TECHNICAL INFORMATION REPORT
Parking Lot Renovations
405 Commerce Center
Renton, Washington
Prepared for:
KGIP
11225 SE 6th Street, Suite 215
Bellevue, WA 98004
February 18, 2020
Our Job No. 20822
18215 72ND AVENUE SOUTH KENT, WA 98032 (425) 251-6222 (425) 251-8782 FAX
BRANCH OFFICES ¨ TUMWATER, WA ¨ KLAMATH FALLS, OR ¨ LONG BEACH, CA ¨ ROSEVILLE, CA ¨ SAN DIEGO, CA
www.barghausen.com
2/18/2020
TABLE OF CONTENTS
1.0 PROJECT OVERVIEW
Figure 1 – Technical Information Report (TIR) Worksheet
Figure 2 – Site Location
Figure 3 – Drainage Basins, Subbasins, and Site Characteristics
Figure 4 – Soils
2.0 CONDITIONS AND REQUIREMENTS SUMMARY
2.1 Analysis of the Core Requirements
2.2 Analysis of the Special Requirements
3.0 OFF-SITE ANALYSIS
4.0 FLOW CONTROL, LOW IMPACT DEVELOPMENT, AND WATER QUALITY FACILITY ANALYSIS
AND DESIGN
5.0 CONVEYANCE SYSTEM ANALYSIS AND DESIGN (TO BE SUBMITTED LATER)
6.0 SPECIAL REPORTS AND STUDIES
7.0 OTHER PERMITS
8.0 CONSTRUCTION STORMWATER POLLUTION PREVENTION PLAN ANALYSIS AND DESIGN
9.0 BOND QUANTITIES, FACILITY SUMMARIES, AND DECLARATION OF COVENANT
10.0 OPERATIONS AND MAINTENANCE MANUAL
1.0 PROJECT OVERVIEW
1.0 PROJECT OVERVIEW
The project site is located within the Northeast quarter of Section 19, Township 23 North, Range 5
East, Willamette Meridian, City of Renton, King County, Washington. More particularly, the site is
located at 1415 Maple Avenue SW, Renton, WA. The site is parcel no. 33404-3805.
The total area of redevelopment on this project site is approximately 4,750 sq. ft. of replaced
impervious surface, and approximately 1,250 sq. ft. of additional grind and overlay of the existing
asphalt. The scope of the project is to update the existing 3-ft tall truck dock to be a 4-ft tall truck
dock, and provide drainage for the revised grades. Existing onsite exterior equipment such as
generators, fuel tanks, and cooling equipment will also be removed as part of the project.
The project site drains currently drains to onsite catch basins that discharge to a bioswale on the
eastern side of the site that then discharges in to the public storm system that drains northerly in
Maple Ave SW. Since the proposed project replaces less than 5,000 sq. ft. of impervious surface,
no modifications are proposed to the existing flow control and water quality facilities.
Based on the 2017 City of Renton Surface Water Design Manual, this project is subject to a full
drainage review. However, based on the scope of work, the project is exempt from many of the
core and special requirements. See section 2.0 of this report for a summary of the requirements.
FIGURE 1
TECHNICAL INFORMATION
REPORT (TIR) WORKSHEET
CITY OF RENTON SURFACE WATER DESIGN MANUAL
2017 City of Renton Surface Water Design Manual 12/12/2016 8-A-1
REFERENCE 8-A
TECHNICAL INFORMATION REPORT (TIR)
WORKSHEET
Part 1 PROJECT OWNER AND
PROJECT ENGINEER Part 2 PROJECT LOCATION AND
DESCRIPTION
Project Owner _____________________________
Phone ___________________________________
Address __________________________________
_________________________________________
Project Engineer ___________________________
Company _________________________________
Phone ___________________________________
Project Name __________________________
CED Permit # ________________________
Location Township ________________
Range __________________
Section _________________
Site Address __________________________
_____________________________________
Part 3 TYPE OF PERMIT APPLICATION Part 4 OTHER REVIEWS AND PERMITS
Land Use (e.g., Subdivision / Short Subd.)
Building (e.g., M/F / Commercial / SFR)
Grading
Right-of-Way Use
Other _______________________
DFW HPA
COE 404
DOE Dam Safety
FEMA Floodplain
COE Wetlands
Other ________
Shoreline Management
Structural Rockery/Vault/_____
ESA Section 7
Part 5 PLAN AND REPORT INFORMATION
Technical Information Report Site Improvement Plan (Engr. Plans)
Type of Drainage Review
(check one):
Date (include revision
dates):
Date of Final:
Full
Targeted
Simplified
Large Project
Directed
____________________________________
__________________
Plan Type (check
one):
Date (include revision
dates):
Date of Final:
Full
Modified
Simplified
____________________________________
__________________
Josh Shearer
(425) 766-7040
11225 SE 6th Street, Suite 215
Bellevue, WA 98004
Dan Balmelli
Barghausen Consulting Engineers, Inc.
(425) 251-6222
405 Commerce Center
23N
5E
19
1415 Maple Avenue SW
X
X
X
September 4, 2019
X
REFERENCE 8: PLAN REVIEW FORMS AND WORKSHEET
TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
12/12/2016 2017 City of Renton Surface Water Design Manual 8-A-2
Part 6 SWDM ADJUSTMENT APPROVALS
Type (circle one): Standard / Blanket
Description: (include conditions in TIR Section 2)
____________________________________________________________________________________
____________________________________________________________________________________
____________________________________________________________________________________
Approved Adjustment No. ______________________ Date of Approval: _______________________
Part 7 MONITORING REQUIREMENTS
Monitoring Required: Yes / No
Start Date: _______________________
Completion Date: _______________________
Describe: _________________________________
_________________________________________
_________________________________________
Re: SWDM Adjustment No. ________________
Part 8 SITE COMMUNITY AND DRAINAGE BASIN
Community Plan: ____________________________________________________________________
Special District Overlays: ______________________________________________________________
Drainage Basin: _____________________________________________________________________
Stormwater Requirements: _____________________________________________________________
Part 9 ONSITE AND ADJACENT SENSITIVE AREAS
River/Stream ________________________
Lake ______________________________
Wetlands ____________________________
Closed Depression ____________________
Floodplain ___________________________
Other _______________________________
_______________________________
Steep Slope __________________________
Erosion Hazard _______________________
Landslide Hazard ______________________
Coal Mine Hazard ______________________
Seismic Hazard _______________________
Habitat Protection ______________________
_____________________________________
Turbidity monitoring is required for
discharges leaving the site.
Renton
REFERENCE 8-A: TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
2017 City of Renton Surface Water Design Manual 12/12/2016 Ref 8-A-3
Part 10 SOILS
Soil Type
______________________
______________________
______________________
______________________
Slopes
________________________
________________________
________________________
________________________
Erosion Potential
_________________________
_________________________
_________________________
_________________________
High Groundwater Table (within 5 feet)
Other ________________________________
Sole Source Aquifer
Seeps/Springs
Additional Sheets Attached
Part 11 DRAINAGE DESIGN LIMITATIONS
REFERENCE
Core 2 – Offsite Analysis_________________
Sensitive/Critical Areas__________________
SEPA________________________________
LID Infeasibility________________________
Other________________________________
_____________________________________
LIMITATION / SITE CONSTRAINT
_______________________________________
_______________________________________
_______________________________________
_______________________________________
_______________________________________
_______________________________________
Additional Sheets Attached
Part 12 TIR SUMMARY SHEET (provide one TIR Summary Sheet
per Threshold Discharge Area)
Threshold Discharge Area:
(name or description)
Core Requirements (all 8 apply):
Discharge at Natural Location Number of Natural Discharge Locations:
Offsite Analysis Level: 1 / 2 / 3 dated:__________________
Flow Control (include facility
summary sheet)
Standard: _______________________________
or Exemption Number: ____________
On-site BMPs: _______________________________
Conveyance System Spill containment located at: _____________________________
Erosion and Sediment Control /
Construction Stormwater Pollution
Prevention
CSWPP/CESCL/ESC Site Supervisor: _____________________
Contact Phone: _________________________
After Hours Phone: _________________________
REFERENCE 8: PLAN REVIEW FORMS AND WORKSHEET
TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
12/12/2016 2017 City of Renton Surface Water Design Manual 8-A-4
Part 12 TIR SUMMARY SHEET (provide one TIR Summary Sheet
per Threshold Discharge Area)
Maintenance and Operation Responsibility (circle one): Private / Public
If Private, Maintenance Log Required: Yes / No
Financial Guarantees and Liability Provided: Yes / No
Water Quality (include facility
summary sheet)
Type (circle one): Basic / Sens. Lake / Enhanced Basic / Bog
or Exemption No. _______________________
Special Requirements (as applicable):
Area Specific Drainage
Requirements
Type: SDO / MDP / BP / Shared Fac. / None
Name: ________________________
Floodplain/Floodway Delineation Type (circle one): Major / Minor / Exemption / None
100-year Base Flood Elevation (or range): _______________
Datum:
Flood Protection Facilities Describe:
Source Control
(commercial / industrial land use)
Describe land use:
Describe any structural controls:
Oil Control High-Use Site: Yes / No
Treatment BMP: _________________________________
Maintenance Agreement: Yes / No
with whom? _____________________________________
Other Drainage Structures
Describe:
REFERENCE 8-A: TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
2017 City of Renton Surface Water Design Manual 12/12/2016 Ref 8-A-5
Part 13 EROSION AND SEDIMENT CONTROL REQUIREMENTS
MINIMUM ESC REQUIREMENTS
DURING CONSTRUCTION
Clearing Limits
Cover Measures
Perimeter Protection
Traffic Area Stabilization
Sediment Retention
Surface Water Collection
Dewatering Control
Dust Control
Flow Control
Control Pollutants
Protect Existing and Proposed BMPs/Facilities
Maintain Protective BMPs / Manage Project
MINIMUM ESC REQUIREMENTS
AFTER CONSTRUCTION
Stabilize exposed surfaces
Remove and restore Temporary ESC Facilities
Clean and remove all silt and debris, ensure operation of Permanent BMPs/Facilities, restore
operation of BMPs/Facilities as necessary
Flag limits of sensitive areas and open space
preservation areas
Other _______________________
Part 14 STORMWATER FACILITY DESCRIPTIONS (Note: Include Facility Summary and Sketch)
Flow Control Type/Description Water Quality Type/Description
Detention
Infiltration
Regional Facility
Shared Facility
On-site BMPs
Other
________________
________________
________________
________________
________________
________________
Vegetated Flowpath
Wetpool
Filtration
Oil Control
Spill Control
On-site BMPs
Other
________________
________________
________________
________________
________________
________________
________________
Part 15 EASEMENTS/TRACTS Part 16 STRUCTURAL ANALYSIS
Drainage Easement
Covenant
Native Growth Protection Covenant
Tract
Other ____________________________
Cast in Place Vault
Retaining Wall
Rockery > 4′ High
Structural on Steep Slope
Other _______________________________
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
REFERENCE 8: PLAN REVIEW FORMS AND WORKSHEET
TECHNICAL INFORMATION REPORT (TIR) WORKSHEET
12/12/2016 2017 City of Renton Surface Water Design Manual 8-A-6
Part 17 SIGNATURE OF PROFESSIONAL ENGINEER
I, or a civil engineer under my supervision, have visited the site. Actual site conditions as observed were incorporated into this worksheet and the attached Technical Information Report. To the best of my
knowledge the information provided here is accurate.
____________________________________________________________________________________ Signed/Date
FIGURE 2
SITE LOCATION
Horizontal:
Scale:
Vertical:
For:
Title:
VICINITY MAP
Job Number
N.T.S.N/A 20822
DATE: 11/01/19
405 Commerce Center
Renton, Washington
P:\20000s\20822\exhibit\graphics\20822 vmap.cdr
REFERENCE: Rand McNally (2019)
SITE
FIGURE 3
ASSESSOR MAP
Horizontal:
Scale:
Vertical:
For:
Title:
ASSESSOR MAP
Job Number
N.T.S.N/A 20822
DATE: 11/01/19
405 Commerce Center
Renton, Washington
P:\20000s\20822\exhibit\graphics\20822 amap.cdr
SITE
REFERENCE: King County Department of Assessments (Jan. 2019)
FIGURE 4
FEMA MAP
Horizontal:
Scale:
Vertical:
For:
Title:
FEMA MAP
Job Number
N.T.S.N/A 20822
DATE: 11/01/19
405 Commerce Center
Renton, Washington
P:\20000s\20822\exhibit\graphics\20822 fema.cdr
REFERENCE: Federal Emergency Management Agency (Portion of Map 53033C0978 F, May 1995)
Areas determined to be outside 500-year
floodplain.
ZONE X
OTHER AREAS
LEGEND
SITE
FIGURE 5
SOILS MAP
Horizontal:
Scale:
Vertical:
For:
Title:
SOIL SURVEY MAP
Job Number
N.T.S.N/A 20822
DATE: 11/01/19
405 Commerce Center
Renton, Washington
P:\20000s\20822\exhibit\graphics\20822 soil.cdr
HSG
-
REFERENCE: USDA, Natural Resources Conservation Service
LEGEND:
Ur = Urban land
SITE
FIGURE 6
SENSITIVE AREAS MAP
Horizontal:
Scale:
Vertical:
For:
Title:
SENSITIVE AREAS
MAP
Job Number
N.T.S.N/A 20822
DATE: 11/01/19
405 Commerce Center
Renton, Washington
P:\20000s\20822\exhibit\graphics\20822 sens.cdr
SITE
REFERENCE: King County iMAP (2019)
2.0 CONDITIONS AND REQUIREMENTS
SUMMARY
2.0 CONDITIONS AND REQUIREMENTS SUMMARY
2.1 Analysis of the Eight Core Requirements
Core Requirement No. 1: Discharge at the Natural Location.
