Loading...
HomeMy WebLinkAboutD_Mod_Decision_Form_Allura_at_Tiffany_Park_191216_v1DEPARTMENT OF COMMUNITY AND ECONOMIC DEVELOPMENT For City Use Only Project Number:_____LUA19-000316______ DECISION: Staff agrees with the applicant’s justification for Modification of Residential Design Requirements. The proposal satisfies the criteria listed in RMC 4-2-115.A.2 for approval of residential design modifications. Therefore, the Allura at Tiffany Park Residential Design Modification of the residential design requirements for the proposed single-family residential structures on Lot 47 of Allura at Tiffany Park, Project Number LUA19-000316, MOD is approved with conditions. Modification Granted Modification Partially Granted Modification Denied (See attached staff comments) ___________________________________________ _____ _____ Jennifer Henning, Planning Director Date Department of Community & Economic Development Conditions of Approval: 1. The applicant shall install a 2’ x 8’ upper floor belly band with the siding enhancements, as shown in the south facing elevation (Exhibit 4). The decision to approve the modification(s) will become final if not appealed in writing together with the required fee to: Hearing Examiner, City of Renton, 1055 South Grady Way, Renton, WA 98057 on or before 5:00 pm, on January 2, 2019. Additional information regarding the appeal process may be obtained from the Renton City Clerk’s office, Renton City Hall – 7th Floor, (425) 430-6510. This decision expressly approves the specific request(s) to: reduce the minimum windows and doors requirement from twenty-five percent (25%) of all façades facing street frontage or public spaces based on a thorough analysis of the building elevations facing the secondary front yard or south facing elevation (Exhibit 1). The proposed glazing on Allura at Tiffany Park, specifically Lot 47 (Exhibits 2 and 3, Site Plan), includes a maxed out combination of additional and enlarged windows and siding enhancements in an attempt to reach the twenty five percent (25%) window and door coverage requirement (Exhibit 4, Sheet A6-DTL and Exhibit 5, Building Drawings). Moreover, the submitted elevations were found to sufficiently comply with the guidelines and intent of the residential design windows and doors provision of Renton Municipal Code (RMC 4-2-115.E.3). Other design elements or representations, provided within the submitted application materials, are excluded from this approval and would be subject to the Renton Municipal Code in effect at the time of building permit application. If you have any further questions regarding this decision, feel free to contact the project manager, Clark H. Close, at (425) 430-7289 or cclose@rentonwa.gov. DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 12/18/2019 | 2:33 PM PST DEPARTMENT OF COMMUNITY AND ECONOMIC DEVELOPMENT 1 H:\CED\Data\Forms-Templates\Self-Help Handouts\Planning\Modification Application.doc Rev: 12/2015 MODIFICATION OF RESIDENTIAL DESIGN REQUIREMENTS FOR PROJECTS WITHIN THE R-4, R-6, R-8, R-10 AND R-14 ZONES EVALUATION FORM & DECISION Planning Division 1055 South Grady Way-Renton, WA 98057 Phone: 425-430-7200 | www.rentonwa.gov APPLICANT CONTACT INFORMATION Applicant Name: Company (if applicable): Mailing Address: Phone: City/State: Zip: PROJECT INFORMATION Project Name: Parcel Number: Zoning Designation: Project Location: Brief Summary of Request: Please explain how your project proposal meets the "guidelines" for each design element, rather than the standards. Code Section: 4-2-115E.3. “Roofs” Guideline: Roofs shall represent a variety of forms and profiles that add character and relief to the landscape of the neighborhood. The use of bright colors, as well as roofing that is made of material like gravel and/or a reflective material, is discouraged. Compliance with Guidelines: Code Section: 4-2-115E.3. “Architectural Detailing” Guideline: Architectural detail shall be provided that is appropriate to the architectural character of the home. Detailing like trim, columns, and/or corner boards shall reflect the architectural character of the house. Compliance with Guidelines: EXHIBIT 1 RECEIVED Clark Close 12/18/2019 PLANNING DIVISION Print Form Reset Form Save Form Mainvue Homes Mainvue Homes LLC 1110 112th Ave NE, Suite 202 (425) 998-9077 Bellevue WA 98004 98004 Allura at Tiffany Park lot 47 018880-0470 Residential-8 (R-8) 3475 SE 18th St, Renton, WA 98058 Requesting approval of modification to secondary front. We have enlarged windows and added additional siding enhancements (see side elevation for details). Total added glazing is 89.5 sq ft for a total of 24.35% and added enhanced siding is 205 sq ft for a total of 17.8%. GRAND TOTAL area of enhancement is 41.9%. Combination of siding and windows used since plan and room configuration don't allow for ONLY added glazing. Yes Yes DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 2 H:\CED\Data\Forms-Templates\Self-Help Handouts\Planning\Modification Application.doc Rev: 12/2015 Code Section: 4-2-115E.1. “Garages” Guidelines: The visual impact of garages shall be minimized, while porches and front doors shall be the emphasis of the front of the home. Garages shall be located in a manner that minimizes the presence of the garage and shall not be located at the end of view corridors. Alley access is encouraged. If used, shared garages shall be within an acceptable walking distance to the housing unit it is intended to serve Compliance with Guidelines: Code Section: 4-2-115E.3. “Windows and Doors” Guidelines: Windows and front doors shall serve as an integral part of the character of the home. Primary windows shall be proportioned vertically rather than horizontally. Vertical windows may be combined together to create a larger window area. Front doors shall be a focal point of the dwelling and be in scale with the home. All doors shall be of the same character as the home. Compliance with Guidelines: Code Section: 4-2-115E.3. “Primary Entry” Guidelines: Entrances to homes shall be a focal point and allow space for social interaction. Front doors shall face