Loading...
HomeMy WebLinkAboutR_4013169UNIT SUBSTATION BREAKER RATINGS F — FRAME S — SENSOR X — RATING PLUG 5000 AF 5000 AS 5000 AX 5000A 10 14B SWBD BUS 13B �o TIE TO VAULT 49A l 800AF SEE SHEET 04-020—E4G—V49A of 0) VA6 800A 480/ 277 3" C, 3-500KC IL 235' 3"C, 3-500KCMIL 20' 175' 1-1 /2"C, 4#4 22,000 35,000 B3 400A 480/ 277 16,012/13,501 A3 VA6-4 100A 40A 480/ 480/277 277 FLOODS 19,156/15,686 28,071 /22,250 10' 1 1/2", 3#4 ------ 451<VA 4#1/0 10,000 3,351 /3,314 SYM REVISION — APRON R INFRASTRUCTURE (2) 4"C, 4#600, #2GND 85' 56,044/33,445 65,000 25' �1-1/2"C 3#2 35,000 VA6-3 100A 480/277 FLOODS 30,292/23,572 BY APPROVED DATE SYM W47003311 CASNE I CEC 1 06.08.18 12B •11: ALT.FDR. 2612A Q 13,244 11B 800AF b 800AF > 400AS ) 400AS 400AX 400AX 4"C, 3-500KCMIL & 1 #2 GND 200' 400 A AC-4 24,974/20,530 4 #4/0 & 1 #2GND(EA) 265' 25,000 PANEL A2-2 400 A MAIN BREAKER 22,627/18,352 2-1/2", 3#2/0 10' 45KVA (2)2-1/2", 4#4/0, #2 GND 6,042/5,892 A2-3 400A PDF.FDR. O 1A56 13,433 150E VAULT—V496 (4-20 COL. A6 OUTDOORS) 0 2500/4200KVA 13.8KV-480Y/277V �• FANS INSTALLED 5000 AF 5000 AS 1B p/ 5000 AX I 76 66 800AF > 400AS 400AX 4"C, 3-500KCMIL & 1 #2 GND 224' 400 A AC-3 22,919/19,168 5' 5' 2-1/2", 4#4/0 10,000 10,000 A2-4 5,925/5,782 A2-5 5,925/5,782 225A 225A BY I APPROVED I DATE 800AF 400AS 400AX - 4"C, 3-500KCMIL & 1 #2 GND 239' 400 A AC-2 21,803/18,407 ,. ,.m Erne up. 800AF 400AS 400AX -4"C, 3-500KCMIL & 1 #2 GND 254' 400 A AC-1 20,795/17,707 SECTION 1 5B 99,341/49,884> 4B 600AF 600AS 400AX (2) 2 1 /2"C, 4#4/0 THHN 85' 48,162/33,073 PNL VA6-2 277/480V LTG. HB 65,000 LINE 1 SECTION 2 SECTION 3 b) soonF 0 SECTION 4 111 b� 800AF 0 SECTION 5 6A 66 METERING WC-1 METERING AC-1 METERING 1A 7A 10 76 16 TIE BREAKER MAIN BREAKER PANEL A2 AC-2 MAIN BREAKER V49A V496 2A 4A 8A 136 116 86 46 213 PANEL A6-1 VA6 PANEL A2-2 AC-3 3A 5A 9A 146 126 96 56 313 HPU-1 AC-4 VA6-2 VAULT V49A VAULT V49B Q� BOE/NG C'— N. N �4� of WAS L�T� t14 16� 35276 c�,4 o�� S -IOIST 08 ELEVATION ACCEPTABILITY HGG THIS DESIGN AND/OR CHE( SPECIFICATION IS APPROVED DAT ENGI *&OVED BY DEPT. DATE DAT 41 L SUBTITLE 05.05.17 05.05.17 TITLE 05.05.17 LEGEND XXX/XXX AVAILABLE FAULT CURRENT 0 (CLOSED TRANSITION NORMAL) C XXX AIC RATING OF EQUIPMENT C C XXXX FEEDER LENGTH Q T C REFER TO DRAWING 04-020—E549 FOR VAULT 49A ELEVATION AND SCHEDULE. MAIN & TIEBREAKERS — CAT. NO. MDS85003WEA-501 GA—NAN4Y—NANAX FEEDER BREAKERS — CAT.NO. MDS8083WEA-121GA—MAN2Y—NANAX FEEDER BREAKERS — CAT. NO. MDS8163WEA-121GA— MAN2Y—NANAX REFERENCE DRAWINGS REFER TO DRAWING 04-020-E549 FOR VAULT 49B T ELEVATION AND SCHEDULE. cy 04-020-HBE500 ELECTRICAL VAULT DETAILS C C r T W»�ral011ralILImil ra,II�� DISCONNECT AND REMOVE CONDUCTORS FROM SOURCE BREAKER TO HARDSTAND TAP BOXES. REMOVE ABOVE GRADE CONDUIT AND ABANDON BELOW GRADE CONDUIT IN PLACE. DISCONNECT AND REMOVE APRON R HARDSTAND AND ALL ASSOCIATED EQUIPMENT, DISCONNECTS, RECEPTACLES AND TAP BOXES. CECASNE ENGINEERING, INC. ELECTRICAL AND TECHNOLOGY CONSULTANTS 10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033 (425) 522-1000 WWW. CASNE. COM JOB NO. 161-140 CIVIL PERMIT] W47003311 06.08.18 APRON R INFRASTRUCTURE E4FI-V49BR El BUILDING 04-020 J06 N0. COMP N0. VAULT V49B W4700331 ELECTRICAL MASTER COL. A6 EXTERIOR RENTON, WA DWG No. 04-020—E4H—V49BR REMOVAL ONE LINE DIAGRAM