HomeMy WebLinkAboutMFP20001971.pdfDEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
Major Franchise Permit: MFP20001971
IVR Number: 20001971
Permit Information
Permit Name: Puget Sound Energy - Electric
Address/Location:05/13/2020Application Date:1023059081Parcel Number: 1160 DUVALL AVE NE
Permit Type:06/25/2020Issue Date:Franchise
Permit Work Class:06/25/2021Expiration Date:Major Utility
Job Number: 101120019
Description: Puget Sound Energy Electric OH to UG conversion along Duvall Ave NE between NE 7th Pl and NE Sunset Blvd.
Please see attached
POTHOLE ALL EXISTING UTILITIES. RESTORATION PER CITY OF RENTON STANDARDS
Contacts
Name Address PhoneTypeBilling
Corrie Rydberg
Puget Sound Energy
6905 S 228TH St
KENT, WA 98032
C: (425) 892-0416ApplicantX
FRICKS ROBERT E SR 1621 CAMAS AVE NE
RENTON , WA 98056
Owner
Marita Bond
Puget Sound Energy - Billing
6905 S 228th St
Kent, WA 98032
B: (253) 395-6346Specialized
Billing
General Conditions & Signature
Permission is hereby given for the work described on this permit according to the conditions hereon and according to the
approved plans and specifications pertaining thereto, subject to compliance with the Ordinance of the City of Renton.
Ÿ
This permit and plans must be posted at the job site at all times.Ÿ
I hereby certify that no work is to be done except as described above and in approved plans, and that work is to conform to
Renton Trench Restoration and Street Overlay Requirements.
Ÿ
Call 425.430.7203 or go to: https://permitting.rentonwa.gov one working day in advance to schedule an inspections and for ANY
work in the Right of Way.
Ÿ
Call 8 1 1 to locate underground utilities at least two full business days prior to any excavation.Ÿ
In accordance with RCW 19.122.033(4) the permit holder is required to contact (Williams Northwest Pipeline at 425.868.1010)
(Olympic Pipeline at 206.510.0575) (Puget Sound Energy at 425.375.3397) to request a consultation with the transmission
pipeline company prior to performing any construction or excavation activities. This requirement to consult with the
transmission pipeline company is in addition to the requirement to Call before You Dig as required in RCW 19.122.
Ÿ
(Date)(Signature)
Page 1 of 1THIS PERMIT AND PLANS MUST BE POSTED AT THE JOB SITE AT ALL TIMES
DEPARTMENT OF PUBLIC WORKS
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 1 of 2 | Published: 1ϭ/Ϯϱ/2019
Transportation Division | 1055 South Grady Way, 5th Floor | Renton, WA 98057 | 425-430-7380
Website: rentonwa.gov
TRAFFIC CONTROL PLAN (TCP) APPLICATION
Published: 1ϭ/Ϯϱ/2019
TRAFFIC CONTROL PLAN (TCP) MUST BE SUBMITTED TO PUBLIC WORKS TRANSPORTATION DIVISION
FOR REVIEW/APPROVAL NO LATER THAN FIVE (5) WORKING DAYS BEFORE THE DATE OF WORK.
The City of Renton requires any contractor, firm, corporation, or other public/private agency to prepare a TCP and
obtain City of Renton's approval of that plan when construction, repair, or maintenance work is to be conducted
within the city's right-of-way.
TO THE APPLICANT: Submit the TCP application form and required submittal documents to
TCP@rentonwa.gov with the subject line “TCP Application – [Project Name]” or the above address.
The following items, electronic copies preferred, are all required for submittal of the TCP Application:
1.܆ A copy of the Traffic Control Plan (TCP) Application form.
2.܆ A copy of the required TCP layout, preferred 11” X 17” paper size format, which shall:
܆ Include map(s) showing the location of the project and work area.
܆ Be legible lettering and clear, contrasting, symbols of viewing or printing.
܆ Must indicate street names, and north arrow and scale.
܆ All signs and detour routes shall conform to the MUTCD, WSDOT TCPs, and the Washington State
Traffic Control Flagger Certification handbook, by the Evergreen Safety Council.
܆ Types of plans required:
܆ Work hour plan – show all mobility impacts during construction hours.
܆ Non-work plan - show all mobility impacts after work hours when limited or no work is
happening in the right-of-way (ROW), if applicable.
܆ Changing construction phases – show construction sequence and each construction phase
change even if the traffic control is not modified, if applicable.
܆ Pedestrian access/detour plan, if applicable.
Project Name: ______________________________________________ Permit #: _____________________
Project Address: ____________________________________________________________________________
Work Date: From _____________ To _____________ Work Time: Start ______________ End ______________
Description of Work, Work Schedule, Equipment Used: _____________________________________________
___________________________________________________________________________________________
___________________________________________________________________________________________
Construction Company: ________________________________________ Phone/Cell: (_____) _____-________
Applicant Name: _________________________________ Email: ______________________________________
Business Address: _________________________________ City/State: __________________ Zip: __________
Approved By: _______________________________________________ Date: ________________________
Transportation Operations Engineering
MFP20001971
This permit is for Major construction work in the ROW and will be billed at an additional
$60/HR for inspections. After hours and weekend work will be billed at $125/HR
Scott Warlick CED 6/25/2020
Monday - Friday 8:00AM - 3:00PM
Note: The Applicant is responsible for compliance with all codes and regulations, whether or not described in this document.
Page 2 of 2 | Published: 1ϭ/Ϯϱ/2019
APPLICANT AGREES TO ALL THE FOLLOWING:
x TCP must be approved prior to commencing the work, and all permit conditions shall be met.
x Existing pedestrian access shall be maintained. The work on pedestrian facilities shall be limited to one corner
at a time, with the least possible inconvenience or delay to pedestrians.
x Signage shall be used to warn motorcyclists/bicyclists of the potential hazards on any uneven surfaced or
slippery road conditions during work and non-work hours.
x The start of Work Time begins when any street or travel lane is fully/partially closed or impacts the follow of
traffic. This includes set up within the traveled way or immediately adjacent to the roadway.
x Emergency services (253-852-2121) shall be notified twenty-four (24) hours before any street or lane closures.
x Contractor or entity must call Renton School District (425-204-4455) or any public/private agency, including
public transit, to be affected by a temporary lane or road closure.