Response: This project area will continue to discharge per the existing conditions to the
bioswale on the eastern side of the site prior to discharging to the public storm drainage
located in Maple Avenue SW. The added drainage for the project area will tie in to the
existing onsite catch basins.
Core Requirement No. 2: Off-Site Analysis.
Response: This proposed project adds less than 2,000 sq. ft. of new impervious surface,
less than ¾ acre of new pervious surface, and does not construct of modify a drainage
pipe/ditch that is 12 inches or more in size/depth. Based on these criteria, the project is
exempt from this core requirement.
Core Requirement No. 3: Flow Control.
Response: The proposed project has less than 5,000 sq. ft. of new plus replaced
impervious surface and less than ¾ acres of new pervious surface will be added. Based
on these criteria, the project is exempt from this core requirement.
Core Requirement No. 4: Conveyance System.
Response: The conveyance system has been sized based on the modified Rational
Method, designed to convey the 100-year runoff from the developed site.
Core Requirement No. 5: Erosion and Sediment Control.
Response: This project will concur with all erosion and sediment control requirements of
the 2017 Renton Surface Water Design Manual.
Core Requirement No. 6: Maintenance and Operations.
Response: A Maintenance and Operations Manual consistent with the City of Renton
requirements has been prepared for this project. See section 10.
Core Requirement No. 7: Financial Guarantees and Liability.
Response: This project will concur with all financial guarantees and liabilities requirements
of the City of Renton for projects of this nature.
Core Requirement No. 8: Water Quality.
Response: The proposed project has less than 5,000 sq. ft. of new plus replaced
impervious surface and less than ¾ acres of new pervious surface will be added. Based
on these criteria, the project is exempt from this core requirement.
Core Requirement No. 9: On-Site BMPs.
Response: The proposed project removes existing equipment that is mounted on concrete
pads in the asphalt lot, including a generator and fuel tank. Upon removal of the existing
equipment, the project proposes to reshape the existing asphalt lot and concrete pads in
order to ensure there is adequate drainage from the formerly flat concrete pads. There is
no expansion of impervious surface or significant hydrologic impacts as the current
drainage system and impervious coverage will simply be maintained and reshaped to
accommodate the repurposed lot and removal of existing equipment. The maintenance of
the site will include the restoration an existing onsite biofiltration ditch to the condition that
it was originally designed to. No other BMP requirements apply to the maintenance
activities.
2.2 Analysis of the Six Special Requirements
Special Requirement No. 1: Other Adopted Area-Specific Requirements.
Response: There are no known area-specific requirements applicable to this area of the
City of Renton, beyond those specified previously for flow-control and water quality.
Special Requirement No. 2: Flood Hazard Area Delineation.
Response: This project is not located in a flood hazard area as the site is over 30 feet
higher in elevation than Panther Creek lying northerly of the project site. Panther Creek
never would overtop that ravine to flood this project.
Special Requirement No. 3: Flood Protection Facilities.
Response: This project does not rely on an existing flood protection facility nor does it
propose to modify or construct a new flood protection facility; therefore, this Special
Requirement does not apply.
Special Requirement No. 4: Source Control.
Response: This project will provide Source Control in accordance with the King County
pollution prevention manual and King County Code Section 9.12 such that the owner will
be educated about the proper use of pesticides and fertilizers and the parking lot will be
swept on a regular basis.
Special Requirement No. 5: Oil Control.
Response: This project does not meet the requirements for a high-use site, therefore oil
control is not a requirement for this project. See the excerpt from the ITE manual below for
verification that the average daily traffic count for hospitals is less than 100 per 1,000
square feet of gross building area.
Special Requirement No. 6: Aquifer Protection Area.
Response: Per the City of Renton maps, the proposed project is not located in an Aquifer
Protection Area; therefore, this special requirement is not applicable to this site.
3.0 OFF-SITE ANALYSIS
3.0 OFF-SITE ANALYSIS
This project is exempt from off-site analysis because the project does not change the rate, volume,
duration, or location of discharges to and from the project site.
4.0 FLOW CONTROL AND WATER QUALITY
FACILITY ANALYSIS AND DESIGN
4.0 FLOW CONTROL, LOW IMPACT DEVELOPMENT, AND WATER QUALITY FACILITY
ANALYSIS AND DESIGN
The proposed project has less than 5,000 sq. ft. of new plus replaced impercious surface and less
than ¾ acres of new pervious surface will be added. Based on these criteria, the project is exempt
from this core requirement
5.0 CONVEYANCE SYSTEM ANALYSIS
AND DESIGN
5.0 CONVEYANCE SYSTEM ANALYSIS AND DESIGN
The conveyance system for this project site has been sized in accordance with Section 1.2.4.1 of
the 2017 Renton Surface Water Design Manual. For the conveyance sizing an initial time of
concentration of 6.3 minutes, a Manning's 'n' value of 0.014, and a 100-year precipitation of 3.95
inches were used. The total drainage area flowing to the proposed trench drain measures 0.117
ac. By utilizing the rational method, we have determined that the total design flowrate is 0.34 cfs,
whereas the capacity of the pipe is 0.37 cfs. All pipes conveyed the flow contributing to them without
overtopping any catch basins. The same criteria and results apply to the road improvements. See
attached calculations for details.
KING COUNTY DESIGN FOR 100YEAR STORMJOB NAME: 405 Commerce CenterNOTE: ENTER DEFAULTS AND STORM DATA BEFORE BEGINNING JOB#: 20822 DEFAULTS C=0.9n=0.014FILE NO.: 20822-Conveyance Calcs-2019-12-09d=12Tc=6.3`A= Contributing Area (Ac)Qd= Design Flow (cfs)COEFFICIENTS FOR THE RATIONAL METHOD "Ir"-EQUATIONC= Runoff Coefficient Qf= Full Capacity Flow (cfs)STORMAr BrTc= Time of Concentration (min)Vd= Velocity at Design Flow (fps)2YR1.580.58I= Intensity at Tc (in/hr)Vf= Velocity at Full Flow (fps)10YR2.440.64PRECIP=3.95d= Diameter of Pipe (in) s= Slope of pipe (%) 25YR 2.66 0.65 Ar=2.61L= Length of Pipe (ft)n= Manning Roughness Coefficient50YR2.750.65Br=0.63D= Water Depth at Qd (in)Tt= Travel Time at Vd (min)100YR2.610.63FROM TO A s L d Tc n C SUM A A*C SUM A*C I Qd QfQd/QfD/d D Vf Vd Tt=================================================================================================================================TD1 EX CB0.12 0.50 46 66.3 0.014 0.9 0.117 0.11 0.11 3.23 0.34 0.370.9240.753 4.52 1.88 2.12 0.36BARGHAUSEN CONSULTING ENGINEERS - PIPE FLOW CALCULATORusing the Rational Method & Manning Formula
6.0 SPECIAL REPORTS AND STUDIES
6.0 SPECIAL REPORTS AND STUDIES
7.0 OTHER PERMITS
7.0 OTHER PERMITS
Other permits for this site include:
· Separate building permit for Tenant Improvements
· Separate demolition permit
8.0 CONSTRUCTION STORMWATER POLLUTION
PREVENTION PLAN ANALYSIS AND DESIGN
8.0 CONSTRUCTION STORMWATER POLLUTION PREVENTION PLAN ANALYSIS AND DESIGN
i 20822-R-CSWPPP-WORKING.docx
Stormwater Pollution Prevention Plan
For
405 Commerce Center
Prepared For
KGIP
11225 Southeast 6th Street, Suite 215
Bellevue, Washington 98004
Owner Developer Operator/Contractor
Everwest Advisors LLC KGIP T.B.D.
Project Site Location
405 Commerce Center
Renton, Washington
Certified Erosion and Sediment Control Lead
T.B.D.
SWPPP Prepared By
Barghausen Consulting Engineers, Inc.
18215 72nd Avenue South
Kent, WA 98032
(425) 251-6222
Zayin Wall, Project Engineer
SWPPP Preparation Date
December 9, 2019
Approximate Project Construction Dates
March 2020
March 2021
Stormwater Pollution Prevention Plan
Contents
1.0 Introduction ..................................................................................................................... 1
2.0 Site Description ............................................................................................................... 3
2.1 Existing Conditions .............................................................................................. 3
2.2 Proposed Construction Activities .......................................................................... 3
3.0 Construction Stormwater BMPs ....................................................................................... 5
3.1 The 14 BMP Elements ......................................................................................... 5
3.1.1 Element #1 – Mark Clearing Limits .......................................................... 5
3.1.2 Element #2 – Establish Construction Access .......................................... 5
3.1.3 Element #3 – Control Flow Rates ............................................................ 6
3.1.4 Element #4 – Install Sediment Controls ................................................... 6
3.1.5 Element #5 – Stabilize Soils .................................................................... 7
3.1.6 Element #6 – Protect Slopes ................................................................... 7
3.1.7 Element #7 – Protect Drain Inlets ............................................................ 8
3.1.8 Element #8 – Stabilize Channels and Outlets .......................................... 8
3.1.9 Element #9 – Control Pollutants .............................................................. 9
3.1.10 Element #10 – Control Dewatering ........................................................ 10
3.1.11 Element #11 – Maintain BMPs .............................................................. 11
3.1.12 Element #12 – Manage the Project ....................................................... 11
3.1.13 Element #13 – Construction Stormwater Chemical Treatment .............. 13
3.1.14 Element #14 – Construction Stormwater Filtration ................................. 19
3.2 Site Specific BMPs ............................................................................................. 20
4.0 Construction Phasing and BMP Implementation ............................................................ 21
5.0 Pollution Prevention Team ............................................................................................. 22
5.1 Roles and Responsibilities ................................................................................. 22
5.2 Team Members .................................................................................................. 23
6.0 Site Inspections and Monitoring ..................................................................................... 24
6.1 Site Inspection ................................................................................................... 24
6.1.1 Site Inspection Frequency ..................................................................... 24
6.1.2 Site Inspection Documentation .............................................................. 24
6.2 Stormwater Quality Monitoring ........................................................................... 25
6.2.1 Turbidity Sampling ................................................................................ 25
6.2.2 pH Sampling ......................................................................................... 26
7.0 Reporting and Recordkeeping ....................................................................................... 27
7.1 Recordkeeping ................................................................................................... 27
7.1.1 Site Log Book ........................................................................................ 27
7.1.2 Records Retention ................................................................................ 27
7.1.3 Access to Plans and Records ................................................................ 27
7.1.4 Updating the SWPPP ............................................................................ 27
7.2 Reporting ........................................................................................................... 28
7.2.1 Discharge Monitoring Reports ............................................................... 28
7.2.2 Notification of Noncompliance ............................................................... 28
Stormwater Pollution Prevention Plan
Appendix A Site Plans
Appendix B Construction BMPs
Appendix C Alternative BMPs
Appendix D General Permit
Appendix E Site Inspection Forms (and Site Log)
Appendix F Engineering Calculations
Stormwater Pollution Prevention Plan
1.0 Introduction
This Stormwater Pollution Prevention Plan (SWPPP) has been prepared as part of the NPDES
stormwater permit requirements for the 405 Commerce Center Parking Lot Renovations project
in Renton, Washington. The proposed site is located at 1415 Maple Avenue SW in Renton,
Washington.
Construction activities will include the renovation of the existing truck docks from 3-ft tall to 4-ft
tall and providing drainage for the revised grading of the parking lot. Existing onsite exterior
equipment such as generators, fuel tanks, and cooling equipment will be removed as part of this
development. The purpose of this SWPPP is to describe the proposed construction activities
and all temporary and permanent erosion and sediment control (TESC) measures, pollution
prevention measures, inspection/monitoring activities, and recordkeeping that will be
implemented during the proposed construction project. The objectives of the SWPPP are to:
1. Implement Best Management Practices (BMPs) to prevent erosion and
sedimentation, and to identify, reduce, eliminate or prevent stormwater
contamination and water pollution from construction activity.
2. Prevent violations of surface water quality, ground water quality, or
sediment management standards.
3. Prevent, during the construction phase, adverse water quality impacts
including impacts on beneficial uses of the receiving water by controlling
peak flow rates and volumes of stormwater runoff at the Permittee’s
outfalls and downstream of the outfalls.
This SWPPP was prepared using the Ecology SWPPP Template downloaded from the Ecology
website. This SWPPP was prepared based on the requirements set forth in the Construction
Stormwater General Permit, Stormwater Management Manual for Western Washington. The
report is divided into seven main sections with several appendices that include stormwater
related reference materials. The topics presented in the each of the main sections are:
Section 1 – INTRODUCTION. This section provides a summary
description of the project, and the organization of the SWPPP document.
Section 2 – SITE DESCRIPTION. This section provides a detailed
description of the existing site conditions, proposed construction activities,
and calculated stormwater flow rates for existing conditions and
post-construction conditions.
Section 3 – CONSTRUCTION BMPs. This section provides a detailed
description of the BMPs to be implemented based on the 12 required
elements of the SWPPP.
Section 4 – CONSTRUCTION PHASING AND BMP IMPLEMENTATION.
This section provides a description of the timing of the BMP
implementation in relation to the project schedule.
Stormwater Pollution Prevention Plan
Section 5 – POLLUTION PREVENTION TEAM. This section identifies the
appropriate contact names (emergency and non-emergency), monitoring
personnel, and the onsite temporary erosion and sedimentation control
inspector
Section 6 – INSPECTION AND MONITORING. This section provides a
description of the inspection and monitoring requirements such as the
parameters of concern to be monitored, sample locations, sample
frequencies, and sampling methods for all stormwater discharge locations
from the site.
