HomeMy WebLinkAboutzR-3955 SetU7 z O 75 O 0 z O I- z w rr a z J LL SURFACE WATER STANDARD PLAN NOTES 1. THESE NOTES SHALL APPEAR ON PROJECTS FOR THE SURFACE WATER UTILITY. 2. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRE -CONSTRUCTION MEETING MUST BE HELD BETWEEN THE CITY OF RENTON PLAN REVIEW SECTION AND THE APPLICANT. 3. ALL DESIGN AND CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE RENTON MUNICIPAL CODE (RMC), THE LATEST EDITION OF THE STANDARD SPECIFICATIONS FOR ROAD, BRIDGE AND MUNICIPAL CONSTRUCTION PREPARED BY WSDOT AND THE AMERICAN PUBLIC WORKS ASSOCIATION (APWA), AS AMENDED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. IT SHALL BE THE SOLE RESPONSIBILITY OF THE APPLICANT AND THE PROFESSIONAL CIVIL ENGINEER TO CORRECT ANY ERROR, OMISSION OR VARIATION FROM THE ABOVE REQUIREMENTS FOUND IN THIS PLANS. ALL CORRECTIONS SHALL BE AT NO ADDITIONAL COST TO THE CITY. 4. APPROVAL OF THIS ROAD, GRADING, PARKING AND DRAINAGE PLAN DOES NOT CONSTITUTE AN APPROVAL OF ANY OTHER CONSTRUCTION (E.G. DOMESTIC WATER CONVEYANCE, SEWER CONVEYANCE, GAS, ELECTRICAL. ETC.)THE SURFACE WATER DRAINAGE SYSTEM SHALL BE CONSTRUCTED ACCORDING TO THE APPROVED PLANS, WHICH ARE ON FILE IN WITH THE CITY. ANY DEVIATION FROM THE APPROVED PLANS WILL REQUIRE WRITTEN APPROVAL FROM THE CITY OF RENTON PUBLIC WORKS DEPARTMENT, SURFACE WATER UTILITY SECTION. 5. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 6. GRADING ACTIVITIES (SITE ALTERATION) ARE LIMITED TO THE HOURS OF 7 AM. TO 7 P.M. MONDAY THROUGH SATURDAY AND NO WORK ON SUNDAY IS ALLOWED, UNLESS OTHERWISE APPROVED WITH A WRITTEN DECISION BY THE CITY OF RENTON. 7. IT SHALL BE THE APPLICANT'S/CONTRACTOR'S RESPONSIBILITY TO OBTAIN ALL CONSTRUCTION EASEMENTS NECESSARY BEFORE INITIATING OFF -SITE WORK. EASEMENTS REQUIRE CITY REVIEW AND APPROVAL PRIOR TO CONSTRUCTION. 8. FRANCHISED UTILITIES OR OTHER INSTALLATIONS THAT ARE NOT SHOWN ON THESE APPROVED PLANS SHALL NOT BE CONSTRUCTED UNLESS AN APPROVED SET OF PLANS THAT MEET ALL REQUIREMENTS OF CHAPTER 4 OF THE SURFACE WATER DESIGN MANUAL ARE SUBMITTED TO THE CITY OF RENTON. 9. DATUM SHALL BE NAVD 88 UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS. 10. ANY DEWATERING SYSTEM NECESSARY FOR THE CONSTRUCTION OF STORMWATER FACILITIES MUST BE SUBMITTED TO THE CITY FOR REVIEW AND APPROVAL. 11. ALL UTILITY TRENCHES AND ROADWAY SUBGRADE SHALL BE BACKFILLED AND COMPACTED TO 95 PERCENT DENSITY, STANDARD PROCTOR. 12. OPEN CUTTING OF EXISTING ROADWAYS FOR NON -FRANCHISED UTILITY OR STORM DRAINAGE WORK IS NOT ALLOWED UNLESS SPECIFICALLY APPROVED BY THE CITY OF RENTON AND NOTED ON THESE APPROVED PLANS. ANY OPEN CUT SHALL BE RESTORED IN ACCORDANCE WITH THE CITY OF RENTON TRENCH RESTORATION STANDARDS. 13. ALL SEDIMENTATION/EROSION FACILITIES MUST BE IN OPERATION PRIOR TO CLEARING AND BUILDING CONSTRUCTION, AND THEY MUST BE SATISFACTORILY MAINTAINED UNTIL CONSTRUCTION IS COMPLETED AND THE POTENTIAL FOR ON -SITE EROSION HAS PASSED. 14. ALL RETENTION/DETENTION FACILITIES MUST BE INSTALLED AND IN OPERATION PRIOR TO OR IN CONJUNCTION WITH ALL CONSTRUCTION ACTIVITY UNLESS OTHERWISE APPROVED BY THE PUBLIC WORKS DEPARTMENT, SURFACE WATER UTILITY SECTION. 15. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. ALL PIPE BEDDING SHALL BE APWA CLASS "C", WITH THE EXCEPTION OF PVC PIPE. 16. STEEL PIPE SHALL BE ALUMINIZED, OR GALVANIZED WITH ASPHALT TREATMENT #1 OR BETTER INSIDE AND OUTSIDE. 17. ALL DRAINAGE STRUCTURES, SUCH AS CATCH BASINS AND MANHOLES SHALL HAVE SOLID LOCKING LIDS. ALL DRAINAGE STRUCTURES ASSOCIATED WITH A PERMANENT RETENTION/DETENTION FACILITY SHALL HAVE SOLID LOCKING LIDS. 18. BUILDING AND OTHER STRUCTURES SHALL BE PLACED IN ACCORDANCE WITH TABLE 4.1 EASEMENT WIDTHS AND BUILDING SETBACKS LINES. 19. ALL CATCH BASIN GRATES SHALL BE DEPRESSED 0.10 FEET BELOW PAVEMENT LEVEL. 20. ALL DRIVEWAY CULVERTS LOCATED WITHIN CITY OF RENTON RIGHT-OF-WAY SHALL BE OF SUFFICIENT LENGTH TO PROVIDE A MINIMUM 3:1 SLOPE FROM THE EDGE OF THE DRIVEWAY TO THE BOTTOM OF THE DITCH. ROCK FOR EROSION PROTECTION OF ROADSIDE DITCHES, WHERE REQUIRED, SHALL BE OF SOUND QUARRY ROCK PLACED TO A DEPTH OF ONE (1) FOOT AND MUST MEET THE FOLLOWING SPECIFICATIONS: 4 -8 INCH ROCK / 40 -70% PASSING; 2 -4 INCH ROCK! 30 -40% PASSING; AND LESS THAN 2 INCH ROCK / 10 -20% PASSING. 21. ALL BUILDING DOWNSPOUTS AND FOOTING DRAINS SHALL BE CONNECTED TO THE STORM DRAINAGE SYSTEM, UNLESS APPROVED BY THE CITY PLAN REVIEWER OR SURFACE WATER UTILITY SECTION. AN ACCURATELY DIMENSIONED, CERTIFIED AS -BUILT DRAWING OF THIS DRAINAGE SYSTEM WILL BE SUBMITTED TO THE CITY UPON COMPLETION. 22. DRAINAGE OUTLETS (STUB -OUTS) SHALL BE PROVIDED FOR EACH INDIVIDUAL LOT, EXCEPT FOR THOSE LOTS APPROVED FOR INFILTRATION BY THE CITY. STUB -OUTS SHALL CONFORM TO THE FOLLOWING: a. EACH OUTLET SHALL BE SUITABLY LOCATED AT THE LOWEST ELEVATION ON THE LOT, SO AS TO SERVICE ALL FUTURE ROOF DOWNSPOUTS AND FOOTING DRAINS, DRIVEWAYS, YARD DRAINS, AND ANY OTHER SURFACE OR SUBSURFACE DRAINS NECESSARY TO RENDER THE LOTS SUITABLE FOR THEIR INTENDED USE. EACH OUTLET SHALL HAVE FREE -FLOWING, POSITIVE DRAINAGE TO AN APPROVED STORMWATER CONVEYANCE SYSTEM OR TO AN APPROVED OUTFALL LOCATION. b. OUTLETS ON EACH LOT SHALL BE LOCATED WITH AFIVE-FOOT-HIGH, 2" X 4" STAKE MARKED "STORM" OR "DRAIN". THE STUB -OUT SHALL EXTEND ABOVE SURFACE LEVEL, BE VISIBLE, AND BE SECURED TO THE STAKE. c. PIPE MATERIAL SHALL CONFORM TO UNDERDRAIN SPECIFICATIONS DESCRIBED IN CHAPTER 4 OF THE SURFACE WATER DESIGN MANUAL AND, IF NON-METALLIC, THE PIPE SHALL BE PLACED IN A TRENCH WITH A TRACING WIRE ABOVE OR OTHER ACCEPTABLE DETECTION. d. PRIVATE DRAINAGE EASEMENTS ARE REQUIRED FOR DRAINAGE SYSTEMS DESIGNED TO CONVEY FLOWS THROUGH INDIVIDUAL LOTS. e. THE APPLICANT/CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE LOCATIONS OF ALL STUB -OUT CONVEYANCE LINES WITH RESPECT TO OTHER UTILITIES (E.G. POWER, GAS, TELEPHONE, TELEVISION). f. ALL INDIVIDUAL STUB -OUTS SHALL BE PRIVATELY OWNED AND MAINTAINED BY THE LOT HOME OWNER. g. STORM DRAINAGE PIPE SYSTEMS SHALL NOT PENETRATE BUILDING FOUNDATIONS, EXCEPT FOR SUMP PUMP DISCHARGE LINES USED TO DRAIN CRAWL SPACES, PROVIDED THE SUMP PUMP SYSTEM INCLUDES BACKFLOW PREVENTION OR A CHECK VALVE. 23. ALL DISTURBED PERVIOUS AREAS (COMPACTED, GRADED, LANDSCAPED, ETC.) OF THE DEVELOPMENT SITE MUST DEMONSTRATE ONE OF THE FOLLOWING: THE EXISTING DUFF LAYER SHALL BE STAGED AND REDISTRIBUTED TO MAINTAIN THE MOISTURE CAPACITY OF THE SOIL, OR; AMENDED SOIL SHALL BE ADDED TO MAINTAIN THE MOISTURE CAPACITY. 