Loading...
HomeMy WebLinkAboutD_Admin Report_ShorelineElevatorInstallation VAR_200305_FINALDEPARTMENT OF COMMUNITY AND ECONOMIC DEVELOPMENT Project Location Map D_Admin Report_Shoreline Elevator Exemption_200225_v1 A. ADMINISTRATIVE REPORT & DECISION Decision: APPROVED APPROVED SUBJECT TO CONDITIONS DENIED Report Date: March 5, 2020 Project File Number: PR19-000244 Project Name: Shoreline Elevator Installation / Harwood SFR Elevator Land Use File Number: LUA20-000047, V-A Project Manager: Brittany Gillia, Assistant Planner Owner/Applicant: Douglas and Marjorie Harwood, 3713 Lake Washington Blvd N, Renton, WA 98056 Contact: Douglas Harwood, 3713 Lake Washington Blvd N, Renton, WA 98056 Project Location: 3713 Lake Washington Blvd N Project Summary: The applicant is requesting an Administrative Variance from the maximum height requirements for the construction of a new 75 square foot, 3-story elevator to be installed within the existing footprint of a 3,140 square foot residential home. The 11,060 square foot project site is located within the Residential-6 (R-6) zone and is situated on the shoreline of Lake Washington in the Shoreline Residential Designation, Reach D. Shoreline impacts are being evaluated in a Shoreline Exemption, LUA20-000048. The property is mapped with a High Landslide Hazard. The existing single-family residence is proposed to have the front stairs removed and replaced with a spiral staircase along with the installation of the 5’6”x5’6” elevator on the front of the building next to the new spiral staircase and existing garage. An Administrative Variance is needed from the maximum wall plate height found in RMC4-2-110A to allow a 26’ 2” wall plate height for the elevator installation instead of the required maximum height of 24’ that applies to the R-6 zone. The proposed elevator shaft would remain below the highest peak of the current roofline and is needed so that the doors may fully open on the third floor of the residence. Proposed access to the site will be from Lake Washington Boulevard and no job shacks, trailers, or model homes will be necessary for this project. There are no trees proposed to be removed as part of this project. Site Area: 0.25 acres DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 2 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 B. EXHIBITS: Exhibit 1: Administrative Decision Exhibit 2: Site Plan Exhibit 3: Site Photos Exhibit 4: Elevations Exhibit 5: Certificate of Exemption from Shoreline Substantial Development, dated November 19, 2019 Exhibit 6: Elevator Plans Exhibit 7: Elevator Installation Technical Specifications C. GENERAL INFORMATION: 1. Owner(s) of Record: Douglas Harwood 2. Zoning Classification: Residential-6 (R-6) 3. Comprehensive Plan Land Use Designation: Residential Medium Density (MD) 4. Existing Site Use: Single-family Residential 5. Critical Areas: High Landslide Hazard, Shoreline Residential Environmental Designation - Lake Washington Reach D. 6. Neighborhood Characteristics: a. North: Single-family Residential, Residential- 6 (R-6) b. East: King County rail-to-trail, Residential- 6 (R-6) c. South: Single-family Residential, Residential- 6 (R-6) d. West: Lake Washington 7. Site Area: 0.25 acres D. HISTORICAL/BACKGROUND: Action Land Use File No. Ordinance No. Date Comprehensive Plan N/A 5758 06/22/2015 Zoning N/A 5758 06/22/2015 Friends of Youth Annexation N/A 1791 09/09/1959 Shoreline Exemption (for sewer repair) LUA98-170 N/A 11/19/1998 DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 3 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 E. APPLICABLE SECTIONS OF THE RENTON MUNICIPAL CODE: 1. Chapter 2 Land Use Districts a. Section 4-2-110: Residential Development Standards 2. Chapter 3 Environmental Regulations and Overlay Districts a. Section 4-3-090: Shoreline Master Program Regulations 3. Chapter 9 Variances, Waiver, Modifications, and Alternates 4. Chapter 11 Definitions F. FINDINGS OF FACT (FOF): 1. The Planning Division of the City of Renton accepted the above master application for review on February 12, 2020 and determined the application complete February 18,2020. The project complies with the 120- day review period. 2. The applicant’s submittal materials comply with the requirements necessary to process the administrative variance and shoreline exemption requests. 3. The project site is located 3713 Lake Washington Blvd N (APN 3342700240). 4. The project site is currently developed with a single-family residence with an attached garage. 5. Access to the site would be provided via the existing driveway off of Lake Washington Blvd N. 6. The site is located within the Residential-6 (R-6) zoning classification and Residential Medium Density (MD) Comprehensive Plan land use designation. 7. No trees or vegetation would be removed. 8. The proposed project would not increase the building footprint or impervious surface coverage on the site. 9. The site is mapped with a High Landslide Hazard and the Shoreline Residential Environmental Designation - Lake Washington Reach D. 10. The applicant is proposing to have construction completed within a 2 month span following building permit approval. 11. The following variance to regulations have been requested by the applicant: RMC Code Citation Required Standard Requested Variance RMC 4-2-110A Residential Development Standards Maximum Wall Plate Height: 24 feet Requesting variance to allow for a 26’2” wall plate height 12. No public or agency comments were received. 13. A Certificate of Exemption from a Shoreline Substantial Development Permit was issued on March 5, 2020 (Exhibit 6). 14. Representatives from various city departments have reviewed the application materials to identify and address issues raised by the proposed development. These comments are contained in the official file, DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 4 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 and the essence of the comments has been incorporated into the appropriate sections of this report and the Departmental Recommendation at the end of this report. 15. The property is located within the Residential Medium Density (MD) Comprehensive Plan land use designation. The project complies with the goals and policies of this Comprehensive Plan land use designation. Compliance Comprehensive Plan Analysis  Goal L-P: Minimize adverse impacts to natural systems, and address impacts of past practice where feasible, through leadership, policy, regulation, and regional coordination.  Goal L-U: Preserve, protect, and enhance the quality and functions of the City’s sensitive areas including: lakes, rivers, major and minor creeks, intermittent stream courses and their floodplains, wetlands, ground water resources, wildlife habitats, and areas of seismic and geological hazards.  Policy L-50: Respond to specific site conditions such as topography, natural features, and solar access to encourage energy savings and recognize the unique features of the site through the design of subdivisions and new buildings.  Policy SH-3: All shoreline policies, regulations, and development shall recognize and protect private rights consistent with the public interest and, to the extent feasible, shall be designed and constructed to protect the rights and privacy of adjacent property owners. Shoreline uses and activities should be discouraged if they would cause significant noise or odor or unsafe conditions that would impede the achievement of shoreline use preferences on the site or on adjacent or abutting sites. 16. Critical Areas: Project sites which contain critical areas are required to comply with the Critical Areas Regulations (RMC 4-3-050). The proposal is consistent with the Critical Areas Regulations: Compliance Critical Areas Analysis Compliance not yet determined Geologically Hazardous Areas: Based upon the results of a geotechnical report and/or independent review, conditions of approval for developments may include buffers and/or setbacks from buffers. A standard 15-foot building setback is required for all structures from Protected Slope areas. A 50-foot buffer and 15-foot building setback are required from Very High Landslide Hazard Areas. Staff Comment: A high landslide hazard was mapped on or within 50 feet of the project site. A geotechnical report prepared by a qualified professional is required to be submitted at the time of building permit application for all development on sites located within 50 feet of a geological hazard, unless waived by the Building Official. Compliance for this standard would be verified at the time of building permit review. 