HomeMy WebLinkAboutR-38831210 CURB RAMP (MOTH 1'- D• MIN. TRADING TO MATCH (A \ NOTES
��v CURB RAMP MOTH -SEE CONTRACT PLANS \T' / CURB RAMP WIDTH f - T MIN. 1 Provide a separate Curb Ramp for each marked or unmarked Uosswalk
LANDING TO MATCH CURB RAMP
MOTH - SEE CONTRACT PLANS Curo Ramp location Shall be placed within the width of the associated
LANDING - GRADE BREAK LANDINGD I I vOsewalk or Be shown In the Contract Plans.
GRADE BRFAK \ SEE CONTRACT PLANS - CURB RAMP - GRADE BREAK 2 Where "GRADE BREAK"is Called oul, the entire length of the grade
4' - T MIN. CEMENT CONCRETE SIDEWALK I break between the two adjacent Surface planes shall be flush.
SEE CONTRACT4 PLANS - SEE NOTE 5
p • - 7 MIN. , I PROVIDE $MOOTN 3. Do not place Gratings, Junction Boxes, AcceorDI Access Covers, Of other appuf's-
CEMENT CONCRETE TRANSITION TO �,-o, nancee in front of the Cum Ramp or on any part of Dte Curb Ramp or
SMEWALK
SIDEWALK- SEE NOTE 5 1 OlN (tYP.1 SEE CONTRACT PLANS - I MIK SEE CONTRACT PLANS - Landing.
Z MAX 4'-PAW RS1 MAX 4'.PMIN.
FLARE (TYP.) SIT ExPANSION 4. See Me Contract Plants for the curb design specified. Sea Standard Plan
JOINT (TYP I SUPFE0. WDTN--H TO F-10.12 for Curb. Cu'b and Gutter, Depressed Curb and Gutter. aid
1B-FXPANS10N I CURB RAMP lmmaw PUNF-70.10 CURB RAMP DEPTH (TYP.) Pedestrian Curb details
.
JOM (Tor .) -SEE I ,� I 5. See Standard Plan F-30.10 for Cement Concrete Sidewalk details.
STANDARD PLAN F411.10 BREAK
Jam" See Contract Plane for width and placement of sidewalk.
GMOE BREAK IWFAK TRANSITION TO SIDEWALK Bl1FFER, IF w
' PRESENT, OR TO BACK OF CURB (TYP.) - 6- SEE CONTRACT PLANS B. The Bid Item "Cement Concrete Curb Ramp Type _" does not include
'40%A1{k=«;z))`i` tom - the actacerlt Curb, Cum and Gutter, Depressed Curb and Gutter,
.. ....... ...
:::, ..L:.i: a
•:.._._ ..:- •..:•1`..::: Pedestrian Curb or Sidewalk.
CAND, UT CURB CEMENT CONCRETE
AND GUTTER - _-- - CURB, OR CURB PEDESTRIAN CURB - 7. The Curb Ram maximum running Slope shell not require the ram length
SEE NOTE 4 . _ _ - _ `f AND GUTTER - - SEE NOTE 4 P 9P ng
1 DETECTABLE WARNING SURFACE - SEE NOTE 4 D I to exceed 15-feel to avoid chasing the cope Ihde(Im:ely when Connecting
SEE aTANDARD PUN F416.10 _ DELECTABLE NYIRNHG 5URFACE- to steep grades. When applying the 15-foot maximum length. the running
FACE OF CURB 1 _ _ _ FACE OF CURB I SEE STANDARD PUN P• 5.10 slope Of the Curb Ramp shall as flat as feasible.
MEASURED PARALLEL DEPRESSED CURB AND GUTTER - E DEPRESSED CURB AND GUTTER S_ Curb Ramp, Landing, and Flares shall receive broom finish See
TO CURB (TYP.) CRDB6imiu, SEE NOTE a CROSSWALK Standard SpeClOeadons 8-14.