x TCP for all street and/or lane closures shall be implemented and performed in compliance with the Manual on
Uniform Traffic Control Devices (MUTCD) and/or State of Washington Department of Transportation (WSDOT)
and all traffic regulations of the City of Renton and Revised Code of Washington (RCW).
x Any lane or street closures not in conformance with the approved traffic control plan and/or without
notification of emergency services may result in receiving a citation for violation of RCW 47.36.200 Signs or
Flaggers at thoroughfare work sites and RCW 9A.36.050 Reckless Endangerment, and other applicable State
and City codes.
x Indemnify and hold harmless the City of Renton from any and all claims, actions, and judgments, including all
costs of defense and attorney’s fees incurred in defending against same, arising from and related to
implementation of the approved traffic control plans including claims arising from towing of private vehicles
and the acts of the Applicant’s agents and employees.
x The City of Renton shall be entitled, in its reasonable discretion, to settle claims prior to suit or judgment, and
in such event shall indemnify and hold harmless the City for any such claims paid, including the City’s
reasonable attorney’s fees and litigation costs incurred resulting from such claim.
x In the event any claim or suit is brought against the City within the scope of this Agreement, Applicant will pay
for legal counsel chosen by the City to defend against same.
x Flagger and sign placement are subject to revision by the City Inspector on site, if needed to address traffic or
pedestrian safety or travel.
x Total road closure lasting more than twenty-four (24) hours is subject to the approval by the City Council.
x Approved Temporary TCP must be at the work site during work hours.
x Complete assistance and accommodation shall be provided to all kinds of pedestrian traffic when sidewalk or
walkway is impeded to safely redirect pedestrians around a work zone.
x Any vehicle, equipment, barricade, or portable tow-away sign used within the work area must display a
company logo or any legally acceptable sign showing the company name, address, and telephone number at a
conspicuous place on the vehicle or equipment.
In the case of Temporary No Parking Zones, all the following apply in addition to previous:
x Contractor must complete form to show limits of Temporary No Parking Zone identifying barricade locations
for vacate parking or curb lane usage.
x Contractor must post notice of dates and time of Temporary No Parking Zone with at least two signs per block
seventy-two (72) hours in advance of effective date and time.
x The cover sheet of this TCP form must be attached to each Temporary No Parking Sign on the project site.
x Temporary traffic control devices must be removed immediately when work is done or no construction
activities are going on. If deemed abandoned, City crews will remove and store them at the City’s maintenance
shop (3555 NE 2nd Street; 425-430-7423).
_______________________________ _______________________________ _______________________
Applicant’s Signature Print Name Date
11111111
1111111111
11111111
1515
1212DUVALL AVE NENE 7TH PLCHELAN PL NEDUVALL AVE NEDUVALL AVE NE1717NE 8TH ST
11101011
P01V01
P02
J01
ARRW-BRD
ROAD
WORK
AHEAD W20-1350'350'350'RIGHT LANECLOSEDAHEAD W20-5RW4-2LROADWORKAHEADW20-1350'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROADWORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLANPuget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 1 of 13
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
55 +
60/65
45/55
35/40
30
25
SIGN SPACING
"X"
800
500'
350'
200'
100'
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
MFP20001971
1111111111
11111111
1515
1212DUVALL AVE NENE 7TH PLCHELAN PL NEDUVALL AVE NEDUVALL AVE NE1717NE 8TH ST
11101011
P01V01
P02
J01
ARRW-BRD
ROADWORK
AHEAD W20-1350'350'350'RIGHT LANECLOSEDAHEAD W20-5RW4-2LROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1350'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORKAHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLANPuget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 2 of 13
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
55 +
60/65
45/55
35/40
30
25
SIGN SPACING
"X"
800
500'
350'
200'
100'
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
MFP20001971
1111111111
11111111
1515
1212DUVALL AVE NENE 7TH PLCHELAN PL NEDUVALL AVE NE1717NE 8TH ST
11101011
P02
J01
ARRW-BRD
ROAD
WORK
AHEAD W20-1350'X'350'RIGHT LANECLOSED
AHEAD W20-5RW4-2LUSE MAXIMUM AVAILABLE
SPACE FOR SIGNSROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1350'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROADWORKAHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLANPuget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 3 of 13
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
55 +
60/65
45/55
35/40
30
25
SIGN SPACING
"X"
800
500'
350'
200'
100'
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
MFP20001971
1111111111
11111111
1515
1212DUVALL AVE NENE 7TH PLCHELAN PL NENE 9TH ST 1717DUVALL AVE NEDUVALL AVE NE1717NE 8TH ST
11101011
J02
J02A
1111 1111
ARRW-BRDROADWORKAHEADW20-1350'ROAD
WORK
AHEAD W20-1350'350'350'RIGHT LANECLOSED
AHEAD W20-5RW4-2LROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1100'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROADWORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 4 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
1111111111
11111111
1515
1212DUVALL AVE NENE 7TH PLCHELAN PL NENE 9TH ST 1717DUVALL AVE NEDUVALL AVE NEDUVALL AVE NE1717NE 8TH ST
11101011
P01V01
J02
J02A
1111 1111
ARRW-BRD
ROAD
WORKAHEAD W20-1350'350'350'RIGHT LANECLOSEDAHEAD W20-5RW4-2LROADWORKAHEADW20-1350'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 5 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NEP04
P03
J03
V03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD ROADWORKAHEADW20-1350'350'350'RIGHT LANECLOSEDAHEADW20-5RW4-2LROADWORKAHEADW20-1100'
ROAD
WORK
AHEAD W20-1350'ROADWORKAHEADW20-1