17. Variance Analysis: The applicant is requesting a variance to allow an elevator shaft addition to an existing single-family residence to reach a 26’2” foot wall plate height, exceeding the maximum 24 foot height in the R-6 zone. The proposal is compliant with the following variance criteria, pursuant to RMC 4-9-250.B.5. Therefore, staff recommends approval of the requested variance. DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 5 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 Compliance Variance Criteria and Analysis  a. That the applicant suffers practical difficulties and unnecessary hardship and the variance is necessary because of special circumstances applicable to subject property, including size, shape, topography, location or surroundings of the subject property, and the strict application of the Zoning Code is found to deprive subject property owner of rights and privileges enjoyed by other property owners in the vicinity and under identical zone classification. Staff Comment: The subject property is located on a private street adjacent to Lake Washington Blvd N with very narrow travel lanes and no frontage improvements (Exhibit 2). The buildable area of both the subject site and the neighboring properties directly north and south on the private street is extremely limited due to the King County parcel (previously railroad ROW and now functioning as a public trail) to the east and Lake Washington to the west. The existing single family home is a legal, non-conforming structure that was constructed in 1990. Current Renton Municipal Code states that the R-6 zone shall have a maximum wall plate height of 24’, however, the current wall plate height of the existing structure reaches slightly above at 26’ 2”. There is no space within the existing, enclosed structure to retrofit an elevator shaft that will allow elevator access to all three levels of the home. Due to the existing height constraint, the applicant has proposed to meet the existing wal l plate height of the structure to allow the elevator full access to the third floor while also maintaining architectural compatibility to the rest of their home (Exhibit 4). The existing nonconformity of structures in the vicinity creates difficulties for property owners wishing to construct multi-story additions along this street that would meet current code. The applicant contends that without granting of the variance, strict adherence to the maximum wall plate height requirements would deprive them of privileges enjoyed by other property owners in the vicinity. Staff has reviewed the proposed variance request and concurs that strict adherence to the R -6 maximum wall plate height requirement would cause unnecessary hardship by depriving the applicant of the ability to have elevator access to all floors of their home.. The elevator access is important for guests and family members of the property owner that are not able to use stairs to reach all levels of the home. Staff also concurs that by keeping the addition within the existing footprint as well as the existing roof line, the proposal is requesting the minimum amount of height variance to allow the property owner the same rights and privileges enjoyed by other property owners in the vicinity under identical zone classification. According to RMC 4-10-050 Nonconforming Structures, this addition does not violate subsection 4. Limits on Enlargement. The proposed addition will not detract from the character of the neighborhood or impact issues with views of Lake Washington.  b. That the granting of the variance will not be materially detrimental to the public welfare or injurious to the property or improvements in the vicinity and zone in which subject property is situated. Staff Comment: The applicant contends that granting of the variance would not be materially detrimental to the public welfare or injurious to the property or improvements in the vicinity and zone in which the subject property is situated due to two factors. Firstly, the proposed addition does not propose any disruption to the land surrounding the property. There are no job shacks, trailers, or model homes proposed as part of this project that would impede local access across the private road that runs parallel to Lake Washington Boulevard. Secondly, the new addition will add symmetry to the existing structure and provide an additional architectural element (Exhibits 3 and 4). The addition does not block any view corridors for pedestrians along Lake Washington Boulevard, no r users of the King County Eastside Rail Corridor Trail. The new addition would have a minimal visual impact on all abutting properties. Staff has reviewed the applicant’s justifications and concurs with their analysis. Staff finds that the proposed addition would not be detrimental to the public welfare or injurious to the property DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 6 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 or improvements in the vicinity and zone in which the subject property is situated based on the site characteristics and existing encroachment by the structure. The granting of the variance would not result in a structure that is significantly different than that of the existing home, which has been located on the site for approximately 30 years. Staff concurs that the proposed improvements would not create a negative visual impact on the surrounding property owners due to the existing conditions on the site and the location of the existing structure in relation to the adjacent homes.  c. That approval shall not constitute a grant of special privilege inconsistent with the limitation upon uses of other properties in the vicinity and zone in which the subject property is situated. Staff Comment: The applicant contends that the approval of the variance would not be considered a special privilege due to the fact that adjacent p roperties also have structures that exceed a wall plate height of 24 feet. In addition, the property is a legal nonconforming structure and this addition does not violate the listed limits on enlargement. Staff has reviewed the applicant’s justifications and concurs that the granting of the variance would not constitute a grant of special privilege inconsistent with other properties in the vicinity and a part of the Garden of Eden subdivision and the same zoning designation. The granting of this variance would allow the property owners as well as any family or guests access to all levels of the home without concern for any impediments due to mobility issues. A new structure built in the R-6 zone under current code would be allowed to install an elevator tha t fully reaches and provides access to all floors of said structure, and due to nonconforming circumstances, this variance is needed to allow the property owners access to meet the current and established wall plate height of the existing structure.  d. That the approval is a minimum variance that will accomplish the desired purpose. Staff Comment: The applicant contends that the variance request only allows for the proposed addition to the home the minimum height needed to allow access to all three floors of the existing structure while maintaining the lowest possible wall plate height. The new addition would remain within the existing footprint of the building, while also remaining below the highest peak of the current roofline. Staff reviewed the variance request and concludes that the proposed exceedance of the maximum wall plate height for the R-6 zone would be the minimum required in order to meet the goal of constructing an addition to their home to support their elevator shaft and giving access to the entire building, while allowing the home be of a similar size and location as the neighboring homes. Therefore, the requested height increase would be the minimum necessary to accomplish the desired purpose. 18. Shoreline Exemption Analysis: The site is within Shoreline Jurisdiction of Lake Washington, Reach D (LW- D), designated Shoreline Residential. The proposed addition has been evaluated under Shoreline Exemption LUA20-000048 (Exhibit 6). DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 7 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 G. CONCLUSIONS: 1. The subject site at 3619 Lake Washington Blvd N is located in the Residential Medium Density (MD) Comprehensive Plan designation and complies with the goals and policies established with this designation, see FOF 15. 2. The subject site is at 3713 Lake Washington Blvd N located in the Residential-6 (R-6) zoning designation. Compliance with R-6 development standards in their entirety would be reviewed at the time of building permit application. 3. The requested variance application complies with the Critical Areas Regulations provided the applicant complies with City Code, see FOF 16. 4. The requested variance meets the four (4) criteria to be considered in making a decision on a variance request as specified in RMC 4-9-250.B.5. The analysis of the proposal according to variance criteria is found in the body of the Staff Report, see FOF 17. 