Section 7 – RECORDKEEPING. This section describes the requirements
for documentation of the BMP implementation, site inspections,
monitoring results, and changes to the implementation of certain BMPs
due to site factors experienced during construction.
Supporting documentation and standard forms are provided in the following Appendices:
Appendix A – Site Plans
Appendix B – Construction BMPs
Appendix C – Alternative BMPs
Appendix D – General Permit
Appendix E – Site Inspection Forms (and Site Log)
Appendix F – Engineering Calculations
Stormwater Pollution Prevention Plan
2.0 Site Description
2.1 Existing Conditions
The site is currently developed with a commercial development that will not be affected as part
of this development. The site is largely developed with a commercial building, parking areas,
and other commercial features. Since the City has indicated that Conservation Flow Control is
the required flow control menu to be followed for this site, the pre-developed condition
regardless of the existing land cover must be modeled as till forest.
2.2 Proposed Construction Activities
The total area of redevelopment on this project site totals 4,750 sq. ft. of replaced impervious
surface and approximately 1,250 sq. ft. of additional grind and overlay of the existing asphalt.
There is no proposed landscaping for this development.
The project site is located within the Northeast quarter of Section 19, Township 23 North, Range
5 East, Willamette Meridian, City of Renton, King County, Washington. More particularly, the
site is located at 1415 Maple Avenue SW, Renton, WA. The site is parcel no. 33404-3805.
The project site drains currently drains to onsite catch basins that discharge to a bioswale on
the eastern side of the site that then discharges in to the public storm system that drains
northerly in Maple Ave SW. Since the proposed project replaces less than 5,000 sq. ft. of
impervious surface, no modifications are proposed to the existing flow control and water quality
facilities.
For purposes of sizing flow control and water quality facilities, the City of Renton has indicated
that the duration standard, pre-developed forested, is the required means of providing flow
control for this site. Because this development is proposing less than 5,000 sq. ft. of new
impervious area, flow control is not required to be met for this development. Additionally, please
note there are no changes to the amount of impervious area onsite as part of this development.
Because the site is proposing less than 5,000 sq. ft. of new or replaced pollution generating
impervious area, water quality is not required to be addressed. We are proposing to utilize a
new trench drain that will connect to the existing catch basin to mitigate the stormwater from the
proposed concrete apron. From the catch basin, the stormwater flows to the existing storm
system maintained by the City of Renton. Because the total impervious area onsite will remain
unchanged from the current usage, there will be no appreciable change in stormwater flowing to
the facility; therefore, the facility has ample capacity.
Due to the limited scope of this project, SEPA review is not required for this development.
Construction activities will include site preparation, TESC installation, stormwater installation,
and asphalt paving. The schedule and phasing of BMPs during construction is provided in
Section 4.0.
Stormwater runoff rates and volumes were calculated using the modified rational method and
have been designed to convey the 100-year storm event runoff from the site. See below for a
summary of site areas.
Stormwater Pollution Prevention Plan
The following summarizes details regarding site areas:
Total site area: 0.12 acres
Percent impervious area before construction: 100%
Percent impervious area after construction: 100%
Disturbed area during construction: 0.12 acres
Disturbed area that is characterized as impervious (i.e., access
roads, staging, parking): 0.12 acres
All stormwater flow calculations are provided in Appendix F.
Stormwater Pollution Prevention Plan
3.0 Construction Stormwater BMPs
3.1 The 14 BMP Elements
3.1.1 Element #1 – Mark Clearing Limits
To protect adjacent properties and to reduce the area of soil exposed to construction, the limits
of construction will be clearly marked before land-disturbing activities begin. Areas that are to be
preserved, as well as all sensitive areas and their buffers, shall be clearly delineated, both in the
field and on the plans. The BMPs relevant to marking the clearing limits that will be applied for
this project include:
High Visibility Plastic or Metal Fence (BMP C103)
The clearing limits shall be as shown on the plans and all vegetation outside of the clearing
limits preserved.
Alternate BMPs for marking clearing limits are included in Appendix C as a quick reference tool
for the onsite inspector in the event the BMP(s) listed above are deemed ineffective or
inappropriate during construction to satisfy the requirements set forth in the General NPDES
Permit (Appendix D). To avoid potential erosion and sediment control issues that may cause a
violation(s) of the NPDES Construction Stormwater permit (as provided in Appendix D), the
Certified Erosion and Sediment Control Lead will promptly initiate the implementation of one or
more of the alternative BMPs listed in Appendix C after the first sign that existing BMPs are
ineffective or failing.
3.1.2 Element #2 – Establish Construction Access
Construction access or activities occurring on unpaved areas shall be minimized, yet where
necessary, access points shall be stabilized to minimize the tracking of sediment onto public
roads. Street sweeping and street cleaning shall be employed to prevent sediment from entering
state waters. All wash wastewater shall be controlled on site. The specific BMPs related to
establishing construction access that will be used on this project include:
The roads shall be swept daily should sediment collect on them.
Alternate construction access BMPs are included in Appendix C as a quick reference tool for the
onsite inspector in the event the BMP(s) listed above are deemed ineffective or inappropriate
during construction to satisfy the requirements set forth in the General NPDES Permit
(Appendix D). To avoid potential erosion and sediment control issues that may cause a
violation(s) of the NPDES Construction Stormwater permit (as provided in Appendix D), the
Certified Erosion and Sediment Control Lead will promptly initiate the implementation of one or
more of the alternative BMPs listed in Appendix C after the first sign that existing BMPs are
ineffective or failing.
Stormwater Pollution Prevention Plan
3.1.3 Element #3 – Control Flow Rates
Because of the limited size and scope of this project, flow control is not anticipated to be an
issue for this development. As previously mentioned, this development is proposing to add less
than 5,000 sq. ft. of new plus replaced impervious surfacing and less than ¾ acres of new
pervious surfacing.
Alternate flow control BMPs are included in Appendix C as a quick reference tool for the onsite
inspector in the event the BMP(s) listed above are deemed ineffective or inappropriate during
construction to satisfy the requirements set forth in the General NPDES Permit (Appendix D).
To avoid potential erosion and sediment control issues that may cause a violation(s) of the
NPDES Construction Stormwater permit (as provided in Appendix D), the Certified Erosion and
Sediment Control Lead will promptly initiate the implementation of one or more of the alternative
BMPs listed in Appendix C after the first sign that existing BMPs are ineffective or failing.
In general, discharge rates of stormwater from the site will be controlled where increases in
impervious area or soil compaction during construction could lead to downstream erosion, or
where necessary to meet local agency stormwater discharge requirements (e.g., discharge to
combined sewer systems).
3.1.4 Element #4 – Install Sediment Controls
All stormwater runoff from disturbed areas shall pass through an appropriate sediment removal
BMP before leaving the construction site or prior to being discharged to the downstream
drainage course. The specific BMPs to be used for controlling sediment on this project include:
Silt Fence (BMP C233)
A silt fence shall be installed along the downstream perimeter of the proposed site. Alternate
sediment control BMPs are included in Appendix C as a quick reference tool for the onsite
inspector in the event the BMP(s) listed above are deemed ineffective or inappropriate during
construction to satisfy the requirements set forth in the General NPDES Permit (Appendix D).
To avoid potential erosion and sediment control issues that may cause a violation(s) of the
NPDES Construction Stormwater permit (as provided in Appendix D), the Certified Erosion and
Sediment Control Lead will promptly initiate the implementation of one or more of the alternative
BMPs listed in Appendix C after the first sign that existing BMPs are ineffective or failing.
In addition, sediment will be removed from paved areas in and adjacent to construction work
areas manually or using mechanical sweepers, as needed, to minimize tracking of sediments on
vehicle tires away from the site and to minimize washoff of sediments from adjacent streets in
runoff.
Whenever possible, sediment-laden water shall be discharged into onsite, relatively level,
vegetated areas (BMP C240 paragraph 5, page 4-102).
In some cases, sediment discharge in concentrated runoff can be controlled using permanent
stormwater BMPs (e.g., infiltration swales, ponds, trenches). Sediment loads can limit the
effectiveness of some permanent stormwater BMPs, such as those used for infiltration or
Stormwater Pollution Prevention Plan
biofiltration; however, those BMPs designed to remove solids by settling (wet ponds or sediment
ponds) can be used during the construction phase. When permanent stormwater BMPs will be
used to control sediment discharge during construction, the structure will be protected from
excessive sedimentation with adequate erosion and sediment control BMPs. Any accumulated
sediment shall be removed after construction is complete and the remainder of the site has
been stabilized.
For this development, it is not anticipated that measures such as a Baker tank or construction
stormwater chemical treatment (BMP C250) will be required due to the small scope.
3.1.5 Element #5 – Stabilize Soils
Exposed and unworked soils shall be stabilized with the application of effective BMPs to prevent
erosion throughout the life of the project. The specific BMPs for soil stabilization that shall be
used on this project include:
Temporary and Permanent Seeding (BMP C120)
Mulching (BMP C121)
Dust Control (BMP C 140)
Seeding shall occur on all areas to remain unworked pursuant to below. Dust shall be controlled
if construction occurs during the summer. Alternate soil stabilization BMPs are included in
Appendix C as a quick reference tool for the onsite inspector in the event the BMP(s) listed
above are deemed ineffective or inappropriate during construction to satisfy the requirements
set forth in the General NPDES Permit (Appendix D). To avoid potential erosion and sediment
control issues that may cause a violation(s) of the NPDES Construction Stormwater permit (as
provided in Appendix D), the Certified Erosion and Sediment Control Lead will promptly initiate
the implementation of one or more of the alternative BMPs listed in Appendix C after the first
sign that existing BMPs are ineffective or failing.
No soils shall remain exposed and unworked for more than 7 days during the dry season (May 1
to September 30) and 2 days during the wet season (October 1 to April 30). Regardless of the
time of year, all soils shall be stabilized at the end of the shift before a holiday or weekend if
needed based on weather forecasts.
In general, cut and fill slopes will be stabilized as soon as possible and soil stockpiles will be
temporarily covered with plastic sheeting. All stockpiled soils shall be stabilized from erosion,
protected with sediment trapping measures, and where possible, be located away from storm
drain inlets, waterways, and drainage channels. Because this development is relatively flat, we
do not anticipate that soil stabilization will be an issue for this development.
3.1.6 Element #6 – Protect Slopes
All cut and fill slopes will be designed, constructed, and protected in a manner that minimizes
erosion. The following specific BMPs will be used to protect slopes for this project:
Stormwater Pollution Prevention Plan
Temporary and Permanent Seeding (BMP C 120)
Temporary and permanent seeding shall be used at all exposed areas pursuant to the prior
mentioned schedule (seasonal restrictions).
Alternate slope protection BMPs are included in Appendix C as a quick reference tool for the
onsite inspector in the event the BMP(s) listed above are deemed ineffective or inappropriate
during construction to satisfy the requirements set forth in the General NPDES Permit
(Appendix D). To avoid potential erosion and sediment control issues that may cause a
violation(s) of the NPDES Construction Stormwater permit (as provided in Appendix D), the
Certified Erosion and Sediment Control Lead will promptly initiate the implementation of one or
more of the alternative BMPs listed in Appendix C after the first sign that existing BMPs are
ineffective or failing.
Due to the relatively flat slopes onsite, we do not anticipate that protecting slopes will be an
issue for this development.
3.1.7 Element #7 – Protect Drain Inlets
All storm drain inlets and culverts made operable during construction shall be protected to
prevent unfiltered or untreated water from entering the drainage conveyance system. However,
the first priority is to keep all access roads clean of sediment and keep street wash water
separate from entering storm drains until treatment can be provided. Storm Drain Inlet
Protection (BMP C220) will be implemented for all drainage inlets and culverts that could
potentially be impacted by sediment-laden runoff on and near the project site. The following inlet
protection measures will be applied on this project:
· Excavated Drop Inlet Protection
· Block and Gravel Drop Inlet Protection
· Gravel and Wire Drop Inlet Protection
· Catch Basin Filters
If the BMP options listed above are deemed ineffective or inappropriate during construction to
satisfy the requirements set forth in the General NPDES Permit (Appendix D), or if no BMPs are
listed above but deemed necessary during construction, the Certified Erosion and Sediment
Control Lead shall implement one or more of the alternative BMP inlet protection options listed
in Appendix C.
3.1.8 Element #8 – Stabilize Channels and Outlets
Where site runoff is to be conveyed in channels, or discharged to a stream or some other
natural drainage point, efforts will be taken to prevent downstream erosion. The specific BMPs
for channel and outlet stabilization that shall be used on this project include:
· Site runoff shall be discharged to existing system
Stormwater Pollution Prevention Plan
Alternate channel and outlet stabilization BMPs are included in Appendix C as a quick reference
tool for the onsite inspector in the event the BMP(s) listed above are deemed ineffective or
inappropriate during construction to satisfy the requirements set forth in the General NPDES
Permit (Appendix D). To avoid potential erosion and sediment control issues that may cause a
violation(s) of the NPDES Construction Stormwater permit (as provided in Appendix D), the
Certified Erosion and Sediment Control Lead will promptly initiate the implementation of one or
more of the alternative BMPs listed in Appendix C after the first sign that existing BMPs are
ineffective or failing.
All temporary on-site conveyance channels shall be designed, constructed, and stabilized to
prevent erosion from the expected peak 10 minute velocity of flow from a Type 1A, 10-year, 24-
hour recurrence interval storm for the developed condition. Alternatively, the 10-year, 1-hour
peak flow rate indicated by an approved continuous runoff simulation model, increased by a
factor of 1.6, shall be used. Stabilization, including armoring material, adequate to prevent
erosion of outlets, adjacent streambanks, slopes, and downstream reaches shall be provided at
the outlets of all conveyance systems.