100'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 6 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NE12 12 12 12
P04
P03
J03
V03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD
ARRW-BRD
ROAD
WORKAHEAD W20-1350'350'350'W4-2RLEFT LANECLOSED
AHEAD W20-5LROADWORKAHEADW20-1350'350'350'W4-2RLEFT LANECLOSEDAHEADW20-5LROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1RIGHTKEEPR4-7BN
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 7 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NE12 12 12 12
P04
P03
J03
V03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD
ROAD
WORK
AHEAD W20-1350'350'350'RIGHT LANECLOSEDAHEAD W20-5RW4-2LROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1350'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORKAHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 8 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NEP04
P03
J03
V03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD
ROAD
WORK
AHEAD W20-1350'350'350'RIGHT LANE
CLOSED
AHEAD W20-5RW4-2LROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1350'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 9 of 13
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between 9 a.m. and 4 p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NE12 12 12 12
P04
P03
J03
V03
J04
P05
J05
J06
121212 12
POLICEUPO W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4X'X'X'
STOP
FLAGGERW20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4350'350'350'W20-7AROADWORKAHEADW20-1 BEPREPAREDTOSTOPW3-4
100'100'100'
ROAD
WORK
AHEAD W20-1350'350'350'RIGHT LANECLOSED
AHEAD W20-5RW4-2LW20-7ABE
PREPARED
TO
STOP W3-4350'350'X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1ARRW-BRD
N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 10 of 13
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between ____a.m. and ____
p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
LEGEND
TRENCH
28" TRAFFIC CONE
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NEP04
P03
J03
V03
J04
P05
J05
J06
12121212
ARRW-BRD
STOP
FLAGGER
POLICEUPOW20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4350'350'350'W20-7AROADWORKAHEADW20-1 BEPREPAREDTOSTOPW3-4
100'100'100'W20-7AW20-7ABE
PREPARED
TOSTOP W3-4350'350'ROADWORK
AHEAD W20-1350'350'350'RIGHT LANE
CLOSED
AHEAD W20-5RW4-2LS/WCLOSEDR9-9S/WCLOSEDR9-9X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORK
AHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 11 of 13
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between ____a.m. and ____
p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
LEGEND
TRENCH
28" TRAFFIC CONE
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
MFP20001971
12 12 12 121111 11111212121212
NE 12TH ST
DUVALL AVE NEDUVALL AVE NEP04
P03
J03
V03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD
ARRW-BRD
ROADWORK
AHEAD W20-1350'350'350'W4-2RLEFT LANE
CLOSEDAHEAD W20-5LW20-7ABE
PREPAREDTOSTOP W3-4350'350'W20-7AROADWORKAHEADW20-1BEPREPAREDTOSTOPW3-4X'X'X'
W20-7AROADWORKAHEADW20-1 BEPREPAREDTOSTOPW3-4
100'100'100'ROADWORKAHEADW20-1350'350'350'W4-2RLEFT LANECLOSEDAHEADW20-5LW20-7ABEPREPAREDTOSTOPW3-4350'350'R9-3C/WCLOSEDR9-3C/WCLOSEDX'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROADWORK
AHEAD W20-1ROADWORKAHEADW20-1POLICEUPO
N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 12 of 13
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between ____a.m. and ____
p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
LEGEND
TRENCH
28" TRAFFIC CONE
TRAFFIC FLOW
SIGN LOCATION
FLAGGER
UNIFORMED
POLICE OFFICERPOLICE
STOP
CHEVRON
ARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
MFP20001971
111111111212121212
NE 12TH ST
DUVALL AVE NEV03
J04
P05
J05
J06
J07
J08
12121212
ARRW-BRD
ROAD
WORKAHEAD W20-1350'ROADWORKAHEADW20-1100'ROADWORKAHEADW20-1
100'ROADWORKAHEADW20-1350'350'350'RIGHT LANECLOSEDAHEADW20-5RW4-2LDUVALL AVE NER9-3C/WCLOSEDS/WCLOSEDR9-9S/WCLOSEDR9-9X'X'PLACE W20-1 SIGNS ON ALL
ADJACENT STREETS WITHIN
100 FEET OF WORK AREA
ROAD
WORKAHEAD W20-1ROADWORKAHEADW20-1N
TEMPORARY TRAFFIC CONTROL PLAN
Puget Sound Energy
Traffic Control Supervisor:
Gregory Harwood
Card No. 012238
Card Exp. 09/30/2023
gregory.harwood@pse.com
(425)424-6425
PSE PUGETSOUNDENERGY
JOB#101120019
1100 Duvall Ave NE, Renton, WA
2/11/2020
safaa.neema@pse.com
(425) 398-6077
SHEET 13 of 13
Notes:
1. All signs and spacing to conform to the
MUTCD and King County standards.
2. All sidewalks, driveways, exits and egresses
shall be completely clear unless otherwise indicated.
3. Channelizing devices are 28" traffic cones.
Use traffic drums (barrels) with steady burning
Type C lights on all State State Routes and Hwys.
4. Sign size can be a minimum of 36" x 36" and
shall not obstruct pedestrian access.
5. Crew is required to leave a minimum of 11' for
traveling lane width.
6. Alert affected residents and businesses.
7. Work to take place between ____a.m. and ____
p.m
unless otherwise specified. All work for arterials
and major roadways will be from 9 a.m. to 3 p.m.
PRINT ON
11X17" SHEETS ONLY
CHANNELIZATION
DEVICE SPACING
MPH
55/70
35/45
25/30
TAPER
40
30
20
TANGENT
80
60
40
MINIMUM TAPER LENGTH=L (FT.)
LANE
WIDTH
10
11
12
20
70
75
80
25
105
115
125
30
150
165
180
35
205
225
245
40
270
295
320
45
475
495
540
POSTED SPEED (MPH)
50
500
550
600
55
550
605
660
60
-
660
720
65
-
-
780
70
-
-
840
SIGN SPACING
MPH
60/65
45/55
35/40
30
25
"X"
1000'
500'
350'
200'
100'
TRAFFIC FLOW
SIGN LOCATION
LEGEND
TRENCH
28" TRAFFIC CONE
CHEVRONARROW BOARD
WORK VEHICLE/
FLASHING LIGHTS
RIGHT OF WAY
MFP20001971
P01
NE 7TH ST
P01
NE 7TH ST N
Vicinity Map
101120019ARE TO BE INSTALLED, CROSS SECTION DETAILS OF THE TYPICAL EROSION
STRUCTURES, & SPECIAL REQUIREMENTS FOR WORK IN SENSITIVE AREAS.)
EROSION & SEDIMENT CONTROL REQUIREMENTS
NOTES DETAILING WHERE EROSION OR SEDIMENT CONTROL STRUCTURES
(LOCAL JURISDICTIONS MAY HAVE ADDITIONAL REQUIREMENTS INCLUDING
0150.3200 TECHNIQUES FOR TEMPORARY EROSION & SEDIMENT CONTROL
EROSION & SEDIMENT CONTROL SHALL BE PER PSE STANDARD PRACTICE
& ANY ADDITIONAL LOCAL JURISDICTION REQUIREMENTS.
