HomeMy WebLinkAboutR_4013202I E510
I HP
IE51(
HE
I
I
I
E�
I
E51
HAF
MATCH LINE, SEE SHEET E362
i
i
i
i
i
i
i
V
i
)RELINE SETBACK
OF RENTON��
I I
ji
I I
I
I
g I
E51 -4 E3 1
I
I
I
MATCH LINE, SEE SHEET E360
..
04-/20 G /TOWER //
4-02Q' E58'1/- 11 E3
1 10 1 10 20 40
ice,_
1•_I•ll�_�-
SCALE: IN FEET
i
4-20
BUILDING
GENERAL NOTES
1.
NO EXPOSED GALVANIZED STEEL TO BE INSTALLED
ABOVE GRADE ON APRON. PVC COATED OR PAINTED
RIGID STEEL IS ACCEPTABLE.
0
2.
UNDERGROUND STRAIGHT SECTIONS OF CONDUITS
c
SHALL BE CONSTRUCTED OF RIGID NONMETALLIC
C'
SCHEDULE 40 PVC.
C'
C
3.
UNDERGROUND DISTRIBUTION CONDUITS SHALL BE
C
TRADE SIZE 4 OR 4" CONDUITS UNLESS NOTED
0
OTHERWISE ON DRAWINGS.
T
4.
UNDERGROUND CONDUITS SHALL BE INSTALLED A
MINIMUM OF 36" BELOW GRADE.
5.
CONDUIT SWEEPS SHALL BE CONSTRUCTED OF RIGID
STEEL (PVC COATED IF UNDERGROUND) WITH A
MINIMUM 48" BEND RADIUS.
6.
UNDERGROUND CONDUITS SHALL HAVE 3/8" DIAMETER
NYLON PULLING TAPE, ROPE, OR STRAP, WITH A
TENSILE RATING EXCEEDING 2500 LBS INSTALLED.
PULLING TAPE SHALL HAVE 36" TAILS, SECURED AT
EACH END OF CONDUIT.
7.
UNDERGROUND DATA CONDUITS SHALL BE SPACED A
MINIMUM OF 12" AWAY FROM ELECTRICAL CONDUITS.
THIS ALSO INCLUDES GAS, OIL, OR WATER PIPING.
MINIMUM SPACING IS REDUCED TO 3" WHEN
EMBEDDED IN CONCRETE.
cy
a
8.
CONDUIT PENETRATIONS IN HANDHOLES SHALL BE
c
INSTALLED WITH SCHEDULE 40 PVC BELL ENDS.
C
9.
CONTRACTOR TO COORDINATE INSTALLATION OF
T
DATA/TELECOM PATHWAY, PRIOR TO INSTALLATION, WITI-
BOEING'S CONTRACTED I.T. INSTALLER.
10.
NO SECTION OF UNDERGROUND CONDUIT SHALL
EXCEED 600 FEET BETWEEN PULLING POINTS WITH NO
MORE THAN 180 DEGREES IN CONDUIT BENDS.
11.
HORIZONTAL DATUM: WASHINGTON STATE COORDINATE
SYSTEM, NORTH ZONE, NORTH AMERICAN DATUM
1983(91). VERTICAL DATUM: NATIONAL GEODETIC
VERTICAL DATUM 1929 (NGVD29). VERTICAL DATUM
CONVERSION: NGVD29 TO THE NORTH AMERICAN
VERTICAL DATUM 1988 (NAVD88) = NGVD29 + 3.60
FEET.
CONSTRUCTION NOTES
PROVIDE 12"x12"x6" NEMA 4X SS, DATA PULL BOX
ON EQUIPMENT HARDSTAND.
PROVIDE BURIED CONDUIT WITH NYLON PULL STRING.
PROVIDE OLDCASTLE 3030-LA, OPEN -BOTTOM
CONCRETE HAND HOLE WITH ALUMINUM LID AND
HARDWARE. SEE CIVIL PLANS FOR LID RATING.
KEY PLAN
SCALE: N.T.S.
LAKE WASHINGTON
L
CCASNE ENGINEERING, INC.
ELECTRICAL AND TECHNOLOGY CONSULTANTS
10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033
(425) 522-1000 WWW. CA SNE. COM JOB NO. 161-140
CIVIL PERMIT
SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE L SUBTITLE CURRENT REVISIONSYMBOLSYMBOL n DATE 06.08.18
A APRON R INFRASTRUCTURE W4700331 CASNE CEC 06.08.18 4 �� was THIS DESIGN BAND/ R CHECKED 05.05.17 /�
�, ��, .� PARTIAL DATA PLAN
SPECIFICATION IS APPROVED DAT 05.05.17 SHEET
VIED BY DEPT. DATE DATINEER 05.05.17 TITLE APRON R INFRASTRUCTURE E361 E34
CHECKED
276 APPROVED
RENTON SITE
35�v� JOB N0. COMP N0.
�SS�rsTER� I W4700331 IONAL �� 8ll APPROVED ELECTRICAL MASTER SITE RENTON, WA DWG NO. 04-APRON-R-E361