Because this site is largely developed with existing impervious areas and an existing storm
system, the opportunities for erosion to enter the system are minimal. By utilizing all applicable
BMPs, the existing system will retain its integrity during the construction process.
3.1.9 Element #9 – Control Pollutants
All pollutants, including waste materials and demolition debris, that occur onsite shall be
handled and disposed of in a manner that does not cause contamination of stormwater. Good
housekeeping and preventative measures will be taken to ensure that the site will be kept clean,
well organized, and free of debris. If required, BMPs to be implemented to control specific
sources of pollutants are discussed below. Vehicles, construction equipment, and/or petroleum
product storage/dispensing:
All vehicles, equipment, and petroleum product storage/dispensing areas
will be inspected regularly to detect any leaks or spills, and to identify
maintenance needs to prevent leaks or spills.
On-site fueling tanks and petroleum product storage containers shall
include secondary containment.
Spill prevention measures, such as drip pans, will be used when
conducting maintenance and repair of vehicles or equipment.
In order to perform emergency repairs on site, temporary plastic will be
placed beneath and, if raining, over the vehicle.
Contaminated surfaces shall be cleaned immediately following any
discharge or spill incident.
Demolition:
Stormwater Pollution Prevention Plan
Dust released from demolished sidewalks, buildings, or structures will be
controlled using Dust Control measures (BMP C140).
Storm drain inlets vulnerable to stormwater discharge carrying dust, soil,
or debris will be protected using Storm Drain Inlet Protection (BMP C220
as described above for Element 7).
Process water and slurry resulting from sawcutting and surfacing
operations will be prevented from entering the waters of the State by
implementing Sawcutting and Surfacing Pollution Prevention measures
(BMP C152).
Concrete and grout:
Process water and slurry resulting from concrete work will be prevented
from entering the waters of the State by implementing Concrete Handling
measures (BMP C151).
Because this development is proposing less than 5,000 sq. ft. of new and replaced
impervious area, controlling pollutants is not anticipated to be an issue for this
development. By utilizing all applicable BMPs, pollution will be controlled onsite.
3.1.10 Element #10 – Control Dewatering
All dewatering water from open cut excavation, tunneling, foundation work, trench, or
underground vaults shall be discharged into a controlled conveyance system prior to discharge
to the downstream drainage course. Channels will be stabilized, per Element #8. Clean, non-
turbid dewatering water will not be routed through stormwater sediment ponds, and will be
discharged to systems tributary to the receiving waters of the State in a manner that does not
cause erosion, flooding, or a violation of State water quality standards in the receiving water.
Highly turbid dewatering water from soils known or suspected to be contaminated, or from use
of construction equipment, will require additional monitoring and treatment as required for the
specific pollutants based on the receiving waters into which the discharge is occurring. Such
monitoring is the responsibility of the contractor.
However, the dewatering of soils known to be free of contamination will trigger BMPs to trap
sediment and reduce turbidity. At a minimum, geotextile fabric socks/bags/cells will be used to
filter this material. Other BMPs to be used for sediment trapping and turbidity reduction include
the following:
Concrete Handling (BMP C151)
Concrete shall be handled pursuant to BMP C151 wherever and whenever concrete is mixed
and poured at the project site.
Alternate dewatering control BMPs are included in Appendix C as a quick reference tool for the
onsite inspector in the event the BMP(s) listed above are deemed ineffective or inappropriate
during construction to satisfy the requirements set forth in the General NPDES Permit
Stormwater Pollution Prevention Plan
(Appendix D). To avoid potential erosion and sediment control issues that may cause a
violation(s) of the NPDES Construction Stormwater permit (as provided in Appendix D), the
Certified Erosion and Sediment Control Lead will promptly initiate the implementation of one or
more of the alternative BMPs listed in Appendix C after the first sign that existing BMPs are
ineffective or failing. It is not anticipated that dewatering will be an issue for this development.
3.1.11 Element #11 – Maintain BMPs
All temporary and permanent erosion and sediment control BMPs shall be maintained and
repaired as needed to assure continued performance of their intended function. Maintenance
and repair shall be conducted in accordance with each particular BMP's specifications. Visual
monitoring of the BMPs will be conducted at least once every calendar week and within 24
hours of any rainfall event that causes a discharge from the site. If the site becomes inactive,
and is temporarily stabilized, the inspection frequency will be reduced to once every month.
All temporary erosion and sediment control BMPs shall be removed within 30 days after the final
site stabilization is achieved or after the temporary BMPs are no longer needed. Trapped
sediment shall be removed or stabilized on site. Disturbed soil resulting from removal of BMPs
or vegetation shall be permanently stabilized.
3.1.12 Element #12 – Manage the Project
Erosion and sediment control BMPs for this project have been designed based on the following
principles:
Design the project to fit the existing topography, soils, and drainage
patterns.
Emphasize erosion control rather than sediment control.
Minimize the extent and duration of the area exposed.
Keep runoff velocities low.
Retain sediment on site.
Thoroughly monitor site and maintain all ESC measures.
Schedule major earthwork during the dry season.
In addition, project management will incorporate the key components listed below:
The project will be managed according to the following key project components:
Stormwater Pollution Prevention Plan
Phasing of Construction
The construction project is being phased to the extent practicable in order
to prevent soil erosion, and, to the maximum extent possible, the
transport of sediment from the site during construction.
Revegetation of exposed areas and maintenance of that vegetation shall
be an integral part of the clearing activities during each phase of
construction, per the Scheduling BMP (C 162).
Seasonal Work Limitations
From October 1 through April 30, clearing, grading, and other soil
disturbing activities shall only be permitted if shown to the satisfaction of
the local permitting authority that silt-laden runoff will be prevented from
leaving the site through a combination of the following:
Site conditions including existing vegetative coverage, slope, soil type,
and proximity to receiving waters; and
Limitations on activities and the extent of disturbed areas; and
Proposed erosion and sediment control measures.
Based on the information provided and/or local weather conditions, the
local permitting authority may expand or restrict the seasonal limitation on
site disturbance.
The following activities are exempt from the seasonal clearing and
grading limitations:
Routine maintenance and necessary repair of erosion and sediment
control BMPs;
Routine maintenance of public facilities or existing utility structures that do
not expose the soil or result in the removal of the vegetative cover to soil;
and
Activities where there is 100 percent infiltration of surface water runoff
within the site in approved and installed erosion and sediment control
facilities.
Coordination with Utilities and Other Jurisdictions
Care has been taken to coordinate with utilities, other construction
projects, and the local jurisdiction in preparing this SWPPP and
scheduling the construction work.
Inspection and Monitoring
All BMPs shall be inspected, maintained, and repaired as needed to
assure continued performance of their intended function. Site inspections
Stormwater Pollution Prevention Plan
shall be conducted by a person who is knowledgeable in the principles
and practices of erosion and sediment control. This person has the
necessary skills to:
Assess the site conditions and construction activities that could impact
the quality of stormwater, and
Assess the effectiveness of erosion and sediment control measures used
to control the quality of stormwater discharges.
A Certified Erosion and Sediment Control Lead shall be on-site or on-call
at all times.
Whenever inspection and/or monitoring reveals that the BMPs identified
in this SWPPP are inadequate, due to the actual discharge of or potential
to discharge a significant amount of any pollutant, appropriate BMPs or
design changes shall be implemented as soon as possible.
Maintaining an Updated Construction SWPPP
This SWPPP shall be retained on-site or within reasonable access to the
site.
The SWPPP shall be modified whenever there is a change in the design,
construction, operation, or maintenance at the construction site that has,
or could have, a significant effect on the discharge of pollutants to waters
of the state.
The SWPPP shall be modified if, during inspections or investigations
conducted by the owner/operator, or the applicable local or state
regulatory authority, it is determined that the SWPPP is ineffective in
eliminating or significantly minimizing pollutants in stormwater discharges
from the site. The SWPPP shall be modified as necessary to include
additional or modified BMPs designed to correct problems identified.
Revisions to the SWPPP shall be completed within seven (7) days
following the inspection.
3.1.13 Element #13 – Construction Stormwater Chemical
Treatment
Turbidity is difficult to control once fine particles are suspended in stormwater runoff from a
construction site. Sedimentation ponds are effective at removing larger particulate matter by
gravity settling, but are ineffective at removing smaller particulates such as clay and fine silt.
Sediment ponds are typically designed to remove sediment no smaller than medium silt
(0.02 mm). Chemical treatment may be used to reduce the turbidity of stormwater runoff.
Chemical treatment can reliably provide exceptional reductions of turbidity and associated
pollutants. Very high turbidities can be reduced to levels comparable to what is found in streams
during dry weather. Traditional BMPs used to control soil erosion and sediment loss from sites
under development may not be adequate to ensure compliance with the water quality standard
for turbidity in the receiving water. Chemical treatment may be required to protect streams from
Stormwater Pollution Prevention Plan
the impact of turbid stormwater discharges, especially when construction is to proceed through
the wet season.
Formal written approval from Ecology and the Local Permitting Authority is required for the use
of chemical treatment regardless of site size. The intention to use Chemical Treatment shall be
indicated on the Notice of Intent for coverage under the General Construction Permit. Chemical
treatment systems should be designed as part of the Construction SWPPP, not after the fact.
Chemical treatment may be used to correct problem sites in limited circumstances with formal
written approval from Ecology and the Local Permitting Authority.
The SEPA review authority must be notified at the application phase of the project review (or the
time that the SEPA determination on the project is performed) that chemical treatment is
proposed. If it is added after this stage, an addendum will be necessary and may result in
project approval delay.
See Appendix II-B for background information on chemical treatment.
Criteria for Chemical Treatment Product Use
Chemically treated stormwater discharged from construction sites must be nontoxic to aquatic
organisms. The following protocol shall be used to evaluate chemicals proposed for stormwater
treatment at construction sites. Authorization to use a chemical in the field based on this
protocol does not relieve the applicant from responsibility for meeting all discharge and
receiving water criteria applicable to a site.
Treatment chemicals must be approved by EPA for potable water use.
Petroleum-based polymers are prohibited.
Prior to authorization for field use, jar tests shall be conducted to
demonstrate that turbidity reduction necessary to meet the receiving
water criteria can be achieved. Test conditions, including but not limited to
raw water quality and jar test procedures, should be indicative of field
conditions. Although these small-scale tests cannot be expected to
reproduce performance under field conditions, they are indicative of
treatment capability.
Prior to authorization for field use, the chemically treated stormwater shall
be tested for aquatic toxicity. Applicable procedures defined in
Chapter 173-205 WAC, Whole Effluent Toxicity Testing and Limits, shall
be used. Testing shall use stormwater from the construction site at which
the treatment chemical is proposed for use or a water solution using soil
from the proposed site.
Stormwater Pollution Prevention Plan
The proposed maximum dosage shall be at least a factor of five lower
than the no observed effects concentration (NOEC).
The approval of a proposed treatment chemical shall be conditional,
subject to full-scale bioassay monitoring of treated stormwater at the
construction site where the proposed treatment chemical is to be used.
Treatment chemicals that have already passed the above testing protocol
do not need to be reevaluated. Contact the Department of Ecology
Regional Office for a list of treatment chemicals that have been evaluated
and are currently approved for use.
Treatment System Design Considerations
The design and operation of a chemical treatment system should take into consideration the
factors that determine optimum, cost-effective performance. It may not be possible to fully
incorporate all of the classic concepts into the design because of practical limitations at
construction sites. Nonetheless, it is important to recognize the following:
The right chemical must be used at the right dosage. A dosage that is
either too low or too high will not produce the lowest turbidity. There is an
optimum dosage rate. This is a situation where the adage "adding more is
always better" is not the case.
The coagulant must be mixed rapidly into the water to insure proper
dispersion.
A flocculation step is important to increase the rate of settling, to produce
the lowest turbidity, and to keep the dosage rate as low as possible.
Too little energy input into the water during the flocculation phase results
in flocs that are too small and/or insufficiently dense. Too much energy
can rapidly destroy floc as it is formed.
Since the volume of the basin is a determinant in the amount of energy
per unit volume, the size of the energy input system can be too small
relative to the volume of the basin.
Care must be taken in the design of the withdrawal system to minimize
outflow velocities and to prevent floc discharge. The discharge should be
directed through a physical filter such as a vegetated swale that would
catch any unintended floc discharge.
Stormwater Pollution Prevention Plan
Treatment System Design
Chemical treatment systems shall be designed as batch treatment systems using either ponds
or portable trailer-mounted tanks. Flow-through continuous treatment systems are not allowed
at this time.
A chemical treatment system consists of the stormwater collection system (either temporary
diversion or the permanent site drainage system), a storage pond, pumps, a chemical feed
system, treatment cells, and interconnecting piping.
The treatment system shall use a minimum of two lined treatment cells. Multiple treatment cells
allow for clarification of treated water while other cells are being filled or emptied. Treatment
cells may be ponds or tanks. Ponds with constructed earthen embankments greater than six
feet high require special engineering analyses. Portable tanks may also be suitable for some
sites.
The following equipment should be located in an operations shed:
the chemical injector;
secondary containment for acid, caustic, buffering compound, and
treatment chemical;
emergency shower and eyewash, and
monitoring equipment which consists of a pH meter and a turbidimeter.
