HomeMy WebLinkAboutR_4013185FROM PLATFORM "V9"
PFD FDR
1A6B
v/ ALT. FDR.
i 2B12A
EXIST. IN
BEDG 4-20
2B12A PE
„F„ „F„
1A6B
12,387
I
LJ �
600A,15KV,FUSED S1
MV SELECTOR SW.
SYM REVISION
A SUBSTATION V45A AND V45B INSTALLATION
B ARC FLASH STUDY
- RECORD DRAWING
C APRON R INFRASTRUCTURE
BY
W1808396 CASNE
CASNE
CASNE
W4700331 CASNE
LOAD —--- --T :f14
PANEL "A9"
MAXIMUM PEAK
DEMAND
METERED FOR
30
DAYS OF 2/25/13
76.7
AMPS
PEAK DEMAND
@
125%
PER NEC 220-87
95.9
AMPS
PANEL "XA7-1
"
MAXIMUM PEAK
DEMAND
METERED FOR
30
DAYS OF 2/25/13
21.1
AMPS
PEAK DEMAND
@
125%
PER NEC 220-87
26.4
AMPS
15KV CABLE
13,129
F----------------------�
-I rl
`1 1 I K
PT/S2 CPT
1000/1333 kVA
125E 13,800-480Y/277V
30,4W
.A. oa— _
TAP BOX
LOADBANK
200A
�200A
150KW@.8PF =_
277/48OV, 30,4W
CUMMINS
MODEL 6CTA8.3-GSL
S/N E890236048
SEE NOTE 1
(2) 1 A
TB
MAIN
2000:5(3)
2000AF1 N
2000AT
25T-1
52 86 25X-1 �o 0
25-1 11'
�
2 SETS OF 800:5
4"C, 4#50OKCMIL,
#1/0 GND
26,268/16,852 207
25,000 A9
2",4#4/0 800A
DIST.
+ #2/0 GND LMAIN
85,000 72
NORMAL
EMERGENCY
225A,3P
AUTO TRANSFER
SWITCH
O
17,113/12,715
XA-7
14,000 225A
LMLR & LTG DST
NEW M LO
11 /2"C3#4
UNIT SUB V45A
CIRCUIT BREAKER TRIP SETTINGS EATON MAGNUM DS WITH DIGITRIP 1150
BREAKER
NO.
SENSOR
RATING
PLUG
RATING
LONG TIME
SHORT TIME
INST.
PICKUP
GROUND FAULT
MAINTENANCE
MODE
PICKUP
DELAY
PICKUP
DELAY
PICKUP
DELAY
MAIN
2000A
2000A
1
17.5
2.5
0.3
0.4
0.2
2.5
1 D
800A
800A
1
24
2.5
0.45
5
2.5
2A
2B
800A
800A
2C
800A
800A
2D
800A
800A
1
21
4
0.2
6
2.5
2B12A
65,000 48OV, 2000 BUS7
, 5,752/22,89
Ln
�� � �
00 00
�oo �oo
0000 S S
A 800:5 A 800:5
PB 110
2 SETS OF (2)4"C PVC, 3#600kcmil
105 4"C, 3#50OKCM1 ,
0,F #2/0 GND
#1/0 GND
MCC #1 1
800A (2)4"C PVC, 3#600kcmil 2
480V V45 #2/0 GND R14
35,000 34,886/20,362 -1 PULL BOX TAP BOX
L 645 L
67 2
1-1 /2",3#2/0 „
O
2"RGS,
4#4/0
3#4/0 25 15,310/11,734
65,000
MCC #2
400A (225A)
480V
480V,30 1 /2" 3#8
EXIST.
11 /2"C3#6
65
�rr
30KVA XFMR,
XA71 480
120/208V 2"C 4#4/0
30.44W
O
O
�11/4",4#2
POWER XA7-1
TO MPZ (S. OF 100A
E. BRIDGE APPROACH) EVER LTC
M LO
APPROVED
DATE
SYM
CEC
07.16.14
RJJ
09.22.16
RJJ
12.20.17
DAL
06.08.18
REVISION
XA7-2
225A 16,718/12,505
LMLR & LTG DIST
MEO 14,000
—SEE NOTE 1
3"RGS,
4#4/0
112.5 KVA XFMR, A9- 2 C, 3#3/0,
48OV-120/208V 30,4W #1/0 GND
� IY7
5
3"C-4#
500 MCM
A9-2
500 400A
PWR & LTG DST
M EO
2",4#4/0
B8 l
225A
PWR & LTG
MAIN
TO BLDG. 4-67
"BOATHOUSE"
(CITY OF RENTON)
_ - NOTE #1
D31
225A
PWR & L_
MAIN
VAULT V45A ORE E H E D AC RAM
BY I APPROVED I DATE
"T
rrh A
mzm
3 200A 12,214/9,737
MCB
O
3/4"C, 2# 12,
#12 GND
KIRK KEY INTERLOCK TABLE
SUBSTATION 45A
S1
S2
MAIN
OPEN EITHER SWITCH DOOR
0
0
0
CLOSE S1
0
0
CLOSE S2
0
0
OPEN S1
0
OPEN S2
0
"0" OPEN POSITION REQUIRED FOR OPERATION
"S1" SWITCH 1
"S2" SWITCH 2
2000AF
135
(2)4"C PVC, 3#600kcmil
#2/0 GND
MPZ 365/364
R14-1 � R13
30A L TAP BOX
MCB 0 2"C, 3#3/0,
#1/0 GND
5 KVA
480V:120/240V
R 13 10,804/8,825
3 200A
MCB
oy waste LUG
���
`6 35276 w�
SIST
I DNA�
0
0 3/4„C 2#12
#12 GND
MPZ 364/363
R131
4 30A
MCB
5 KVA
48OV:120/240V
ACCEPTABILITY R. FARLEY
THIS DESIGN AND/OR CHECKED
SPECIFICATION IS APPROVED
- ENGINEER
'ROVED BY DEPT. I DATE L.BOYER
APPROVED
25X-
EECOD/SCHCCE
XXX/XXX AVAILABLE FAULT CURRENT SHOWN
(CLOSED TRANSITION/NORMAL)
XXX AIC RATING OF EQUIPMENT
0
XXX FEEDER LENGTH N FEET
C
0
GENERAL MOTES
c
c
1. UNLESS OTHERWISE NOTED PROVIDE/INSTALL ALL
p
CONDUIT, WIRE, SUPPORTS, PANELS, TRANSFORMERS,
T
BREAKERS.