5. The proposed project is consistent with the City of Renton Shoreline Master Program and qualifies for an exemption from a Shoreline Management Substantial Development Permit in accordance with RMC 4-9- 190C, see Exhibit 6. H. DECISION: 1. The Shoreline Elevator Installation Variance, File No. LUA20-000047, V-A, as depicted in Exhibit 2, is approved. DATE OF DECISION ON LAND USE ACTION: SIGNATURE: Jennifer Henning, Planning Director Date TRANSMITTED on March 5, 2020 to the Owner/Applicant/Contact: Owner/Applicant/Contact: Douglas and Marjorie Harwood 3713 Lake Washington Blvd N Renton, WA 98056 TRANSMITTED on March 5, 2020 to the Parties of Record: None TRANSMITTED on March 5, 2020 to the following: Chip Vincent, CED Administrator Brianne Bannwarth, Development Engineering Manager Amanda Askren, Property Services DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 3/5/2020 | 4:42 PM PST City of Renton Department of Community & Economic Development Shoreline Elevator Exemption Administrative Report & Decision LUA20-000047, V-A Report of March 5, 2019 Page 8 of 8 D_Admin Report_Shoreline Elevator Exemption_200303_v1 Vanessa Dolbee, Current Planning Manager Anjela Barton, Fire Marshal I. LAND USE ACTION APPEALS, REQUEST FOR RECONSIDERATION, & EXPIRATION: The administrative land use decision will become final if the decision is not appealed within 14 days of the decision date. APPEAL: This administrative land use decision will become final if not appealed in writing to the Hearing Examiner on or before 5:00 PM on March 19, 2020. An appeal of the decision must be filed within the 14-day appeal period (RCW 43.21.C.075(3); WAC 197-11-680), together with the required fee to the Hearing Examiner, City of Renton, 1055 South Grady Way, Renton, WA 98057. RMC 4-8-110.B governs appeals to the Hearing Examiner and additional information regarding the appeal process may be obtained from the City Clerk’s Office, (425) 430-6510. EXPIRATION: The Variance decision will expire two (2) years from the date of decision. A single one (1) year extension may be requested pursuant to RMC 4-9-250. RECONSIDERATION: Within 14 days of the decision date, any party may request that the decision be reopened by the approval body. The approval body may modify his decision if material evidence not readily discoverable prior to the original decision is found or if he finds there was misrepresentation of fact. After review of the reconsideration request, if the approval body finds sufficient evidence to amend the original decision, there will be no further extension of the appeal period. Any person wishing to take further action must file a formal appeal within the 14-day appeal time frame. THE APPEARANCE OF FAIRNESS DOCTRINE: provides that no ex parte (private one-on-one) communications may occur concerning the land use decision. The Doctrine applies not only to the initial decision, but to Appeals to the Hearing Examiner as well. All communications after the decision/approval date must be made in writing through the Hearing Examiner. All communications are public record and this permits all interested parties to know the contents of the communication and would allow them to openly rebut the evidence in writing. Any violation of this doctrine could result in the invalidation of the appeal by the Court. DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 CITY OF RENTON DEPARTMENT OF COMMUNITY AND ECONOMIC DEVELOPMENT ADMINISTRATIVE REPORT & DECISION EXHIBITS Project Name: Shoreline Elevator Installation / Harwood SFR Elevator Land Use File Number: LUA20-000047, V-A Date of Report March 5, 2020 Staff Contact Brittany Gillia Assistant Planner Project Contact/Applicant Douglas Harwood 3713 Lake Washington Blvd N Renton, WA 98056 Project Location 3713 Lake Washington Blvd N The following exhibits are included with the Administrative report: Exhibit 1: Administrative Decision Exhibit 2: Site Plan Exhibit 3: Site Photos Exhibit 4: Elevation and Construction Plans Exhibit 5: Elevator Installation Technical Specifications Exhibit 6: Certificate of Exemption from Shoreline Substantial Development, dated November 19, 2019 DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 Pictom etr y, Ki ng C o u nty, K ing C ounty As se ss or 's O ffi ce , Ki ng C oun ty G ISCenter, Kin g C o unty, Ki n g coun ty Asses sor's Offic e, K ing C ounty GIS C en ter Date : 6/4/201 9 ±The informati on included on this map has been compi led by King County staff from a variety of sour ces and issubject to change wi thout notice. King County makes no r epresentati ons or w ar ranties, expr ess or impl ied,as to accurac y, completenes s, timeli ness , or ri ghts to the use of such infor mation. This document is not intendedfor use as a s urvey pr oduct. King County shall not be liable for any gener al, s pecial, i ndir ect, incidental , orconsequential damages incl uding, but not li mited to, lost revenues or lost pr ofits resulting fr om the use or misuseof the information contained on this map. Any sale of this map or infor mati on on this map is pr ohibited except bywritten per mi ssi on of Ki ng County. King C ou nty EXHIBIT 2 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 EXHIBIT 3 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION HARWOOD SFR- CONSTRUCT 5X5 3-STOP ELEVATOR/SHAFT TO EXISTING STRUCTURE WITHIN THE FOOTPRINT OF FRONT PORCH ROOF LINE. REMOVE EXISTING ENTRY STAIRS AND UNDER STAIR STORAGE AND REPLACE WITH SPIRAL STAIRCASE. DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 GUARDRAILS & LANDINGBY OTHERSSPIRAL STAIRBY OTHERSELEVATOR WALLELEVATOR WALL BEYOND26'-2"/314" T/ELEVATORROOF FRMG ELEV17'-10" 3RD FLR FRMG ELEVSOUTH ELEVATION14"=1'-0"101 4 " T/ELEVATOR PIT SLAB 0'-0" BATH/GARAGE 1ST FLR ELEV8'-11" MAIN 2ND FLR FRMG ELEV7'-8" LOW ENTRY 2ND FLR ELEV0'-214" PATIO/STORAGE ELEV8'-1" T/ TOP PL (MAIN) 8'-1" T/ TOP PL 10" 10" 7'-5 3 4 " T/TOP PL 1'-3"-1014" ELEVATOR PIT SLAB ELEV7' T/ TOP PL (LOW ENTRY) 8"2GUARDRAILS &LANDINGBY OTHERSSPIRAL STAIR CASE& LANDING BY OTHERS(E) FULL HEIGHTCOLUMN(E) DOOR(N) ELEVATORDOOR(E) GARAGEDOOREXISTINGBEYOND(E) LOW ROOF(E) UPPER ROOFBEYONDSPIRAL STAIRCASECOLUMN BY OTHERSELEVATOR ALCOVE26'-2"/314"ELEVATOR ROOFFRMG ELEV17'-10" 3RD FLR FRMG ELEV-1014" T/ELEVATOR SLAB ELEV8'-11" MAIN 2ND FLR ELEVEAST ELEVATION14"=1'-0"7'-8" LOW ENTRY 2ND FLR ELEV0'-214" PATIO/STORAGE FLR ELEV7'T/ TOP PL(LOW ENTRY)8"1'-3"8'-1"T/TOP PL 10"0'-0" GARAGE/BATH FLR ELEV101 4 "T/ELEVATORSLAB ELEV 7'-5 3 4 "T/ TOP PL 24' MAX WALL PLATE HEIGHT PERPLAN REVIEW COMMENT314" NEW ELEVATOR HEIGHT24' 26'-2"/314"21ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED DIMESIONING 1 8/13/2019 PLAN REVIEW COMMENTS 2 12/26/2019 NEW ELEVATOR WALL REVISIONEXHIBIT 4RECEIVEDClark Close 01/15/2020PLANNING DIVISIONDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 FOUNDATION PLAN14" = 1'-0"(E) FOUNDATIONTO REMAINDEMOLISH(E) STEM WALL(E) FOUNDATION TO REMAINDEMOLISH (E) STEM WALL(E) FOUNDATIONTO REMAIN(E) FOUNDATION TO REMAINELEVATOR PIT6" SLAB ON GRADEw/ #4's @ 12" o/cE/W(N) 6" CONC STEMCENTERED ABOVEw/ 1'-4"W x 12" DPCONC FTG TYPICAL1'-6" SQx12"DP CONC FTG &38"x8"x0'-8" BASE PLATE w/(4) 12"Ø x 4 12" SIMP TITEN HDTYPE 300 SERIES STAINLESS STEEL(E) FOUNDATION TO REMAINFR=5'-1"1/S32/S34/S33/S3FR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'2'-312"TYP10"TYP1℄1st FLOOR FRAMING PLAN14" = 1'-0"66"Ø SPIRAL STAIRCASE& LANDING BY OTHERSTYPICAL RAIL SUPPORT2x10DBL 12" PLYWOOD(2) 2x102x6 EA SIDEFR=5'-1"(E) 12" SW-SHTG(E) 2x6 WALL STUDS(E) 58" GWB(N) 12" GWB(N) 2x6 STUDS @ 16" o/c(N) 12" SW-SHTGFR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'RAIL SUPPORT @ (E) POST2x1012" PLYWOODDBL 2x4(E) 4x6 POST2'-312"TYP10"TYP(N) 12" GWB(E) 12" SW-SHTG(E) 2x6 WALL STUDS(E) 58" GWB21122nd FLOORFRAMING PLAN14" = 1'-0"66"Ø SPIRAL STAIRCASE &LANDING BY OTHERS(N) FLOOR SHTGPER PLAN NOTE #82'-9"4' FR=5'-1"6/S35/S34x10 BEAM FR=4'-7"3'2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'2'-312"TYP10"TYP3rd FLOORFRAMING PLAN14" = 1'-0"2x10@16" o/cFLOOR SHTGPER PLAN NOTE #8(E) LOW ROOF(E) LOW ROOFFR=5'-1"10/S37/S38/S39/S311/S311/S3SIM12/S34x10BEAM(N) FLR SHTG PERPLAN NOTE #8(N) 12" GWB(N) 12" SW-SHTG(N) 2x6 WALL STUD(N) 12" WALL SHTGFR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-21 2 "3'-51 2 "4'ELEVATOR DOOROPENS INTO(E) EXTERIOR WALLIN CURRENT GEOMETRY2'-312"TYP10"TYPROOF FRAMING PLAN14" = 1'-0"LOW ROOF LINE BELOW2x10 ROOF JOISTS @ 24" o/c'SISTER' w/ 2x4 CEILING JOISTS(CONNECT TOGETHERw/ (4) 10d NAILS) TYPROOF SHEATHINGPER PLAN NOTE #81/S4BELOW3/S4ABOVE2/S43/S42/S42134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-21 2 "3'-51 2 "4' LATERAL NOTES:SHEARWALL REQUIREMENTSSW-6REPRESENTS 12" NOMINAL APA RATED WALL SHEATHING* WITH 8d COMMONS AT 6" ON CENTER AT PANEL EDGESAND 12" ON CENTER IN FIELD. ATTACH DOUBLE TOP PLATES TO 2x BLOCKING ABOVE WITH SIMPSON SDWSx6"SCREWS @ 16" o/c. ATTACH BOTTOM PLATE TO 2x BLOCKING OR RIM JOIST WITH 16d @ 5" o/c. ATTACHPRESSURE TREATED HEM-FIR #2 PLATE TO DOWNTURNED CONCRETE EDGE WITH 12" Ø SIMPSON TITEN HDCONCRETE SCREWS (EMBED 234") AT 16" o/c.SW-4REPRESENTS 12" NOMINAL APA RATED WALL SHEATHING* WITH 8d COMMONS AT 6" ON CENTER AT PANEL EDGESAND 12" ON CENTER IN FIELD. ATTACH DOUBLE TOP PLATES TO 2x BLOCKING ABOVE WITH SIMPSON SDWSx6"SCREWS @ 16" o/c. ATTACH BOTTOM PLATE TO 2x BLOCKING OR RIM JOIST WITH 16d @ 5" o/c. ATTACHPRESSURE TREATED HEM-FIR #2 PLATE TO DOWNTURNED CONCRETE EDGE WITH 12"Ø SIMPSON TITEN HDCONCRETE SCREWS (EMBED 234") AT 12" o/c.