1. FIRE HYDRANTS SHALL BE WATEROUS PACER HYDRANT, MODEL
WB67-250, U.L. AND F.M. APPROVED, DUCTILE IRON, 3-WAY WITH 5
1/4" PUMPER CONNECTION. HYDRANTS SHALL HAVE STORZ ADAPTER
AND CAP INSTALLED. PIPING SHALL HAVE 3-FEET (MIN.) COVER.
FURNISH EXTENSION KIT IF GREATER COVER IS NEEDED. FERGUSON
ITEM AND DESCRIPTION A FOLLOWS:
HYDRANT DESCRIPTION: 5-1/4 WB67 UL/FM 4'OL/A MJ
WHITE HYDRANT NO: P-WB67LAOLPUL/FM STORZ ADAPTER AND
CAP DESCRIPTION: 4-1/2X5 FNST STORZ ADPT W/CAP
NEW FIRE HYDRANT
MATCH EXISTING HOSE PORT
SIZES AND THREADS
PUMPER CONNECTION
TO FACE AS PER PLAN
cV
GRADE
CONC THRUST BLOCK
3000 PSI @ 28 DAYS
BEARING AREA = 3 SF
POLY COVER o 0
OVER GRAVEL
NEW 6" GATE
VALVE (FLXMJ)-
\\ �^00 D°
o O Op°
o °
o
CONC BLOCK 4"x16"x16"
DO NOT COVER DRAIN
1/2 CY OF GRAVEL
BACKFILL FOR DRAINS
TWO 3/4" DIA
SHACKLE RODS
COAT W/ BITUMASTIC
2. SEE FACILITIES DESIGN STANDARD D38108-1, FIGURE 3.
3. ALL NEW FIRE LINES ARE DESIGNED WITH RESTRAINED JOINTS.
4. THE FIRE HYDRANT BOLLARD LAYOUT SHOWN REPRESENTS TYPICAL
SPACING ONLY. REFER TO SITE PLANS AND DETAILS FOR LOCATIONS
WHERE ADDITIONAL OBSTRUCTIONS DICTATE SPECIAL CONFIGURATIONS.
5. OMIT BOLLARDS WHERE OTHER BARRIERS PREVENT RISK OF DAMAGE.
NEW CAST IRON VALVE
BOX W/ SLIDE EXTENSION
�NEW TEE OR REDUCER
AS IDENTIFIED PER PLAN
UNDISTURI
SUBGRADE
CONC THRUST BLOCK
-3000 PSI @ 28 DAYS
FIRE HYDRANT ASSEMBLY SECTION
M260 SCALE: NTS
THRU
M265
00 3„
NI MIN. LETTERS
ENTERED
CN�Fill
SEC
2,-0"
4" STEEL GUARD POST
TYPICAL 4-PLACES
0
2.5' (MIN.)
I
I
i
0 0
FIRE HYDRANT BOLLARD LAYOUT (TYP.
PAINT RED BLOCK LETTERS
SIZED TO FIT AVAILABLE
SPACE, TYP
PAINT WHITE
BACKGROUND
STAND PIPE
VALCOM
POSITION
INDICATOR -
3"
MIN.
RED 3" INTERIOR PAINT MARKINGS DETAIL
LETTERS, TYP
SURFACE PAINT MARKINGS DETAIL
00
I
N
of
w
0
U
.__-
O
I
N
"OPEN" TARGET PLATE
NOTE: TARGET PLATES SHALL BE
ORIENTED TO BE READ WHEN
LOOKING IN DOWNSTREAM DIRECTION
OF FIRE WATER FLOW.
SHUT" TARGET PLATE
-ADJUSTABLE
INDICATOR POST
GRADE
FIRE RISER PIV ONLY:
1 " CONDUIT FOR TAMPER SWITCH
VALVE (FL)
4" STEEL GUARD POST
TYPICAL 4-PLACES
r--------------0
171
z
2.5' (MIN.)
LO
N
I � I
I I
I I
I I
I I
I I
I I
I I
I I
O O
PIV BOLLARD LAYOUT (TYP.)
NOTE:
THE PIV BOLLARD LAYOUT SHOWN REPRESENTS
TYPICAL SPACING ONLY. REFER TO SITE PLANS
AND DETAILS FOR LOCATIONS WHERE ADDITIONAL
OBSTRUCTIONS DICTATE SPECIAL CONFIGURATIONS.
OMIT BOLLARDS WHERE OTHER BARRIERS
/\\/\\/\\ 71a \ \\/\\/\\/ PREVENT RISK OF DAMAGE.