Sizing Criteria
The combination of the storage pond or other holding area and treatment capacity should be
large enough to treat stormwater during multiple day storm events. It is recommended that at a
minimum the storage pond or other holding area should be sized to hold 1.5 times the runoff
volume of the 10-year, 24-hour storm event. Bypass should be provided around the chemical
treatment system to accommodate extreme storm events. Runoff volume shall be calculated
using the methods presented in Volume 3, Chapter 2. If no hydrologic analysis is required for
the site, the Rational Method may be used.
Primary settling should be encouraged in the storage pond. A forebay with access for
maintenance may be beneficial.
There are two opposing considerations in sizing the treatment cells. A larger cell is able to treat
a larger volume of water each time a batch is processed. However, the larger the cell the longer
the time required to empty the cell. A larger cell may also be less effective at flocculation and
therefore require a longer settling time. The simplest approach to sizing the treatment cell is to
multiply the allowable discharge flow rate times the desired drawdown time. A 4-hour drawdown
time allows one batch per cell per 8-hour work period, given 1 hour of flocculation followed by
two hours of settling.
Stormwater Pollution Prevention Plan
The permissible discharge rate governed by potential downstream effect can be used to
calculate the recommended size of the treatment cells. The following discharge flow rate limits
shall apply:
If the discharge is directly or indirectly to a stream, the discharge flow rate
shall not exceed 50 percent of the peak flow rate of the 2-year, 24-hour
event for all storm events up to the 10-year, 24-hour event.
If discharge is occurring during a storm event equal to or greater than the
10-year, 24-hour event, the allowable discharge rate is the peak flow rate
of the 10-year, 24-hour event.
Discharge to a stream should not increase the stream flow rate by more
than 10 percent.
If the discharge is directly to a lake, a major receiving water listed in
Appendix C of Volume I, or to an infiltration system, there is no discharge
flow limit.
If the discharge is to a municipal storm drainage system, the allowable
discharge rate may be limited by the capacity of the public system. It may
be necessary to clean the municipal storm drainage system prior to the
start of the discharge to prevent scouring solids from the drainage
system.
Runoff rates shall be calculated using the methods presented in Volume
3, Chapter 2 for the pre-developed condition. If no hydrologic analysis is
required for the site, the Rational Method may be used.
Monitoring
The following monitoring shall be conducted. Test results shall be recorded on a daily log kept
on site:
Operational Monitoring
pH, conductivity (as a surrogate for alkalinity), turbidity and temperature
of the untreated stormwater
Total volume treated and discharged
Discharge time and flow rate
Type and amount of chemical used for pH adjustment
Amount of polymer used for treatment
Settling time
Stormwater Pollution Prevention Plan
Compliance Monitoring
pH and turbidity of the treated stormwater
pH and turbidity of the receiving water
Biomonitoring: Treated stormwater shall be tested for acute (lethal) toxicity. Bioassays shall be
conducted by a laboratory accredited by Ecology, unless otherwise approved by Ecology. The
performance standard for acute toxicity is no statistically significant difference in
survival between the control and 100 percent chemically treated stormwater.
Acute toxicity tests shall be conducted with the following species and protocols:
Fathead minnow, Pimephales promelas (96 hour static-renewal test,
method: EPA/600/4-90/027F). Rainbow trout, Oncorhynchus mykiss
(96 hour static-renewal test, method: EPA/600/4-90/027F) may be used
as a substitute for fathead minnow.
Daphnid, Ceriodaphnia dubia, Daphnia pulex, or Daphnia magna (48 hour
static test, method: EPA/600/4-90/027F).
All toxicity tests shall meet quality assurance criteria and test conditions in the most recent
versions of the EPA test method and Ecology Publication # WO-R-95-80, Laboratory Guidance
and Whole Effluent Toxicity Test Review Criteria.
Bioassays shall be performed on the first five batches and on every tenth batch thereafter, or as
otherwise approved by Ecology. Failure to meet the performance standard shall be immediately
reported to Ecology.
Discharge Compliance: Prior to discharge, each batch of treated stormwater must be
sampled and tested for compliance with pH and turbidity limits. These limits may be
established by the water quality standards or a site-specific discharge permit. Sampling and
testing for other pollutants may also be necessary at some sites. Turbidity must be within
5 NTUs of the background turbidity. Background is measured in the receiving water, upstream
from the treatment process discharge point. pH must be within the range of 6.5 to 8.5 standard
units and not cause a change in the pH of the receiving water of more than 0.2 standard units. It
is often possible to discharge treated stormwater that has a lower turbidity than the receiving
water and that matches the pH.
Treated stormwater samples and measurements shall be taken from the discharge pipe or
another location representative of the nature of the treated stormwater discharge. Samples used
for determining compliance with the water quality standards in the receiving water shall not be
taken from the treatment pond prior to decanting. Compliance with the water quality standards is
determined in the receiving water.
Stormwater Pollution Prevention Plan
Operator Training
Each contractor who intends to use chemical treatment shall be trained by an experienced
contractor on an active site for at least 40 hours.
Standard BMPs
Surface stabilization BMPs should be implemented on site to prevent significant erosion. All
sites shall use a truck wheel wash to prevent tracking of sediment off site.
Sediment Removal and Disposal
Sediment shall be removed from the storage or treatment cells as
necessary. Typically, sediment removal is required at least once during a
wet season and at the decommissioning of the cells. Sediment remaining
in the cells between batches may enhance the settling process and
reduce the required chemical dosage.
Sediment may be incorporated into the site away from drainages.
3.1.14 Element #14 – Construction Stormwater Filtration
Filtration removes sediment from runoff originating from disturbed areas of the site.
Traditional BMPs used to control soil erosion and sediment loss from sites under development
may not be adequate to ensure compliance with the water quality standard for turbidity in the
receiving water. Filtration may be used in conjunction with gravity settling to remove sediment
as small as fine silt (0.5 µm). The reduction in turbidity will be dependent on the particle size
distribution of the sediment in the stormwater. In some circumstances, sedimentation and
filtration may achieve compliance with the water quality standard for turbidity.
Unlike chemical treatment, the use of construction stormwater filtration does not require
approval from Ecology.
Filtration may also be used in conjunction with polymer treatment in a portable system to assure
capture of the flocculated solids.
Design and Installation Specifications – Background Information
Filtration with sand media has been used for over a century to treat water and wastewater. The
use of sand filtration for treatment of stormwater has developed recently, generally to treat
runoff from streets, parking lots, and residential areas. The application of filtration to
construction stormwater treatment is currently under development.
Two types of filtration systems may be applied to construction stormwater treatment: rapid and
slow. Rapid sand filters are the typical system used for water and wastewater treatment. They
can achieve relatively high hydraulic flow rates, on the order of 2 to 20 gpm/sf, because they
Stormwater Pollution Prevention Plan
have automatic backwash systems to remove accumulated solids. In contrast, slow sand filters
have very low hydraulic rates, on the order of 0.02 gpm/sf, because they do not have backwash
systems. To date, slow sand filtration has generally been used to treat stormwater. Slow sand
filtration is mechanically simple in comparison to rapid sand filtration but requires a much larger
filter area.
Filtration Equipment
Sand media filters are available with automatic backwashing features that can filter to 50 µm
particle size. Screen or bag filters can filter down to 5 µm. Fiber wound filters can remove
particles down to 0.5 µm. Filters should be sequenced from the largest to the smallest pore
opening. Sediment removal efficiency will be related to particle size distribution in the
stormwater.
Treatment Process Description
Stormwater is collected at interception point(s) on the site and is diverted to a sediment pond or
tank for removal of large sediment and storage of the stormwater before it is treated by the
filtration system. The stormwater is pumped from the trap, pond, or tank through the filtration
system in a rapid sand filtration system. Slow sand filtration systems are designed as flow
through systems using gravity.
If large volumes of concrete are being poured, pH adjustment may be necessary.
Maintenance Standards
Rapid sand filters typically have automatic backwash systems that are triggered by a pre-set
pressure drop across the filter. If the backwash water volume is not large or substantially more
turbid than the stormwater stored in the holding pond or tank, backwash return to the pond or
tank may be appropriate. However, land application or another means of treatment and disposal
may be necessary.
Screen, bag, and fiber filters must be cleaned and/or replaced when they
become clogged.
Sediment shall be removed from the storage and/or treatment ponds as
necessary. Typically, sediment removal is required once or twice during a
wet season and at the decommissioning of the ponds.
3.2 Site Specific BMPs
Site specific BMPs are shown on the TESC Plan Sheets and Details in Appendix A. These site
specific plan sheets will be updated annually.
Stormwater Pollution Prevention Plan
4.0 Construction Phasing and BMP
Implementation
The BMP implementation schedule will be driven by the construction schedule. The following
provides a sequential list of the proposed construction schedule milestones and the
corresponding BMP implementation schedule. The list contains key milestones such as wet
season construction.
The BMP implementation schedule listed below is keyed to proposed phases of the construction
project, and reflects differences in BMP installations and inspections that relate to wet season
construction. The project site is located west of the Cascade Mountain Crest. As such, the dry
season is considered to be from May 1 to September 30 and the wet season is considered to be
from October 1 to April 30.
Estimate of Construction start date: March 2020
Estimate of Construction finish date: March 2021
Mobilize equipment on site:
Mobilize and store all ESC and soil stabilization products
(store materials on hand BMP C150):
Install ESC measures:
Install stabilized construction entrance:
Begin clearing and grubbing:
Temporary erosion control measures (hydroseeding):
Site inspections reduced to monthly:
Begin concrete pour and implement BMP C151:
Excavate and install new utilities and services (Phase 1):
Complete utility construction:
Begin implementing soil stabilization and sediment
control BMPs throughout the site in preparation for wet
season:
WET SEASON STARTS: October 1, 2019
Stormwater Pollution Prevention Plan
5.0 Pollution Prevention Team
5.1 Roles and Responsibilities
The pollution prevention team consists of personnel responsible for implementation of the
SWPPP, including the following:
Certified Erosion and Sediment Control Lead (CESCL) – primary
contractor contact, responsible for site inspections (BMPs, visual
monitoring, sampling, etc.); to be called upon in case of failure of any
ESC measures.
Resident Engineer – For projects with engineered structures only
(sediment ponds/traps, sand filters, etc.): site representative for the owner
that is the project's supervising engineer responsible for inspections and
issuing instructions and drawings to the contractor's site supervisor or
representative
Emergency Ecology Contact – individual to be contacted at Ecology in
case of emergency. Go to the following website to get the name and
number for the Ecology contact information:
http://www.ecy.wa.gov/org.html.
Emergency Owner Contact – individual that is the site owner or
representative of the site owner to be contacted in the case of an
emergency.
Non-Emergency Ecology Contact – individual that is the site owner or
representative of the site owner than can be contacted if required.
Monitoring Personnel – personnel responsible for conducting water
quality monitoring; for most sites this person is also the Certified Erosion
and Sediment Control Lead.
Stormwater Pollution Prevention Plan
5.2 Team Members
Names and contact information for those identified as members of the pollution prevention team
are provided in the following table.
Title Name(s) Phone Number
Certified Erosion and Sediment Control
Lead (CESCL)
T.B.D.
Resident Engineer Ali Sadr (425) 251-6222
Emergency Ecology Contact T.B.D.
Emergency Owner Contact T.B.D.
Non-Emergency Ecology Contact Ali Sadr (425) 251-6222
Monitoring Personnel T.B.D.
Stormwater Pollution Prevention Plan
6.0 Site Inspections and Monitoring
Monitoring includes visual inspection, monitoring for water quality parameters of concern, and
documentation of the inspection and monitoring findings in a site log book. A site log book will
be maintained for all on-site construction activities and will include:
A record of the implementation of the SWPPP and other permit
requirements;
Site inspections; and,
Stormwater quality monitoring.
For convenience, the inspection form and water quality monitoring forms included in this
SWPPP include the required information for the site log book. This SWPPP may function as the
site log book if desired, or the forms may be separated and included in a separate site log book.
However, if separated, the site log book but must be maintained on-site or within reasonable
access to the site and be made available upon request to Ecology or the local jurisdiction.
6.1 Site Inspection
All BMPs will be inspected, maintained, and repaired as needed to assure continued
performance of their intended function. The inspector will be a Certified Erosion and Sediment
Control Lead (CESCL) per BMP C160. The name and contact information for the CESCL is
provided in Section 5 of this SWPPP.
Site inspection will occur in all areas disturbed by construction activities and at all stormwater
discharge points. Stormwater will be examined for the presence of suspended sediment,
turbidity, discoloration, and oily sheen. The site inspector will evaluate and document the
effectiveness of the installed BMPs and determine if it is necessary to repair or replace any of
the BMPs to improve the quality of stormwater discharges. All maintenance and repairs will be
documented in the site log book or forms provided in this document. All new BMPs or design
changes will be documented in the SWPPP as soon as possible.
6.1.1 Site Inspection Frequency
Site inspections will be conducted at least once a week and within 24 hours following any
rainfall event which causes a discharge of stormwater from the site. For sites with temporary
stabilization measures, the site inspection frequency can be reduced to once every month.
6.1.2 Site Inspection Documentation
The site inspector will record each site inspection using the site log inspection forms provided in
Appendix E. The site inspection log forms may be separated from this SWPPP document, but
will be maintained on-site or within reasonable access to the site and be made available upon
request to Ecology or the local jurisdiction.
Stormwater Pollution Prevention Plan
6.2 Stormwater Quality Monitoring
6.2.1 Turbidity Sampling
Monitoring requirements for the proposed project will include either turbidity or water
transparency sampling to monitor site discharges for water quality compliance with the 2005
Construction Stormwater General Permit (Appendix D). Sampling will be conducted at all
discharge points at least once per calendar week.