FOREMAN (CHECK BOX WHEN COMPLETED)
PSE Equipment LOCKED/SECURED & Work Area left in CLEAN/SAFE Condition.
Grid, Cable, and Switch numbers INSTALLED & VERIFIED.
Field Changes RED-LINED on As-built.
Indicate correct FUSE SIZE on As-built & VERIFY proper PHASE.
Foreman's Signature _______________________________________________
Print Name ___________________________________ Date ______________
Material VERIFIED and CHANGES noted on Paperwork.
Total PRIMARY Cable noted on As-built.
Company ID#'s RECORDED in correct location on As-built.
Deviations noted on the As-built and their reason.
I certify that the work performed meets PSE's standards and procedures
and that all quality requirements are met.
Yes
Yes
Yes
"Flagging Required"
"Outages Required"
"Locates Required"
LEGEND
EXISTING PROPERTY LINE
EXISTING UG RISER
NEW UG RISER
SVC STUB
J-BOX
NEW TRENCH LINE
EXIST. 3Ø WIRE
EXISTING CENTER LINE
EXISTING CONDUCTOR TO BE REMOVED
DISCONNECT - FUSED
EXIST. 1Ø WIRE
EXISTING RIGHT OF WAY
PROPOSED PULL VAULT
EXISTING POLE
DOWN GUY
EXISTING SECONDARY SERVICE LINE
DISCONNECT - UNFUSED
EXISTING STREETLIGHT
NEW POLE
PROPOSED PADMOUNT TRANSFORMER
EXISTING PADMOUNT TRANSFORMER
PROPOSED TOTAL UNDERGROUND TRANSFORMER
EXISTING TOTAL UNDERGROUND TRANSFORMER
HANDHOLE
PRIMARY METERING POINT
RENTON DUVALL AVE NE
SCHEDULE 74
OH TO UG CONVERSION
PSE GENERAL SPECIFICATIONS
Scope of Work
- OH to UG conversion along Duvall Ave NE between NE 7th Pl and NE Sunset Blvd.
General
-All work is to be completed per PSE Standards & Practices. Copies of all PSE Standards
are available upon request.
-Work sites shall be kept clear of debris and all construction materials; equipment and
packing shall be removed daily.
-Return all unused and removed poles, transformers and hardware to PSE, storeroom. All
copper shall be coiled and returned the day it is removed from the poles. Remove all
unused pins and insulators.
-Return all streetlights, area lights and floodlights to Sumner yard.
Pre-Construction
-Notify appropriate city, County or DOT authorities 48 to 72 hours, or as required by
permitting agency, in advance of starting work in Right-of-way involving a Permit.
-All system switching shall be approved by System Operations (425-882-4652) a minimum
of 48 hours in advance.
-Notify customers of all outages 48 hours in advance.
Work Drawings & Documents
-PSE Project Manager or Engineer shall approve field design changes.
-Mark all field changes, equipment ID numbers and Underground cable information in red on
Foreman's copy of work sketch.
-Return one Foreman's copy of work sketch to Project Manger at completion of job.
-When permits are required, a copy of the permits shall be available on work site at all times.
Safety
- efer to PSE standards 6275.3000 for requirements on System Grounding
-Refer to PSE standards 6275.9210, 6275.9230 and 6275.6250 for personal protective
grounding requirements.
-Refer to PSE standards 6275.9150 for vehicle grounding and barricading requirements.
-Proper line clearances shall be taken at the beginning, and released at the end, of each
workday, or as otherwise instructed by the System Operator.
-Provide signs, barricades, and traffic control in conformance with permit regulations.
-Utilize flagging and other vehicle traffic control as necessary and in conformance with local
traffic regulations.
-Maintain traffic flow as required by permitting agency.
Joint Facilities
-Coordinate with Communication Companies for transfers.
OVERHEAD CONSTRUCTION
Poles & Structures
-Poles are to be installed or relocated as staked. Unless otherwise noted, all pole location
measurements are from the center of the pole.
-All new poles set shall be the class indicated on the sketch, or better. Do not set a lower
class pole than specified.
-Install ground plate assembly on all new poles. Install Switch Ground Assembly per
standard specification 6014.1000 at new gang operated switch locations.
-Install grid numbers on all new and existing poles as shown on sketch.
-Straighten existing poles as indicated or as necessary.
-Treat all field-drilled poles with copper napthenate wood preservative.
-Remove old poles after communication companies have transferred off and return to PSE
storeroom. Fill and crown pole holes and restore the area similar to adjacent landscaping.
Conductors & Equipment
-Transfer all overhead and underground primary, secondary and service conductors and
guys to new poles set, unless otherwise indicated on this sketch.
-Transfer existing transformers to new poles unless otherwise indicated on this sketch.
-Use stirrups to connect all overhead and underground primary taps, and all transformers.
Install at all sites being worked within the scope of the project where they are currently
missing.
- For 12vK construction, install avian protection with #4 CU-covered jumpers (MID#9998076)
and #4 SD Aluminum covered tie-wire (MID#8309760). For 34vK construction use bare
wire primary jumpers with pre-formed helical-grip ties and avian protection devices when
required per Std. 6015.2000. Jumpers for poles that are double dead ended with tree wire
can be either the same size tree wire conductor or covered CU.
-Apply grit inhibitor on all Ampact, stirrup, and dead-end connections.
-Connect primary taps and transformers to same phase as existing unless otherwise shown
on the drawing.
-All neutral connections to be made with solid compression connectors. Connect all pole
grounds to common neutral.
-Use Load-interrupter cutouts (with arc shields) on all primary overheads and underground
taps with fused protection above 40T.
-Install Wildlife Protectors on all transformers.
Cable Tags and Pulling
-Primary Underground Cable Identification Tag installation shall conform to PSE standards
6825.6050.
-Cable Pulling shall conform to PSE standards 6825.6100 and 6825.6150
RESPONSIBILITIES OF THE CITY
Documentation
-The city and their contractor shall attend a pre-construction meeting specifically for
installation of bare duct and vault system.
-PSE will provide to the city contractor with construction plans for the installation of PSE
duct and vault system.
-All installations shall conform to specifications contained in this document and all relevant
PSE standards.
Safety
-Field changes shall be pre-approved by PSE or designated representative prior to
construction with proof of acceptance required prior to PSE acceptance of completed duct
and vault system.