24. PROOF OF LIABILITY INSURANCE SHALL BE SUBMITTED TO THE CITY PRIOR TO CONSTRUCTION PERMIT ISSUANCE. 25. ISSUANCE OF THE BUILDING OR CONSTRUCTION PERMITS BY THE CITY OF RENTON DOES NOT RELIEVE THE OWNER OF THE CONTINUING LEGAL OBLIGATION AND/OR LIABILITY CONNECTED WITH STORM SURFACE WATER DISPOSITION. FURTHER, THE CITY OF RENTON DOES NOT ACCEPT ANY OBLIGATION FOR THE PROPER FUNCTIONING AND MAINTENANCE OF THE SYSTEM PROVIDED DURING CONSTRUCTION. 26. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADEQUATE SAFEGUARD, SAFETY DEVICES, PROTECTIVE EQUIPMENT, FLAGGERS, AND ANY OTHER NEEDED ACTIONS TO PROTECT THE LIFE, HEALTH, AND SAFETY OF THE PUBLIC, AND TO PROTECT PROPERTY IN CONNECTION WITH THE PERFORMANCE OF WORK. ANY WORK WITHIN THE TRAVELED RIGHT-OF-WAY THAT MAY INTERRUPT NORMAL TRAFFIC FLOW SHALL REQUIRE A TRAFFIC CONTROL PLAN APPROVE BY THE PUBLIC WORKS DEPARTMENT, TRANSPORTATION SYSTEMS DIVISION. ALL SECTIONS OF THE WSDOT STANDARD SPECIFICATIONS 1-07-23 TRAFFIC CONTROL SHALL APPLY. 27. PROJECT LOCATED WITHIN THE AQUIFER PROTECTION AREA (APA) SHALL COMPLY WITH SPECIAL REQUIREMENT #6 OF THE SURFACE WATER DESIGN MANUAL AND AQUIFER PROTECTION REGULATIONS (RMC 4-3-050). Al design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION :4Oei�col 11LKOL011LIm001m1Lcol I*:? 1. THESE NOTES SHALL APPEAR FOR ALL PROJECTS -SITE IMPROVEMENTS, SURFACE WATER UTILITY, WASTEWATER UTILITY, WATER UTILITY, AND TRANSPORTATION PLANS: 2. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRE -CONSTRUCTION MEETING MUST BE HELD WITH THE CITY OF RENTON, PUBLIC WORKS DESIGN ENGINEER. 3. THE BOUNDARIES OF THE CLEARING LIMITS AND AREAS OF VEGETATION PRESERVATION AS PRESCRIBED ON THE PLAN(S) SHALL BE CLEARLY FLAGGED BY SURVEY TAPE AR FENCING IN THE FIELD PRIOR TO CONSTRUCTION IN ACCORDANCE WITH APPENDIX D OF THE SURFACE WATER DESIGN MANUAL AND OBSERVED DURING CONSTRUCTION. DURING THE CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE CLEARING LIMITS SHALL BE PERMITTED. THE CLEARING LIMITS SHALL BE MAINTAINED BY THE APPLICANT/BC SUPERVISOR FOR THE DURATION OF CONSTRUCTION. 4. STABILIZED CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE PROJECT. ADDITIONAL MEASURES, SUCH AS CONSTRUCTED WHEEL WASH SYSTEMS OR WASH PADS, MAY BE REQUIRED TO ENSURE THAT ALL PAVED AREAS ARE KEPT CLEAN AND TRACK OUT TO ROAD RIGHT OF WAY DOES NOT OCCUR FOR THE DURATION OF THE PROJECT. 5. ALL REQUIRED SEDIMENTATION/EROSION CONTROL FACILITIES MUST BE CONSTRUCTED AND IN OPERATION PRIOR TO LAND CLEARING AND/OR CONSTRUCTION TO PREVENT TRANSPORTATION OF SEDIMENT TO SURFACE WATER, DRAINAGE SYSTEMS AND ADJACENT PROPERTIES. ALL EROSION AND SEDIMENT FACILITIES SHALL BE MAINTAINED IN A SATISFACTORY CONDITION UNTIL SUCH TIME THAT CLEARING AND/OR CONSTRUCTION IS COMPLETE AND POTENTIAL FOR ON -SITE EROSION HAS PASSED. THE IMPLEMENTATION, MAINTENANCE, REPLACEMENT AND ADDITIONS TO EROSION/SEDIMENTATION CONTROL SYSTEMS SHALL BE THE RESPONSIBILITY OF THE PERMITEE. 6. THE EROSION AND SEDIMENTATION CONTROL SYSTEMS DEPICTED ON THIS DRAWING ARE INTENDED TO BE MINIMUM REQUIREMENTS TO MEET ANTICIPATED SITE CONDITIONS. AS CONSTRUCTION PROGRESSES AND UNEXPECTED OR SEASONAL CONDITIONS DICTATE, THE PERMITEE SHALL ANTICIPATE THAT MORE EROSION AND SEDIMENTATION CONTROL FACILITIES WILL BE NECESSARY TO ENSURE COMPLETE SILTATION CONTROL ON THE PROPOSED SITE. DURING THE COURSE OF CONSTRUCTION, IT SHALL BE THE OBLIGATION AND RESPONSIBILITY OF THE PERMITEE TO ADDRESS ANY NEW CONDITIONS THAT MAY BE CREATED BY THE ACTIVITIES AND TO PROVIDE ADDITIONAL FACILITIES, OVER AND ABOVE MINIMUM REQUIREMENTSI AS MAY BE NEEDED, TO PROTECT ADJACENT PROPERTIES AND WATER QUALITY OF THE RECEIVING DRAINAGE SYSTEM. 7. APPROVAL OF THIS PLAN IS FOR EROSION/SEDIMENTATION CONTROL ONLY. IT DOES NOT CONSTITUTE AN APPROVAL OF STORM DRAINAGE DESIGN, SIZE NOR LOCATION OF PIPES, RESTRICTORS, CHANNELS, OR RETENTION FACILITIES. 8. ANY AREAS OF EXPOSED SOILS, INCLUDING ROADWAY EMBANKMENTS, THAT WILL NOT BE DISTURBED FOR TWO DAYS DURING THE WET SEASON (OCTOBER 1sT TROUGH MARCH 3oTH) OR SEVEN DAYS DURING THE DRY SEASON (APRIL 1 N TOUGH SEPTEMBER 30) SHALL BE IMMEDIATELY STABILIZED WITH THE APPROVED ESC COVER METHODS (E.G., SEEDING, MULCHING, PLASTIC COVERING, ETC.). 9. WET SEASON SEASONAL EROSION AND SEDIMENT CONTROL REQUIREMENTS APPLY TO ALL CONSTRUCTION SITES CLEARING BETWEEN OCTOBER 1 AND MARCH 30 INCLUSIVE, UNLESS OTHERWISE APPROVED BY THE CITY THROUGH AN ADJUSTMENT PROCESS. 10. COVER MEASURES WILL BE APPLIED IN CONFORMANCE WITH APPENDIX D OF THE SURFACE WATER DESIGN MANUAL. PROJECT AREA S 2ND ST co co w Q Z W co co z a > J m Y U 0 a 0) S 3RD ST � 0 N ----- S -3RD PL --------------- S 4TH ST VICINITY MAP NTS T U T Q J CONTACT 11. ANY AREA NEEDING ESC MEASURES, NOT REQUIRING IMMEDIATE ATTENTION, SHALL BE ADDRESSED WITHIN SEVEN (7) DAYS. CIVIL ENGINEER: MARC ERRICHETTI, PE 12. THE ESC FACILITIES ON INACTIVE SITES SHALL BE INSPECTED AND MAINTAINED A MINIMUM OF ONCE A MONTH OR WITHIN 24 HOURS FOLLOWING A STORM (206) 402-4644 � coEVENT. SITEWISE DESIGN PLLC C) C) 13. AT NO TIME SHALL MORE THAN ONE (1) FOOT OF SEDIMENT BE ALLOWED TO ACCUMULATE WITHIN A CATCH BASIN. ALL CATCH BASINS AND CONVEYANCE LINES 219 FIRST AVE S, SUITE 401 p SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING OPERATION SHALL NOT FLUSH SEDIMENT -LADEN WATER INTO THE DOWNSTREAM SYSTEM. SEATTLE, WA 14. DURING THE TIME PERIOD OF OCTOBER L- THROUGH MARCH 3oTH ALL PROJECT DISTRIBUTED SOIL AREAS GREATER, THAT ARE TO BE LEFT UN -WORKED FOR ARCHITECT: PAM DERRY, AIA T MORE THAN 12 HOURS, SHALL BE COVERED BY MULCH, SODDING OR PLASTIC COVERING. (206) 624-7880 15. ANY PERMANENT RETENTION/DETENTION FACILITY USED AS A TEMPORARY SETTLING BASIN SHALL BE MODIFIED WITH THE NECESSARY EROSION CONTROL TONKIN ARCHITECTURE MEASURES AND SHALL PROVIDE ADEQUATE STORAGE CAPACITY. IF THE PERMANENT FACILITY IS TO FUNCTION ULTIMATELY AS AN INFILTRATION SYSTEM, THE 204 FIRST AVE S TEMPORARY FACILITY MUST BE ROUGH GRADED SO THAT THE BOTTOM AND SIDES ARE AT LEAST THREE FEET ABOVE THE FINAL GRADE OF THE PERMANENT FACILITY. SEATTLE, WA 98104 16. PRIOR TO THE BEGINNING OF THE WET SEASON (OCT. 1), ALL DISTURBED AREAS SHALL BE REVIEWED TO IDENTIFY WHICH ONES CAN BE SEEDED IN PREPARATION FOR THE WINTER RAINS. DISTURBED AREAS SHALL BE SEEDED WITHIN ONE WEEK OF THE BEGINNING OF THE WET SEASON. A