I• L_ LEGEND
SLOPE IN EITHER DIRECTION
PLAN VIEW PLAN VIEW
TYPE PERAFJOIgJLARA TYPE PERPENDICULAR B
DETECTABLE WARNING SURFACE - (SHOWM WITH BUFFER) CEMENT CONCRETE OFTFCTABLE WARNING SURFACE -
SEE STANDARD PLAN F-4&10 - PEDESTRIAN CURB - SEr STANDARD PLAIN F46.10
'
GRADE BREAK SEE
PMIK_ -`�.0' MAX. :'.:::� t,.'. •:
SlDPE 7RFATIENT- BIi NOT
CONORACTPTRNS SEE COUNTER SLOPE -
SEE STANDARD I Fd0.10 -GRADE BREAK /r 5.0% IAAX r R. TYP. - .• •• DEPRESSED CURB AND GUTTER -
2.D%YAX. d3%" \ T.1 OF ROADWRY
`1 •••• . SEE NOTE 4
CEIACNT LONG ETE CURB pATRI(.a.
LANDING- CURB RAMP - ND DUTTER - SEF NOTE A
LANDING �O OT a
DEPRESSED CUM AND GUTTER -
SEE STANDARD PLAN P40.12 CLUB RADIUS DETAIL
SECTION O m
CEMENT S' PA CURB RAMP RYPE
PERPENDICULAR�-A q4o +56sAA0 2Q'
PPPERPENDICULARULAR UTAR B' PAY LINT - 8tF fKYfE B e I STb
10 AL eNG
S•30 (3
PERPENDICULAR
CURB RAMP
STANDARD PLAN F-40.15-02
SHEET 1 0= 1 SHEET
APPR OF R BLIGATION
auo
ISOMETRIC VIEW ISOMETRIC VIEW '•rco "r,:c.Aw ,a
TYPE PERPENDICULAR A PAY LIMIT TYPE PERPENDICULAR B PAY LIMIT w.Mk,.s" sra. 0..."i.-..r -----
NOTES:
1. TRUNCATED DOMES TO BE HIGH CONTRAST, NOT YELLOW
5tt utlAll 10 3/6" PREMOLDED
c JOINT MATERIAL
FLUSH WITH PAVEMENT LIT. PERP. OR RADIAL
TO CURB (TYP)
NOTES:
1. RAMP AND APPROACHES SHALL BE KEPT CLEAR OF
OBSTACLES INCLUDING HYDRANTS, POLES AND INLETS.
2. DETERMINATION OF RAMPING OF SIDEWALKS SHALL BE
AS DIRECTED BY THE ENGINEER.
3. 24" WIDE WARNING STRIP SHALL BE PROVIDED ADJACENT
TO THE EXPANSION JOINT AS SHOWN.
VERTICAL CONCRETE CURB
OR EXTRUDED CURB
I
F
O
PRIVATE ON -SIZE
ONLY
NTS
In -Line Access Ramp 5
1' TAnrn
.LT PAVEMENT
GRADE
PRIVATE ON -SIZE
ONLY
NTS
Tapered Curb End
9
City Of Renton Std Dtl F-40.15-02
Standard Access Ramp
CONCRETE SIDEWALK
SEE DETAIL
�1
3/8" PREMOLDED
DEPRESSED CURB FLUSH W/ PAVEMENT
SEE DETAIL
c
CONCRETE VERTICAL CURB
SEE DETAIL
\ CC3.1100
DRIVEWAY APPROACH OR ASPHALT PAVING
SEE DETAIL (a)OR ; ' 1
C3.1-2 C
NOTES:
1. RAMP AND APPROACHES SHALL BE KEPT CLEAR OF
OBSTACLES INCLUDING HYDRANTS, POLES AND INLETS.
z
PRIVATE ON -SITE
ONLY
NTS
Corner Access Ramp
CONCRETE WHEEL STOP W/
(1) NO. 4 BAR (EACH END)
APPLY EPDXY RESIN TO
CONTACT SURFACES
ASPHALT PAVING
a a a EMBED DOWEL
0 00 00 0 6" MIN.