Turbidity or transparency monitoring will follow the analytical methodologies described in
Section S4 of the 2005 Construction Stormwater General Permit (Appendix D). The key
benchmark values that require action are 25 NTU for turbidity (equivalent to 32 cm
transparency) and 250 NTU for turbidity (equivalent to 6 cm transparency). If the 25 NTU
benchmark for turbidity (equivalent to 32 cm transparency) is exceeded, the following steps will
be conducted:
1. Ensure all BMPs specified in this SWPPP are installed and functioning as
intended.
2. Assess whether additional BMPs should be implemented, and document
revisions to the SWPPP as necessary.
3. Sample discharge location daily until the analysis results are less than
25 NTU (turbidity) or greater than 32 cm (transparency).
If the turbidity is greater than 25 NTU (or transparency is less than 32 cm) but less than
250 NTU (transparency greater than 6 cm) for more than 3 days, additional treatment BMPs will
be implemented within 24 hours of the third consecutive sample that exceeded the benchmark.
If the 250 NTU benchmark for turbidity (or less than 6 cm transparency) is exceeded at any
time, the following steps will be conducted:
1. Notify Ecology by phone within 24 hours of analysis (see Section 5.0 of
this SWPPP for contact information).
2. Continue daily sampling until the turbidity is less than 25 NTU (or
transparency is greater than 32 cm).
3. Initiate additional treatment BMPs such as off-site treatment, infiltration,
filtration and chemical treatment within 24 hours of the first 250 NTU
exceedance.
4. Implement additional treatment BMPs as soon as possible, but within
7 days of the first 250 NTU exceedance.
5. Describe inspection results and remedial actions taken in the site log
book and in monthly discharge monitoring reports as described in Section
7.0 of this SWPPP.
Stormwater Pollution Prevention Plan
6.2.2 pH Sampling
Stormwater runoff will be monitored for pH starting on the first day of any activity that includes
more than 40 yards of poured or recycled concrete, or after the application of "Engineered Soils"
such as Portland cement treated base, cement kiln dust, or fly ash. This does not include
fertilizers. For concrete work, pH monitoring will start the first day concrete is poured and
continue until 3 weeks after the last pour. For engineered soils, the pH monitoring period begins
when engineered soils are first exposed to precipitation and continue until the area is fully
stabilized.
Stormwater samples will be collected daily from all points of discharge from the site and
measured for pH using a calibrated pH meter, pH test kit, or wide range pH indicator paper. If
the measured pH is 8.5 or greater, the following steps will be conducted:
1. Prevent the high pH water from entering storm drains or surface water.
2. Adjust or neutralize the high pH water if necessary using appropriate
technology such as CO2 sparging (liquid or dry ice).
3. Contact Ecology if chemical treatment other than CO2 sparging is
planned.
Stormwater Pollution Prevention Plan
7.0 Reporting and Recordkeeping
7.1 Recordkeeping
7.1.1 Site Log Book
A site log book will be maintained for all on-site construction activities and will include:
A record of the implementation of the SWPPP and other permit
requirements;
Site inspections; and,
Stormwater quality monitoring.
For convenience, the inspection form and water quality monitoring forms included in this
SWPPP include the required information for the site logbook.
7.1.2 Records Retention
Records of all monitoring information (site log book, inspection reports/checklists, etc.), this
Stormwater Pollution Prevention Plan, and any other documentation of compliance with permit
requirements will be retained during the life of the construction project and for a minimum of
three years following the termination of permit coverage in accordance with permit condition
S5.C.
7.1.3 Access to Plans and Records
The SWPPP, General Permit, Notice of Authorization letter, and Site Log Book will be retained
on site or within reasonable access to the site and will be made immediately available upon
request to Ecology or the local jurisdiction. A copy of this SWPPP will be provided to Ecology
within 14 days of receipt of a written request for the SWPPP from Ecology. Any other
information requested by Ecology will be submitted within a reasonable time. A copy of the
SWPPP or access to the SWPPP will be provided to the public when requested in writing in
accordance with Permit Condition S5.G.
7.1.4 Updating the SWPPP
In accordance with Conditions S3, S4.B, and S9.B.3 of the General Permit, this SWPPP will be
modified if the SWPPP is ineffective in eliminating or significantly minimizing pollutants in
stormwater discharges from the site or there has been a change in design, construction,
operation, or maintenance at the site that has a significant effect on the discharge, or potential
for discharge, of pollutants to the waters of the State. The SWPPP will be modified within seven
days of determination based on inspection(s) that additional or modified BMPs are necessary to
correct problems identified, and an updated timeline for BMP implementation will be prepared.
Stormwater Pollution Prevention Plan
7.2 Reporting
7.2.1 Discharge Monitoring Reports
Discharge Monitoring Report (DMR) forms will be submitted to Ecology because water quality
sampling is being conducted at the site.
7.2.2 Notification of Noncompliance
If any of the terms and conditions of the permit are not met, and it causes a threat to human
health or the environment, the following steps will be taken in accordance with permit
section S5.F:
1. Ecology will be immediately notified of the failure to comply.
2. Immediate action will be taken to control the noncompliance issue and to
correct the problem. If applicable, sampling and analysis of any
noncompliance will be repeated immediately and the results submitted to
Ecology within five (5) days of becoming aware of the violation.
3. A detailed written report describing the noncompliance will be submitted
to Ecology within five (5) days, unless requested earlier by Ecology.
Stormwater Pollution Prevention Plan
Appendix A – Site Plans
~~~~~~~~~~~~~~~~~~
~
~~~~~~~~~~~~~~CONSTRUCTION EASEMENTMAPLE AVENUE S.W.405 COMMERCE CENTERPORTION OF THE SE1/4, OF THE NW1/4 OF SEC. 19,TWP 23 N., RGE 5 EAST, W. M.CITY OF RENTON KING COUNTY WASHINGTONCITY OFRENTONTED-40-4107
405 COMMERCE CENTEREVERWEST ADVISORS LLC1099 -18TH STREET, SUITE 2900DENVER, CO 80202BCE#20822 - 405 COMMERCE CENTER
--405 COMMERCE CENTER -DEMOLITION AND TESCSCALE: 1"=20'
Stormwater Pollution Prevention Plan
Appendix B – Construction BMPs
High Visibility Plastic or Metal Fence (BMP C103)
Stabilized Construction Entrance (BMP C105)
Silt Fence (BMP C233)
Temporary and Permanent Seeding (BMP C120)
Mulching (BMP C121)
Dust Control (BMP C140)
Check Dams (BMP C207)
Grass-Lined Channels (BMP C201)
Construction Stormwater Chemical Treatment (BMP C250)
Construction Stormwater Filtration (BMP C251)
Stormwater Pollution Prevention Plan
Appendix C – Alternative BMPs
The following includes a list of possible alternative BMPs for each of the 12 elements not
described in the main SWPPP text. This list can be referenced in the event a BMP for a specific
element is not functioning as designed and an alternative BMP needs to be implemented.
Element #1 - Mark Clearing Limits
Element #2 - Establish Construction Access
Element #3 - Control Flow Rates
Element #4 - Install Sediment Controls
Advanced BMPs:
Element #5 - Stabilize Soils
Element #6 - Protect Slopes
Element #8 - Stabilize Channels and Outlets
Element #10 - Control Dewatering
Additional Advanced BMPs to Control Dewatering:
Stormwater Pollution Prevention Plan
Appendix D – General Permit
Stormwater Pollution Prevention Plan
Appendix E – Site Inspection Forms (and Site Log)
The results of each inspection shall be summarized in an inspection report or checklist that is
entered into or attached to the site log book. It is suggested that the inspection report or
checklist be included in this appendix to keep monitoring and inspection information in one
document, but this is optional; however, it is mandatory that this SWPPP and the site inspection
forms be kept onsite at all times during construction, and that inspections be performed and
documented as outlined below.
At a minimum, each inspection report or checklist shall include:
a. Inspection date/times
b. Weather information: general conditions during inspection, approximate amount
of precipitation since the last inspection, and approximate amount of precipitation
within the last 24 hours.
c. A summary or list of all BMPs that have been implemented, including
observations of all erosion/sediment control structures or practices.
d. The following shall be noted:
i. locations of BMPs inspected,
ii. locations of BMPs that need maintenance,
iii. the reason maintenance is needed,
iv. locations of BMPs that failed to operate as designed or intended, and
v. locations where additional or different BMPs are needed, and the reason(s)
why
e. A description of stormwater discharged from the site. The presence of
suspended sediment, turbid water, discoloration, and/or oil sheen shall be noted,
as applicable.
f. A description of any water quality monitoring performed during inspection, and
the results of that monitoring.
g. General comments and notes, including a brief description of any BMP repairs,
maintenance or installations made as a result of the inspection.
h. A statement that, in the judgment of the person conducting the site inspection,
the site is either in compliance or out of compliance with the terms and conditions
of the SWPPP and the NPDES permit. If the site inspection indicates that the site
is out of compliance, the inspection report shall include a summary of the
remedial actions required to bring the site back into compliance, as well as a
schedule of implementation.
i. Name, title, and signature of person conducting the site inspection; and the
following statement: “I certify under penalty of law that this report is true,
accurate, and complete, to the best of my knowledge and belief”.
When the site inspection indicates that the site is not in compliance with any terms and
conditions of the NPDES permit, the Permittee shall take immediate action(s) to: stop, contain,
and clean up the unauthorized discharges, or otherwise stop the noncompliance; correct the
Stormwater Pollution Prevention Plan
problem(s); implement appropriate Best Management Practices (BMPs), and/or conduct
maintenance of existing BMPs; and achieve compliance with all applicable standards and permit
conditions. In addition, if the noncompliance causes a threat to human health or the
environment, the Permittee shall comply with the Noncompliance Notification requirements in
Special Condition S5.F of the permit.
Stormwater Pollution Prevention Plan
Site Inspection Form
General Information
Project Name: Valley Medical Center Medical Office Building
Inspector Name: T.B.D. Title:
CESCL # :
Date: Time:
Inspection Type: □ After a rain event
□ Weekly
□ Turbidity/transparency benchmark exceedance
□ Other
Weather
Precipitation Since last inspection In last 24 hours
Description of General Site Conditions:
Inspection of BMPs
Element 1: Mark Clearing Limits
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Element 2: Establish Construction Access
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Stormwater Pollution Prevention Plan
36
Element 3: Control Flow Rates
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Element 4: Install Sediment Controls
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Stormwater Pollution Prevention Plan
37
Element 5: Stabilize Soils
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Element 6: Protect Slopes
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Stormwater Pollution Prevention Plan
38
Element 7: Protect Drain Inlets
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Element 8: Stabilize Channels and Outlets
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Stormwater Pollution Prevention Plan
39
Element 9: Control Pollutants
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Element 10: Control Dewatering
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
BMP:
Location Inspected Functioning Problem/Corrective Action Y N Y N NIP
Stormwater Discharges From the Site
Observed? Problem/Corrective Action Y N
Location
Turbidity
Discoloration
Sheen
Location
Turbidity
Discoloration
Sheen
Stormwater Pollution Prevention Plan
40
Water Quality Monitoring
Was any water quality monitoring conducted? □ Yes □ No
If water quality monitoring was conducted, record results here:
If water quality monitoring indicated turbidity 250 NTU or greater; or transparency 6 cm
or less, was Ecology notified by phone within 24 hrs?
□ Yes □ No
If Ecology was notified, indicate the date, time, contact name and phone number below:
Date:
Time:
Contact Name:
Phone #:
General Comments and Notes
Include BMP repairs, maintenance, or installations made as a result of the inspection.