*IT IS ACCEPTABLE TO USE EXISTING WALL SHEATHING. ENSURE SUFFICIENT NAILING PER SHEARWALL TYPE IS MET.HOLDOWN REQUIREMENTSMSTC40: ATTACH SIMPSON MSTC40 TO DOUBLE STUD VERTICALLY w/ (28) 8d COMMONS OVER WALL SHEATHING (HALFABOVE WIND GIRT AND HALF BELOW WIND GIRT.HDU2: INSTALL SIMPSON HDU2 TO CONCRETE WITH SIMP SSTB24 INTO NEW STEM WALL OR 58"Ø THREADED ROD(EMBED 7") w/ SIMP SET EPOXY INTO EXISTING STEM WALL AND (6) 14"x212" SDS TO DOUBLE STUDS MINIMUM.HDU5: INSTALL SIMPSON HDU5 TO CONCRETE WITH SIMP SSTB28 AND (10) 14"x2 12" SDS TO DOUBLE STUDS MINIMUM.ALL SIMPSON HARDWARE SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. FOR REFERENCE THE FOLLOWINGSIMPSON CATALOGS SHALL BE ON THE JOB SITE AT THE TIME OF INSPECTION: a) WOOD CONSTRUCTION CONNECTORS(C-C-2019) b) ANCHORING AND FASTENING SYSTEMS FOR CONCRETE+ MASONRY (C-A-2018).1PLAN NOTES:1. ELEVATOR RAIL BRACKET PER MANUFACTURER. CONNECTBRACKET TO 6x6 RAIL w/ (4) 38"x3" LAG SCREWS. ENSURE 3"SPACING AS SHOWN IN ELEVATOR MANUFACTURER DRAWINGS.2. IF EXISTING CONDITIONS VARY FROM WHAT IS SHOWN,CONTACT THE ENGINEER ON RECORD.3. ALL ELEVATOR DOOR HEADERS SHALL BE 4x6 DF-L #2 AND BEARON DOUBLE STUD MINIMUM, UNLESS NOTED OTHERWISE. ROUGHOPENINGS AND DOOR SIZE PER ELEVATOR MANUFACTURER.4. ALL BUILT UP MEMBERS SHALL BE LAMINATED WITH (2) ROWS10d BOX NAILS STAGGERED AT 12" o/c5. ALL ELEVATOR WALLS SHALL BE 2x6 STUDS @ 16" o/c. IT ISASSUMED ELEVATOR WALLS ARE COVERED IN 12" GYPSUM(INTERIOR) & 12" NOMINAL APA RATED WALL SHEATHING(EXTERIOR).6. SAWCUT AND EXCAVATE EXISTING PATIO.7. ENSURE FOOTINGS BEAR ON UNDISTURBED NATIVE SOIL.8. FLOOR SHEATHING SHALL MATCH EXISITNG THICKNESS &FASTENED AT PANEL EDGES w/ 10d COMMONS @ 6" o/c & 12"o/c IN FIELD.ROOF SHEATHING SHALL BE 1532" APA RATED SHEATHING w/ 8dCOMMONS @ 6" o/c & 12" o/c IN FIELD.9. GRIDLINES ARE LOCATED AT EDGE OF STUD/STEM WALLS WITHTHE EXCEPTION OF GRIDLINE C, LOCATED AT CENTER OF SPIRALSTAIRCASE PIPE.ABBREVIATIONS:CONC: CONCRETEDEMO: DEMOLISH(E) : EXISTINGE/W: EACH WAYELEV:ELEVATIONFDN: FOUNDATIONFTG: FOOTINGFR: FINISHED ELEVATOR RUNWAY TYPICAL AT ALL LEVELSGWB: GYPSUM WALL BOARDHD: HOLDOWNHDR: HEADERLONG: LONGITUDINAL(N): NEWSHTG: SHEATHINGSW: SHEARWALLT/ : TOP OFTRANSV: TRANSVERSETYP: TYPICAL FOR SIMILAR CONFIRGURATIONSSW-6SW-6SW-6 HDU2HDU2HDU5HDU21st LEVEL SHEARWALLS14"=1'-0"2'-312"TYP10"TYPSW-6SW-6MSCT40MSCT40MSTC402nd LEVEL SHEARWALLS14"=1'-0"MSCT402'-312"TYP10"TYPSW-6SW-6SW-6 SW-6 MSTC40MSTC40MSTC403rd LEVEL SHEARWALLS14"=1'-0"MSTC402'-312"TYP10"TYP1'-8"1'-8"℄MSTC,FLR JOISTMSTCPER PLANHDU PER PLANw/ SIMP SSTBINTO NEWSTEM WALLHOLDOWN STUDSPER PLANHDU PER PLANw/ 58"Ø THREADEDROD w/ SIMP SETEPOXY (EMBED 7")TYPHOLDOWN STUDSPER PLAN TYP7" TYP WALL AS OCCURSPER PLANNEW STEMPER PLANEXISTING STEMPER PLANTYPICAL HOLDOWNSTO CONCRETE STEMWALLS1"=1'-0"TYPICAL HOLDOWNSTO WOOD FRAMING1"=1'-0"2PLANS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED GRID-LINE DIMESIONING PR19000244B19002967V2DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 (E) FOOTING(E) 8" CONCSTEM WALL(E) GARAGESLAB ON GRADE(E) PT MUD PL w/12"Ø ANCHOR BOLTS@ 48" o/c MIN(E) 2x6 WALL(E) WALL SHTG(E) SHEARWALLEDGE NAILINGT/ ELEVATOR PITDEMO (E) PATIOSLAB ON GRAGEDETAIL #1ELEVATOR TO (E) GARAGE WALL CONNECTIONS1"=1'-0"101 4 "#4 REBAR DOWELS @ 18"w/ SIMP SET EPOXY(EMBED 3")1'-6"VERIFY (E) 58"TYPE 'X' GWB(N) 12" GWBVERIFY (E) PERF DRAIN8" ELEV PIT T/ GARAGESLAB ON GRADE(N) 6" SLAB ON GRADEw/ #4's @ 18" o/c E/W11'-4"1' 101 4 " 3" CLRTYP 3" CLRTYP(2) #4 CONT(E) PATIOSLAB ON GRADET/ PATIOSLAB ON GRADET/ ELEVATOR PIT(N) 6" CONC SLAB ON GRADEw/ #4's @ 18" o/c E/WWALL SHTG PERSHEARWALL SCHEDULE2x6 PT SILL PL w/ANCHOR BOLTS PERSHEARWALL SCHEDULESW-EDGE NAILINGDEMO (E) PATIOSLAB ON GRADE2x6 WALL STUDS@ 16" o/c12" GWBDETAIL #2NEW ELEVATOR @ NEW FOUNDATION1"=1'-0"4" PERF DRAIN(TIE TO (E) OR INSTALL(N) DRAIN SYSTEM#4's 36"o/c, CENTERED#4 CROSS-TIES 36"o/c#4 HORZ.TOP & BTTM4"18" ELEV PIT (E) 6" CONC STEM WALLWALL SHTGPER SW-SCHEDULET/ ELEVATOR PITDETAIL #3NEW ELEVATOR WALL@ EXISTING STEM WALL1"=1'-0"8" PER EXISTING (E) DRAWINGS1'-4" PER(E) DRAWINGS(N) 6" CONC SLAB ON GRADEw/ #4's @ 18" o/c E/WSW-EDGE NAILING2x6 PT BOTTOM PL w/ANCHOR BOLTS PERSHEARWALL SCHEDULE2x6 WALL STUDS@ 16" o/c#4 DOWELS INTO (E) STEM w/SIMP SET EPOXY (EMBED 3")@ 18" o/cNOTE:THE STEM WALL CONFIGURATION IS BASED ONTHE EXISTING DRAWINGS SUPPLIED. CONTACTENGINEER OF RECORD IF CONDITIONS VARY.T/ BATH/GARAGE FLR(E) 12" GWB(E) CRAWLSPACE BEAM(E) CRAWLSPACE JOISTSDEMO (E) PATIOSLAB ON GRADE101 4 "VERIFY (E) PERF DRAIN1(E) ASPHALTT/ ASPHALT DRIVEWAYT/ GARAGEDETAIL #4NEW INTERIOR ELEVATOR WALL@ EXISTING STEM WALL1"=1'-0"(E) 8" CONCSTEM WALL(2) CONT #4'sT/ ELEVATORPIT(N) 6" SLAB ON GRADEw/ #4's @ 18" o/c E/W2x6 PT SILL PL w/ ANCHOR BOLT PERSHEARWALL SCHEDULE2x6 WALLSTUDS @ 16" o/cSHEARWALLEDGE NAILING12" GWBWALL SHTGPER SHEARWALLSCHEDULE(N)ELEVATOR ENTRYSLAB ON GRADEDEMO (E) PATIOSLAB ON GRADE8" ELEV PIT 101 4 "VERIFY (E) PERFDRAINDEMO (E)SLAB ON GRADE#4's 36"o/c, VERT. CENTERED#4's HORZ TOP & BTTM#4 CROSS-TIES 36"o/c7 3 4 " 4"1SHEARWALL EDGENAILING TYP12" GWB(2) SIMP SDWSx6"@ 6" o/c(2) SIMP SDWSx6"@ 6" o/cWALL SHTG PERSHEARWALL SCHEDULE2x6 WALL STUDS@ 16" o/c TYP2x10 JOIST TYPT/ (E) CEILINGDETAIL #5TYPICAL WIND GIRT1"=1'-0"2x6 WALL STUDS@ 16" o/c TYPDIAPHRAGMEDGE NAILINGWALL SHTG PERSW-SCHEDULEDETAIL #6NEW ELEVATOR WALL @EXISTING MAIN FLOOR1"=1'-0"BEAM PER PLAN w/SIMP SDWSx6" @ 6" o/cTOP & BOTNOTE:1. REFERENCE 5/S3 FOR CALLOUTS IN COMMON.2. ATTACH SHEATHING AT PANEL EDGES WITH 10d COMMONS AT 6"o/c AND 12" o/c IN FIELD.SILL PL w/ SIMP SDWSx6"TOP & BOTTSW-EDGE NAILSPER SW-SCHED TYP12" GWB12" GWB34" SHTGPER NOTE2x6 WALL STUDS@ 16" o/c TYP(E) WALL SHTGDETAIL #7NEW ELEVATOR WALL TOEXISTING EXTERIOR WALL1"=1'-0"(E) 2x WALL(N) FLR JOIST PER PLAN(E) 2x6 WALL BEYONDT/ UPPERLEVEL(N) FLR SHTG(E) RIM JOIST(N) 4x HDR TYP(E) GWBDIAPHRAGM EDGE NAILINGSIMP LUS(N) DBL RIM JOISTDIAPHRAGM EDGE NAILINGDIAPHRAGM EDGE NAILING12" GWB21 4 " 1 3 8 "2x10 LEDGER w/(2) SIMP SDWSx5" @ 16" o/c(E) 2x JOIST(E) FLR SHTG(E) 2x BLKG(E) 2x6 WALL(E) GWBTYPFLOORJOISTPER PLANCONT 2x4LEDGER w/10d @ 6" o/cDIAPHRAGMEDGE NAILINGFLOOR SHTGPER PLANT/ UPPPERLEVELDETAIL #8NEW ELEVATOR FLOOR LANDINGTO EXISTING INTERIOR WALL1"=1'-0"(E) WALLDIAPHRAGMEDGE NAILINGREMOVE(E) GUARDRAIL(E) FLR SHTGT/ UPPPERLEVEL(N) FLR JOISTPER PLAN w/SIMP LUS(N) 2x10 ATTACHED TO(E) DBL 2x10 w/(2) ROWS 10d NAILS@ 24" o/c(E) DBL 2x10(E) FLR JOISTPER PLAN w/(E) HANGERDETAIL #9NEW ELEVATOR LANDINGTO EXISTING FLOOR1"=1'-0"(N) FLR SHTGPER PLAN2x6 WALL STUDSSW-EDGE NAILSPER SW-SCHED TYP12" GWBWALL SHTG PERSW-SCHEDULE TYP2x6 WALL STUDS@ 16" o/c TYPT/ (E) CEILINGDEMO (E) ROOF TRUSSDETAIL #10ELEVATOR WALL ATUPPER FLOOR1"=1'-0"NOTE: REFERENCE 5/S3 FOR CALLOUTS IN COMMON.BEAM PER PLAN w/SIMP SDWSx6"@ 6" o/cTOP & BOT12" GWB34" SHTGPER NOTET/ UPPER LEVEL(E) WALL(E) WALL SHTGFLOOR SHTGPER PLANDIAPHRAGMEDGE NAILING(N) FLOORJOISTPER PLANCONT 2x4LEDGERw/ 10d@ 6" o/cDETAIL #12(N) ELEVATOR FLOORLANDING DIAPHRAGMTO (E) EXTERIOR1"=1'-0"(E) GWB12" GWB2x6 WALL STUDS@ 16" o/c TYPWALL SHTG PER SW-SCHEDULET/ LOW ROOF(2) SIMP SDWSx6" INTOEA STUD w/ SOLID SHIM(E) ROOF TRUSSGAP < 112"DETAIL #11ELEVATOR WALL TO LOW ROW ROOF1"=1'-0"8d @ 6" o/cCONT 2x4 LEDGER w/SIMP SDWSx6"SCREW INTO EA STUD24">GAP>112"SIMILAR8d @ 6" o/c3ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED NOTES PR19000244B19002967V2DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 DETAIL #1ELEVATOR WALL TO EXISTING ROOF1"=1'-0"2x6 WALL STUDS @ 16" o/c TYPWALL SHTG PER SW-SCHEDULESILL PL w/ (2) ROWS16d @ 24" o/cINTO EA BLOCKSW-EDGE NAILING(E) 2x BLKG(E) 2x6WALL STUDS(E) PRE MFRTRUSS @24" o/c(E) ROOF SHTGT/ (E) CEILING(E) WALL SHTGBEVELED 4x BLKG w/(2) SIMP SDWSx6"@ 24" o/c2x FASCIA w/(2) 16d INTOEA RAFTER2x6 WALL STUDS@ 16" o/cWALL SHTGPER SW-SCHEDSW-EDGENAILING(4) 10d ROOF RAFTERTO CEILING JOISTSIMP H2.5A2x4 CEILING JOIST@ 24" o/c1'-6" MAXDIAPHRAGM EDGE NAILINGROOF SHTG PER PLANROOF RAFTERPER PLANDETAIL #2ROOF CONNECTION (PERPENDICULAR)1"=1'-0"SIMP SDWSx6"PER SW-SCHEDCONT 2x BLKG1'-6" MAX1'-10"2x FACIA w/(2) 16d INTOEA OUTRIGGER2xOUTRIGGERS@ 24" o/cSW-EDGE NAILINGDIAPHRAGMEDGE NAILING2x BLKG(2) 16d INTOEA OUTRIGGERSIMP SDWSx6"PER SW-SCHEDULEWALL SHTGPER SW-SCHEDULEBALLOON FRAMING2x6 STUDS @ 16" o/c2x4 CEILING JOIST@ 24" o/c w/ (4) 10d2x ROOF RAFTERDETAIL #3ROOF CONNECTION (PARALLEL)1"=1'-0"DIAPHRAGMEDGE NAILINGSIMP SDWSx6"PER SHEARWALLSCHEDULESIMP LTP5@ 24" o/cROOF SHTGPER PLANGENERAL NOTES:1.All design and construction shall conform to the 2015 International Residential Code.2.Read structural drawings together with Architectural, Mechanical, Electrical and other drawingsfor detail dimensions, locations of door and window openings, duct work, recesses, inserts andother items. In the event discrepancies between drawings, the more stringent requirementsshall be followed. Under no circumstance shall structural elements be modified without thewritten approval of the structural engineer.3.The contractor shall verify all dimensions and examine site conditions prior to fabrication of allitems to ensure proper installation.4.The contractor shall have a complete working knowledge of standard residential constructiontechniques that are commonly used in the profession. The contractor shall request clarification fromthe structural engineer on items that cannot be constructed as detailed or with standard constructiontechniques.5.The structural drawings illustrate the completed structure with elements intheir final positions. The contractor shall provide adequate shoring and bracing duringconstruction to resist all forces including wind, seismic and unbalanced forces due toconstruction sequence.6.Foundations: Required soil bearing pressure:1,500-psf at surfaceMinimum depth of stair footings exposed to exterior elements shall have a minimum bury depthof 12-in. for frost protection.Remove free water from excavations and forms prior to placement of the concrete.Footings shall be placed on solid bearing ground a minimum of 1-ft below grade. Footingsmay exceed the 1-ft minimum depth due to poor upper level soil conditions.7.Wood properties:Structural framing, except studs:Douglas Fir-Larch #2Fb:850-psiFt:500-psiFv:170-psiFcperp:625-psiFcpar:1,400-psiE1,600,000-psiStructural studs:Doug Fir-Larch StudFb:700-psiFt:450-psiFv:180-psiFcperp:625-psiFcpar:850-psiE1,400,000-psi8.Concrete properties:F'c: 3,000-psi @ 28-days footings & std stem wall.Air Entrained: 5%-7%Slump: 4"-5" measured before superplasticizer if used.Cement: Portland Type I or II.Calcium Chloride:Not permitted.Grout: Non-shrink, non-ferrous, developing minimum compressive strength of4,500-psi in 3-days, 8,000-psi in 28-days.9.The contractor is responsible for the design and construction of all the formwork, false-work,and temporary shoring. Vibration is essential for proper placement of concrete. Overvibration will cause separation of cement and rock and is cause for rejection of placed concrete.10.Forms shall not be removed for a minimum of 24-hours after concrete