-The city contractor shall not access energized power vaults without the assistance of PSE
line workers.
Trench and Excavation
-The city contractor shall not expose energized power conductors (direct buried or in
conduit) without the assistance of PSE line workers.
-The city shall provide all trench excavation and backfill for the installation of new or
modified PSE underground distribution system within the construction area.
-All trench excavation shall conform to PSE standards 6790.0075, 6790.0130, 6790.0140,
6790.0250, and 6790.3050.
-PSE plans show general trench alignment. They do not show specific cross sections with
existing or proposed other utilities. It is the City's responsibility to install PSE facilities at
necessary depths to avoid and provide required clearances to other existing or proposed
utilities.
-Construct the shared utility trench where the various utilities can transition in and out of the
trench line in an orderly fashion without altering duct bank alignments of other utility.
Separation of crossing utilities sharing the common utility trench is 6”.
-After the new underground system is installed an energized, additional excavation may be
necessary to re-train existing underground cables into the new vaults. This excavation will
be provided by the city with 48 hours notice.
- Placement of other utility vaults within the trench line alignment encumbering access to
PSE facilities is not allowed.
- If four or more six inch conduits are installed in a trench, fluidized thermal backfill (FTB)
shall be installed around the conduits to a depth of six inches above and to the sides of the
conduit, and two inches underneath, per PSE Standard 6790.0140.
Vault Installation
-City shall install PSE vaults in accordance with PSE standards 6775.0035 and 6775.0040.
-Vault hole excavation shall be prepared level and free of debris with a minimum 6” base of
crushed rock to prevent vault settling.
-PSE Vaults in planter areas shall be set 2” above final grade.
-PSE Vaults in hard surface locations such as sidewalks shall be adjusted to match finished
grade prior to the installation of PSE conductors and equipment. Maximum adjustment up is
5”- more than 5” require and additional riser.
- Note: The city contractor will not be allowed to make vault adjustments after PSE
conductors and equipment are energized. PSE line crew will perform the adjustments on a
change order basis.
-City shall provide all surveying necessary to assure all PSE vaults are installed in the
alignment location specified in this document. The city shall be responsible for establishing
grade elevation for PSE vaults.
-All PSE vaults shall be clean and clear of construction debris with all knockouts and cover
adjustments grouted to PSE satisfaction prior to PSE accepting delivery of bare conduit &
vault system.
Conduit Installation
-All PSE conduit installations shall conform to PSE standards 6800.6000, 6800.8050, and
6825.6505.
-All conduits shall be routed and installed per conduit tables, installation diagrams, and
details in this work sketch.
-The city shall proof every PSE conduit run prior to final PSE acceptance. Proofing is
defined as pulling a mandrel of the same diameter through the conduit. Mule tape provided
by PSE shall be pulled in behind the mandrel in each conduit run as evidence of proofing.
A plug shall be installed in all spare conduits.
-All conduits entering PSE vaults shall be through the appropriate knockouts to ensure
proper cable lay. Vault entries causing cables to cross each other in the vault, or lay in the
vault unevenly, will be rejected and corrected at the expense of the city contractor.
- All conduit entries into PSE vault shall be straight and level with a minimum of 6' straight
section outside the vault wall and 2” on conduit extending into the vault with bell ends
installed.
- PSE conduits shall be placed in the trench maintaining a minimum of 1-1/2” of separation.
Use conduit spacers (provided by PSE) every 10'.
-PSE conduit runs shall be placed straight and level. Should it become necessary to alter
conduit alignments to avoid other utilities the maximum bend radius allowed is 22-1/2
degrees. Bend radius greater than 22-1/2 degrees require prior approval from PSE
engineering representatives.
-All PSE conduits shall be placed with the minimum separation between other utility facilities
as specified in PSE standard 6790.0130. Refer to the typical utility trench cross section
detail in this work sketch.
-All PSE conduits shall have a minimum of 36” of cover. Cover of less than 36” is
permissible on a case by case basis provided that such installations adhere to PSE
standard 6790.0130 figure 2. Pre-approval by PSE engineering representatives is required.
-City installed empty conduit is not able to be located by normal means. It is the City's
responsibility to note the location and depth of the installed conduit and protect it from
damage by themselves or others throughout the duration of the project.
Materials
-The city shall not backfill PSE facilities until authorized by the PSE Inspector.
-City shall be responsible for the security all PSE materials delivered to the job site.
-The city contractor shall sign material manifest slips for all PSE materials delivered to the
job site.
-Initial delivery of PSE materials to the job site requires 10 days minimum advanced notice
to PSE storeroom.
-After the initial delivery of materials subsequent bulk material deliveries to the job site by
PSE vendors require a minimum of 5 days- advanced notice to PSE storeroom.
-PSE representatives will provide delivery of all miscellaneous material necessary for duct &
vault installation, such as couplings, glue, bends, etc., with minimum 3 days advanced
notice to the PSE storeroom.
-City shall provide equipment and labor necessary to off load material on site.
-All vaults will be delivered by the manufacture to the job site as follows:
--575 and smaller with a minimum 3 days advanced notice to PSE storeroom.
--5106 and larger with a minimum 5 days advanced notice to PSE storeroom.
-If vault excavation is not ready when vaults are delivered, city contractor will provide
necessary equipment to install vaults. Install mastic sealant between the sections of
mult-section vaults (sealant provided by manufacturer).
-All unused material shall be returned to PSE stores and reconciled after PSE duct & vault
installations are complete.
Inspection
-PSE will provide an Inspector during city contractor installation of PSE bare duct and vault
system.
-The roll of the PSE Inspector is limited to verification of compliance to all relevant PSE
standards and practices. The PSE Inspector will not approve changes to planned PSE
facility locations or change orders.
-The PSE Inspector will be the contact for all issues concerning installation of bare duct and
vault system for PSE and provide a liaison between the field and engineering for change
requests.
-The city shall provide the PSE Inspector the means (survey staking) to verify proper depth
of burial and location for all PSE facilities to the satisfaction of the PSE Inspector on site. If
the Inspector is unable to verify proper depth of burial, location, or grade of PSE facilities a
non-compliance document will be issued effecting PSE final acceptance of city installed
facilities for PSE.