)oo a000a000aoo
NTS I 0
Wheel Stop
W
0
2
z
cc
a
0
Approved By:
Approved By:
Approved By:
Approved By:
In Compliance W/ City Of Renton Standards
Date: _
Date:
Date:
Date:
VARIES (SEE CONTRACT)
BROOMED
(SEE NOTE 1)
1 VARIES (SEE CONTRACT)
FINISH (TYP.)
GROOMED
CEMENT CONIC PEDESTRIAN CURB (TYP.) 3/8" (IN) EXPANSION JOINT (TYP.) -
SEE STANDARD PLAN F-30.10
(SEE NOTE 1)
FINISH (TYP,) DRIVEWAY
ENTRANCE
(WHEN SPECIFIED IN CONTRACT) -
SIDEWALK
SEE STANDARD PLAN F-10.12
(TYP )
318" (IN) EXPANSION JOINT
(TYP.) -SEE STANDARD -
CEMENT CONC SIDEWALK CEMENT CONCRETE
3" (IN) R.
(TYP-)
PLI AN F-30.10
SIDEWALK
MATCH SIDEWALK WIDTH
(SEE CONTRACT)
*�
*�
A
(SEE CONTRACT)
I
I
I
PLAN VIEW CEMENT CONCRETE CURB
B CEMENT CONCRETE AND GUTTER (SEE NOTE 3) 5' - 0 2' - 6"
DRIVEWAY
TAPER (TYP) C
DRIVEWAY ENTRANCE
TYPE 1 CURB AND GUTTER NOTES
(SEE NOTE 3)
(TYP•)
(TVP)
PLAN VIEW
SIDE SLOPE (TYP)
TYPE 2
1. When the driveway width exceeds 15' (ft), construct a full depth
15' MAX. (SEE NOTE 8)
VARIES
15' MAX. (SEE NOTE 6)
expansion joint with 318" (in) joint filler along the driveway centerline.
112" (IN) UP BETWEEN
GRADE
(TYP)
(SEE CONTRACT)
(TYP) >
See Standard Plan F-30.10. Construct expansion joints parallel
ROADWAY GUTTER
BREAK
GRADE
GRADE BREAK
with the centerline as required at 15' (ft) maximum spatting when (SEE CONTRACT)
AND CURB,OR SEE
BREAK
NOT STEEPER THAN
* *
- (SEE CONTRACT)
e driveway widths exceed 30' (ft).
CONTRACT PLANS
ROAD GRADE
�^
,.-,•::...•'-. 2. See Standard Plan F-30.10 for sidewalk details. 112" (IN) R- (TYPO
*
ra
DEPRESSED CURB AND
•'
3. Curb and Gutter shown: see the Contract Plans for the
GUTTER (SEE NOTE 3)
PEDESTRIAN RAMP
a 4
1 PEDESTRIAN RAMP curb design specified. See Standard Plan F-10.12 forto
-
CEMENT CONCRETE
�� Curb Details.
3/8" (IN) EXPANSION JOINT (TYP.) - DRIVEWAY
SIDEWALK (TYP-) SECTION L N 1 SEE STANDARD PLAN F-30.10 4. Avoid placing drainage structures, junction boxes (SEE NOTE 7) SIDEWALK
DRIVEWAY RAMP
or other obstructions in front of driveway entrances. 318" (IN) EXPANSION JOINT MP) -
112" (IN) LIP BETWEEN SEE STANDARD PLAN F-30.10
ROADWAY GUTTER 5. Where "GRADE BREAK" is called out, the entire length of the SECTION C
(SEE CONTRACT) (SEE CONTRACT) AND CURB (OR SEE line between the two adjacent surface planes shall be flush.
1l2" (IN) R
CONTRACT) LEGEND
6, The Pedestrian Ramp length is not required to exceed15 feet
(TYP.)
(SEE CONTRACT)
a
rrAND
DEPRESSED CURB (unless otherwise shown in the Contract Plans). When applying SLOPE IN EITHER DIRECTION
ON
GUTTER the 15-foot max. length (measured from back of sidewalk) the
•. ,.... ,.. -y
: . •
* fD
C
(SEEN E 3) p 1.5% OR FLATTER RECOMMENDED FOR
running slope of the pedestrian ramp is allowed to exceed 8.3 /o. * DESIGNIFORMWORK MAX.)
