200' SHORELINE SETBACK
PER CITY OF RENTON
GENERAL NOTES
1.
NO EXPOSED GALVANIZED STEEL TO BE INSTALLED ABOVE
GRADE ON APRON. PVC COATED OR PAINTED RIGID STEEL
IS ACCEPTABLE.
Q
2.
UNDERGROUND STRAIGHT SECTIONS OF CONDUITS SHALL BE
Cc'
CONSTRUCTED OF RIGID NONMETALLIC SCHEDULE 40 PVC.
0
C
3.
UNDERGROUND DISTRIBUTION CONDUITS SHALL BE TRADE
C
SIZE 4 OR 4" CONDUITS UNLESS NOTED OTHERWISE ON
0
DRAWINGS.
T
C
4.
UNDERGROUND CONDUITS SHALL BE INSTALLED A MINIMUM
OF 36" BELOW GRADE.
5.
CONDUIT SWEEPS SHALL BE CONSTRUCTED OF RIGID STEEL
(PVC COATED IF UNDERGROUND) WITH A MINIMUM 48"
BEND RADIUS.
6.
UNDERGROUND CONDUITS SHALL HAVE 3/8" DIAMETER
NYLON PULLING TAPE, ROPE, OR STRAP, WITH A TENSILE
RATING EXCEEDING 2500 LBS INSTALLED. PULLING TAPE
SHALL HAVE 36" TAILS, SECURED AT EACH END OF
CONDUIT.
7.
UNDERGROUND DATA CONDUITS SHALL BE SPACED A
MINIMUM OF 12" AWAY FROM ELECTRICAL CONDUITS. THIS
ALSO INCLUDES GAS, OIL, OR WATER PIPING. MINIMUM
SPACING IS REDUCED TO 3" WHEN EMBEDDED IN
CONCRETE.
cy
c
8.
CONDUIT PENETRATIONS IN HANDHOLES SHALL BE
C
INSTALLED WITH SCHEDULE 40 PVC BELL ENDS.
C
C
9.
CONTRACTOR TO COORDINATE INSTALLATION OF
r
DATA/TELECOM PATHWAY, PRIOR TO INSTALLATION, WITH
T
BOEING'S CONTRACTED I.T. INSTALLER.
G
10.
NO SECTION OF UNDERGROUND CONDUIT SHALL EXCEED
600 FEET BETWEEN PULLING POINTS WITH NO MORE THAN
180 DEGREES IN CONDUIT BENDS.
11.
HORIZONTAL DATUM: WASHINGTON STATE COORDINATE
SYSTEM, NORTH ZONE, NORTH AMERICAN DATUM 1983(91).
VERTICAL DATUM: NATIONAL GEODETIC VERTICAL DATUM 1929
(NGVD29). VERTICAL DATUM CONVERSION: NGVD29 TO THE
NORTH AMERICAN VERTICAL DATUM 1988 (NAVD88) _
NGVD29 + 3.60 FEET.
CONSTRUCTION NOTES
PROVIDE 12"x12"x6" NEMA 4X SS, DATA PULL
BOX ON EQUIPMENT HARDSTAND.
PROVIDE BURIED CONDUIT WITH NYLON PULL
STRING.
I C6
w
O KEY PLAN
I SCALE: N.T.S.
J LAKE WASHINGTON ,_83 HOTEL AT SOUTHPORT
J
o
N9
b
N. 8TH
g m .
dwxiNMU .:
i/�// ��^ i � tlHMHHMNMIHMNIHIXNry,1IM�pINb µp � - 1 PARKING
Q — \ �x -a SARAGE
MMHMMWH�YM,YIW 6WI�XNXXO nc�i
NA�IYIp A.4HWMWMfi1111®
_ 10-20
(>, N. 61H SiREEi
Q 5-407
O J 10-1fi
Q, oob r N
-- o b LOT 8JIIII -
MATCH LINE, SEE SHEET E362
1 10 1 10 20 41 �. /- %)
SCALE: IN FEET
i�
CCASNE ENGINEERING, INC.
ELECTRICAL AND TECHNOLOGY CONSULTANTS
10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033
(425) 522-1000 WWW. CA SNE. COM JOB NO. 161-140
CIVIL PERMIT
SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE L SUBTITLE CURRENT REVISIONSYMBOLSYMBOL n DATE 06.08.18
A APRON R INFRASTRUCTURE W4700331 CASNE CEC 06.08.18 4 �� was � THIS DESIGN BAND/ R CHECKED 05.05.17 / 1
�, �.�ILITY PARTIAL DATA PLAN
SPECIFICATION IS APPROVED DAT 05.05.17 SHEET
VIED BY DEPT. I DATE DATINEER 05.05.17 TITLE APRON R INFRASTRUCTURE E363 E36
CHECKED
35276 w� APPROVED RENTON SITE JOB N0. COMP N0.
°� ISTEg� I W4700331
�SS10 L �� 8ll APPROVED ELECTRICAL MASTER SITE RENTON, WA DWG NO. 04-APRON-R-E363