%/%i%/ii,// °////�//�//\� UNDISTURBED
SUBGRADE
d D 9
ONC THRUST BLOCK
D a D
D 3000 PSI @ 28 DAYS
�2 POST INDICATOR VALVE (PIV) TYPICAL SECTIO
M263 SCALE: NTS
M264
PLAN VIEW
NEENAH FRAME AND LID MODEL # R5900-B
WITH CASTING INSERT READING "FIRE"
PAINT WHITE MOUNTED FLUSH WITH EXISTING GRADE SEE INTERIOR PAINT
MARKINGS DETAIL
BACKGROUND
FINISH GRADE _j
-INSERT ACTUAL SECTION
VALVE NUMBER FOR XXX
NOTES:
1. COORDINATE ALL WORK WITH BOEING.
2. INSTALL THE VALCOM MODEL 179-LP6 LOW PROFILE POSITION INDICATOR PER THE
MANUFACTURER'S RECOMMENDATIONS. THE TOP OF THE 2-INCH AWWA NUT SHOULD BE
APPROXIMATELY 3-INCHES BELOW THE FINISHED GROUND ELEVATION. THE VALVE POSITION
INDICATION SHALL BE LOCATED FACING THE ADJACENT BUILDING, OR ORIENTED AWAY FROM
WHERE THE VALVE WILL MOST LIKELY BE OPERATED TO ALLOW THE OPERATOR TO READ THE
VALVE POSITION EASILY.
3. PLACE THE REBAR, NEENAH MODEL R-5900-B FRAME AND LID, AND CONCRETE AS SHOWN TO
THE FINISHED ELEVATION.
4. PAINT WHITE BOX AROUND THE VALVE (AS SHOWN). PAINT "FIRE" AND "SEC ###" ON TWO
SEPARATE LINES IN RED BLOCK LETTERING WITHIN THE WHITE PAINT BOX BENEATH THE VALVE
AS SHOWN. ### SHALL REFER TO THE ACTUAL VALVE NUMBER IN THE FIELD.
`4� FUSH SECTION VANE DETAILS
M262 SCALE: NTS
1__1/
THRU
M263
M265
#4 x 30" EPDXY
COATED REBAR
(8 PLACES)
SEE SURFACE PAINT
MARKINGS DETAIL
U
#4 REBAR (BEYOND)
a<
a ° a
� ° a
N 2" AWWA NUTa V'ALC0�1 IOW °PROFILE
° a a POSITION INDICATOR a °
a ° ° a o °a
° MODEL, # 179-6P6 v v
°
ADJU$T VALVE STEM AND'INSTALL 2" AWWA NUT
° a g TO` -BE APPROXIMATELY' 12" ,FROM FINISHED GRADE.
a a o
a °STANO°PIPE
° v
SECTION A
PIPE BEDDING NOTES:
1. ALL BACKFILL MATERIAL SHALL BE PLACED IN LOOSE
LAYERS OF NOT MORE THAN 6" DEPTH AND COMPACTED
TO AT LEAST 95% OF MAX. DENSITY PER ASTM D1557.
2. FOR ADDITIONAL REQUIREMENTS SEE THE GENERAL NOTES
ON SHEET G2.
3. IF TRENCH SUBGRADE IS DETERMINED TO BE UNSUITABLE
BY THE GEOTECHNICAL ENGINEER DURING CONSTRUCTION,
PROVIDE GEOTEXTILE FABRIC FOR SUBGRADE
STABILIZATION AS DIRECTED BY THE BOEING
CONSTRUCTION MANAGER PER THE GEOTECHNICAL
ENGINEER'S RECOMMENDATIONS.
4. MINIMUM COVER OVER PIPE WITH PERMANENT CONCRETE
PAVEMENT SECTION AS SHOWN IS REQUIRED TO PREVENT
DAMAGE DUE TO LOADING. CONTRACTOR SHALL PROVIDE
ALTERNATIVE METHOD OF PIPE AND TRENCH PROTECTION
IF TEMPORARY PAVEMENT SECTION IS USED.
RIGID PIPE FLEXIBLE PIPE
(DUCTILE IRON, STEEL) (PLASTIC, PVC)
DETECTABLE WARNING TAPE PAVEMENT, SEE PAVEMENT SECTIONS
CSBC, SEE PAVEMENT SECTIONS
o °a
° 14 1/2" 30" MIN COVER
° o
MIN SEE NOTES
TRENCH BACKFILL
SHALL BE CSBC
PER WSDOT STD
SPEC 9-03.9(3) -
/ °° '0- 000°000 000°00°°000 0
GEOTEXTILE FOR o ° °oo o °00 0 °o o °00 00 00 00 00
AS REQUIRED FOR \ 0000 0000000o 000o 0000 °oo ° °o°
/1000 0000000°000°o00°00°°0°°
OVEREXCAVATION. 00 °°00°° °° 0°°00°° 0°0
SEE NOTE 2. °
QUARRY SPACES FOR
AS REQUIRED FOR MIN TRENCH WIDTH
OVEREXCAVATION.