• • `'' '
(2%
Use a single constant slope from bottom of ramp to top of
7 5% OR FLATTER RECOMMENDED FOR
OTT 2�
c�G L
DRIVEWAY RAMP ramp to match into the sidewalk over a horizontal distance * * DESIGNIFORMWORK (8.3% MAX.)
A, O1 USg!
DRIVEWAY 3/8" (IN) EXPANSION JOINT (TYP) - of 15 feet. (SEE NOTE 6)
4 yAti�
(SEE NOTE 7) SEE STANDARD PLAN F•30.10 7. Beyond limits shown. Pay item does not include driveway.
All,
SECTION O See Contract Plans -
"CEMENT CONCRETE DRIVEWAY
C
ENTRANCE TYPE 2" PAY LIMITS
"CEMENT CONCRETE DRIVEWAY 1� CONTRACTION JOINT (TYP.) - SEE STANDARD PLAN F-30.10
ENTRANCE TYPE 1" PAY LIMITS FOR RAMP LENGTHS GREATER THAN 8' - 0" PROVIDE
S T BV t�
CONTRACTION JOINT EQUALLY SPACED 4'- 0" MIN. OC.
sSIONAL g�G
DRIVEWAY
(SEE NOTE 7) �/ u
DRIVEWAv ;}.} 1.-I -I .�.T.Zn i'V
CL 4000 CONCRETE
PER STANDARD SPEC. 5-06.3
ISOMETRIC VIEW
TYPE 1 - PAY LIMITS
o n' MIN _ --
�LXISIING A5PHA
PAVEMENT
SAWCUT
(SEE NOTE 2)
ARTERIAL STREET MINIM
7" HMA (or ACP Class B)
(SEE NOTE 1), OVER
6.. CRUSHED ROCK
RESIDENTIAL STREET MINIMUM I
4" HMA (or ACP Class B)
(SEE NOTE 1). OVER
6" CRUSHED ROCK
NOTES:
1. MUST MATCH EXISTING THICKNESS IF GREATER,
2. SAWCUT SHALL BE POSITIONED 1' - 0" BEYOND EDGE OF
DAMAGED PAVEMENT.
3. THE INTENT OF THIS DESIGN IS TO DESCRIBE PAVEMENT
PLACEMENT AT THE GUTTER FACE. SEE STANDARD PLAN
FOR CEMENT CONCRETE CURBS -
PUBLIC WORKS
?E�1• DEPARTMENT
Fc14s7m;if;`: tli;!
CURB AND GUTTER
REPLACEMENT DETAIL
(SEE N
CL 40DO CONCRE
PER STANDARD SPEC. 84
City Of Renton Std Plan 103 I I
Curb And Gutter Replacement
CEMENT CONCRETE
DRIVEWAY ENTRANCE
TYPES 1, 2, 3, & 4
STANDARD PLAN F-80.10-04
SHEET 1 OF 2 SHEETS
APPROVED FOR PUBLICATION
�q�cra:,. kIT
_ . �a �,IL.�L ]J,'ll
STATE DESIGN ENGINEER
Alllllllh
Washington State D•portmenl of Tronsporlalion
170
City of Renton Std Dtl F-80.10-04
Cement Concrete Driveway
:3
Not UseNd 12
TITLE
LONGACRES
BUSINESS
CENTER
SW 27TH ST & NACHES
AVE SW
CONSULTANT COUGHLIN
PORTER
LUNDEEN
801 SECOND AVENUE - SUITE 900
SEATTLE, WA 98104
P: 206/343-0460
F: 206/343-569 I
A CONSULTING
STRUCTURAL AND CIVIL
ENGINEERING CORPORATION
ISSUED:
DATE DESCRIPTION
03/09/2016 BUILDING PERMIT RESUBMITTAL
KEY MAP:
PROJECT NUMBER C152268-03
DRAWN BY SAS
ISSUE DATE 05/04/2017
SEAL
SHEET TITLE / NUMBER
Paving Details
C30
R-388312