C
2. ALL WORK SHOWN ON THE DRAWINGS AND INCLUDED IN
THE SPECIFICATIONS SHALL BE INCLUDED IN THIS JOB,
EXCEPT ASA SPECIFICALLY INDICATED OTHERWISE.
3. ELECTRICAL DEMOLITION: THIS ELECTRICAL
SUBCONTRACTOR SHALL BE FULLY RESPONSIBLE FOR ALL
ELECTRICAL DEMOLITION OF EXISTING ELECTRICAL
SYSTEMS NOT BEING RE -USED. DELIVER ALL EXPLOSION
PROOF ELECTRICAL EQUIPMENT TO THE OWNER FOR USE,
DISPOSAL, OR INSTRUCTIONS. SEE DEMOLITION DRAWINGS
OBSERVING AND EXECUTING THE GENERAL DEMOLITION
NOTES AND THE NOTES ON EACH SHEET. ALSO INCLUDE
THE SAME FOR THE DEMOLITION PHOTO BOOK.
4. THIS ELECTRICAL SUBCONTRACTOR SHALL ACQUAINT
THEMSELVES WITH ALL THE DRAWINGS OF THE BID
DOCUMENTS. THEY SHALL ESPECIALLY NOTE THE TYPE OF
CONSTRUCTION N THE AIRCRAFT PAINT AREA AND
T
COORDINATE THE ELECTRICAL INSTALLATION WITH ALL
a
ASPECTS OF THIS CONSTRUCTION.
C
C
5. ALL CONTROL PANELS AND CONTROL STATIONS WHICH
C
ARE ELECTRICAL AND WHICH ARE FURNISHED WITH
r
EQUIPMENT PURCHASED BY OTHER TRADES SHALL BE
T
MOUNTED AND WIRED INTO THE SYSTEM.
d
6. CLASSIFIED WIRING IN AND OUT OF CLASSIFIED AREAS:
-
THIS ELECTRICAL SUBCONTRACTOR SHALL BE
RESPONSIBLE FOR ALL CODE REQUIRED SEALS, DRAINS,
ETC. FOR COMPLETION OF ALL WIRING IN CLASSIFIED
AREAS SUCH AS CLASS 1, DIVISION 1, GROUP C & D
AREA WHETHER SHOWN ON THE DRAWINGS OR NOT.
7. WIRING INSIDE AIRCRAFT PAINT HANGAR: ALL WIRING
INSIDE THE AIRCRAFT PAINT HANGAR AREA SHALL BE
CONCEALED OUTSIDE THE AREA IN SO FAR AS IS
PHYSICALLY POSSIBLE. SEALS AND DRAINS FOR
CLASSIFIED WIRING SHALL BE ACCESSIBLE.
CONNECT PRIMARY SWITCH AUXILIARY CONTACTS
TO POWER MONITOR FOR SWITCH POSITION
STATUS REPORTING.
TAP BOX
REFERENCE DRAIIII NGS
0441E4
04-41-E8OX
C CONSTRUCTOEI NOTSo
PROVIDE PARALLEL SETS OF CONDUCTORS
FROM SOURCE BREAKER TO HARDSTAND R13
TAP BOX. USE EXISTING CONDUIT RACEWAY TO
PULL BOX ON 4-41 BUILDING. PROVIDE AND
EXTEND RACEWAY FROM PULL BOX/PULE BOX
TO HARDSTAND.
PROVIDE NEMA 4X STAINLESS STEEL, OR
APPROVED EQUAL, TAP BOX/PULE BOX.
C
PROVIDE 225A RATED, NEMA 4X SS, 48OV, 30,
3W PANELBOARD WITH 2O0A MAIN CIRCUIT
BREAKER AND MOLDED CASE BRANCH
BREAKERS.
4
PROVIDE 5KVA, 48OV:120/240V MINI POWER
ZONE RATED FOR OUTDOOR INSTALLATIONS.
PROVIDE BELOW GRADE CONDUIT AND
CONDUCTORS. SEE PARTIAL PLAN VIEW
DRAWINGS FOR ROUTING.
SUBTITLE
VAULT V45A - ONE LINE DIAGRAM
TITLE APRON R INFRASTRUCTURE
BUILDING 04-041
ELECTRICAL MASTER
CECASNE ENGINEERING, INC.
ELECTRICAL AND TECHNOLOGY CONSULTANTS
10604 NE 38th PL., SUITE 205 KIRKLAND, WA 98033
(425) 522-1000 WWW. CASNE. COM JOB NO. 161-140
CIVIL PERMIT
CURRENT REVISION SYMBOL DATE
W4700331 C 06.08.18
SHEET
E4 E17
JOB NO. COMP N0.
W4700331
RENTON, WA DWG N0. 0441E4