HomeMy WebLinkAboutR_4013201MATCH LINE. SEE SHEET E361
1 10 1 10 20 '1 �. /- %)
SCALE: IN FEET
i�
GENERAL NOTES
1. NO EXPOSED GALVANIZED STEEL TO BE INSTALLED
ABOVE GRADE ON APRON. PVC COATED OR PAINTED
RIGID STEEL IS ACCEPTABLE.
2. UNDERGROUND STRAIGHT SECTIONS OF CONDUITS
SHALL BE CONSTRUCTED OF RIGID NONMETALLIC
SCHEDULE 40 PVC.
3. UNDERGROUND DISTRIBUTION CONDUITS SHALL BE
TRADE SIZE 4 OR 4" CONDUITS UNLESS NOTED
OTHERWISE ON DRAWINGS.
4. UNDERGROUND CONDUITS SHALL BE INSTALLED A
MINIMUM OF 36" BELOW GRADE.
5. CONDUIT SWEEPS SHALL BE CONSTRUCTED OF RIGID
STEEL (PVC COATED IF UNDERGROUND) WITH A
MINIMUM 48" BEND RADIUS.
6. UNDERGROUND CONDUITS SHALL HAVE 3/8"
DIAMETER NYLON PULLING TAPE, ROPE, OR STRAP,
WITH A TENSILE RATING EXCEEDING 2500 LBS
INSTALLED. PULLING TAPE SHALL HAVE 36" TAILS,
SECURED AT EACH END OF CONDUIT.
7. UNDERGROUND DATA CONDUITS SHALL BE SPACED A
MINIMUM OF 12" AWAY FROM ELECTRICAL CONDUITS.
THIS ALSO INCLUDES GAS, OIL, OR WATER PIPING.
MINIMUM SPACING IS REDUCED TO 3" WHEN
NG EMBEDDED IN CONCRETE.
8. CONDUIT PENETRATIONS IN HANDHOLES SHALL BE
INSTALLED WITH SCHEDULE 40 PVC BELL ENDS.
9. CONTRACTOR TO COORDINATE INSTALLATION OF
DATA/TELECOM PATHWAY, PRIOR TO INSTALLATION,
WITH BOEING'S CONTRACTED I.T. INSTALLER.
10. NO SECTION OF UNDERGROUND CONDUIT SHALL
EXCEED 600 FEET BETWEEN PULLING POINTS WITH
NO MORE THAN 180 DEGREES IN CONDUIT BENDS.
11. HORIZONTAL DATUM: WASHINGTON STATE COORDINATE
SYSTEM, NORTH ZONE, NORTH AMERICAN DATUM
1983(91). VERTICAL DATUM: NATIONAL GEODETIC
VERTICAL DATUM 1929 (NGVD29). VERTICAL DATUM
CONVERSION: NGVD29 TO THE NORTH AMERICAN
VERTICAL DATUM 1988 (NAVD88) = NGVD29 + 3.60
FEET.
CONSTRUCTION NOTES
PROVIDE 12"x12"x6" NEMA 4X SS, DATA PULL
BOX ON EQUIPMENT HARDSTAND.
PROVIDE BURIED CONDUIT WITH NYLON PULL
STRING.
KEY PLAN
SCALE: N.T.S.
LAKE WASHINGTON
L
CCASNE ENGINEERING, INC.
ELECTRICAL AND TECHNOLOGY CONSULTANTS
10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033
(425) 522-1000 WWW. CA SNE. COM JOB NO. 161-140
CIVIL PERMIT
SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE C4 UKAWN UAIt SUBTITLE CURRENT REVISION SYMBOL DATE
A APRON R INFRASTRUCTURE W4700331 CASNE CEC 06.08.18 wash j �� THIS DESIGN BAND/ R CHECKED 05.05.17 W4700331 A 06.08.18
�, �.�ILITY PARTIAL DATA PLAN
SPECIFICATION IS APPROVED DAT 05.05.17 SHEET
VIED BY DEPT. DATE DATINEER 05.05.17 TITLE APRON R INFRASTRUCTURE E360 E33
CHECKED
"d,p 35276 w� APPROVED RENT 0 N SITE JOB N0. COMP N0.
0 rsTER� ' W4700331
�SSIONAL�� 8ll APPROVED ]ELECTRICAL MASTER SITE RENTON, WA DWG No. 04-APRON-R-E360