placement.11.Reinforcing steel:Deformed bars:ASTM-A615 Grade 60Welded wire fabric:ASTM-A185Cover:3", concrete surfaces cast against earth,2", formed surfaces exposed to earth1-1/2", ties to concrete face, not exposed to earth.12.Anchor bolts/threaded rods:ASTM-A307 or F1554 Gr 36 hot dipped galvanized (per ASTM A153) orSimpson Titen HD Concrete Screws (zinc plated by manufacturer) Post installed anchors shall be installed per manufacturer's instructions. For reference Simpson Anchoring and Fastening Systems for Concrete+Masonry (C-A-2018) catalog shall be on site.3"x3"x1/4" hot dipped galvanized (per ASTM A153) washers and standard nuts required for anchorrod.13.Fastners:All fasteners and connectors installed in or on preservative-treated wood shall be hot dippedzinc-coated galvanized with a minimum coating weight per ASTM A153.14.Amended Construction Documents (IBC 106.4)Work shall be installed in accordance with the approved construction documents, and any changesmade during construction that are not in compliance with the approved construction documentsshall be submitted to the Engineer in responsible charge whoshall review them and forward them to the building official with notation indicating that the changedconditions have been found to be in general conformance to the design ofthe building.15.Deferred Submittal (IBC 106.3.4.2):Deferred Submittal List:Spiral StaircaseDocuments for deferred submittal items shall be submitted to the Engineer in responsiblecharge who shall review them and forward them to the building official with notationindicating that the deferred submittal documents have been reviewed and been found tobe in general conformance to the design of the building. The deferred submittal itemsshall not be installed until the design and submittal documents have been approved bythe building official.11Posts and Timbers:Doug Fir-Larch #2Fb:875-psiFt:425-psiFv:170-psiFcperp:625-psiFcpar:850-psiE1,300,000-psiAll wood in contact with concrete shall bepreservative treated (PT) per AWPA U1and field treated per AWPA M4.14ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED NOTES PR19000244B19002967V2DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 EXHIBIT 5 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 10"10"61" FINISHED DIMENSION912"10"2712"ȭ 55" FINISHED DIMENSION 49" INSIDE 40" INSIDE4112" OUTSIDE5212" OUTSIDE 2834"ȭ36" DOORHALL CALL TYPICAL 114" 3614"3234"ȭ36" DOORHALL CALL TYPICAL 114"45716"36" CLR1634"1112"4558"36" CLRCOP PB NOTES: -CAR FLOORING AND FINISHINGS MUST NOT EXCEED 25 LBS -IN ORDER TO MEET THE 3/4" AND 4" REQIUREMENTS, A MAXIMUM OF 1/4" HOISTWAY DOOR SETBACK IS ALLOWED, WHEN USING ACCORDION CAR DOOR(S). 4" MAXIMUM THE INSIDE FACE OF HOISTWAY DOOR TO OUTSIDE OF CAR DOOR MUST REJECT A 4" BALL. 14" MAXIMUM (INSIDE FACE OF HOISTWAY DOOR TO SILL) 12" - 1 14" RUN CLR (SILL TO SILL) ACCORDION CAR DOOR (LOCKING MECHANICAL HINGE) TYPICAL DOOR LOCATION DETAIL ACCORDION (FOLDING) CAR DOOR HOISTWAY DOOR ȭ TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION 40 x 54 OPPOSITE RH RH NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 FLOORS 2-3 FLOOR 1 OLYMPIC ELEVATOR DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 4"2" OVERTRAVELTOTAL CAR TRAVELOVERHEADOVERALL HOISTWAY(PIT+TRAVEL+OVERHEAD)PIT DEPTHHOISTWAY OPENINGHOISTWAY OPENINGHOISTWAY OPENINGINTERIOR CAR HEIGHTPIT DEPTH FLOOR TO FLOOR TRAVEL OVERHEAD OVERALL HOISTWAY 8" 210" 96" 314" JOB SPECIFIC INFORMATION: NOTES: 1) CONSULT LOCAL AUTHORITY TO ENSURE COMPLIANCE WITH STATE AND LOCAL CODES. 2) THE HOISTWAY IS REQUIRED TO BE FREE OF ALL PIPES, WIRING, AND OBSTRUCTIONS NOT RELATED TO THE OPERATION OF THE ELEVATOR. Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" Hydro Static Load (lbs) 2552 2942 3399 Hydro Impact Load (lbs) 5277 5667 6124 Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" IGD Static Load (lbs) 3082 3374 3764 IGD Impact Load (lbs) 5807 6099 6489 Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" Drum Static Load (lbs) 2552 2942 3399 Drum Impact Load (lbs) 5277 5667 6124 TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION 3 STOP ELEVATION NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 10' MAXAllow for drywall thickness (pit flush with hoistway)Pit wall 10 " Rail Backing Centerline Pit Floor 10 " Drywall Construction Details of Rail Backing: x Laminate (2) 2x10's and (2) 2x4's using wood glue and #8x2-1/4" minimum screws x All joints must be staggered x 12" plywood between Typical Hoistway Construction Details Floor Joists Subfloor Header Corner Post Construction 2 x 4 2 x 4 2 x 10's 12" 2" 2" 12" 12" vertical screw spacing and 2" from each side of 2x10 centerline Drywall (shown cutaway) Typical Rail Backing Construction 2 x 4 2 x 4 2 x 10's 12" 2" 2" 12" x Laminate (2) 2x10's and (2) 2x4's using wood glue and #8x2-1 4" (min.) screws x All joints must be staggered x 12" plywood between 10 " 10 " 12" CENTERLINE OF RAIL BACKING R2 380# 4  56#6+%4#+. 4'#%6+10 12" plywood TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION TYPICAL HOISTWAY CONSTRUCTION NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 48" 3'-0" SELF CLOSING, SELF LOCKING, ACCESS DOOR 24" LIGHT SWITCH & DUPLEX RECEPTACLE TELEPHONE CONNECTION MAIN CONTROL BOX 18"H X 18"W X 10"D HYDRAULIC POWER UNIT 331 2"H X 24 1 4"W X 123 4"D LIGHT HYDRAULIC POWER UNIT 115-15 AMP SERVICE 208/230-30 AMP SERVICE 6"6" MAIN CONTROL BOX OVERHEAD VIEW FRONT VIEW Motor Controller Disconnect (Fusible and Lockable) Car Light Disconnect (Fusible and Lockable) 208/230VAC, 30 AMP, Single Phase (3 Wire Dedicated Circuit) *Feeding breaker must not be a G.F.I. 115VAC, 15 AMP, Dedicated Single Phase *Feeding breaker must not be a G.F.I. Telephone Service For Elevator HYDRAULIC POWER UNIT MAIN CONTROL BOX 1/2"-3/4" PLYWOOD BACKING BEHIND DRYWALL 6'-6" MAXIMUM HEIGHT NOTES: 1)THE ELEVATOR MACHINE ROOM LOCATION AND LAYOUT MUST MEET CODE REQUIREMENTS DEFINED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 2)30" WIDE x 36" DEEP CLEAR WORKING SPACE REQUIRED IN FRONT OF THE MAIN CONTROL BOX BY NEC. 3)LIGHT SWITCH TO BE LOCATED ON THE STRIKE SIDE OF THE MACHINE ROOM DOOR. 4)THE HYDRAULIC POWER UNIT SHOULD BE LOCATED WITHIN 40' FROM THE CYLINDER. 5)MACHINE SPACE SHALL BE FREE OF ANY EQUIPMENT OR APPURTENANCES NOT RELATED TO THE ELEVATOR. 6)KEEP THE CONTROL ROOM 7(03(5$785(%(7:((1ž)72ž) BETWEEN 0 TO 95% RELATIVE HUMIDITY NON-CONDENSING. TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION COMPACT MACHINE ROOM NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 PLANNING DIVISION CERTIFICATE OF EXEMPTION FROM SHORELINE SUBSTANTIAL DEVELOPMENT DEPARTMENT OF COMMUNITY AND ECONOMIC DEVELOPMENT DATE: PROJECT NUMBER: PROJECT NAME: PROJECT MANAGER: Brittany Gillia, Assistant Planner LUA20-000048, SME Shoreline Elevator Installation March 05, 2020 OWNER: DOUGLAS B AND MARJORIE A HARWOOD 3713 LK WASHINGTON BLVD N RENTON, WA 98056 PROJECT LOCATION: 3713 LAKE WASHINGTON BLVD N PROJECT DESCRIPTION: The applicant is requesting a Shoreline Exemption for the construction of a new 75 square foot, 3-story elevator to be installed within the existing footprint of a 3,140 square foot residential home (Exhibit 1 and 4). The 11,060 square foot project site is located within the Residential-6 (R-6) zone and is situated on the shoreline of Lake Washington in the Shoreline Residential Designation, Reach D. The property is mapped with a High Landslide Hazard. The existing single-family residence is proposed to have the front stairs removed and replaced with a spiral staircase along with the installation of the 5’6”x5’6” elevator on the front of the building next to the new spiral staircase and existing garage (Exhibit 2). Proposed access to the site will be from Lake Washington Boulevard and no job shacks, trailers, or model homes will be necessary for this project. There are no trees proposed to be removed as part of this project. The proposal would be exempt from SEPA under WAC 197-11 -800(1), minor new construction. PROJECT ANALYSIS: This project meets criteria listed in RMC 4-10-095.F.2. Partial Compliance for Single Family Development. Lawfully constructed single family homes built before the adoption of the Shoreline Master Program (October 24, 2011) shall be considered conforming if expansion or replacement is consistent with the standards below: Alteration without expansion: Expansion or remodel that does not change the building footprint or increase impervious surface. Staff Comment: The proposed addition does not expand the building footprint or increase impervious surface. Compliance standards state that no site changes are required. This project meets criteria listed in RMC 4-3-090.D.3.b View Compatibility and Aesthetic Effects; View Obstruction and Visual Quality. The following standards and criteria shall apply to developments and uses within the jurisdiction of the Shoreline Master Program: i. View Corridors Required: Where commercial, industrial, multiple use, multi-family and/or multi-lot developments are proposed, primary structures shall provide for view corridors between buildings where views of the shoreline are available from public right-of-way or trails. Staff Comment: The proposed roofline for the elevator shaft does not exceed the current roof line of the existing structure. (Exhibit 2) The view from the King County Eastside Rail Corridor Trail will not impede or be obstructed by the proposed development. Page 1 of 3 DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758E EXHIBIT 6 DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Certificate