Owner / Developer Contact Info
officeATTN:
FLORA LEE
CITY OF RENTON
FLEE@RENTONWA.GOV 425-430-7303PHONE
CABLE TV
11504976 101120019
583061726
108113555
PROJECT PHASE
PWR
NOTIF#ORDER#
Superior
UG Expense
Removal
OH Expense 593207689
594127951
OH Expense
E-Mail:
Cell Phone:
Project Manager Contact Information:
Manager:HONG NGUYEN
425-449-6609
HONG.NGUYEN@PSE.COM
THIS SKETCH NOT TO BE RELIED UPON FOR EXACT LOCATION OF EXISTING FACILITIES
CALL 811 TWO BUSINESS DAYS BEFORE YOU DIG
For contacts below dial 1-888-CALL PSE (225-5773)
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 1/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
JOB SITE
141..Fiber
MFP20001971
This permit is for Major construction work in the ROW and will be billed at an additional
$60/HR for inspections. After hours and weekend work will be billed at $125/HR
PRE14
PRE14
101120019SCALE: NONE
OVERHEAD CIRCUIT MAP (2305E040)
UNIVERSAL CIRCUIT MAP (2305E011, 38)
SCALE: NONE
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 2/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
UNIVERSAL CIRCUIT MAP (2305E011, 38)
SCALE: NONE
JOB SITE
JOB SITE
JOB SITE
MFP20001971
GROUND ROD
895+00896+00897+00898+00EXIST OH SL SVC318416
167323
318394
167322DUVALL AVE NE"809"
"818"
"824"
"815"
"821"
"830"
"836"
"842"
"848"
MATCHLINE - STA 895+00
PAGE 3
MATCHLINE - STA 898+50
PAGE 3
899+00900+00NE 9TH ST
J02
318434
167331
EXIST
EXIST UG
EXIST OH SL SVCSLAH3608
DUVALL AVE NER/WNEW 3-4"R/W"861"
FB1
318433
167331
NEW
MATCHLINE - STA 898+50
PAGE 3
BREAKLINE TO STA 916+50
PAGE 4
UTILITY EASEMENTNEW 2-4"
NEW 1-4"892+00893+00894+00895+00NE 8TH ST
NE 7TH PLDUVALL AVE NE"4704"
"800"
"806"
P01
318357
167324
EXIST
P02
318373
167324
REMOVE
15T
UNK
#2 ACSRABM906-B EXIST OH SVCJ01
318372
167324
NEW
HH1
NEW R/W#2 ACSR
NEW 3-4"
NEW 1-2"
INTERCEPT SPARES IF FOUND
NEW 1-3"
"803"
"CITY OF RENTON"
"809"
NEW 3-4"
"812"
R/W
PRE-14
IP01
NEW 1-4" FIBER
MATCHLINE - STA 895+00
PAGE 3
V02
318386
167308
EXIST
25kVA
120/240v
T83471
EXISTING OH TPX
NEW 2-4"
NEW 2-4"
SITE PLAN 101120019SCALE: 1" = 20'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 3/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Vault & Equipment Table
Site Working Space Grid
Number
Vault Size
& Cover
Type & Size
Equipment
In Vault
Primary Bushings Transformer
ID Numbers
(Company ID)
MATERIAL
INFORMATION
ASBUILT INFORMATION
Foreman-CompleteLBDC
J01 NEW 318372
167324
4'8"X7'X5'
w/ (2) 3' Sq Doors
Mat ID: 7663200
J-Box below grade
w/ 4-pos J-Bus
Mat ID: 7625900
5 7
JBOX15L
INSTALL 5-ELB10J
INSTALL 7 DC-7630600
J02 EXISTING 318434
167331 3 -INSTALL 3-ELB10J
FB1 NEW 318443
167331 SEE DETAIL (PAGE 6)
SITE SPECIFIC NOTES:
P01-EXISTING 318357-167324
INSTALL 12kV 1Ø TERM, LB (TSU1C1) [6043.1000]
INSTALL SWITCH #T83471 FUSE @ 25T (3412400)
INSTALL (3) 4" CONDUIT RISERS (RIS4CSS) 6042.1000
CAP (2) SPARE 4" CONDUIT RISERS 10' UP POLE
INSTALL (1) 3" CONDUIT RISER (RIS3CSS) 6042.1000
IP01
EXPOSE AND INTERCEPT EXISTING 1-4" CONDUIT AND EXTEND EAST TO J01
SECONDARY HH TABLE
Site Vault Size & Cover Type & Size
Equipment in Vault REMARKS
HH1
HH14350AS (1Ø)
With 2'-4" sq AS Cover
PER STD 6050.2020
(3) 4 Position Connector
MAT ID: 7651005
INSTALL 3-POS
CONNECTOR BARS
NOTE: Per Standard 6050.2000 all metal lids of secondary hand holes
must be grounded.