SKETCH MAP OF LANDSCAPE ARCHITECT: ROB FAZIO, PLA THOSE AREAS TO BE SEEDED AND THOSE AREAS TO REMAIN UNCOVERED SHALL BE SUBMITTED TO THE CITY OF RENTON FOR REVIEW. (206) 774-9490 FAZIO ASSOCIATES INC. 17. ALL ESC MEASURES MUST BE REMOVED AFTER CONSTRUCTION ACTIVITY IS COMPLETE. LANDSCAPE ARCHITECTURE 2244 NW MARKET ST, SUITE B SEATTLE, WA 98107 ERC MITIGATION MEASURE 1. A SURVEY SHALL BE SUBMITTED TO THE CURRENT PLANNING PROJECT MANAGER THAT CONFORMS TO THE REQUIREMENTS AND STANDARDS IF THE WASHINGTON STATE OFFICE OF ARCHAEOLOGY AND HISTORIC SHEET INDEX PRESERVATION AND MUST BE CONDUCTED UNDER THE ONSITE SUPERVISION OF A STATE APPROVED C1.0-C1.1 COVER AND NOTES ARCHAEOLOGIST PRIOR TO CONSTRUCTION PERMIT APPROVAL. C2.0 SITE DEMO AND TESC PLAN C3.0 SITE DRAINAGE AND UTILITY PLAN C4.0 SITE GRADING AND PAVING PLAN C5.0-05.1 ROW UTILITY PLAN AND PROFILE C6.0 ROW FRONTAGE IMPROVEMENT AND RESTORATION PLAN ABBREVIATIONS C7.0-C7.1 CIVIL DETAILS C7.2-C7.6 COR STD DETAILS ACP ASPHALT CONCRETE PAVEMENT LA LANDSCAPE APPROX APPROXIMATE LF LINEAL FEET ARCH ARCHITECTURAL MECH MECHANICAL ATB ASPHALT TREATED BASE MJ MECHINICAL JOINT CB CATCH BASIN N NORTH CEM PORTLAND CEMENT OC ON CENTER CL CLASS OD OUTSIDE DIAMETER CONIC CONCRETE POC POINT OF CONNECTION COS CITY OF SEATTLE PROP PROPOSED COR CITY OF RENTON PVMT PAVEMENT COORD COORDINATE REF REFERENCE CSTC CRUSHED SURFACING TOP COURSE REM REMOVE DEMO DEMOLITION REQ REQUIRED DIA DIAMETER S SOUTH E EAST SCH SCHEDULE ELEC ELECTRICAL SD STORM DRAIN ELEV ELEVATION SDOT SEATTLE DEPARTMENT OF TRANSPORTATION EX, EXIST EXISTING SPKLR FIRE SPRINKLER FDC FIRE DEPARTMENT CONNECTION SPU SEATTLE PUBLIC UTILITIES FF FINISH FLOORSQUARE R-395501 U) FIG FINISHED GRADE SSQ SANITARY SEWER FL FLANGE STRUCT STRUCTURAL IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 GA GAUGE TYP TYPICAL _ GV GATE VALVE LINO UNLESS NOTED OTHERWISE m HMA HOT MIX ASPHALT W WEST U) IE INVERT ELEVATION W/ WITH z z L LENGTH WA WATER CALL 48 HOURS 73 BEFORE YOU DIG! 2 811 0 8 18 2017 SURVEYED_ SCALE: 1"= 10' VERTICAL. NAVD 1988 HORIZONTAL-NAD 1983/1991 ` --� CITY OF R E N TO N COMMONS L LC RENTON 215 WHITWORTH AVE S, RENTON, WA 98057 DATE: 1 1 / 15 /2017 z O 0829 2017 DESIGNED: nG FIELDBOOK: 11 15 2017 RENTON PAGE: DRAWN: TTG ONE INCH DATUM 0 z DRAWING NO: CHECKED: WE AT FULL SCALE IF Na ONE INCH Planning/Building/Public Works Dept. COVER AND NOTES C1.0 w BY DATE APPR SCALE ACCORDINGLY APPROVED: SHEET: OF: 1 15 z O 2 75 O U z O I- z w rr a z J LL WATER GENERAL NOTES 1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION. 2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT AT (425) 430-7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY. 3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48-HOUR LOCATORS 800-424-5555. 4. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE -CONSTRUCTION MEETING. 5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN VERTICAL DATUM 1988 METERS, AND FOR HORIZONTAL CONTROL SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE NOTED ON THE PLANS. 6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA C105/A21.5-93 STANDARDS. 7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA C110/A21.10-87. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/421/4-90. IF FITTINGS ARE 3 TO 12 INCHES IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI/AWWA C110-A21.10-87 OR ANSI/AWWA C153/A21.53-94. THREE (3) INCH TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS, SHALL BE IN ACCORDANCE WITH ANSI/AWWA C110/A21.10.87 OR A COMBINATION OF ANSI/AWWA C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINT(S) MAY BE WITH ANSI/AWWA C153/A21.53 94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN ACCORDANCE WITH AWWA C110/A21.10 87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA SECTION 10-4.3 OF ANSI/AWWA C110/A21.10-87 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER. 8. GATE VALVES SHALL BE IRON BODY, BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND 0-RING STUFFING BOX (AWWA C500) OR OF RESILIENT SEATED TYPE (AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H. 9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE) CONFORMING TO AWWA C-502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2-1/2 INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER 4.6263. HYDRANTS SHALL HAVE A 1-1/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT). 10. THE TWO 2-1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER TEST PRESSURES. 11. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH STORT STORZ ADAPTER SHALL BE FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND TWO SET SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO HYDRANT ADAPTER WITH 1 /8 INCH, COATED, STAINLESS STEEL, AIRCRAFT CABLE. 12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43- 655 SAFETY YELLOW OR APPROVED EQUAL. 13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY. 14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION. 15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE LOWERED TO CLEAR. 16. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING 'PIGS" PRIOR TO DISINFECTION. THE 'POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER COATING ON THE REAR OF `PIG" ONLY. 17. 'PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION. 18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS & SPECIFICATIONS 7-11.3(11). THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD. 19. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED/INJECTED IN ACCORDANCE WITH SECTION 7- 11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED ABOVE. 20. A PRE -CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING. 21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. 22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. 23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON. 24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION AND MATERIALS ARE TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS. 25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS. 26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN. 27. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT. 28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT. 29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH. * 30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS. Al design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 HEARING EXAMINERS CONDITIONS OF APPROVAL SANITARY SEWER NOTES AND SPECIFICATIONS � Ln 1. THE APPLICANT SHALL COMPLY WITH THE MITIGATION MEASURE ISSUED AS PART OF THE DETERMINATION OF NON -SIGNIFICANCE MITIGATED, DATED 1. ALL WORK AND WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON r JULY 25, 2016. PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND O MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL O 2. THE APPLICANT SHALL OBTAIN A PERMANENT RIGHT-OF-WAY USE PERMIT IN ORDER TO ENCROACH INTO RIGHT-OF-WAY BY NO MORE THAN TWO TIMES DURING CONSTRUCTION. -FEET FOR THE CENTRAL BAY. THE RIGHT-OF-WAY USE PERMIT SHALL BE OBTAINED PRIOR TO CONSTRUCTION/BUILDING PERMIT APPROVAL. 2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE PER CITY SPECIFICATIONS ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY r U THE PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT. AN APPROVED TRAFFIC CONTROL PLAN MUST BE OBTAINED PRIOR TO BEGINNING ANY WORK 3. THE APPLICANT SHALL DEMONSTRATE COMPLIANCE WITH THE PART 77 HORIZONTAL SURFACE HEIGHT LIMIT PRIOR TO CONSTRUCTION/BUILDING PERMIT WITHIN PUBLIC RIGHT OF WAY. APPROVAL. 3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 4. THE APPLICANT SHALL BE REQUIRED TO SUBMIT A REVISED LANDSCAPE PLAN TO THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. THE REVISED LANDSCAPE PLAN SHALL INCLUDE THE FOLLOWING: COMPLIANCE WITH THE DRAFT DOWNTOWN STREETSCAPE DESIGN 4. A PRE -CONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE STANDARDS AND GUIDELINES (DSDSG) (DATED MARCH 16, 2016) OR AS MAY BE AMENDED OR APPROVED PRIOR TO PLANS BEING SUBMITTED FOR CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. INSPECTION WILL BE ACCOMPLISHED BY A BUILDING PERMITS; SPECIFIC DETAIL FOR COURTYARD SCREENING AND FURNITURE; THE ADDITION OF ONE LITTER RECEPTACLE TO THE FRONTAGE REPRESENTATIVE OF THE CITY OF RENTON.) IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE PUBLIC WORKS INSPECTOR 24 HOURS IN IMPROVEMENTS LOCATED AS CLOSE TO PRIMARY BUILDING ENTRANCE AS POSSIBLE; AND LANDSCAPE PLANTERS TO DENOTE PEDESTRIAN ENTRY ADVANCE OF BACKFILLING ALL CONSTRUCTION. POINTS. 5. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS 5. THE APPLICANT SHALL PROVIDE A COPY OF A JOINT PARKING AGREEMENT FOR ANY PARKING STALLS LOCATED OFF SITE. AN EXECUTED JOINT ON THE CONSTRUCTION SITE. Lid PARKING AGREEMENT (IF ANY) SHALL BE SUBMITTED TO THE CURRENT PLANNING PROJECT MANAGER PRIOR TO OCCUPANCY. N 6. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION. O 6. THE PROVISION OF AN ADA VAN ACCESSIBLE PARKING STALL SHALL BE REQUIRED. THE REVISED PARKING PLAN SHALL BE SUBMITTED TO, AND 7. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. O APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. O 8. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 7. THE APPLICANT SHALL BE REQUIRED TO SUBMIT A RECORDED PEDESTRIAN EASEMENT IN SUFFICIENT WIDTH (UP TO 2 FEET) TO CONSTRUCT r REQUIRED STREET IMPROVEMENTS BEHIND THE EXISTING CURB. THE EASEMENT SHALL BE SUBMITTED TO, AND APPROVED BY, THE PLAN REVIEWER 9. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE SANITARY SEWER SYSTEM, WHICH HAS BEEN STAMPED AND Q PRIOR TO CONSTRUCTION PERMIT APPROVAL. SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR. J 10. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 8. THE APPLICANT SHALL SUBMIT A REVISED PAVING PLAN WHICH INCLUDES A SUITABLE TRANSITION TO THE EXISTING SIDEWALK, NORTH AND SOUTH OF INCHES, THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER THE SUBJECT PROPERTY. THE REVISED PAVING PLAN SHALL BE SUBMITTED TO, AND APPROVED BY, THE PLAN REVIEWER PRIOR TO CONSTRUCTION ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED. PERMIT APPROVAL. 11. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY 9. THE APPLICANT SHALL IDENTIFY AN OFF -SITE STAGING AREA FOR CONSTRUCTION. THE AREA SHALL BE WITHIN A REASONABLE DISTANCE FROM SITE COMPACTED UNLESS OTHERWISE APPROVED BY THE PUBLIC WORKS INSPECTOR. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH SAW IN TO LIMIT CONSTRUCTION TRAFFIC TO AND FROM THE SITE. PEDESTRIAN PATHS TO AND FROM RENTON HIGH SCHOOL SHOULD BE CAREFULLY STUDIED A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL TO ENSURE A WELL -COORDINATED, SIGNED, AND MAINTAINED TRAFFIC CONTROL PLAN. THE TRAFFIC CONTROL PLAN SHALL BE SUBMITTED TO, AND BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT STANDARDS. APPROVED BY, THE PLAN REVIEWER PRIOR TO CONSTRUCTION PERMIT APPROVAL. ADDITIONALLY, THE APPLICANT SHALL BE REQUIRED TO NOTIFY SURROUNDING PROPERTY OWNERS (WITHIN 300-FOOT RADIUS OF THE SITE) IN ADVANCE OF THE START OF CONSTRUCTION (NO LESS THAN 30 12. DATUM SHALL BE CITY OF RENTON, 1988 NAVD. DAYS), AND PROVIDE UPDATES NO LESS THAN QUARTERLY DURING THE CONSTRUCTION PERIOD. 13. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION O OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. ~ C) 10. THE APPLICANT SHALL BE REQUIRED TO SUBMIT A LIGHTING ANALYSIS DEMONSTRATING COMPLIANCE WITH RMC 4-6-060(I)(3). THE LIGHTING O ANALYSIS SHALL BE SUBMITTED TO, AND APPROVED BY, THE PLAN REVIEWER PRIOR TO CONSTRUCTION PERMIT APPROVAL 14. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH THE STANDARDS AND SPECIFICATIONS OF O THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, O 11. THE APPLICANT SHALL PROVIDE A LIGHTING/SAFETY PLAN WHICH INCLUDES THE FOLLOWING: LIGHTING WITHIN THE COVERED GARAGE DURING ALL AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. THIS SHALL INCLUDE NECESSARY LEVELING ' ~ OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL, TO HOURS; LIGHTING TO ILLUMINATE THE ALLEY; A LIMITED ACCESS GATE FOR THE GARAGE; A SURVEILLANCE SYSTEM INSTALLED IN THE COVERED UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE r GARAGE TO HELP DETER INCIDENTS OF CRIME AND SUSPICIOUS ACTIVITY; AND AN EMERGENCY COMMUNICATIONS DEVICE WITHIN THE COVERED GARAGE. PEA GRAVEL 6 INCHES ABOVE AND BELOW THE PIPE. THE LIGHTING/SAFETY PLAN SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 15. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 50, UNLESS OTHERWISE APPROVED BY THE WASTEWATER UTILITY. 12. THE APPLICANT SHALL PROVIDE A PAVEMENT DESIGN FOR WHITWORTH AVE S. THE PAVEMENT DESIGN SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO CONSTRUCTION PERMIT APPROVAL. 16. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES ABOVE FINISHED GRADE OR MUST HAVE MINIMUM 2' DIAMETER CONCRETE RING POURED AT GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. 