of Exemption from Shoreline Substantial Development Shoreline Elevator Installation LUA20-000048, SME ii. Maximum Building Height: Buildings shall be limited to a height of no more than thirty five feet (35') above average finished grade level except at specific locations specified in Table 4-3-090D7a, Shoreline Bulk Standards. Staff Comment: The proposed building height will reach 26’ 9” at the top of the roof peak and therefore complies with the Maximum Building Height standard (Exhibit 2). iii. Minimum Setbacks for Commercial Development Adjacent to Residential or Park Uses: Staff Comment: Not applicable. iv. Lighting Requirements: Staff Comment: Not applicable. v. Reflected Lights to Be Limited: Staff Comment: Not applicable. vi. Integration and Screening of Mechanical Equipment: Building mechanical equipment shall be incorporated into building architectural features, such as pitched roofs, to the maximum extent feasible. Where mechanical equipment cannot be incorporated into architectural features, a visual screen shall be provided consistent with building exterior materials that obstructs views of such equipment. Staff Comment: The proposed elevator shaft has an intentional height and style to create architectural symmetry for the building. The addition reflects an architectural feature to the right of the structure that also bumps out and aligns with the existing roofline (Exhibit 2 and 3) vii. Visual Prominence of Freestanding Structures to Be Minimized: Staff Comment: Not applicable viii. Maximum Stair and Walkway Width: ix. Other Design Standards: Staff Comment: Not applicable SEC-TWN-R: NW32 - 24 - 5 LEGAL DESCRIPTION: (King County Assessor) HILLMANS LK WA GARDEN OF EDEN #2 LOT 45 TGW S 10.84 FT LOT 44 & N 16.26 FT LOT 46 AS MEAS ALG E LN TGW SH LDS ADJ TGW WLY 15 FT OF NP R/R ADJ AKA LOT 1 RENTON LLA 003-88 REC NO 8806219003 WATER BODY/REACH: Lake Washington Reach D EXEMPTION JUSTIFICATION: An exemption from a Shoreline Management Substantial Development Permit is hereby Approved on the proposed project in accordance with RMC 4.9.190C 'Exemption from Permit System' and for the following reasons: Construction on shorelands by an owner, lessee or contract purchaser of a single.family residence for their own use or for the use of their family, which residence does not exceed a height of thirty.five feet above average grade level and which meets all requirements of the state agency or local government having jurisdiction thereof, other than requirements imposed pursuant to chapter 90.58 RCW. "Single.family residence" means a detached dwelling designed for and occupied by one family including those structures and developments within a contiguous ownership which are a normal appurtenance. An "appurtenance" is necessarily connected to the use and enjoyment of a single.family residence and is located landward of the ordinary high water mark and the perimeter of a wetland. On a statewide basis, normal appurtenances include a garage; deck; driveway; utilities; fences; installation of a septic tank and drainfield and grading which does not exceed two hundred fifty cubic yards and which does not involve placement of fill in any wetland or waterward of the ordinary high water mark. Local circumstances may dictate additional interpretations of normal Page 2 of 3 DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 City of Renton Department of Community & Economic Development Certificate of Exemption from Shoreline Substantial Development Shoreline Elevator Installation LUA20-000048, SME appurtenances which shall be set forth and regulated within the applicable master program. Construction authorized under this exemption shall be located landward of the ordinary high water mark; The proposed development is: Consistent with the policies of the Shoreline Management Act. Not Applicable to the guidelines of the Department of Ecology where no Master Program has been finally approved or adopted by the Department. Consistent with the City of Renton Shoreline Master Program. SIGNATURE & DATE OF DECISION: Date Jennifer Henning, AICP, Planning Director Department of Community & Economic Development RECONSIDERATION: Within 14 days of the decision date, any party of record may request that the decision be reopened by the approval body. The approval body may modify his decision if material evidence not readily discoverable prior to the original decision is found or if he finds there was misrep resentation of fact. After review of the reconsideration request, if the approval body finds sufficient evidence to amend the original decision, there will be no further extension of the appeal period. Any person wishing to take further action must file a formal appeal within the 14 day appeal time frame. APPEALS: The administrative land use decision will become final if not appealed in writing together with the required fee to: Hearing Examiner, City of Renton, 1055 South Grady Way, Renton, WA 98057 on or before 5:00 pm, on March 19, 2020 (RCW 43.21.C075(3); WAC 197-11 -680). RMC 4-8-110 governs appeals to the Hearing Examiner and additional information regarding the appeal process may be obtained from the Renton City Clerk's office, Renton City Hall, 7th Floor, (425) 430-6510. EXPIRATION: Two (2) years from the date of decision (date signed) Attachments: Site Plan DOUGLAS B AND MARJORIE A HARWOOD - Owner cc: Page 3 of 3 DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758E 3/5/2020 | 12:55 PM PST DocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 Pictom etr y, Ki ng C o u nty, K ing C ounty As se ss or 's O ffi ce , Ki ng C oun ty G ISCenter, Kin g C o unty, Ki n g coun ty Asses sor's Offic e, K ing C ounty GIS C en ter Date : 6/4/201 9 ±The informati on included on this map has been compi led by King County staff from a variety of sour ces and issubject to change wi thout notice. King County makes no r epresentati ons or w ar ranties, expr ess or impl ied,as to accurac y, completenes s, timeli ness , or ri ghts to the use of such infor mation. This document is not intendedfor use as a s urvey pr oduct. King County shall not be liable for any gener al, s pecial, i ndir ect, incidental , orconsequential damages incl uding, but not li mited to, lost revenues or lost pr ofits resulting fr om the use or misuseof the information contained on this map. Any sale of this map or infor mati on on this map is pr ohibited except bywritten per mi ssi on of Ki ng County. King C ou nty EXHIBIT 1 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 GUARDRAILS & LANDINGBY OTHERSSPIRAL STAIRBY OTHERSELEVATOR WALLELEVATOR WALL BEYOND26'-2"/314" T/ELEVATORROOF FRMG ELEV17'-10" 3RD FLR FRMG ELEVSOUTH ELEVATION14"=1'-0"101 4 " T/ELEVATOR PIT SLAB 0'-0" BATH/GARAGE 1ST FLR ELEV8'-11" MAIN 2ND FLR FRMG ELEV7'-8" LOW ENTRY 2ND FLR ELEV0'-214" PATIO/STORAGE ELEV8'-1" T/ TOP PL (MAIN) 8'-1" T/ TOP PL 10" 10" 7'-5 3 4 " T/TOP PL 1'-3"-1014" ELEVATOR PIT SLAB ELEV7' T/ TOP PL (LOW ENTRY) 8"2GUARDRAILS &LANDINGBY OTHERSSPIRAL STAIR CASE& LANDING BY OTHERS(E) FULL HEIGHTCOLUMN(E) DOOR(N) ELEVATORDOOR(E) GARAGEDOOREXISTINGBEYOND(E) LOW ROOF(E) UPPER ROOFBEYONDSPIRAL STAIRCASECOLUMN BY OTHERSELEVATOR ALCOVE26'-2"/314"ELEVATOR ROOFFRMG ELEV17'-10" 3RD FLR FRMG ELEV-1014" T/ELEVATOR SLAB ELEV8'-11" MAIN 2ND FLR ELEVEAST ELEVATION14"=1'-0"7'-8" LOW ENTRY 2ND FLR ELEV0'-214" PATIO/STORAGE FLR ELEV7'T/ TOP PL(LOW ENTRY)8"1'-3"8'-1"T/TOP PL 10"0'-0" GARAGE/BATH FLR ELEV101 4 "T/ELEVATORSLAB ELEV 7'-5 3 4 "T/ TOP PL 24' MAX WALL PLATE HEIGHT PERPLAN REVIEW COMMENT314" NEW ELEVATOR HEIGHT24' 26'-2"/314"21ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED DIMESIONING 1 8/13/2019 PLAN REVIEW COMMENTS 2 12/26/2019 NEW ELEVATOR WALL REVISIONEXHIBIT 2RECEIVEDClark Close 01/15/2020PLANNING DIVISIONDocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 FOUNDATION PLAN14" = 1'-0"(E) FOUNDATIONTO REMAINDEMOLISH(E) STEM WALL(E) FOUNDATION TO REMAINDEMOLISH (E) STEM WALL(E) FOUNDATIONTO REMAIN(E) FOUNDATION TO REMAINELEVATOR PIT6" SLAB ON GRADEw/ #4's @ 12" o/cE/W(N) 6" CONC STEMCENTERED ABOVEw/ 1'-4"W x 12" DPCONC FTG TYPICAL1'-6" SQx12"DP CONC FTG &38"x8"x0'-8" BASE PLATE w/(4) 12"Ø x 4 12" SIMP TITEN HDTYPE 300 SERIES STAINLESS STEEL(E) FOUNDATION TO REMAINFR=5'-1"1/S32/S34/S33/S3FR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'2'-312"TYP10"TYP1℄1st FLOOR FRAMING PLAN14" = 1'-0"66"Ø SPIRAL STAIRCASE& LANDING BY OTHERSTYPICAL RAIL SUPPORT2x10DBL 12" PLYWOOD(2) 2x102x6 EA SIDEFR=5'-1"(E) 12" SW-SHTG(E) 2x6 WALL STUDS(E) 58" GWB(N) 12" GWB(N) 2x6 STUDS @ 16" o/c(N) 12" SW-SHTGFR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'RAIL SUPPORT @ (E) POST2x1012" PLYWOODDBL 2x4(E) 4x6 POST2'-312"TYP10"TYP(N) 12" GWB(E) 12" SW-SHTG(E) 2x6 WALL STUDS(E) 58" GWB21122nd FLOORFRAMING PLAN14" = 1'-0"66"Ø SPIRAL STAIRCASE &LANDING BY OTHERS(N) FLOOR SHTGPER PLAN NOTE #82'-9"4' FR=5'-1"6/S35/S34x10 BEAM FR=4'-7"3'2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-2 1 2 "3'-5 1 2 "4'2'-312"TYP10"TYP3rd FLOORFRAMING PLAN14" = 1'-0"2x10@16" o/cFLOOR SHTGPER PLAN NOTE #8(E) LOW ROOF(E) LOW ROOFFR=5'-1"10/S37/S38/S39/S311/S311/S3SIM12/S34x10BEAM(N) FLR SHTG PERPLAN NOTE #8(N) 12" GWB(N) 12" SW-SHTG(N) 2x6 WALL STUD(N) 12" WALL SHTGFR=4'-7"2134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-21 2 "3'-51 2 "4'ELEVATOR DOOROPENS INTO(E) EXTERIOR WALLIN CURRENT GEOMETRY2'-312"TYP10"TYPROOF FRAMING PLAN14" = 1'-0"LOW ROOF LINE BELOW2x10 ROOF JOISTS @ 24" o/c'SISTER' w/ 2x4 CEILING JOISTS(CONNECT TOGETHERw/ (4) 10d NAILS) TYPROOF SHEATHINGPER PLAN NOTE #81/S4BELOW3/S4ABOVE2/S43/S42/S42134521345DBACDBAC5'-514"2'-1012"1'-10"2'-912"5'-21 2 "3'-51 2 "4' LATERAL NOTES:SHEARWALL REQUIREMENTSSW-6REPRESENTS 12" NOMINAL APA RATED WALL SHEATHING* WITH 8d COMMONS AT 6" ON CENTER AT PANEL EDGESAND 12" ON CENTER IN FIELD. ATTACH DOUBLE TOP PLATES TO 2x BLOCKING ABOVE WITH SIMPSON SDWSx6"SCREWS @ 16" o/c. ATTACH BOTTOM PLATE TO 2x BLOCKING OR RIM JOIST WITH 16d @ 5" o/c. ATTACHPRESSURE TREATED HEM-FIR #2 PLATE TO DOWNTURNED CONCRETE EDGE WITH 12" Ø SIMPSON TITEN HDCONCRETE SCREWS (EMBED 234") AT 16" o/c.SW-4REPRESENTS 12" NOMINAL APA RATED WALL SHEATHING* WITH 8d COMMONS AT 6" ON CENTER AT PANEL EDGESAND 12" ON CENTER IN FIELD. ATTACH DOUBLE TOP PLATES TO 2x BLOCKING ABOVE WITH SIMPSON SDWSx6"SCREWS @ 16" o/c. ATTACH BOTTOM PLATE TO 2x BLOCKING OR RIM JOIST WITH 16d @ 5" o/c. ATTACHPRESSURE TREATED HEM-FIR #2 PLATE TO DOWNTURNED CONCRETE EDGE WITH 12"Ø SIMPSON TITEN HDCONCRETE SCREWS (EMBED 234") AT 12" o/c.