MFP20001971
917+00918+00919+00920+00"1155"
"1160"
P04
318612
167316
EXIST
P03
318612
167326
RELC
75kVA
120/240v#2 ACSRE
X
O
H
S
V
C
J03
318611
167326
NEW
NE 12TH ST
"1155"
J04
318628
167330
NEW
P05
318629
167330
REMV
25T
UNK
EXIST UG SVC
EXIST 115kV
HH2
NEW
J05
318633
167322
EXIST
318630
167312
42158-B
30469-C
R/WR/WR/WDUVALL AVE NENEW 1-3", 1-4"
EXIST OH SVC
NEW 2-4", 1-3"
318630
167300
NEW 2-4"
BREAKLINE TO STA 900+00
PAGE 3
MATCHLINE - STA 920+00
PAGE 4
NEW 1-2"
NEW 2-4", 2-6"
J06
EXIST
NEW 2-4"
NEW 1-3"
EX
O
H
S
V
C
NEW 1-3"
TRANSFER
318610
167332
5' X 15' EASEMENT
5' X 25' EASEMENT DWY920+00921+00"4621"DUVALL AVE NEEXIST
318630
167312
42155-A
42156-B
42157-C
"1332"
318644
167315
J07
REMV
318644
167314
J08
NEW
AAS310-A
AAS311-B
AAS312-C
30467-A
30468-B
30469-C R/WR/WV03
318650
167308
EXIST
500kVA
120/208v
MATCHLINE - STA 920+00
PAGE 4
NEW 2-4", 2-6"
J06
EXIST
30464-A
30465-B
30456-C
IP04
IP02
318650
167295
FEED
PRE
14J09
EXIST
5' X 15'
EASEMENT
IP03
SITE PLAN 101120019SCALE: 1" = 20'
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 4/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Vault & Equipment Table
Site Working Space Grid
Number
Vault Size
& Cover
Type & Size
Equipment
In Vault
Primary Bushings Transformer
ID Numbers
(Company ID)
MATERIAL
INFORMATION
ASBUILT INFORMATION
Foreman-CompleteLBDC
J03 NEW 318611
167326
4'8"X7'X5'8"
w/ (2) 3' Anti-Skid Doors
Mat ID: 9996162
J-Box below grade
w/ 4-pos J-Bus
Mat ID: 7625900
4 8
JBOX3AS
INSTALL 4-ELB10J
INSTALL 8 DC-7630600
J04 NEW 318628
167330
4'8"X7'X5'8"
w/ (2) 3' Anti-Skid Doors
Mat ID: 9996162
J-Box below grade
w/ 4-pos J-Bus
Mat ID: 7625900
6 6
JBOX3AS
INSTALL 6-ELB10J
INSTALL 6 DC-7630600
J08 NEW 318611
167326
4'8"X7'X5'8"
w/ (2) 3' Anti-Skid Doors
Mat ID: 9996162
J-Box below grade
w/ 4-pos J-Bus
Mat ID: 7625900
9 3
JBOX3AS
INSTALL 9-ELB10J
INSTALL 3 DC-7630600
V03 EXISTING 318650
167308 3 -
J09 EXISTING 318650
167285 3 -INSTALL 3-ELB10J
SITE SPECIFIC NOTES:
P03-NEW 318612-167326
INSTALL 45' CL3 DISTRIBUTION POLE (PD453) [6010.1000]
INSTALL 12kV 1Ø TERM, LB, ONE TRF (TSU1C1WT) 6043.1003
INSTALL NEW SWITCH #T83472 FUSE @ 40T (3412500)
INSTALL (2) 3" CONDUIT RISERS (RIS3CSS) [6042.1000]
INSTALL (1) 2" CONDUIT RISERS (RIS2CSS) [6042.1000]
TRANSFER 75kVA TRANSFORMER WITH FUSE AND CUTOUT FROM OLD POLE
INSTALL NEW GRID NUMBERS
TRANSFER OH SVC
P04-EXISTING SERVICE POLE TO REMAIN 318612-167316
INSTALL (1) 3" CONDUIT RISER (RIS3CSS) [6042.1000]
IP02
EXPOSE AND INTERCEPT EXISTING 1-4" CONDUIT AND EXTEND WEST TO J08
EXTEND ANY SPARE CONDUITS IF FOUND
IP03
EXPOSE AND INTERCEPT EXISTING 1-4" CONDUIT AND EXTEND EAST TO J08
IP04
EXPOSE AND INTERCEPT EXISTING 1-4" CONDUIT AND EXTEND NORTHWEST TO V03
POLE RETIREMENT TABLE TEMP TRANSFERS ST. LIGHT TRANSFERS
SITE
#
POLE DATA POLE
TEL TV FIBER TRAN RMVD ID NUMBER
GRID #HEIGHT CLASS YEAR TOPPED RMVD
P05 318629-167330
WIRE REMOVAL TABLE
Location
Wire Size & Type Quantity
Length
(per
conductor)RemarksFromTo
P03 P04 1/0 TRIPLEX 1 190'
P03 P05 #2 ACSR 3 175'
Total Feet (Wire Size & Type) Removed
CABLE REMOVAL SCHEDULE
CABLE
NO.
LOCATIONS CABLE
(LF) EST CABLE TYPE YEAR INST
FROM TO
BØ42158 P05 J05 135 1/0 AL JKT
AØ30467 J06 J07 115 1/0 AL JKT
BØ30467 J06 J07 115 1/0 AL JKT
CØ30467 J06 J07 115 1/0 AL JKT
Total Feet 20 (1/0 AL JKT) ACTUAL________Removed
SECONDARY HH TABLE
Site Vault Size & Cover Type & Size
Equipment in Vault REMARKS
HH2
HH14350AS (1Ø)
With 2'-4" sq AS Cover
PER STD 6050.2020
(3) 4 Position Connector
MATID: 7651005
NOTE: Per Standard 6050.2000 all metal lids of secondary hand holes
must be grounded.
Maintain minimum separation
of 5' from outside edge of
16" water Main and the
power conduits.
MFP20001971
P01
EXIST
H
J
HH1
NEW
J01
NEW
IP01
H
J
J
JJ IP02
J
NEW 1-3"
V02
EXIST
J02
EXIST
FB1
NEW
P04
EXIST
BREAKLINE
J
STA 916+50
J03
NEW
J08
NEW
J06
EXIST
J05
EXIST
HH2
NEW
J04
NEW
P03
RELC
NE 12TH ST
NE 9TH ST
EXIST 1-2"
NEW 2-4"
NEW 2-4"
NEW 2-6"
EXIST 1-4"
NEW 1-3"
NEW 1-4 FIBER"
NE 8TH ST
NEW 1-2"
NEW 2-4"
NEW 1-4"
NEW 1-2"
NEW 2-4"
NEW 2-4"
SPARE 1-4"
FB
J
J09
EXIST
EXIST 1-4"
IP03
NEW 1-4"
V03
EXIST
IP04
EXIST 1-4"
NEW 1-3"
P01
EXIST
H
J
HH1
NEW
J01
NEW
J
J
JJ
J
V02
EXIST
J02
EXIST
BREAKLINE
STA 916+50
J06
EXIST
J05
EXIST
J04
NEW
NE 12TH ST
NE 9TH ST
350 TPX
NEW 350 TPLX
EIJ529-B
NE 8TH ST
EIJ530-B
EIJ535-A
EIJ536-B
EIJ537-C
EIJ534-B