13. THE APPLICANT SHALL REMOVE THE PROPOSED GAZEBO FROM ITS PROPOSAL AS VOLUNTEERED DURING THE PUBLIC HEARING. 14. THE APPLICANT SHALL PROVIDE THE CITY WITH SPU AUTHORIZATION TO CONSTRUCT INFRASTRUCTURE IMPROVEMENTS WITHIN THE SPU RIGHT-OF-WAY CONSTRUCTION SEQUENCE BEFORE CONSTRUCTION PERMITS ARE ISSUED. 15. THE APPLICANT SHALL SUBMIT REVISED ELEVATIONS WHICH INCORPORATE ADDITIONAL HEIGHT FOR THE GROUND LEVEL WINDOWS ALONG THE NORTH, SOUTH, AND EASTERN FACADES TO A HEIGHT THAT EXCEEDS TEN FEET AS SPECIFIED BY STAFF. THE REVISED ELEVATIONS SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 16. THE CANOPY ALONG SOUTHERN AND EASTERN FACADES SHALL BE INCREASED TO A HEIGHT OF NO LESS THAN 14 FEET AT THE BOTTOM OF THE CANOPY. DEPENDING UPON THE FINAL DESIGN, THE CANOPY SHOULD EXTEND 15-FEET ABOVE GRADE. DESIGNING THE CANOPY TO EITHER: TILT UPWARD, REDUCE THE WIDTH OF THE FACE OF THE CANOPY, OR MODULATE CONSISTENT WITH THE BAY WINDOW ENCROACHMENT ABOVE WOULD ALSO HELP EMPHASIZE A TALLER GROUND FLOOR HEIGHT ESPECIALLY AT THE ENTRANCE. THE REVISED ELEVATIONS SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 17. THE APPLICANT SHALL CONSIDER ADDING PUBLIC ARTWORK, ALONG WHITWORTH AVE S., THAT IS PUBLICLY VISIBLE AND IN KEEPING WITH THE VISION OF DOWNTOWN RENTON AS AN ARTS CENTER. A NARRATIVE REGARDING THE ABILITY TO INCORPORATE PUBLIC ART INTO THE PROPOSAL SHALL BE SUBMITTED TO THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. IF APPROPRIATE, PUBLIC ART SHALL BE INCLUDED IN A REVISED LANDSCAPE PLAN TO BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 18. THE APPLICANT SHALL SUBMIT A MATERIALS BOARD SUBJECT TO THE APPROVAL OF THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. ACCEPTABLE MATERIALS INCLUDE A COMBINATION OF BRICK, INTEGRALLY COLORED CONCRETE MASONRY, PRE -FINISHED METAL, STONE, STEEL, GLASS, CAST -IN -PLACE CONCRETE, OR OTHER HIGH QUALITY MATERIAL. THE MATERIALS BOARD SHALL ALSO INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING: STREET LEVEL WINDOWS; FRAMES AND GLASS, CEDAR SIDING STRIPS, ANY PROPOSED FENCING (ESPECIALLY SURROUNDING THE PLAYGROUND), TRELLIS/PERGOLA STRUCTURE ON SOUTH SIDE OF PROPERTY, BICYCLE RACK CANOPY, AND PARAPET CAP. ANY NON -BRICK MASONRY FINISHES PROPOSED AT THE GROUND LEVEL THAT MAY BE ACCESSIBLE TO HUMANS SHALL BE ANTI -GRAFFITI COATED TO ENSURE EASY REMOVAL OF GRAFFITI. 19. A CONCEPTUAL SIGN PACKAGE, WHICH INDICATES APPROXIMATE LOCATIONS OF ALL EXTERIOR BUILDING SIGNAGE SHALL BE SUBMITTED. LOCATIONS AND SUPPORTS ARE REQUIRED TO BE COMPATIBLE WITH THE BUILDING'S ARCHITECTURE AND EXTERIOR FINISHES. THE CONCEPTUAL SIGN PACKAGE SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 20. THE SITE PLAN SHALL BE REVISED TO REMOVE AND/OR RELOCATE THE PROPOSED BICYCLE RACK CURRENTLY PROPOSED ALONG THE NORTHERN PROPERTY LINE TO A MORE VISIBLE LOCATION. THE REVISED SITE PLAN SHALL BE SUBMITTED TO, AND APPROVED BY, THE CURRENT PLANNING PROJECT MANAGER PRIOR TO BUILDING PERMIT APPROVAL. 21. THE APPLICANT SHALL BE REQUIRED TO REPLACE THE EXISTING CURB ALONG THE FRONTAGE OF THE SITE. A REVISED PAVING PLAN SHALL BE SUBMITTED TO, AND BE APPROVED BY, THE PLAN REVIEWER PRIOR TO CONSTRUCTION PERMIT APPROVAL. 22. ALL ROOFTOP EQUIPMENT, STORAGE AREAS, UTILITIES AND LOADING AREAS, IF ANY, SHALL BE LOCATED, DESIGNED AND SCREENED TO MINIMIZE VIEWS FROM SURROUNDING PROPERTIES. LOADING AND DELIVERY AREAS SHALL BE SEPARATED FROM PARKING AND PEDESTRIAN AREAS. 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION 1. PRE -CONSTRUCTION MEETING. 2. POST SIGN WITH NAME AND PHONE NUMBER OF ESC SUPERVISOR (MAY BE CONSOLIDATED WITH THE REQUIRED NOTICE OF CONSTRUCTION SIGN). 3. FLAG OR FENCE CLEARING LIMITS. 4. INSTALL CATCH BASIN PROTECTION AS SHOWN ON PLANS. 5. GRADE AND INSTALL CONSTRUCTION ENTRANCE(S). 6. INSTALL SILT FENCE AS SHOWN ON PLANS. 7. CONSTRUCT SEDIMENT TRAP. 8. GRADE AND STABILIZE CONSTRUCTION ROADS. 9. CONSTRUCT SURFACE WATER CONTROLS (INTERCEPTOR SWALES, TEMP. SUMPS AND PUMPS, ETC.) SIMULTANEOUSLY WITH CLEARING AND GRADING FOR PROJECT DEVELOPMENT. 10. MAINTAIN EROSION CONTROL MEASURES IN ACCORDANCE WITH APPENDIX D OF THE SURFACE WATER DESIGN MANUAL AND MANUFACTURER'S RECOMMENDATIONS. 11. RELOCATE EROSION CONTROL MEASURES OR INSTALL NEW MEASURES SO THAT AS SITE CONDITIONS CHANGE THE EROSION AND SEDIMENT CONTROL IS ALWAYS IN ACCORDANCE WITH THE CITY'S EROSION AND SEDIMENT CONTROL STANDARDS. 12. COVER ALL AREAS THAT WILL BE UNWORKED FOR MORE THAN SEVEN DAYS DURING THE DRY SEASON OR TWO DAYS DURING THE WET SEASON WITH STRAW, WOOD FIBER MULCH, COMPOST, PLASTIC SHEETING OR EQUIVALENT. 13. STABILIZE ALL AREAS THAT REACH FINAL GRADE WITHIN SEVEN DAYS. 14. SEED OR SOD ANY AREAS TO REMAIN UNWORKED FOR MORE THAN 30 DAYS. 15. UPON COMPLETION OF THE PROJECT, ALL DISTURBED AREAS MUST BE STABILIZED AND BMPS REMOVED. R-395502 IN COMPLIANCE WITH CITY OF RENTON STANDARDS CALL 48 HOURS BEFORE YOU DIG! 811 8 18 2017 SURVEYED_ SCALE: 1"= 10, VERTICAL. NAVD 1988 HORIZONTAL° NAD 1983/1991 DATUM ` --� CITY OF 0 RENTON Planning/Building/Public Works Dept. RENTON R E N TO N COMMONS L LC 215 WHITWORTH AVE S, RENTON, WA 98057 COVER AND NOTES DATE: 1 1 / 15 /2017 Oq29 2017 DESIGNED: nG 11 15 2017 FIELDBOOK: PAGE: DRAWN: TTG ONE INCH DRAWING NO: C 1 .1 CHECKED: WE AT FULL SCALE IF Na ONE INCH SCALE ACCORDINGLY BY DATE APPR APPROVED: SHEET: 2 OF: 15 w U) 0 m W z O 73 2 O CU z O I- z w 01 rn co 6 I 0 w z O 75 O U z O z w rr ON RB LINE -NT �B SL I C X� IN V=2J.4 �b S) INV=29.8 (6 �Q I I Q� I I� Al design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 i II IaA WHITWORTH AVE S _5u- SD— N1 °19'51 "E 552.56' 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION nr11 rV f -rnrrT 1 Inl IT Anon :y1 �PMETER BOX u PQV� II � it SANITARY " F-F-WVR NA All SALVAGE EX ROW TREE GRATE TO CITY OF RENTON (TYP) CR-1�1 B 18 2017 SURVEYED_ 8 29 2017 DESIGNED: TTG 1 15 2017 DRAWN: TTG CHECKED: WEDATE APPR APPROVED: SCALE: 1 " = 10' ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY 01W U Oil 010 Id I° I00 00 I Un TELFD Z T O O LEGEND xREM. EX. TREE/STRUCTURE O CATCH BASIN PROTECTION PER COR STD PLAN 216.30 Y X X X X X X X X X X REM. EX. CONC. SURFACING X X X X X REM. EX BLDG UNDER SEPARATE DEMOLITION PLAN REM. EX. WALL SILT FENCE PER COR STD PLAN 214.00 INTERCEPTOR SWALE PER COR STD. PLAN 217.10 NOTES 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. ONLY MAJOR ONSITE DEMOLITION ITEMS ARE INDICATED IN THIS PLAN. REMOVE ADDITIONAL EXISTING FEATURES IN ROW AND AS REQUIRED FOR CONSTRUCTION OF NEW IMPROVEMENTS. DEMOLITION OF EXISTING BUILDING UNDER SEPARATE PERMIT. 