*IT IS ACCEPTABLE TO USE EXISTING WALL SHEATHING. ENSURE SUFFICIENT NAILING PER SHEARWALL TYPE IS MET.HOLDOWN REQUIREMENTSMSTC40: ATTACH SIMPSON MSTC40 TO DOUBLE STUD VERTICALLY w/ (28) 8d COMMONS OVER WALL SHEATHING (HALFABOVE WIND GIRT AND HALF BELOW WIND GIRT.HDU2: INSTALL SIMPSON HDU2 TO CONCRETE WITH SIMP SSTB24 INTO NEW STEM WALL OR 58"Ø THREADED ROD(EMBED 7") w/ SIMP SET EPOXY INTO EXISTING STEM WALL AND (6) 14"x212" SDS TO DOUBLE STUDS MINIMUM.HDU5: INSTALL SIMPSON HDU5 TO CONCRETE WITH SIMP SSTB28 AND (10) 14"x2 12" SDS TO DOUBLE STUDS MINIMUM.ALL SIMPSON HARDWARE SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. FOR REFERENCE THE FOLLOWINGSIMPSON CATALOGS SHALL BE ON THE JOB SITE AT THE TIME OF INSPECTION: a) WOOD CONSTRUCTION CONNECTORS(C-C-2019) b) ANCHORING AND FASTENING SYSTEMS FOR CONCRETE+ MASONRY (C-A-2018).1PLAN NOTES:1. ELEVATOR RAIL BRACKET PER MANUFACTURER. CONNECTBRACKET TO 6x6 RAIL w/ (4) 38"x3" LAG SCREWS. ENSURE 3"SPACING AS SHOWN IN ELEVATOR MANUFACTURER DRAWINGS.2. IF EXISTING CONDITIONS VARY FROM WHAT IS SHOWN,CONTACT THE ENGINEER ON RECORD.3. ALL ELEVATOR DOOR HEADERS SHALL BE 4x6 DF-L #2 AND BEARON DOUBLE STUD MINIMUM, UNLESS NOTED OTHERWISE. ROUGHOPENINGS AND DOOR SIZE PER ELEVATOR MANUFACTURER.4. ALL BUILT UP MEMBERS SHALL BE LAMINATED WITH (2) ROWS10d BOX NAILS STAGGERED AT 12" o/c5. ALL ELEVATOR WALLS SHALL BE 2x6 STUDS @ 16" o/c. IT ISASSUMED ELEVATOR WALLS ARE COVERED IN 12" GYPSUM(INTERIOR) & 12" NOMINAL APA RATED WALL SHEATHING(EXTERIOR).6. SAWCUT AND EXCAVATE EXISTING PATIO.7. ENSURE FOOTINGS BEAR ON UNDISTURBED NATIVE SOIL.8. FLOOR SHEATHING SHALL MATCH EXISITNG THICKNESS &FASTENED AT PANEL EDGES w/ 10d COMMONS @ 6" o/c & 12"o/c IN FIELD.ROOF SHEATHING SHALL BE 1532" APA RATED SHEATHING w/ 8dCOMMONS @ 6" o/c & 12" o/c IN FIELD.9. GRIDLINES ARE LOCATED AT EDGE OF STUD/STEM WALLS WITHTHE EXCEPTION OF GRIDLINE C, LOCATED AT CENTER OF SPIRALSTAIRCASE PIPE.ABBREVIATIONS:CONC: CONCRETEDEMO: DEMOLISH(E) : EXISTINGE/W: EACH WAYELEV:ELEVATIONFDN: FOUNDATIONFTG: FOOTINGFR: FINISHED ELEVATOR RUNWAY TYPICAL AT ALL LEVELSGWB: GYPSUM WALL BOARDHD: HOLDOWNHDR: HEADERLONG: LONGITUDINAL(N): NEWSHTG: SHEATHINGSW: SHEARWALLT/ : TOP OFTRANSV: TRANSVERSETYP: TYPICAL FOR SIMILAR CONFIRGURATIONSSW-6SW-6SW-6 HDU2HDU2HDU5HDU21st LEVEL SHEARWALLS14"=1'-0"2'-312"TYP10"TYPSW-6SW-6MSCT40MSCT40MSTC402nd LEVEL SHEARWALLS14"=1'-0"MSCT402'-312"TYP10"TYPSW-6SW-6SW-6 SW-6 MSTC40MSTC40MSTC403rd LEVEL SHEARWALLS14"=1'-0"MSTC402'-312"TYP10"TYP1'-8"1'-8"℄MSTC,FLR JOISTMSTCPER PLANHDU PER PLANw/ SIMP SSTBINTO NEWSTEM WALLHOLDOWN STUDSPER PLANHDU PER PLANw/ 58"Ø THREADEDROD w/ SIMP SETEPOXY (EMBED 7")TYPHOLDOWN STUDSPER PLAN TYP7" TYP WALL AS OCCURSPER PLANNEW STEMPER PLANEXISTING STEMPER PLANTYPICAL HOLDOWNSTO CONCRETE STEMWALLS1"=1'-0"TYPICAL HOLDOWNSTO WOOD FRAMING1"=1'-0"2PLANS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED GRID-LINE DIMESIONING PR19000244B19002967V2DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 (E) FOOTING(E) 8" CONCSTEM WALL(E) GARAGESLAB ON GRADE(E) PT MUD PL w/12"Ø ANCHOR BOLTS@ 48" o/c MIN(E) 2x6 WALL(E) WALL SHTG(E) SHEARWALLEDGE NAILINGT/ ELEVATOR PITDEMO (E) PATIOSLAB ON GRAGEDETAIL #1ELEVATOR TO (E) GARAGE WALL CONNECTIONS1"=1'-0"101 4 "#4 REBAR DOWELS @ 18"w/ SIMP SET EPOXY(EMBED 3")1'-6"VERIFY (E) 58"TYPE 'X' GWB(N) 12" GWBVERIFY (E) PERF DRAIN8" ELEV PIT T/ GARAGESLAB ON GRADE(N) 6" SLAB ON GRADEw/ #4's @ 18" o/c E/W11'-4"1' 101 4 " 3" CLRTYP 3" CLRTYP(2) #4 CONT(E) PATIOSLAB ON GRADET/ PATIOSLAB ON GRADET/ ELEVATOR PIT(N) 6" CONC SLAB ON GRADEw/ #4's @ 18" o/c E/WWALL SHTG PERSHEARWALL SCHEDULE2x6 PT SILL PL w/ANCHOR BOLTS PERSHEARWALL SCHEDULESW-EDGE NAILINGDEMO (E) PATIOSLAB ON GRADE2x6 WALL STUDS@ 16" o/c12" GWBDETAIL #2NEW ELEVATOR @ NEW FOUNDATION1"=1'-0"4" PERF DRAIN(TIE TO (E) OR INSTALL(N) DRAIN SYSTEM#4's 36"o/c, CENTERED#4 CROSS-TIES 36"o/c#4 HORZ.TOP & BTTM4"18" ELEV PIT (E) 6" CONC STEM WALLWALL SHTGPER SW-SCHEDULET/ ELEVATOR PITDETAIL #3NEW ELEVATOR WALL@ EXISTING STEM WALL1"=1'-0"8" PER EXISTING (E) DRAWINGS1'-4" PER(E) DRAWINGS(N) 6" CONC SLAB ON GRADEw/ #4's @ 18" o/c E/WSW-EDGE NAILING2x6 PT BOTTOM PL w/ANCHOR BOLTS PERSHEARWALL SCHEDULE2x6 WALL STUDS@ 16" o/c#4 DOWELS INTO (E) STEM w/SIMP SET EPOXY (EMBED 3")@ 18" o/cNOTE:THE STEM WALL CONFIGURATION IS BASED ONTHE EXISTING DRAWINGS SUPPLIED. CONTACTENGINEER OF RECORD IF CONDITIONS VARY.T/ BATH/GARAGE FLR(E) 12" GWB(E) CRAWLSPACE BEAM(E) CRAWLSPACE JOISTSDEMO (E) PATIOSLAB ON GRADE101 4 "VERIFY (E) PERF DRAIN1(E) ASPHALTT/ ASPHALT DRIVEWAYT/ GARAGEDETAIL #4NEW INTERIOR ELEVATOR WALL@ EXISTING STEM WALL1"=1'-0"(E) 8" CONCSTEM WALL(2) CONT #4'sT/ ELEVATORPIT(N) 6" SLAB ON GRADEw/ #4's @ 18" o/c E/W2x6 PT SILL PL w/ ANCHOR BOLT PERSHEARWALL SCHEDULE2x6 WALLSTUDS @ 16" o/cSHEARWALLEDGE NAILING12" GWBWALL SHTGPER SHEARWALLSCHEDULE(N)ELEVATOR ENTRYSLAB ON GRADEDEMO (E) PATIOSLAB ON GRADE8" ELEV PIT 101 4 "VERIFY (E) PERFDRAINDEMO (E)SLAB ON GRADE#4's 36"o/c, VERT. CENTERED#4's HORZ TOP & BTTM#4 CROSS-TIES 36"o/c7 3 4 " 4"1SHEARWALL EDGENAILING TYP12" GWB(2) SIMP SDWSx6"@ 6" o/c(2) SIMP SDWSx6"@ 6" o/cWALL SHTG PERSHEARWALL SCHEDULE2x6 WALL STUDS@ 16" o/c TYP2x10 JOIST TYPT/ (E) CEILINGDETAIL #5TYPICAL WIND GIRT1"=1'-0"2x6 WALL STUDS@ 16" o/c TYPDIAPHRAGMEDGE NAILINGWALL SHTG PERSW-SCHEDULEDETAIL #6NEW ELEVATOR WALL @EXISTING MAIN FLOOR1"=1'-0"BEAM PER PLAN w/SIMP SDWSx6" @ 6" o/cTOP & BOTNOTE:1. REFERENCE 5/S3 FOR CALLOUTS IN COMMON.2. ATTACH SHEATHING AT PANEL EDGES WITH 10d COMMONS AT 6"o/c AND 12" o/c IN FIELD.SILL PL w/ SIMP SDWSx6"TOP & BOTTSW-EDGE NAILSPER SW-SCHED TYP12" GWB12" GWB34" SHTGPER NOTE2x6 WALL STUDS@ 16" o/c TYP(E) WALL SHTGDETAIL #7NEW ELEVATOR WALL TOEXISTING EXTERIOR WALL1"=1'-0"(E) 2x WALL(N) FLR JOIST PER PLAN(E) 2x6 WALL BEYONDT/ UPPERLEVEL(N) FLR SHTG(E) RIM JOIST(N) 4x HDR TYP(E) GWBDIAPHRAGM EDGE NAILINGSIMP LUS(N) DBL RIM JOISTDIAPHRAGM EDGE NAILINGDIAPHRAGM EDGE NAILING12" GWB21 4 " 1 3 8 "2x10 LEDGER w/(2) SIMP SDWSx5" @ 16" o/c(E) 2x JOIST(E) FLR SHTG(E) 2x BLKG(E) 2x6 WALL(E) GWBTYPFLOORJOISTPER PLANCONT 2x4LEDGER w/10d @ 6" o/cDIAPHRAGMEDGE NAILINGFLOOR SHTGPER PLANT/ UPPPERLEVELDETAIL #8NEW ELEVATOR FLOOR LANDINGTO EXISTING INTERIOR WALL1"=1'-0"(E) WALLDIAPHRAGMEDGE NAILINGREMOVE(E) GUARDRAIL(E) FLR SHTGT/ UPPPERLEVEL(N) FLR JOISTPER PLAN w/SIMP LUS(N) 2x10 ATTACHED TO(E) DBL 2x10 w/(2) ROWS 10d NAILS@ 24" o/c(E) DBL 2x10(E) FLR JOISTPER PLAN w/(E) HANGERDETAIL #9NEW ELEVATOR LANDINGTO EXISTING FLOOR1"=1'-0"(N) FLR SHTGPER PLAN2x6 WALL STUDSSW-EDGE NAILSPER SW-SCHED TYP12" GWBWALL SHTG PERSW-SCHEDULE TYP2x6 WALL STUDS@ 16" o/c TYPT/ (E) CEILINGDEMO (E) ROOF TRUSSDETAIL #10ELEVATOR WALL ATUPPER FLOOR1"=1'-0"NOTE: REFERENCE 5/S3 FOR CALLOUTS IN COMMON.BEAM PER PLAN w/SIMP SDWSx6"@ 6" o/cTOP & BOT12" GWB34" SHTGPER NOTET/ UPPER LEVEL(E) WALL(E) WALL SHTGFLOOR SHTGPER PLANDIAPHRAGMEDGE NAILING(N) FLOORJOISTPER PLANCONT 2x4LEDGERw/ 10d@ 6" o/cDETAIL #12(N) ELEVATOR FLOORLANDING DIAPHRAGMTO (E) EXTERIOR1"=1'-0"(E) GWB12" GWB2x6 WALL STUDS@ 16" o/c TYPWALL SHTG PER SW-SCHEDULET/ LOW ROOF(2) SIMP SDWSx6" INTOEA STUD w/ SOLID SHIM(E) ROOF TRUSSGAP < 112"DETAIL #11ELEVATOR WALL TO LOW ROW ROOF1"=1'-0"8d @ 6" o/cCONT 2x4 LEDGER w/SIMP SDWSx6"SCREW INTO EA STUD24">GAP>112"SIMILAR8d @ 6" o/c3ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED NOTES PR19000244B19002967V2DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 DETAIL #1ELEVATOR WALL TO EXISTING ROOF1"=1'-0"2x6 WALL STUDS @ 16" o/c TYPWALL SHTG PER SW-SCHEDULESILL PL w/ (2) ROWS16d @ 24" o/cINTO EA BLOCKSW-EDGE NAILING(E) 2x BLKG(E) 2x6WALL STUDS(E) PRE MFRTRUSS @24" o/c(E) ROOF SHTGT/ (E) CEILING(E) WALL SHTGBEVELED 4x BLKG w/(2) SIMP SDWSx6"@ 24" o/c2x FASCIA w/(2) 16d INTOEA RAFTER2x6 WALL STUDS@ 16" o/cWALL SHTGPER SW-SCHEDSW-EDGENAILING(4) 10d ROOF RAFTERTO CEILING JOISTSIMP H2.5A2x4 CEILING JOIST@ 24" o/c1'-6" MAXDIAPHRAGM EDGE NAILINGROOF SHTG PER PLANROOF RAFTERPER PLANDETAIL #2ROOF CONNECTION (PERPENDICULAR)1"=1'-0"SIMP SDWSx6"PER SW-SCHEDCONT 2x BLKG1'-6" MAX1'-10"2x FACIA w/(2) 16d INTOEA OUTRIGGER2xOUTRIGGERS@ 24" o/cSW-EDGE NAILINGDIAPHRAGMEDGE NAILING2x BLKG(2) 16d INTOEA OUTRIGGERSIMP SDWSx6"PER SW-SCHEDULEWALL SHTGPER SW-SCHEDULEBALLOON FRAMING2x6 STUDS @ 16" o/c2x4 CEILING JOIST@ 24" o/c w/ (4) 10d2x ROOF RAFTERDETAIL #3ROOF CONNECTION (PARALLEL)1"=1'-0"DIAPHRAGMEDGE NAILINGSIMP SDWSx6"PER SHEARWALLSCHEDULESIMP LTP5@ 24" o/cROOF SHTGPER PLANGENERAL NOTES:1.All design and construction shall conform to the 2015 International Residential Code.2.Read structural drawings together with Architectural, Mechanical, Electrical