. (�j Groundwater(table/seepage) encountered �, at feet during excavation. Earth Solutions NW��c '