SEE NOTE 2. FOR PIPE DIAMETER < OR = 15";
WIDTH = PIPE DIA + 30"
FOR PIE DIAMETER > 15";
TYP. PPE BEDDING SECTION- WIDTH = (PIPE DIA X1.5) + 18"
�
M110-M115 SCALE: NTS
M260-M265
E110-E115
R360-E365
9 1/2" MIN
6" MIN
PIPE
OUTSIDE
DIAMETER
6" MIN
12" MIN
OVEREXCAVATION
AS REQUIRED
SEE NOTES (TYP)
PIPE BEDDING PER
WSDOT 9-03.12(3)
SEE PAVING PLANS
TRENCH BACKFILL SHALL BE DETECTABLE
CSBC PER WSDOT STD WARNING TAPE. 6" MIN ABOVE CROWN (TYP.)
SPEC 9-03.9(3) SEE WSDOT STANDARD SPEC. 9-29.1(6)
p d. d 1 .p u
pa a d 4.
p d p z d d
d z p . d. d
d d. p' g z p a d p_
9 d• p d d.
p. d p. ^ d d d. p p,
d N 4 d d N d d V p'
p d
d d p d p d. p d• p. d dd
Ai
1' 2.25' 1' 1' 1'
SEE NOTE 6 BELOW
6 MIN.
QDIAM, TYP. OF
6" MEN. UTILITIES
- 3" AIR (TYP.)
PIPE BEDDING PER WSDOT SEE MECHANICAL PLANS FOR SIZE TYP. OF ALL UTILITIES
IN ALL LOCATIONS
STD SPEC 9-03.12(3) 2" DOMESTIC WATER (TYP.) SEE
FIRE PROTECTION AND WATER PLANS
3 - 4" POWER FOR SIZE IN ALL LOCATIONS
+ 1 - 4" SPARE
3-3"COMM
SEE NOTE 6 BELOW
NOTES:
1. ALL BACKFILL MATERIAL SHALL BE PLACED IN LOOSE LAYERS OF NOT MORE THAN 6" DEPTH AND
COMPACTED TO AT LEAST 95% OF MAX. DENSITY PER ASTM D1557.
2. FOR ADDITIONAL REQUIREMENTS SEE THE GENERAL NOTES ON SHEET G2.
3. IF TRENCH SUBGRADE IS DETERMINED TO BE UNSUITABLE BY THE GEOTECHNICAL ENGINEER DURING
CONSTRUCTION, PROVIDE GEOTEXTILE FABRIC FOR SUBGRADE STABILIZATION AS DIRECTED BY THE BOEING
CONSTRUCTION MANAGER PER THE GEOTECHNICAL ENGINEER'S RECOMMENDATIONS.
4. MINIMUM COVER OVER PIPE WITH PERMANENT CONCRETE PAVEMENT SECTION AS SHOWN IS REQUIRED TO
PREVENT DAMAGE DUE TO LOADING. CONTRACTOR SHALL PROVIDE ALTERNATIVE METHOD OF PIPE AND
TRENCH PROTECTION IF TEMPORARY PAVEMENT SECTION IS USED.
5. POWER AND DATA CONDUIT ARRANGEMENT SHOWN REPRESENTS THE WIDEST CASE. REFER TO ELECTRICAL
PLANS FOR VARIOUS ELECTRICAL AND DATA SECTIONS.
5 PPE BEDDING AT JOINT UTILITY TRENCH
M 110-M 115 SCALE: NTS
M260-M265
E110-E115
E360-E365 SEPARATE FIRE PERMITS REQUIRED FROM RENTON
REGIONAL FIRE AUTHORITY R-4013164
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE
�N P. THIS DESIGN B AND/OR CHECKED JLC 06 08 18 MECHANICAL DETAILS - SHEET 1 W4700331 - 06/08/ 18
APRON R INFRASTRUCTURE W4700331 ABAM MGW 06/08/18 T� SPT 06 08 18 SHEET
WAsh��� G SPECIFICATION IS APPROVED
�P ENGINEER TITLE APRON R INFRASTRUCTURE M510-2 M21
APPROVED BY DEPT. DATE JLC 06 08 18
CHECKED
RENTON SITE
31271 o ww JOB NO. COMP NO.
AL
�clAPPROVED
ss�oN�W4700331
APPROVED CIVIL MASTER SITE RENTON, WA DWG NO. 4-APRON-R-M510-2
IWO
BergerABAM
33301 9th Avenue South, Suite 300
Federal Way, Washington 98003-2600
(206) 431-2300 Fax:(206) 431-2250