and other drawingsfor detail dimensions, locations of door and window openings, duct work, recesses, inserts andother items. In the event discrepancies between drawings, the more stringent requirementsshall be followed. Under no circumstance shall structural elements be modified without thewritten approval of the structural engineer.3.The contractor shall verify all dimensions and examine site conditions prior to fabrication of allitems to ensure proper installation.4.The contractor shall have a complete working knowledge of standard residential constructiontechniques that are commonly used in the profession. The contractor shall request clarification fromthe structural engineer on items that cannot be constructed as detailed or with standard constructiontechniques.5.The structural drawings illustrate the completed structure with elements intheir final positions. The contractor shall provide adequate shoring and bracing duringconstruction to resist all forces including wind, seismic and unbalanced forces due toconstruction sequence.6.Foundations: Required soil bearing pressure:1,500-psf at surfaceMinimum depth of stair footings exposed to exterior elements shall have a minimum bury depthof 12-in. for frost protection.Remove free water from excavations and forms prior to placement of the concrete.Footings shall be placed on solid bearing ground a minimum of 1-ft below grade. Footingsmay exceed the 1-ft minimum depth due to poor upper level soil conditions.7.Wood properties:Structural framing, except studs:Douglas Fir-Larch #2Fb:850-psiFt:500-psiFv:170-psiFcperp:625-psiFcpar:1,400-psiE1,600,000-psiStructural studs:Doug Fir-Larch StudFb:700-psiFt:450-psiFv:180-psiFcperp:625-psiFcpar:850-psiE1,400,000-psi8.Concrete properties:F'c: 3,000-psi @ 28-days footings & std stem wall.Air Entrained: 5%-7%Slump: 4"-5" measured before superplasticizer if used.Cement: Portland Type I or II.Calcium Chloride:Not permitted.Grout: Non-shrink, non-ferrous, developing minimum compressive strength of4,500-psi in 3-days, 8,000-psi in 28-days.9.The contractor is responsible for the design and construction of all the formwork, false-work,and temporary shoring. Vibration is essential for proper placement of concrete. Overvibration will cause separation of cement and rock and is cause for rejection of placed concrete.10.Forms shall not be removed for a minimum of 24-hours after concrete placement.11.Reinforcing steel:Deformed bars:ASTM-A615 Grade 60Welded wire fabric:ASTM-A185Cover:3", concrete surfaces cast against earth,2", formed surfaces exposed to earth1-1/2", ties to concrete face, not exposed to earth.12.Anchor bolts/threaded rods:ASTM-A307 or F1554 Gr 36 hot dipped galvanized (per ASTM A153) orSimpson Titen HD Concrete Screws (zinc plated by manufacturer) Post installed anchors shall be installed per manufacturer's instructions. For reference Simpson Anchoring and Fastening Systems for Concrete+Masonry (C-A-2018) catalog shall be on site.3"x3"x1/4" hot dipped galvanized (per ASTM A153) washers and standard nuts required for anchorrod.13.Fastners:All fasteners and connectors installed in or on preservative-treated wood shall be hot dippedzinc-coated galvanized with a minimum coating weight per ASTM A153.14.Amended Construction Documents (IBC 106.4)Work shall be installed in accordance with the approved construction documents, and any changesmade during construction that are not in compliance with the approved construction documentsshall be submitted to the Engineer in responsible charge whoshall review them and forward them to the building official with notation indicating that the changedconditions have been found to be in general conformance to the design ofthe building.15.Deferred Submittal (IBC 106.3.4.2):Deferred Submittal List:Spiral StaircaseDocuments for deferred submittal items shall be submitted to the Engineer in responsiblecharge who shall review them and forward them to the building official with notationindicating that the deferred submittal documents have been reviewed and been found tobe in general conformance to the design of the building. The deferred submittal itemsshall not be installed until the design and submittal documents have been approved bythe building official.11Posts and Timbers:Doug Fir-Larch #2Fb:875-psiFt:425-psiFv:170-psiFcperp:625-psiFcpar:850-psiE1,300,000-psiAll wood in contact with concrete shall bepreservative treated (PT) per AWPA U1and field treated per AWPA M4.14ELEVATIONS ELEVATOR ADDITION 3713 LAKE WASHINGTON BLVD N DOUG HARWOOD A 5/17/2019 ADDED NOTES PR19000244B19002967V2DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 EXHIBIT 3 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION HARWOOD SFR- CONSTRUCT 5X5 3-STOP ELEVATOR/SHAFT TO EXISTING STRUCTURE WITHIN THE FOOTPRINT OF FRONT PORCH ROOF LINE. REMOVE EXISTING ENTRY STAIRS AND UNDER STAIR STORAGE AND REPLACE WITH SPIRAL STAIRCASE. DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 EXHIBIT 4 RECEIVED Clark Close 01/15/2020 PLANNING DIVISION DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 10"10"61" FINISHED DIMENSION912"10"2712"ȭ 55" FINISHED DIMENSION 49" INSIDE 40" INSIDE4112" OUTSIDE5212" OUTSIDE 2834"ȭ36" DOORHALL CALL TYPICAL 114" 3614"3234"ȭ36" DOORHALL CALL TYPICAL 114"45716"36" CLR1634"1112"4558"36" CLRCOP PB NOTES: -CAR FLOORING AND FINISHINGS MUST NOT EXCEED 25 LBS -IN ORDER TO MEET THE 3/4" AND 4" REQIUREMENTS, A MAXIMUM OF 1/4" HOISTWAY DOOR SETBACK IS ALLOWED, WHEN USING ACCORDION CAR DOOR(S). 4" MAXIMUM THE INSIDE FACE OF HOISTWAY DOOR TO OUTSIDE OF CAR DOOR MUST REJECT A 4" BALL. 14" MAXIMUM (INSIDE FACE OF HOISTWAY DOOR TO SILL) 12" - 1 14" RUN CLR (SILL TO SILL) ACCORDION CAR DOOR (LOCKING MECHANICAL HINGE) TYPICAL DOOR LOCATION DETAIL ACCORDION (FOLDING) CAR DOOR HOISTWAY DOOR ȭ TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION 40 x 54 OPPOSITE RH RH NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 FLOORS 2-3 FLOOR 1 OLYMPIC ELEVATOR DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 4"2" OVERTRAVELTOTAL CAR TRAVELOVERHEADOVERALL HOISTWAY(PIT+TRAVEL+OVERHEAD)PIT DEPTHHOISTWAY OPENINGHOISTWAY OPENINGHOISTWAY OPENINGINTERIOR CAR HEIGHTPIT DEPTH FLOOR TO FLOOR TRAVEL OVERHEAD OVERALL HOISTWAY 8" 210" 96" 314" JOB SPECIFIC INFORMATION: NOTES: 1) CONSULT LOCAL AUTHORITY TO ENSURE COMPLIANCE WITH STATE AND LOCAL CODES. 2) THE HOISTWAY IS REQUIRED TO BE FREE OF ALL PIPES, WIRING, AND OBSTRUCTIONS NOT RELATED TO THE OPERATION OF THE ELEVATOR. Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" Hydro Static Load (lbs) 2552 2942 3399 Hydro Impact Load (lbs) 5277 5667 6124 Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" IGD Static Load (lbs) 3082 3374 3764 IGD Impact Load (lbs) 5807 6099 6489 Travel (ft) 0'0"-15'0" 15'1"-30'0" 30'1"-50'0" Drum Static Load (lbs) 2552 2942 3399 Drum Impact Load (lbs) 5277 5667 6124 TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION 3 STOP ELEVATION NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 10' MAXAllow for drywall thickness (pit flush with hoistway)Pit wall 10 " Rail Backing Centerline Pit Floor 10 " Drywall Construction Details of Rail Backing: x Laminate (2) 2x10's and (2) 2x4's using wood glue and #8x2-1/4" minimum screws x All joints must be staggered x 12" plywood between Typical Hoistway Construction Details Floor Joists Subfloor Header Corner Post Construction 2 x 4 2 x 4 2 x 10's 12" 2" 2" 12" 12" vertical screw spacing and 2" from each side of 2x10 centerline Drywall (shown cutaway) Typical Rail Backing Construction 2 x 4 2 x 4 2 x 10's 12" 2" 2" 12" x Laminate (2) 2x10's and (2) 2x4's using wood glue and #8x2-1 4" (min.) screws x All joints must be staggered x 12" plywood between 10 " 10 " 12" CENTERLINE OF RAIL BACKING R2 380# 4  56#6+%4#+. 4'#%6+10 12" plywood TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION TYPICAL HOISTWAY CONSTRUCTION NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 48" 3'-0" SELF CLOSING, SELF LOCKING, ACCESS DOOR 24" LIGHT SWITCH & DUPLEX RECEPTACLE TELEPHONE CONNECTION MAIN CONTROL BOX 18"H X 18"W X 10"D HYDRAULIC POWER UNIT 331 2"H X 24 1 4"W X 123 4"D LIGHT HYDRAULIC POWER UNIT 115-15 AMP SERVICE 208/230-30 AMP SERVICE 6"6" MAIN CONTROL BOX OVERHEAD VIEW FRONT VIEW Motor Controller Disconnect (Fusible and Lockable) Car Light Disconnect (Fusible and Lockable) 208/230VAC, 30 AMP, Single Phase (3 Wire Dedicated Circuit) *Feeding breaker must not be a G.F.I. 115VAC, 15 AMP, Dedicated Single Phase *Feeding breaker must not be a G.F.I. Telephone Service For Elevator HYDRAULIC POWER UNIT MAIN CONTROL BOX 1/2"-3/4" PLYWOOD BACKING BEHIND DRYWALL 6'-6" MAXIMUM HEIGHT NOTES: 1)THE ELEVATOR MACHINE ROOM LOCATION AND LAYOUT MUST MEET CODE REQUIREMENTS DEFINED BY THE LOCAL AUTHORITY HAVING JURISDICTION. 2)30" WIDE x 36" DEEP CLEAR WORKING SPACE REQUIRED IN FRONT OF THE MAIN CONTROL BOX BY NEC. 3)LIGHT SWITCH TO BE LOCATED ON THE STRIKE SIDE OF THE MACHINE ROOM DOOR. 4)THE HYDRAULIC POWER UNIT SHOULD BE LOCATED WITHIN 40' FROM THE CYLINDER. 5)MACHINE SPACE SHALL BE FREE OF ANY EQUIPMENT OR APPURTENANCES NOT RELATED TO THE ELEVATOR. 6)KEEP THE CONTROL ROOM 7(03(5$785(%(7:((1ž)72ž) BETWEEN 0 TO 95% RELATIVE HUMIDITY NON-CONDENSING. TITLE REVDRAWING NO.DRAWN BY SCALE DATE JOB INFORMATION COMPACT MACHINE ROOM NONE GJT 12/06/19 120619-11 R0 HARWOOD 3713 LAKE WASHINGTON BLVD N RENTON, WA 98056 OLYMPIC ELEVATOR DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663 DocuSign Envelope ID: 474A46D9-D54D-4C14-ACE8-38FCFB43758EDocuSign Envelope ID: 753DD1C3-2D0F-4624-9F8C-27036ABDC663