EIJ541-A
EIJ542-B
EIJ543-C
EIJ538-A
EIJ539-B
EIJ540-C
EIJ531-A
EIJ532-B
EIJ533-C
J
J09
EXIST
V03
EXIST
J08
NEWEIJ544-A
EIJ545-B
EIJ546-C
EIJ547-A
EIJ548-B
EIJ549-C
1/Ø AL JKT
H
J
J03
NEW
HH2
NEW
P03
RELC
NEW 1-3"
P04
EXIST
CONDUIT DIAGRAM 101120019SCALE: NONE
UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 5/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Primary Cable & Conduit Table (Foreman to Complete)
LOCATION CONDUIT PRIMARY CABLE QTY OF LUBE
(gal.)AS BUILT INFORMATION
From To Size
(in)
Qty
Design
Length
(ft)
Actual
Length
(ft)
TYPE BENDS PULL
(lbs)
PULL
Rev
(lbs)
Cable
Size
Design
Length
(ft)
Actual
Length
(ft)
CABLE NUMBERS MANUFACTURING INFORMATION FOR FEEDER CABLE ONLY
Check applicable box
DB120 HDPE SCH 80 90°45°22°11°A B C Manufacturer Compound Year Tape CN #4/0 NEU Design As Built Actual Amount Installed
(Conduit & Cable)
P01 J01 4 2 180 X 1 2 1/0 AL JKT 185 EIJ529
P01 FB1 4 1 765
J01 V02 2 1 295 X 2 1/0 AL JKT 300 EIJ530
J01 J02 4 2 605 X 2 2 1 1/0 AL JKT 610 EIJ531 EIJ532 EIJ533
P03 J03 2 1 5 X 1 1/0 AL JKT 15 EIJ534
J03 P04 4 1 85 CONDUIT ONLY
J03 J04 4 2 170 X 4 1/0 AL JKT 175 EIJ535 EIJ536 EIJ537
J04 J05 4 2 140 X 1 2 1/0 AL JKT 145 EIJ538 EIJ539 EIJ540
J05 J06 4 2 120 X 1 CONDUIT ONLY
J05 J06 6 2 120 X 1 CONDUIT ONLY
J06 J08 4 1 125 X 1/0 AL JKT 130 EIJ541 EIJ542 EIJ543
J08 J09 4 1 215 X 1/0 AL JKT 130 EIJ544 EIJ545 EIJ546
J08 V03 4 1 105 X 1 1/0 AL JKT 130 EIJ547 EIJ548 EIJ549
Secondary Cable & Conduit Table
LOCATION CABLE Assumed
Lot Corner
CONDUIT VOLTAGE
DROP
VOLTAGE
FLICKER ASBUILT INFORMATION
SIZE LENGTH
Design
(ft)
SIZE LENGTH
Design
(ft)
BENDS
Foreman - Complete
FROM TO (1/0,4/0,350)to Meter(ft)(in)90°45°22°11°(Percent)(Percent)Actual Amount Installed (Conduit & Cable)
P01 HH1 1/0 40 3 10 1 1
P03 HH2 350 230 3 200 5 4
P03 P04 1/0 120 3 90 1 2
CABLE ONE-LINE DIAGRAM
SCALE: NONE
MFP20001971
101120019UTILITIES
CONTACT
PHONE#
COUNTY
1/4 SEC
U-MAP NO (POWER)
OP MAP
Emer Sect Gas Wk Ctr POWER WK CTR
PLAT MAP
JOINT FACILITIES ARRANGEMENTS
DRAWN BY
CHECKED BY
APPROVED BY
FOREMAN #1
FOREMAN #2
MAPPING
INCIDENT MAOP
Gas Order Elect Order
SCALE PAGE
ENGR - POWER
ENGR - GAS
FUNCTION
PROJECT MGR
PERMITREAL ESTATE/EASEMENT
2
1
REV#
3
DATE DESCRIPTIONBY
CONTACT PHONE NO DATE
OH CKT MAP CIRCUIT NOUG CKT MAP
HONG NGUYEN 425-449-6609 9/13/19
KEANG LIM 253-395-6916 9/13/19
N/A N/A N/A
KEANG LIM 253-395-6916 9/13/19
REQUIRED CITY OF RENTON
RENTON DUVALL AVE NE SCH74
OH TO UG CONVERSION
1100 DUVALL AVE NE RENTON, WA 98059
N/A N/A
N/A 101120019
AS NOTED 6/6
KING N/A N/A CSPSKEPI
S10 T23 R05E N/A N/A
2305E011, 37 2305E040 N/A PRE-14
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2" to 3"
Excavation - 24 cubic yards
SIDE VIEW
6'-4"
to 6'-5"Crushed
6"
Rock
TOP VIEW
9'
11'
7'-0"
4'-0"
8"
4'-8"
Final Grade
(Pavement)
1'-0"
Tubes for 1"
Adjustable Cover
Section
1835 lbs
4760 lbs
(2) 3' Square
Anti-Skid
5'-8"
Adjustable Bolts (4)
Doors
2490 lbs
Top
Handhole
NOTE:
The Top Cover shall be leveled and adjusted to Final Grade
using the Adjustable Bolts. This Installation is for Pavement or
Sidewalks only.
Adjustable Cover
(See NOTE Below)
575 J-BOX & PULL VAULT EXCAVATION DETAIL - J01,J03, J04, J08
SCALE: NONE MID# 9996162
FIBER VAULT DETAIL - FB1
SCALE: NONE CLINK PID# 2378448
COVER WITH
ADJUSTABLE FRAME
No. 38/25-TA
No. 25-TVAULT
A A
PLAN VIEW
SECTION AA END VIEW
SINGLE PHASE SECONDARY CONCRETE HANDHOLE - HH1,HH2
Not to scale 6050.2020-1
TOP VIEW
SIDE VIEW
2'-4"
EXCAVATION: 5-1/3 CUBIC YARDS
7'-0"
6'-0"
6" Crushed rock
2"
2'-6"
Install PVC bell endsand grout into wall
2'-6"
Handhole
820 lbs
Conduits and conductors shall enter from
ends of handhole through knockouts provided
Typical customer runservice conductors in duct
Steel Door
Seal conduitwith foam
Customer-installed grounding wires ( the "4th" wire on the single-phase systems and the "5th" wire on
the three-phase systems)
shall no t be connected to PSE's ground or neutral bus. They shall be
removed by customer or cut off at the vault wall.
Excavated Dirt Pile
Final Grade
24" Min
Backfill for Schedule 40 Conduit
(NO Rocks over 10" Diameter
or foreign objects)Separation
12" Min
18" Min
TYP TRENCH DETAIL
Primary-Schedule 80 (NTS)
48"
Max
36"
Min
Cover
Phone & TV Primary Power Cable
in Customer Provided
Schedule 40 Conduit
ROADSIDE
To Excavated Dirt Pile
MFP20001971