Were Photos Taken? □ Yes □ No
If photos taken, describe photos below:
Stormwater Pollution Prevention Plan
41
Appendix F – Engineering Calculations
9.0 BOND QUANTITIES, FACILITY SUMMARIES,
AND DECLARATIONS OF COVENANT
Planning Division |1055 South Grady Way – 6th Floor | Renton, WA 98057 (425) 430-7200••Section I: Project Information•••Section II: Bond Quantities Worksheets••Section II.a EROSION CONTROL (Stabilization/Erosion Sediment Control (ESC))•Section II.b TRANSPORTATION (Street and Site Improvements)•Section II.c DRAINAGE (Drainage and Stormwater Facilities): •Section II.d WATER - ONLY APPLICABLE IF WATER SERVICE IS PROVIDED BY CITY OF RENTON•Section II.e SANITARY SEWER - ONLY APPLICABLE IF SEWER SERVICE IS PROVIDED BY CITY OF RENTON••••••Section III. Bond Worksheet•BOND QUANTITY WORKSHEET INSTRUCTIONSThis worksheet is intended to be a "working" copy of the bond quantity worksheet, which will be used throughout all phases of the project, from initial submittal to project close-out approval. Submit this workbook, in its entirety, as follows:The following forms are to be completed by the engineer/developer/applicant as applicable to the project: The Bond Worksheet form will auto-calculate and auto-populate from the information provided in Section I and Section II.This section includes all pertinent information for the projectSection II contains a separate spreadsheet TAB for each of the following specialties: (1) electronic copy (.xlsx format) and (1) hard copy of the entire workbook for civil construction permit submittal. Hard copies are to be included as part of the Technical Information Report (TIR).(1) electronic copy (.xlsx format) and (1) hard copy of the entire workbook for final close-out submittal.This section must be completed in its entiretyInformation from this section auto-populates to all other relevant areas of the workbookThis section calculates the required Permit Bond for construction permit issuance as well as the required Maintenance Bond for project close-out submittals to release the permit bond on a project. All unit prices include labor, equipment, materials, overhead and profit. Complete the 'Quantity' columns for each of the appropriate section(s). Include existing Right-of-Way (ROW), Future Public Improvements and Private Improvements.The 'Quantity Remaining' column is only to be used when a project is under construction. The City allows one (1) bond reduction during the life of the project with the exception of the maintenance period reduction.Excel will auto-calculate and auto-populate the relevant fields and subtotals throughout the document. Only the 'Quantity' columns should need completing.Additional items not included in the lists can be added under the "write-in" sections. Provide a complete description, cost estimate and unit of measure for each write-in item. Note: Private improvements, with the exception of stormwater facilities, are not included in the bond amount calculation, but must be entered on the form. Stormwater facilities (public and private) are required to be included in the bond amount.Page 1 of 14Ref 8-H Bond Quantity WorksheetINSTRUCTIONSUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
Planning Division |1055 South Grady Way – 6th Floor | Renton, WA 98057 (425) 430-7200Date Prepared: Name:PE Registration No:Firm Name:Firm Address:Phone No.Email Address:Project Name: Project Owner:CED Plan # (LUA):Phone:CED Permit # (U):Address: Site Address:Street Intersection:Addt'l Project Owner:Parcel #(s):Phone:Address: Clearing and grading greater than or equal to 5,000 board feet of timber? Yes/No:NOWater Service Provided by:If Yes, Provide Forest Practice Permit #:Sewer Service Provided by: AddressAbbreviated Legal Description:Abbreviated LegalCity, State, Zip1415 Maple Avenue SW11225 SE 6th Street, Suite 215Additional Project OwnerMaple/SW 16th########425-766-704011/4/2019Prepared by:FOR APPROVALProject Phase 1dbalmelli@barghausen.comDan Balmelli25672Barghausen Consulting Engineers, Inc.18215 72nd Ave S, Kent, WA 98032425-251-6222SITE IMPROVEMENT BOND QUANTITY WORKSHEETPROJECT INFORMATIONCITY OF RENTONCITY OF RENTON1 Select the current project status/phase from the following options: For Approval - Preliminary Data Enclosed, pending approval from the City; For Construction - Estimated Data Enclosed, Plans have been approved for contruction by the City; Project Closeout - Final Costs and Quantities Enclosed for Project Close-out SubmittalPhoneEngineer Stamp Required (all cost estimates must have original wet stamp and signature)Clearing and GradingUtility ProvidersN/AProject Location and DescriptionProject Owner Information405 Commerce CenterBellevue, WA 9800433404-3805Josh Shearer##-######Page 2 of 14Ref 8-H Bond Quantity WorksheetSECTION I PROJECT INFORMATIONUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########UnitReference #PriceUnitQuantity CostBackfill & compaction-embankmentESC-16.50$ CY100650.00Check dams, 4" minus rockESC-2SWDM 5.4.6.380.00$ Each Catch Basin ProtectionESC-335.50$ Each7248.50Crushed surfacing 1 1/4" minusESC-4WSDOT 9-03.9(3)95.00$ CY DitchingESC-59.00$ CY Excavation-bulkESC-62.00$ CY Fence, siltESC-7SWDM 5.4.3.11.50$ LF400600.00Fence, Temporary (NGPE)ESC-81.50$ LF Geotextile FabricESC-92.50$ SY Hay Bale Silt TrapESC-100.50$ Each HydroseedingESC-11SWDM 5.4.2.40.80$ SY Interceptor Swale / DikeESC-121.00$ LF Jute MeshESC-13SWDM 5.4.2.23.50$ SY Level SpreaderESC-141.75$ LF Mulch, by hand, straw, 3" deepESC-15SWDM 5.4.2.12.50$ SY Mulch, by machine, straw, 2" deepESC-16SWDM 5.4.2.12.00$ SY Piping, temporary, CPP, 6"ESC-1712.00$ LF Piping, temporary, CPP, 8"ESC-1814.00$ LF Piping, temporary, CPP, 12"ESC-1918.00$ LF Plastic covering, 6mm thick, sandbaggedESC-20SWDM 5.4.2.34.00$ SY Rip Rap, machine placed; slopesESC-21WSDOT 9-13.1(2)45.00$ CY Rock Construction Entrance, 50'x15'x1'ESC-22SWDM 5.4.4.11,800.00$ Each Rock Construction Entrance, 100'x15'x1'ESC-23SWDM 5.4.4.13,200.00$ Each Sediment pond riser assemblyESC-24SWDM 5.4.5.22,200.00$ Each Sediment trap, 5' high berm ESC-25SWDM 5.4.5.119.00$ LF Sed. trap, 5' high, riprapped spillway berm section ESC-26SWDM 5.4.5.170.00$ LF Seeding, by handESC-27SWDM 5.4.2.41.00$ SY Sodding, 1" deep, level groundESC-28SWDM 5.4.2.58.00$ SY Sodding, 1" deep, sloped groundESC-29SWDM 5.4.2.510.00$ SY TESC SupervisorESC-30110.00$ HR404,400.00Water truck, dust controlESC-31SWDM 5.4.7140.00$ HR UnitReference #PriceUnitQuantity Cost EROSION/SEDIMENT SUBTOTAL:5,898.50SALES TAX @ 10%589.85EROSION/SEDIMENT TOTAL:6,488.35(A)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR EROSION & SEDIMENT CONTROLDescription No.(A)WRITE-IN-ITEMS Page 3 of 14Ref 8-H Bond Quantity WorksheetSECTION II.a EROSION_CONTROLUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostGENERAL ITEMS Backfill & Compaction- embankmentGI-16.00$ CYBackfill & Compaction- trenchGI-29.00$ CYClear/Remove Brush, by hand (SY)GI-31.00$ SYBollards - fixedGI-4240.74$ EachBollards - removableGI-5452.34$ EachClearing/Grubbing/Tree RemovalGI-610,000.00$ AcreExcavation - bulkGI-72.00$ CYExcavation - TrenchGI-85.00$ CYFencing, cedar, 6' highGI-920.00$ LFFencing, chain link, 4'GI-1038.31$ LFFencing, chain link, vinyl coated, 6' highGI-1120.00$ LFFencing, chain link, gate, vinyl coated, 20' GI-121,400.00$ EachFill & compact - common barrowGI-1325.00$ CYFill & compact - gravel baseGI-1427.00$ CYFill & compact - screened topsoilGI-1539.00$ CYGabion, 12" deep, stone filled mesh GI-1665.00$ SYGabion, 18" deep, stone filled mesh GI-1790.00$ SYGabion, 36" deep, stone filled meshGI-18150.00$ SYGrading, fine, by handGI-192.50$ SYGrading, fine, with graderGI-202.00$ SYMonuments, 3' LongGI-21250.00$ EachSensitive Areas SignGI-227.00$ EachSodding, 1" deep, sloped groundGI-238.00$ SYSurveying, line & gradeGI-24850.00$ DaySurveying, lot location/linesGI-251,800.00$ AcreTopsoil Type A (imported)GI-2628.50$ CYTraffic control crew ( 2 flaggers )GI-27120.00$ HRTrail, 4" chipped woodGI-288.00$ SYTrail, 4" crushed cinderGI-299.00$ SYTrail, 4" top courseGI-3012.00$ SYConduit, 2"GI-315.00$ LFWall, retaining, concreteGI-3255.00$ SFWall, rockeryGI-3315.00$ SFSUBTOTAL THIS PAGE:(B)(C)(D)(E)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR STREET AND SITE IMPROVEMENTSQuantity Remaining (Bond Reduction) (B)(C)Page 4 of 14Ref 8-H Bond Quantity WorksheetSECTION II.b TRANSPORTATIONUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostSITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR STREET AND SITE IMPROVEMENTSQuantity Remaining (Bond Reduction) (B)(C)ROAD IMPROVEMENT/PAVEMENT/SURFACINGAC Grinding, 4' wide machine < 1000syRI-130.00$ SYAC Grinding, 4' wide machine 1000-2000syRI-216.00$ SYAC Grinding, 4' wide machine > 2000syRI-310.00$ SYAC Removal/DisposalRI-435.00$ SYBarricade, Type III ( Permanent )RI-556.00$ LFGuard RailRI-630.00$ LFCurb & Gutter, rolledRI-717.00$ LFCurb & Gutter, verticalRI-812.50$ LFCurb and Gutter, demolition and disposalRI-918.00$ LFCurb, extruded asphaltRI-105.50$ LFCurb, extruded concreteRI-117.00$ LFSawcut, asphalt, 3" depthRI-121.85$ LFSawcut, concrete, per 1" depthRI-133.00$ LFSealant, asphaltRI-142.00$ LFShoulder, gravel, 4" thickRI-1515.00$ SYSidewalk, 4" thickRI-1638.00$ SYSidewalk, 4" thick, demolition and disposalRI-1732.00$ SYSidewalk, 5" thickRI-1841.00$ SYSidewalk, 5" thick, demolition and disposalRI-1940.00$ SYSign, Handicap RI-2085.00$ EachStriping, per stallRI-217.00$ EachStriping, thermoplastic, ( for crosswalk )RI-223.00$ SFStriping, 4" reflectorized lineRI-230.50$ LFAdditional 2.5" Crushed SurfacingRI-243.60$ SYHMA 1/2" Overlay 1.5" RI-2514.00$ SYHMA 1/2" Overlay 2"RI-2618.00$ SYHMA Road, 2", 4" rock, First 2500 SYRI-2728.00$ SYHMA Road, 2", 4" rock, Qty. over 2500SYRI-2821.00$ SYHMA Road, 4", 6" rock, First 2500 SYRI-2945.00$ SYHMA Road, 4", 6" rock, Qty. over 2500 SYRI-3037.00$ SYHMA Road, 4", 4.5" ATBRI-3138.00$ SYGravel Road, 4" rock, First 2500 SYRI-3215.00$ SYGravel Road, 4" rock, Qty. over 2500 SYRI-3310.00$ SYThickened EdgeRI-348.60$ LFSUBTOTAL THIS PAGE:(B)(C)(D)(E)Page 5 of 14Ref 8-H Bond Quantity WorksheetSECTION II.b TRANSPORTATIONUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostSITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR STREET AND SITE IMPROVEMENTSQuantity Remaining (Bond Reduction) (B)(C)PARKING LOT SURFACINGNo.2" AC, 2" top course rock & 4" borrowPL-121.00$ SY2755,775.002" AC, 1.5" top course & 2.5" base coursePL-228.00$ SY4" select borrowPL-35.00$ SY1.5" top course rock & 2.5" base coursePL-414.00$ SYSUBTOTAL PARKING LOT SURFACING:5,775.00(B)(C)(D)(E)LANDSCAPING & VEGETATIONNo.Street TreesLA-1Median LandscapingLA-2Right-of-Way LandscapingLA-3Wetland LandscapingLA-4SUBTOTAL LANDSCAPING & VEGETATION:(B)(C)(D)(E)TRAFFIC & LIGHTINGNo.SignsTR-1Street Light System ( # of Poles)TR-2Traffic SignalTR-3Traffic Signal ModificationTR-4SUBTOTAL TRAFFIC & LIGHTING:(B)(C)(D)(E)WRITE-IN-ITEMSSUBTOTAL WRITE-IN ITEMS:STREET AND SITE IMPROVEMENTS SUBTOTAL:5,775.00SALES TAX @ 10%577.50STREET AND SITE IMPROVEMENTS TOTAL:6,352.50(B)(C)(D)(E)Page 6 of 14Ref 8-H Bond Quantity WorksheetSECTION II.b TRANSPORTATIONUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostDRAINAGE (CPE = Corrugated Polyethylene Pipe, N12 or Equivalent) For Culvert prices, Average of 4' cover was assumed. Assume perforated PVC is same price as solid pipe.) Access