3. COORDINATE ALL UTILITY DEMOLITION WITH CONSTRUCTION OF NEW SYSTEMS. TEMPORARILY MAINTAIN EXISTING UTILITY SYSTEMS AS REQUIRED TO CONVEY FLOWS FROM PORTIONS OF SITE OUTSIDE CONSTRUCTION AREAS AND PROVIDE TEMPORARY BYPASS AND PUMPING SYSTEMS AS REQUIRED BY CONTRACTORS OPERATIONS AND OWNERS USE OF FACILITIES. 4. COORDINATE ALL UTILITY INTERRUPTIONS WITH AFFECTED FACILITY OWNERS. PROVIDE MINIMUM 2 WEEKS ADVANCE NOTICE OF ALL INTERRUPTIONS. 5. ALL LOCATIONS OF EXISTING UTILITIES SHOWN HEREON HAVE BEEN ESTABLISHED BY FIELD SURVEY OR OBTAINED FROM AVAILABLE RECORDS AND SHOULD THEREFORE BE CONSIDERED APPROXIMATE ONLY AND NOT NECESSARILY COMPLETE. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INDEPENDENTLY VERIFY AND AVOID ANY OTHER UTILITIES SHOWN HEREON WHICH MAY BE AFFECTED BY THE IMPLEMENTATION OF THIS PLAN. 6. NOT ALL REQUIRED CB PROTECTION IS INDICATED ON THIS PLAN. INSTALL CB PROTECTION ON ALL EX CB'S TO REMAIN DURING CONSTRUCTION AND ALL INSTALLED CB'S. MAINTAIN PROTECTION UNTIL TRIBUTARY SURFACES ARE STABILIZED. 7. MAINTAIN/RELOCATE TESC MEASURES AND PROVIDE ADDITIONAL TESC MEASURES AS REQUIRED TO STABILIZE EXPOSED SOILS, MINIMIZE SEDIMENT TRANSPORT ON SITE, AND MEET ALL SITE DISCHARGE AND PERMIT REQUIREMENTS. ADDITIONAL FACILITIES BEYOND THOSE INDICATED ON THIS PLAN MAY BE REQUIRED, AND IT IS THE CONTRACTORS RESPONSIBILITY TO DETERMINE AND PROVIDE ADDITIONAL MEASURES THAT ARE NECESSITATED DUE TO THEIR OPERATIONS AND SEQUENCING OF THE WORK. ALL TESC MEASURES SHALL BE REMOVED FOLLOWING SITE STABILIZATION WITH FINAL PAVING AND PLANTING. 8. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL REQUIRED MONITORING, TESTING, REPORTING AND ALL OTHER COMPLIANCE MEASURES AS NECESSARY TO MEET PROJECT PERMIT COVERAGE REQUIREMENTS. 9. CONTRACTOR SHALL DESIGN AND PROVIDE TEMPORARY STORAGE AND WATER QUALITY TREATMENT FACILITIES FOR CONSTRUCTION RUNOFF, INCLUDING BUT NOT LIMITED TO PRETREATMENT AND STORAGE TANKS, SAND FILTRATION, CHEMICAL TREATMENT SYSTEMS, PIPING, PUMPS, AND ANY OTHER FACILITIES REQUIRED TO MEET THE PERMIT WATER QUALITY REQUIREMENTS FOR ALL SITE DISCHARGES. NUMBER, TYPE AND LOCATION OF TREATMENT SYSTEMS SHALL BE DETERMINED BY CONTRACTOR IN ACCORDANCE WITH THEIR OPERATIONS. x„ (� CALL 48 HOURS BEFORE YOU DIG! 811 HORIZONTAL- NAD 1983/1991 CITY OF DATUM } RENTON Planning/Building/Public Works Dept. T Q J O O T w R-395503 IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 SITE DEMO AND TESC PLAN m C/) z O 73 2 O U z O DATE: 11/15/2017 FIELDBOOK: PAGE: DRAWING NO: C2.0 Iz SHEET: 3 OF: 15 I N u vv H i r-\ Ivl H I Iv DRIVE �PQ�� P�PQ�� � Q\� Q�� �URB LINE MET RCD SL ° - BOX II II ----------------- - -- - - -- --------- --- -- ------- SD ------------ ----- CO cY) CB S D M SD A WH ITWORTH AVE S N 6o vIEN T TOP- 32. 35 TOP= 32. 71 SD SD SD _ D• I E of ;URB INV 29.97 INV=28.76 12" I SD SD sD � p � = 28.1 Per Plan Lu INV=29.4 (6 S) o . 12" WATER MAIN AND ~ 2 45 Degree V rtica en s install INV= 2 9.8 (6 SRVCS PER SHEETS N 1 '19' 51 "E g 12.5-.15--C . SSANITARY SERVER MAIN ON CENTERLINE per COR spec. Bends installed in order I- - i- PAVEMENT ST IPING - SS to enter vault flat per COR spec. Install I I I - z PER RFI 57 4 0 NEXT I SIDE SEWER PER STREET I 01 W � �Ps MH. Q I SHEET C5.0 IMPROVEMENTS O 1 � 0 `SF�I S U� 28. I PER SHEET C6.0 I O 75;Z0 I Q n G G 75 I O -d I G G� G G G _G A 12+75.95 22.50' RT z ° W/F RNC TRONG Q I U/ - - - - TE L DUCT BA K FITTING D R I E O ---- ME R 0 HH� I ° V DU T TEL DUCT ° --------------- _ _ _ z TV DUCT - -- -- - ---ELEC. CO sC---- R1 \/ R Fi MEC ��' \- --------------- - -- --- ------------ -- - ----------------- rr SL C 0 N R SIDEWALK i--�----------- �P��------- - ELE CB TYPE 1 W/SOLID COVER E CONNECTION/ PER COR STD PLAN 204.10 ' EANOUT X RIM 33.1 t IE 1. CONNECT T 2" \ / IE 28.55t (12" W,E) �� DOMES TER M�ER Relocated r Kati eter / IE 30.65 ( S) PV W/REQ. FI INGS w SEWER CLEANOU P I STORMFILTER CB Installati Pier I TELEPHONE \/ f i- COR STD PLAN 4 1 RIM 32.60 I i SEE ET 6 .1 CONNECT 0 PIV 5 IE 29.85 �� 0 PRO f�U� IE 31. ASSEMBLY W/REQ N CT TO BLDG i C7.1 i x CONNECT TO E?� 12„ SD FITTINGS. EE NO] 9 WAS W/REQ. FITTINGS. W/FERNCG STRONG 777\ cn IE 2. All Storm, Water, & Sewer BkK FITTIN WILKIIIIIS 350XL DCVA LO 26.1 I Installation was per Ian unless COR STD PLAN 340. ` ; x p p indicated otherwise with RED s� / I a I LINES. 4 D J SPRKL SRVC 0 - Q AREA DRAI New Area � � � �; RIM . I Drain 1A I �- a z J LL IE 29.6 ® I 1 PROP. ELECRVC. 278 LF TO NEXT• I RIM = ■54BEND i REF ELEC � DOWNSTREAM SDMH. 2" W c�i H O U S E N o. 215 4 I I E= 1 ■�b 1 � I Q P AS134 °- SDMH IE 27.21 / � II Q/ / MAIN FLOOR ELEV. = 35.9 1 PROP. TELECOM I SRV . lVE F / " I REF ELECLLJ �XENC� \ _ PATIO A DRAIN I SD LF 1 L� I C)' \X� 3" DIA. STORM / 6.1 I I I LLJ k- PUMP DISCHARGE �� , I xU Cn LINE Q / N O U / 29.1 1 O LWw LLJ \� CONNECT TO BLDG w > Z 8" PUMP STATI WATER W/REQ. FITTINGS 1 Q i ix0 V RFLOU11V­6QNNECTION ` V " SD @ 2% 1 LLJ I i w 72 TF 6 CONNE TO BLDG U_ 1 (� SPKLR W/REQ. FITTINGS i- z i I 57 LF 6" SD @ 2% / I I- w 1 i x Q AREA DRAT w -I 1 RIM 32.20 LLJ J 225 BEND •- I ' IE 29.70 PROP. UILDING , 45• BEND PUMP CONTROLLER, ALARM, MANUAL I I - //Q TRANSFER SWITCH, AND PRIMARY FF 3.35 1 /`�� "\� ELEC. FEED. COORD. WITH ARCH - i I RE �./ M W/DUPLEX STORM AND ATTACH TO BUILDING @ 5' 1 UMPS SEE NOTE 11 ABOVE GRADE. BACKUP POWER TO H A R / 0 RIM 33.20� BE PROVIDED BY ON SITE 1 i 316 0 IE 3 .00 VERFLOW E) PORTABLE GAS GENERATOR 1 P 26.45 _ IE 28.4E) = ' LINE OF BUILDING 1 OVERHANG ABOVE 1 ,I 7.1 Q - CONNECT TO BLDG ROOF DR SEE SHEET L1.01 FOR (TYP) ; v DRAIN 1 W/REQ. FITTINGS (TYP OF 3 GREEN ROOF AREA. \ Q � SEE DETAIL 5 SHEET L202 I RIIE 29.70 00 o I O co � = 1 30 LF 8" SD @ 2% I 1 i AREA DRAIN RIM 32.20 - 105 LF 8" SD 0 2% IE 29.70 , � IIE 29.15 Z T 0 0 T 10 0 10 U SCALE: 1 " = 10' DATUM NAVD 88 LEGEND Lr) 2 CV 0 CLEANOUT C7.0 O O 0 PATIO DRAIN 3 I CTO (C) T 0 AREA DRAIN 4 Q CB TYPE-1 PER COR STD J PLAN 200.00. W/RECTANGULAR FRAME PER COR STD PLAN 204.00 60 SDMH DOWNSPOUT CONNECTION 6 c7.o _,--,--,-_ 6" STORM DRAIN (GASKETED PVC SDR 35) U.N.O. co 8" STORM DRAIN O (GASKETED PVC SDR 35) U.N.O. O 6" SANITARY SERVICE LINE ~ T . - WATER SERVICE LINE WATER MAIN/SPKLR SERVICE - - - ELECTRICAL CONDUITS - - - TEL/DATA CONDUITS NOTES 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. SEE DETAIL 1 SHEET CTO FOR TYPICAL TRENCH DETAIL. 