HomeMy WebLinkAboutR_4013217TO HARDSTANDS R10-R14
V45A/4
4"C, 3#600, #2/0 GNE
V45B/5
4"C, 3#600, #2/0 GND
SYM REVISION
APRON R INFRASTRUCTURE
`t J F P11\ LJ
HH-P1 HANDHOLE BUTTERFLY
SCALE: 1 "=1'-O"
TO HARDSTANDS
R10-R14
OPEN BOTTOM HAND HOLE
11 11E51'0-8
2"C, FIBER
OLDCASTLE
3030-LA
2"C, FIBER
TO 4-20 BLDG
HH-D1 HANDHOLE BUTTERFLY
SCALE: 1 "=1'-O"
BY APPROVED DATE
W4700331 CASNE CEC 06.08.18
SYM
3611E51'0-8
3'-6"
BY I APPROVED I DATE
TO HARDSTAND R3
2"C, FIBER
OPEN BOTTOM HAND HOLE
2"C, FIBER
2'
OLDCASTLE
3030-LA
2"C, FIBER
TO HARDSTAND R4
2"C, FIBER
HH-D2 HANDHOLE BUTTERFLY
SCALE: 1 "=1'-O"
TO HARDSTAND R3
2"C, FIBER
OPEN BOTTOM HAND HOLE
TO BLDG
04-82
OLDCASTLE
3030-LA
2"C, FIBER
TO HARDSTAND R4/
BLDG 04-82
HH-D3 HANDHOLE BUTTERFLY
SCALE: 1 "=1'-O"
Q� BOE/NG
C'—
��� of WAS L�T�
c)
35276IST
O�� ONAL����� �
E3641E510-8
,
SCALE: 1 "=1 '-O"
ACCEPTABILITY CASNE
THIS DESIGN AND/OR CHECK[
SPECIFICATION IS APPROVED CEC
N IN
;,ROVED BY DEPT. I DATE LDB
,
OPEN BOTTOM HAND HOLE
TO
HARDSTAND
R3
GRAPHIC SCALE:
mm��
91141
q I t SUBTITLE
08.22.17
08.22.17
TITLE
08.22.17
2"C, FIBER
GENERAL NOTES
1. HANDHOLE LID TYPE AND LEAD RATING TO BE CALLED OUT
ON CIVIL DETAIL DRAWINGS.
2. CONDUIT STUBS TO HAVEV PVC BELL ENDS INSTALLED. CI
C
3. DUCT BANK ELEVATION SHALL BE SET TO MINIMIZE
VERTICAL OFFSETS TO HANDHOLES WHILE MAINTAINING NO C
LESS THAN CODE MINIMUM BURIAL DEPTH. c
0
4. PROVIDE CONDUCTOR SERVICE LOOPS IN HANDHOLE. T
5. HANDHOLE LID TO HAVE NAME WELDED ON TO EXTERIOR
FOR EASY IDENTIFICATION.
6. BASE SHALL CONTAIN TWO 3" MINIMUM DIAMETER HOLES
TO ALLOW FOR DRAINAGE.
CONSTRUCTION NOTES
1. ALL VAULTS AND JUNCTION BOXES SHALL MEET THE
LOAD RATING SPECIFIED ON SHEET G2.
2. FRAME AND GRATE FOR 3030-LA VAULT SHALL BE
NEENAH FOUNDRY PRODUCT R-3498-K2S OR APPROVED
SIMILAR. COORDINATE FRAME AND GRATE DETAILS WITH
MANUFACTURER BEFORE FABRICATION OF VAULTS.
3. FRAME AND GRATE FOR 444-LA VAULT SHALL BE
NEEMAH FOUNDRY PRODUCT R-3498-R2S OR
APPROVED SIMILAR. COORDINATE FRAME AND GRATE
DETAILS WITH MANUFACTURER BEFORE FABRICATION OF
VAULTS.
�2"C, FIBER
OLDCASTLE
3030-LA
HH-D4 HANDHOLE BUTTERFLY
SCALE: 1 "=1'-0"
HAND HOLE DETAILS
APRON R INFRASTRUCTURE
APRON R
TO
HARDSTAND
R2
651E510-8
CECASNE ENGINEERING, INC.
ELECTRICAL AND TECHNOLOGY CONSULTANTS
10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033
(425) 522-1000 WWW. CA SNE. COM JOB NO. 161-140
[CIVIL PERMIT
a, =====No
W47003311 — 1 06.08.18
E510-8 E49
JOB NO. COMP NO.
W4700331
RENTON, WA DWG N0. 05-APRON-R-E510-8
D
7
D
ELECTRICAL MASTER