Road, R/DD-126.00$ SY* (CBs include frame and lid)BeehiveD-290.00$ EachThrough-curb Inlet FrameworkD-3400.00$ EachCB Type ID-41,500.00$ EachCB Type ILD-51,750.00$ EachCB Type II, 48" diameterD-62,300.00$ Each for additional depth over 4' D-7480.00$ FTCB Type II, 54" diameterD-82,500.00$ Each for additional depth over 4'D-9495.00$ FTCB Type II, 60" diameterD-102,800.00$ Each for additional depth over 4'D-11600.00$ FTCB Type II, 72" diameterD-126,000.00$ Each for additional depth over 4'D-13850.00$ FTCB Type II, 96" diameterD-1414,000.00$ Each for additional depth over 4'D-15925.00$ FTTrash Rack, 12"D-16350.00$ EachTrash Rack, 15"D-17410.00$ EachTrash Rack, 18"D-18480.00$ EachTrash Rack, 21"D-19550.00$ EachCleanout, PVC, 4"D-20150.00$ EachCleanout, PVC, 6"D-21170.00$ EachCleanout, PVC, 8"D-22200.00$ EachCulvert, PVC, 4" D-2310.00$ LFCulvert, PVC, 6" D-2413.00$ LFCulvert, PVC, 8" D-2515.00$ LFCulvert, PVC, 12" D-2623.00$ LFCulvert, PVC, 15" D-2735.00$ LFCulvert, PVC, 18" D-2841.00$ LFCulvert, PVC, 24"D-2956.00$ LFCulvert, PVC, 30" D-3078.00$ LFCulvert, PVC, 36" D-31130.00$ LFCulvert, CMP, 8"D-3219.00$ LFCulvert, CMP, 12"D-3329.00$ LFSUBTOTAL THIS PAGE:(B)(C)(D)(E)Quantity Remaining (Bond Reduction) (B)(C)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR DRAINAGE AND STORMWATER FACILITIESPage 7 of 14Ref 8-H Bond Quantity WorksheetSECTION II.c DRAINAGEUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostQuantity Remaining (Bond Reduction) (B)(C)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR DRAINAGE AND STORMWATER FACILITIESDRAINAGE (Continued)Culvert, CMP, 15"D-3435.00$ LFCulvert, CMP, 18"D-3541.00$ LFCulvert, CMP, 24"D-3656.00$ LFCulvert, CMP, 30"D-3778.00$ LFCulvert, CMP, 36"D-38130.00$ LFCulvert, CMP, 48"D-39190.00$ LFCulvert, CMP, 60"D-40270.00$ LFCulvert, CMP, 72"D-41350.00$ LFCulvert, Concrete, 8"D-4242.00$ LFCulvert, Concrete, 12"D-4348.00$ LFCulvert, Concrete, 15"D-4478.00$ LFCulvert, Concrete, 18"D-4548.00$ LFCulvert, Concrete, 24"D-4678.00$ LFCulvert, Concrete, 30"D-47125.00$ LFCulvert, Concrete, 36"D-48150.00$ LFCulvert, Concrete, 42"D-49175.00$ LFCulvert, Concrete, 48"D-50205.00$ LFCulvert, CPE Triple Wall, 6" D-5114.00$ LFCulvert, CPE Triple Wall, 8" D-5216.00$ LFCulvert, CPE Triple Wall, 12" D-5324.00$ LFCulvert, CPE Triple Wall, 15" D-5435.00$ LFCulvert, CPE Triple Wall, 18" D-5541.00$ LFCulvert, CPE Triple Wall, 24" D-5656.00$ LFCulvert, CPE Triple Wall, 30" D-5778.00$ LFCulvert, CPE Triple Wall, 36" D-58130.00$ LFCulvert, LCPE, 6"D-5960.00$ LFCulvert, LCPE, 8"D-6072.00$ LFCulvert, LCPE, 12"D-6184.00$ LFCulvert, LCPE, 15"D-6296.00$ LFCulvert, LCPE, 18"D-63108.00$ LFCulvert, LCPE, 24"D-64120.00$ LFCulvert, LCPE, 30"D-65132.00$ LFCulvert, LCPE, 36"D-66144.00$ LFCulvert, LCPE, 48"D-67156.00$ LFCulvert, LCPE, 54"D-68168.00$ LFSUBTOTAL THIS PAGE:(B)(C)(D)(E)Page 8 of 14Ref 8-H Bond Quantity WorksheetSECTION II.c DRAINAGEUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostQuantity Remaining (Bond Reduction) (B)(C)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR DRAINAGE AND STORMWATER FACILITIESDRAINAGE (Continued)Culvert, LCPE, 60"D-69180.00$ LFCulvert, LCPE, 72"D-70192.00$ LFCulvert, HDPE, 6"D-7142.00$ LFCulvert, HDPE, 8"D-7242.00$ LFCulvert, HDPE, 12"D-7374.00$ LFCulvert, HDPE, 15"D-74106.00$ LFCulvert, HDPE, 18"D-75138.00$ LFCulvert, HDPE, 24"D-76221.00$ LFCulvert, HDPE, 30"D-77276.00$ LFCulvert, HDPE, 36"D-78331.00$ LFCulvert, HDPE, 48"D-79386.00$ LFCulvert, HDPE, 54"D-80441.00$ LFCulvert, HDPE, 60"D-81496.00$ LFCulvert, HDPE, 72"D-82551.00$ LFPipe, Polypropylene, 6"D-8384.00$ LFPipe, Polypropylene, 8"D-8489.00$ LFPipe, Polypropylene, 12"D-8595.00$ LFPipe, Polypropylene, 15"D-86100.00$ LFPipe, Polypropylene, 18"D-87106.00$ LFPipe, Polypropylene, 24"D-88111.00$ LFPipe, Polypropylene, 30"D-89119.00$ LFPipe, Polypropylene, 36"D-90154.00$ LFPipe, Polypropylene, 48"D-91226.00$ LFPipe, Polypropylene, 54"D-92332.00$ LFPipe, Polypropylene, 60"D-93439.00$ LFPipe, Polypropylene, 72"D-94545.00$ LFCulvert, DI, 6"D-9561.00$ LF462,806.00Culvert, DI, 8"D-9684.00$ LFCulvert, DI, 12"D-97106.00$ LFCulvert, DI, 15"D-98129.00$ LFCulvert, DI, 18"D-99152.00$ LFCulvert, DI, 24"D-100175.00$ LFCulvert, DI, 30"D-101198.00$ LFCulvert, DI, 36"D-102220.00$ LFCulvert, DI, 48"D-103243.00$ LFCulvert, DI, 54"D-104266.00$ LFCulvert, DI, 60"D-105289.00$ LFCulvert, DI, 72"D-106311.00$ LFSUBTOTAL THIS PAGE:2,806.00(B)(C)(D)(E)Page 9 of 14Ref 8-H Bond Quantity WorksheetSECTION II.c DRAINAGEUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostQuantity Remaining (Bond Reduction) (B)(C)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR DRAINAGE AND STORMWATER FACILITIESSpecialty Drainage ItemsDitching SD-19.50$ CYFlow Dispersal Trench (1,436 base+)SD-328.00$ LF French Drain (3' depth)SD-426.00$ LFGeotextile, laid in trench, polypropyleneSD-53.00$ SYMid-tank Access Riser, 48" dia, 6' deepSD-62,000.00$ EachPond Overflow SpillwaySD-716.00$ SYRestrictor/Oil Separator, 12"SD-81,150.00$ EachRestrictor/Oil Separator, 15"SD-91,350.00$ EachRestrictor/Oil Separator, 18"SD-101,700.00$ EachRiprap, placedSD-1142.00$ CYTank End Reducer (36" diameter)SD-121,200.00$ EachInfiltration pond testingSD-13125.00$ HRPermeable PavementSD-14Permeable Concrete SidewalkSD-15Culvert, Box __ ft x __ ftSD-16SUBTOTAL SPECIALTY DRAINAGE ITEMS:(B)(C)(D)(E)STORMWATER FACILITIES (Include Flow Control and Water Quality Facility Summary Sheet and Sketch)Detention PondSF-1Each Detention TankSF-2Each Detention VaultSF-3Each Infiltration PondSF-4Each Infiltration TankSF-5Each Infiltration VaultSF-6Each Infiltration TrenchesSF-7Each Basic Biofiltration SwaleSF-8Each Wet Biofiltration SwaleSF-9Each WetpondSF-10Each WetvaultSF-11Each Sand FilterSF-12Each Sand Filter VaultSF-13Each Linear Sand FilterSF-14Each Proprietary FacilitySF-15Each Bioretention FacilitySF-16Each SUBTOTAL STORMWATER FACILITIES:(B)(C)(D)(E)Page 10 of 14Ref 8-H Bond Quantity WorksheetSECTION II.c DRAINAGEUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostQuantity Remaining (Bond Reduction) (B)(C)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR DRAINAGE AND STORMWATER FACILITIESWRITE-IN-ITEMS (INCLUDE ON-SITE BMPs)Trench DrainWI-1100.00$ LF363,600.00WI-2WI-3WI-4WI-5WI-6WI-7WI-8WI-9WI-10WI-11WI-12WI-13WI-14WI-15SUBTOTAL WRITE-IN ITEMS:3,600.00DRAINAGE AND STORMWATER FACILITIES SUBTOTAL:6,406.00SALES TAX @ 10%640.60DRAINAGE AND STORMWATER FACILITIES TOTAL:7,046.60(B) (C) (D) (E)Page 11 of 14Ref 8-H Bond Quantity WorksheetSECTION II.c DRAINAGEUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostConnection to Existing WatermainW-12,000.00$ EachDuctile Iron Watermain, CL 52, 4 Inch DiameterW-250.00$ LFDuctile Iron Watermain, CL 52, 6 Inch DiameterW-356.00$ LFDuctile Iron Watermain, CL 52, 8 Inch DiameterW-460.00$ LFDuctile Iron Watermain, CL 52, 10 Inch DiameterW-570.00$ LFDuctile Iron Watermain, CL 52, 12 Inch DiameterW-680.00$ LFGate Valve, 4 inch DiameterW-7500.00$ EachGate Valve, 6 inch DiameterW-8700.00$ EachGate Valve, 8 Inch DiameterW-9800.00$ EachGate Valve, 10 Inch DiameterW-101,000.00$ EachGate Valve, 12 Inch DiameterW-111,200.00$ EachFire Hydrant AssemblyW-124,000.00$ EachPermanent Blow-Off AssemblyW-131,800.00$ EachAir-Vac Assembly, 2-Inch DiameterW-142,000.00$ EachAir-Vac Assembly, 1-Inch DiameterW-151,500.00$ EachCompound Meter Assembly 3-inch DiameterW-168,000.00$ EachCompound Meter Assembly 4-inch DiameterW-179,000.00$ EachCompound Meter Assembly 6-inch DiameterW-1810,000.00$ EachPressure Reducing Valve Station 8-inch to 10-inchW-1920,000.00$ EachWATER SUBTOTAL:SALES TAX @ 10%WATER TOTAL:(B) (C) (D) (E)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR WATERQuantity Remaining (Bond Reduction) (B)(C)Page 12 of 14Ref 8-H Bond Quantity WorksheetSECTION II.d WATERUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
CED Permit #:########ExistingFuture PublicPrivateRight-of-WayImprovementsImprovements(D) (E)DescriptionNo. Unit PriceUnitQuant.CostQuant.CostQuant.CostQuant.CostClean OutsSS-11,000.00$ EachGrease Interceptor, 500 gallonSS-28,000.00$ EachGrease Interceptor, 1000 gallonSS-310,000.00$ EachGrease Interceptor, 1500 gallonSS-415,000.00$ EachSide Sewer Pipe, PVC. 4 Inch DiameterSS-580.00$ LFSide Sewer Pipe, PVC. 6 Inch DiameterSS-695.00$ LFSewer Pipe, PVC, 8 inch DiameterSS-7105.00$ LFSewer Pipe, PVC, 12 Inch DiameterSS-8120.00$ LFSewer Pipe, DI, 8 inch DiameterSS-9115.00$ LFSewer Pipe, DI, 12 Inch DiameterSS-10130.00$ LFManhole, 48 Inch DiameterSS-116,000.00$ EachManhole, 54 Inch DiameterSS-136,500.00$ EachManhole, 60 Inch DiameterSS-157,500.00$ EachManhole, 72 Inch DiameterSS-178,500.00$ EachManhole, 96 Inch DiameterSS-1914,000.00$ EachPipe, C-900, 12 Inch DiameterSS-21180.00$ LFOutside DropSS-241,500.00$ LSInside DropSS-251,000.00$ LSSewer Pipe, PVC, ____ Inch DiameterSS-26Lift Station (Entire System)SS-27LSSANITARY SEWER SUBTOTAL:SALES TAX @ 10%SANITARY SEWER TOTAL:(B) (C) (D) (E)SITE IMPROVEMENT BOND QUANTITY WORKSHEETFOR SANITARY SEWERQuantity Remaining (Bond Reduction) (B)(C)Page 13 of 14Ref 8-H Bond Quantity WorksheetSECTION II.e SANITARY SEWERUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
Planning Division |1055 South Grady Way – 6th Floor | Renton, WA 98057 (425) 430-7200Date:Name:Project Name: PE Registration No:CED Plan # (LUA):Firm Name:CED Permit # (U):Firm Address:Site Address:Phone No.Parcel #(s):Email Address:Project Phase: Site Restoration/Erosion Sediment Control Subtotal (a)Existing Right-of-Way Improvements Subtotal (b)(b)-$ Future Public Improvements Subtotal(c)-$ Stormwater & Drainage Facilities (Public & Private) Subtotal(d)(d)7,046.60$ (e)(f)Site RestorationCivil Construction PermitMaintenance Bond1,409.32$ Bond Reduction2Construction Permit Bond Amount 3Minimum Bond Amount is $10,000.001 Estimate Only - May involve multiple and variable components, which will be established on an individual basis by Development Engineering.2 The City of Renton allows one request only for bond reduction prior to the maintenance period. Reduction of not more than 70% of the original bond amount, provided that the remaining 30% willcover all remaining items to be constructed. 3 Required Bond Amounts are subject to review and modification by Development Engineering.* Note: The word BOND as used in this document means any financial guarantee acceptable to the City of Renton.** Note: All prices include labor, equipment, materials, overhead and profit. EST1((b) + (c) + (d)) x 20%9,528.75$ MAINTENANCE BOND */**(after final acceptance of construction)6,488.35$ -$ 7,046.60$ 6,488.35$ 6,352.50$ 7,046.60$ -$ 10,000.00$ P (a) x 100%SITE IMPROVEMENT BOND QUANTITY WORKSHEET BOND CALCULATIONS11/4/2019Dan Balmelli25672Barghausen Consulting Engineers, Inc.R((b x 150%) + (d x 100%))S(e) x 150% + (f) x 100%Bond Reduction: Existing Right-of-Way Improvements (Quantity Remaining)2Bond Reduction: Stormwater & Drainage Facilities (Quantity Remaining)2T(P +R - S)Prepared by:Project InformationCONSTRUCTION BOND AMOUNT */**(prior to permit issuance)425-251-6222dbalmelli@barghausen.com405 Commerce Center##-######1415 Maple Avenue SW33404-3805FOR APPROVAL########18215 72nd Ave S, Kent, WA 98032Page 14 of 14Ref 8-H Bond Quantity WorksheetSECTION III. BOND WORKSHEETUnit Prices Updated: 06/14/2016Version: 04/26/2017Printed 11/4/2019
10.0 OPERATIONS AND MAINTENANCE
MANUAL
10.0 OPERATIONS AND MAINTENANCE MANUAL