3. VERIFY INVERTS OF ALL EX. SYSTEMS AT PROPOSED POC'S TO NEW LINES PRIOR TO ORDERING OF MATERIAL AND NOTIFY ENGINEER OF ANY DISCREPANCIES AT LEAST 4 WORKING DAYS PRIOR TO STARTING PIPE LAYING OPERATIONS. 4. COORDINATE BLDG. SYSTEM CONNECTION LOCATIONS AND INVERT ELEVATIONS WITH MECH/FIRE CONTRACTOR. PROVIDE ALL REQ. FITTINGS FOR CONNECTION. 5. COORDINATE ALL UTILITY INTERRUPTIONS WITH AFFECTED FACILITY OWNERS. PROVIDE MINIMUM 2 WEEKS ADVANCE NOTICE OF ALL INTERRUPTIONS. 6. STORM DRAINS SHALL BE PLACED AT A MINIMUM SLOPE OF 2% AND A MAXIMUM SLOPE OF 25% U.N.O. 7. THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS DURING TRENCH EXCAVATION TO PROTECT EXISTING UTILITIES FROM DAMAGE AND SETTLEMENT. 8. RESTORATION FOR ALL UTILITY CUTS IN EXISTING PVMT SHALL BE PER CITY OF RENTON TRENCH RESTORATION AND OVERLAY REQUIREMENTS. CONTRACTOR SHALL COORDINATE WITH CITY OF RENTON AS REQUIRED AND SHALL PAY ALL COSTS FOR RESTORATION. 9. COORDINATE WITH ELECTRICAL/FIRE FOR PROVISION OF PIV TAMPER SWITCH, WIRING AND CONNECTIONS TO ALERTING SYSTEM. 10. APPLICANT SHALL OBTAIN ALL SPU AND CITY OF SEATTLE PERMITS PRIOR TO CONSTRUCTION PERMIT ISSUANCE FOR STORM DRAIN CONNECTION IN SPU RIGHT OF WAY. 11. PRIMARY PUMP POWER SHALL BE PROVIDED VIA BUILDING SERVICE. BACKUP POWER SHALL BE PROVIDED BY PORTABLE GAS GENERATOR S-395501 W-395501 R-395504 WLu IN COMPLIANCE WITH CITY OF RENTON STANDARDS p m DEVELOPMENT ENGINEERING ` WASTEWATER UTILITY z Fitz -James 11 /09/2017 dchristen 11 /09/2017 O T17--- - x--__ x _ GACALL48HOURS �-' BEFORE YOU DIG! SURFACE WATER UTILITY + 2 o G S RR 1I 811 rstraka 1 1 /09/2017 0 of E DATE. o �� : _. ��, SURVEYED: SCALE: VERTICAL. NAVD 1988 3/1 CITY O F R E N TO N COMMONS L LC 1 1 /03/2017 z e e Q � ` � � 1 " = 10' HORIZONTAL- NAD 1983/1991 DESIGNED: �, 0 - '' TrG - 215 WHITWORTH AVE S, RENTON, WA 98057 FIELDBOOK: design P LLC : 7 DRAWN: RENT 0 N PAGE: 307 4 TTG ONE INCH%MVV DRAWING NO: A CIVIL ENGINEERING COMPANY � � DATUM z 219FirstAvenueS.,Suite401 '�(� �'GISTER�' CHECKED:ATAT FULL SCALE Planning/Building/Public Works Dept. SITE DRAINAGE C3. 0 Uj Seattle WA 98104 vsl pj�� IF NOT ONE INCH ONAL N 0. REVISION BY DATE APPR R APPROVED: SCALE ACCORDINGLY SHEET: OF: 2064024644 _ AND UTILITY PLAN 4 26 10� 11� Zl� P ���t_ - 7rA N= ■DRAIN RIM 32.20 IE 29.70 .� z O 75 O U z O 1- z w rr 1 a Z i JT TOP=32.35 TOP=32.71 - N INV=29.97 INV=28.76 (12") INV=29.4 (6"S) INV=29 8 6"E I- - -7 I- I J= � I Xc) I Q I I G G-Td QS 'Co SD SD SD Sr (_1n `-'D `<A 6 SD SD SD SD WHITWORTH AVE S N1 °19'51 "E 552.5b SANITARY SEWER MAIN 0 � CENTERLINE PAVEMENT STRIPING I I E TEL DUCT DRIVE ° ME R - --- ------ ___ ___ __ _ ___ _ _ 0 --------------------- TV DUCT ELEC. CO -Sc _DRIVE Y ` TW BW + 33.33 + + + + + + + + .o + + :+ + + 33.33 3 0 + 33.25 +� + i 33.33 + o 32.70 i 1 + + p + i 33.33 + + 33.15 i + + i i i i 33.30 33.33 ++++ + + 32.70 + + 32.90 HE 33.30 c () 32.68 1 33.20 33.25 33.33 0 STREET IMPROVEMENT ,PLAN PER SHEET C6.0 c')(TYP) 016 G I O I LLJ � O i � ccf)i� 010 n 00 I� I° IE (J-) SS CD G G� `ECG TV ° V DU T TEL DUCT ° - --------------- -- --- T_ ------- CONC R - - SIDEWALK ---- ---- ------------- P - ELE 0 9 \ 33. 0 32.95. �32.90 x 33.10 3333 TELEPHONE V .. LLJ .. EX 33.0t CD co x C O O 33.33 : 32.75 ` .: 32.75 o Ix oI EX q :... O 32. 3 x HOUSE No. 1 �URB ...:::":::"::::'::.::.'::.'::."'::."'::.".:."':: •'"•'"•'"•'"•'"•'"•'"•'"•'"•'"•'.c� w Q MAIN FLOOR FL H PER ELEV. = 3f4�TYP) °-..:.: : ' : " 0 W 0 x LLJ ' Ld EX 32.8t 6.1 33.33 + + b' "•' "•' "•' "•' "•' "•' "•' "•' "•' "•' "•'. i W 33.33 x U N + + + 3110 co 29.1 + + + + E>1 i ' LLJ IIII + + + �EX 32.6t + + + i Ld El x Z 33.33 3 . 3 33.20 33.30 33D5 D LLJI U U Q LLJ LLJ -i Q TRANSFORMER PAD Li PER ARCH PROP. UILDING 3.20--// 33.20 I FF 3.35 / 33.33 a I a RE� a° a x HAR/ a 316 d d P, a 0 qJ a J �- a 33.33 + + + 00 I / + + 00 33.33 + + + Z I + + I I LINE OF BUILDING 33.20 OVERHANG ABOVE (7YP) x \ ;1 32.20 - - - - i\ orr w.vv---n n x- -- - 32.20 / RETAINING WALL C CLONE FENCE / REF. STRUCTURAL / x 0.85' T�7 i - I SHED �%,%IfrrLl design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION 0 IC) 8 114 2017 SURVEYED_ 08 7n 2017 DESIGNED: 11 15 2017 TTG DRAWN: TTG CHECKED: WE BY DATE APPR APPROVED: 32.85 I \ \� t �32.20 Il O Z T 0 0 N O 0 LEGEND a Q a CEM CONIC WALK 1 a a C7.1 J e. i PERMEABLE PAVERS 2 + + + PERMEABLE PAVEMENT + + + O7 CM CEM CONIC PAVEMENT 4 O C7.1 T RUBBER TILE SURFACING PER LA *-�- xx.xx PROPOSED F.G. ELEVATION � TW xx"xx TOP OF WALL ELEVATION eW xx.xx BOTTOM OF WALL ELEVATION NOTES 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. ALL EARTHWORK AND SUBGRADE PREPARATION SHALL BE PERFORMED IN ACCORDANCE WITH THE REQUIREMENTS AND RECOMMENDATIONS OF GEOTECHNICAL REPORT PREPARED FOR THIS PROJECT. 3. SEE ARCH/LA PLANS FOR ADDITIONAL SURFACING INFO AND SPECIAL FINISHES/SCORING. 4. FINISH GRADE INDICATED IS FINAL SURFACE ELEVATION FOLLOWING PLACEMENT OF ALL SURFACING MATERIALS. 5. GRADE ALL AREAS TO PROVIDE DRAINAGE AWAY FROM THE BUILDINGS. FINE GRADE AREAS TO DIRECT DRAINAGE TO DRAINAGE STRUCTURES. 6. COORDINATE GRADING AROUND BUILDING WITH ARCHITECTURAL DWGS. NOTIFY ENGINEER OF ANY DISCREPANCIES. 7. RESTORATION FOR ALL UTILITY CUTS IN EXISTING PVMT SHALL BE PER CITY OF RENTON TRENCH RESTORATION AND OVERLAY REQUIREMENTS. CONTRACTOR SHALL COORDINATE WITH CITY OF RENTON AS REQUIRED AND SHALL PAY ALL COSTS FOR RESTORATION. 32.20 - - x - - - R-395505 w Lu IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 00 _YCLONE FEN x GATE � X_ z O CALL 48 HOURS 2 BEFORE YOU DIG! 2 811 0 SCALE: 1"= 10' HORIZONTAL- N D 19VD 83/1991 CITY OF RENTON COMMONS LLC DATE: 1 1 /15/2017 z FIELDBOOK: PAGE: } RENTON 215 WHITWORTH AVE S, RENTON, WA 98057 O --- DRAWING NO: C 4.0 ONE INCH AT FULL SCALE DATUM Planning/Building/Public Works Dept. SITE GRADING AND z w IF NOT ONE INCH SCALE ACCORDINGLY PAVING PLAN SHEET: 5 OF: 15 U")LO LO C? M CO N N � � I z O G 75 O U z O z w rr CD / / V I N L L l \\ I \\ L I V TV AND TEL NOT LOCATED IN THIS AREA c0 TELEPHONE VAULT ELEC AND WATER MAIN x / IN CURB LINE TV / 8 PV BRICK STA 12+29.50, 0.33' RT CONCRETE SIDEWALK FIRE HYDRANT MARKER L PER COR STD PLAN 310.3 WHITWO 12+35.7, 13.0' RT TEE ------ ---- - TOP 12" DI ELEV.=27.2'----- ---- -- _...... STA rn 12771i RT CONNECT TO EX. SR 2" DOME C WATER SRVC STUB W/ REQ. FITTINGS I o CO MPER-COR STD PI D f 320.2 S D - 12+74.9, 13.0' RT . TOP 12" DI ELEV.