the street and be on the facade closest to the street. When a home is located on a corner lot (i.e., at the intersection of two roads or the intersection of a road and a common space) a feature like a wrapped porch shall be used to reduce the perceived scale of the house and engage the street or open space on both sides. Compliance with Guidelines: Code Section: 4-2-115E.3. “Façade Modulation” Guidelines: Buildings shall not have monotonous facades along public areas. Dwellings shall include articulation along public frontages; the articulation may include the connection of an open porch to the building, a dormer facing the street, or a well-defined entry element. Compliance with Guidelines: Code Section: 4-2-115E.3. “Eaves” Guidelines: Eaves should be detailed and proportioned to complement the architectural style of the home. Compliance with Guidelines: Yes Enlarged/added windows plus siding enhancement to address requirement. Total added glazing from original design is 89.5 sq ft for a total of 24.35% and added enhanced siding is 205 sq ft for a total of 17.8%. The GRAND TOTAL area of enhancement along the south elevation is 41.9%. Yes Yes Yes DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 3 H:\CED\Data\Forms-Templates\Self-Help Handouts\Planning\Modification Application.doc Rev: 12/2015 Other Design Standard: Code Section: Guidelines: Compliance with Guidelines: In addition to this form, the following attachments are required: Site plan and elevations (8.5x11 size) Built example photos (if available) Criteria for Modification of the Residential Design Standards Renton Municipal Code, section 4-2-115, lists elements that are required to be included in all residential developme in the zones stated in subsection B of this Section. Each element includes both standards and guidelines. Standards a provided for predictability. These standards specify a prescriptive manner in which the requirement can be met. Guidelines for each element are provided for flexibility. These guidelines provide direction for those who seek to me the required element in a manner that is different from the standards. a.The determination as to the satisfaction of the requirement through the use of the guidelines is to be made the Community and Economic Development Administrator when no other permit or approval requires Hear Examiner review. b.When it has been determined that the proposed manner of meeting the design requirement through guidelines is sufficient, the applicant shall have satisfied that design requirement. I, the undersigned, declare under penalty of perjury under the laws of the State of Washington, that to the best of my knowledge the above information is true and complete. Applicant Signature: Date: 12/11/19 - DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 EXHIBIT 2RECEIVEDClark Close 12/11/2019PLANNING DIVISIONDocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 Entire Document Available in Laserfiche Submittals Folder EXHIBIT 3 RECEIVED Clark Close 12/11/2019 PLANNING DIVISION DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 SIDINGENHANCEMENTSA6-DTL DESIGN: SU DRAWN: JZ SHEET1110 112th Ave NE, Suite 202Bellevue, WA 98004Phone: (425) 646-4022Fax: (425) 646-4024DESCRIPTIONDATENo.321- PLAN No: 51-40-01.02.0 NBALMAINE 'N'(51-40-01.02.0)422x34 - 14" = 1'-0" 11x17 - 18" = 1'-0"WA,ALU-47 CUSTOMW:\Seattle\Plan Library\MainVue Plans\40ft Product\51-40 BALMAINE\CAD Files\00 Base Plan\ELEV N - ALU-47\51-40-01 N - ALU-47 2.dwg, 12/17/2019 3:05:59 PM, tom.disethEXHIBIT 4 ADDED GLAZING +11.25 sq ft (Master Bed) +11.25 sq ft (Master Bed) +15 sq ft (Den) +3 sq ft (Den) +20 sq ft (MP Room) +10 sq ft (Bed 4) +10 sq ft (Bed 3) +9 sq ft (Master WIC) +89.5 ADDED sq ft 277.75 TOTAL SQ FT Glazing 24.35% GLAZING COVERAGE SIDING ENHANCEMENT 205 sq ft added enhanced siding TOTAL GLAZING AND SIDING ENHANCED AREA 41.9% DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5 1110 112th Avenue NE, Suite 202, Bellevue WA 98004 | PHONE: 425-646-4022 | FAX 425-646-4024 | MAINVUEHOMES.COM Framing List for Code compliance MainVue homes to meet 2a Energy code requirements. · Subcontractor shall provide and install foam backer rod of proper size around all windows, exterior doors and other such gaps. These locations shall receive an application of low expansion foam on top of the backer rod · All foam used shall be low expansion type. Any bowing, warping or movement caused by the application of foam shall be repaired at the Subcontractors expense. · Subcontractor shall run a bead of sealant on the interior of all exterior plate lines and inside corners · Subcontractor shall foam all penetrations including but not limited to plumbing and electrical. · Subcontractor shall insulate all water pipes in crawl space and garage situations, per Washington State Energy Code. · Subcontractor shall insulate all exposed waterlines in garage including but limited too: Garage Hose-Bib Shut-Off Valve, Waterlines to Tankless Heater, and Main Water Supply. All gaps and corners to be fully wrapped so no piping is exposed. o Pipe Insulation shall not have joints larger than an 1/8” and shall be covered with duct tape when they occur. Zip Ties can be substituted for duct tape to seal and keep foam insulation in place. · Subcontractor shall seal all penetrations through drywall in the garage with Intumescent Firestop Caulking. · 2015 Energy Code o To help meet 2015 blower door test the following shall be done, o 2nd Floor Gasket Sill Sealer at the upper plate between each room opening as it meets the upper plate. o To include outside plate at the outside wall o Attic Air Seal through Can lights and fixtures going through the attic o Caulking is to prevent air flow from upper roof to lower room o Caulking is to be done from the attic before blown insulation is placed or installed o Caulking all open penetration at this so there is an air seal and not gap at the all upper cans o o EXHIBIT 5 Entire Document Available in Laserfiche Submittals Folder RECEIVED Clark Close 12/18/2019 PLANNING DIVISION DocuSign Envelope ID: 47320B08-3315-4794-AE21-C6416237C8C5