=27.6' ' STA RT 6" SIDE SEWER PER �„� o I (1) 12 GATE VALVE (MJ) COR STD PLAN 406 1 STA l i+75. 5, 1 .�T H AVE, 0 �m BRICK GAS VALVE 1 1 CD COORD. COR TRANSFER SERVICE TO NEW 12" All+ r E--------- - ---- U t�_w SERVICE TRANSFER ------ U DON Y COR CREWS AFTER 0 H SD MAIN IS OPERATIONAL. W �u SD- 1 = I� 12.9' SEE OJTE21156 9 BEISIN PIPE nr1 rnTin.i 252 LF 12" DI WATER i W 12+38.0, CD - TOP VALVE ELEV.=28.7. S A N I Thka( E E� M A I 0 I13+50 w - ----jZ 'EMENT T IPING I I I I I GAS MAIN PER I I J FIELD LOCATES I STA 13+30.00, 14.5 RT N I W ' END PIPE DEFLECTIO I = --- --___ - -=---- ---�_ - _�_=12+94.3,13.3'RT G-0� 13+36.1 14.4'RT ff All „ TOP 12" DI ELEV.=27.6' -a - G TOP 1-1/2" IRON H2O RUNNING EAST -WEST ELEV.=30.7' N o cn 13+46.7, 14.6 RT MET R TOP 12" DI ELEV =27 2' 0 0 HH� I V V DU T TEL DUCT ----------- ,UCT 12+17.7, 21.5' RT -- - CQ ---- ------ --- -- ----- ----- - 4" CO D IT PS I V VEY - --- ------------ - R S I D E WA K---- -1--v ---------------- i �RAIVCHiSE E fiE ------ CON. P B W R POLYPIG OBTAINED P OUT UNDE D TO 97 - - - ETER BO ER COR F 0 Q I 12+29.9, y � � � STRE LI HT H N (1) 4" CONDUIT (CLINK) i � x ST 2.00 RT UNDER SEPARATE FRANCHISE / I TE L E P ]ONE V A U L T- RFIYDRANT SERE ER S EET 6.0 �� PERMIT OBTAINED BY I CENTURY LINK 4" FIRE RVICE%D D6 /PIV P� OR STD P N 12+85.1, 13.2' RT 3 PROVIDE' c3'x1.5' / Q F TOP 12' DI ELEV.=27.5' I E HIED ROCK SUMP ( 12+55.8, 13.1' RT TOP TAP WEST ELEV.=27.3' I i Q� EL W VAU1IN HOLE 0 WILKINS 350XL DCVA PE TOP 12" DI ELEV.=27.6' COR S D PLAN 340.8 , n L b 1 I J 12+85.4, 22.8' RT C DAVID EVANS AND ASSOCIATES INC. WATER METER I I x 20300 WOODINVILLE SNOHOMISH ROAD I a _ C)0 Q NORTHEAST, SUITE A. 425-415 2000 i t AS CONSTRUCTED FIELD INFORMATION DEPICTED c G I ON THIS MAP REPRESENTS THE RESULTS OF A SRVEY MADE ON DEC. 13, 2017, DEC. 14, 2017, DEC. 18, 2017, JANUARY 12, 2018 AND MARCH 12, 2018 AND CAN ONLY BE CONSIDERED AS INDICATING THE GENERAL CONDITIONS EXISTING AT THAT TIME. 40 30 . . . . . . . F PROP. 6" _ SS CROSSING SS .PIPE BOTTOM: 28.30 WATER PIPE TOP: 27.63 . . . . . . . . . . . . J W �.� . .M.�. .. o EX. SS CROSSING . . . . . . z �p o r� TO BE ABANDONED . . . . NU �! W r) 4Wi w x" x `-� �. C) . . w 20 :SOY Q Z Yg � J U � J U jam. Q 0 cl cl 0 Q C) LU LLI C' L'U C, cn c:1 0 N � N. j.� Z N o N ZLLI N N Q N� Q N M N O.O . . . + CV w Q CD NJM + N + NCO <t + CV 'x C7 N .+ N x C' Na + C4 W �.N . L Wr7 + CV . . N Um � �U ��cnF_ ���� �p�zZ. U) W �C/) m C/) C/) M a- Cn :�. (/) . :� U) CV U d En � 11+70 12+00 12+50 WATER MAIN PROFILE SCALE: HORX. 1 " = 10' VERT. 1 " = 5' Al design PLLC A CIVIL ENGINEERING COMPANY L,.; 219 First Avenue S., Suite 401 a Seattle WA 98104 J 206 402 4644 LL 1►[•l REVISION PROPOSED 12" WATER MAIN 13+00 SURVEYED: DESIGNED: TTG DRAWN: TTG CHECKED: WE BY DATE APPR APPROVED: 13+50 SCALE: VERnCAL. NAVD 1988 1 " = 10' HORIZONTAL- NAD 1983/1991 ONE INCH DATUM AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY Ell] 35 30 25 K11 15 CALL 48 HOURS BEFORE YOU DIG! 811 } CITY OF RENTON Planning/Building/Public Works Dept. Z T 0 0 LEGEND CONIC THRUST BLOCKING PER COR STD PLAN 330.2 AND 330.3 GATE VALVE AND VALVE BOX PER COR STD PLAN 330.1 FIRE HYDRANT PER COR STD PLAN 310.1 WATER METER PER COR STD PLAN 320.2 1" WATER SERVICE U.N.O. 12" DI CLASS 52 WATER MAIN U.N.O. 6" PVC SDR 35 ASTM 3034 (U.N.O.) SANITARY SEWER SERVICE ELECTRICAL CONDUITS TEL/DATA CONDUITS NOTES 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. SEE SHEET C6.0 FOR PAVEMENT RESTORATION PLAN. 3. VERIFY INVERTS OF ALL EX. SYSTEMS AT PROPOSED POC'S TO NEW LINES PRIOR TO ORDERING OF MATERIAL AND NOTIFY ENGINEER OF ANY DISCREPANCIES AT LEAST 4 WORKING DAYS PRIOR TO STARTING PIPE LAYING OPERATIONS. 4. COORDINATE ALL UTILITY INTERRUPTIONS WITH AFFECTED FACILITY OWNERS. PROVIDE MINIMUM 2 WEEKS ADVANCE NOTICE OF ALL INTERRUPTIONS. 5. THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS DURING TRENCH EXCAVATION TO PROTECT EXISTING UTILITIES FROM DAMAGE AND SETTLEMENT. 6. ALL CONCRETE BLOCKING FOR HORIZONTAL BENDS, TEES AND VERTICAL BENDS SHALL BE PER COR STD PLANS 330.2 AND 330.3. 7. ALL MECHANICAL JOINTS FITTINGS AND VALVES SHALL HAVE RESTRAINED GLANDS EQUAL TO MEGALUG SERIES 1100 OR ROMAC ROMAGRIP, EXCEPT WHERE SHACKLE RODS ARE INDICATED. 8. SHACKLE RODS SHALL BE INSTALLED PER COR STD PLAN 330.5. 9. PIPE JOINT DEFLECTION SHALL NOT EXCEED HALF OF THE MANUFACTURE'S ALLOWABLE DEFLECTION. 10. SCHEDULING FOR THE WATER CUT -IN CONNECTION AT S 3RD STREET SHALL BE COORDINATED BY THE CONTRACTOR WITH THE CITY PUBLIC WORKS INSPECTOR AND CITY PROJECT MANAGER. ALL CONNECTIONS TO THE EXISTING WATER MAIN NEED TO BE COMPLETED BY CITY MAINTENANCE CREWS. THE CONTRACTOR IS RESPONSIBLE FOR EXCAVATION OF THE TRENCH, SHORING OF THE TRENCH AND SUPPLYING THE MATERIALS NEEDED FOR THE CUT -IN. 11. PORTION OF SIDE SEWER CROSSING OVER WATER MAIN SHALL BE CONSTRUCTED WITH (1) STICK OF PVC C-900 PIPE, CENTERED ON WATER MAIN. Q J co O 0 T WE H S-395502 W-395502 R-395506 w IN COMPLIANCE WITH CITY OF RENTON STANDARDS M0 W DEVELOPMENT ENGINEERING (/) a- I I Fitz -James 12/13/2017 zO 73 2 O DATE: U RENTON COMMONS LLC 12/13/2017 z 215 WHITWORTH AVE S, RENTON, WA 98057 FIELDBOOK: O PAGE: DRAWINGZ ROW UTILITY PLAN C 5.0 ` AND PROFILE SHEET:6 OF:26 0� LO LO LO LO M M CO Cy) O N ,:I- CE p � W z O 75 O U z O z W rr ME Lii a Z J Ll 9 35 30 25 ASPHAL I PAVLMLN 1 r' ��Tr POWER VAULTS TELEPHONE VAULT ECi t I E�( OWER Y f PER PSE I UNDERGROUND ELEC, TV AND TEL NOT LOCATED IN THIS AREA CB TOP=32.12 INV=30.6 BUILDING 400 WHITWORTH AVE S i H V P V COORD. COR TRANSFER OF EX CONCRETE SIDEWALK �J ��S� TEL GU IAE� NEIW TEL P� B XER STA 15+13.00, 0.33' RT 4" � W TER MAIN FIRE HY NT MARKER PE -- -- ---- ------ - ONE VV COR STD PLAN 310. ��j' i I ccn 12" MAIN I OPERATIONAL. SD FX ' SD SL SD I I SD SD 15+07.9, 11.2 RT 410 4* I; 4" CONDU�(PSqS M H w _ III 60 STORM DR(#k25 8EO.v'j� 0 OPE W I' NDER SEPARATE _ I v ANCHISE PERMIT TOP = 3 2. 9 4 I I I THRUST BLOCK I, --OBTAINED BY SE TOP 12" DI ELEV.=28.9' w IIo 11,Novi=26.36 W - i , 1 14+50 18 LF 12" DI WATER 15+00 fA I i II 2 6.10 0' 14+90.1, 14.6' RT 5 c.nlZ mI �� 159 LF 12 DI � PAVEM (1) 1 .9 '1 �ND (MJ) J 13+72.0, 14.6 RT WATER I I �, THRUST BLOCK _ [--G ( TOP 12" DI ELEV.=26.5' 14+36.6, 14.8 T TOP 12" DI ELEV.=28.5' G ��-G -c TOP 12" DI ELEV.=28.3' - - - - - - --- A,' v- AB-QVE-GR_0aN-D-------- L--- a INV=30.80 (6" N) c II z II m II Q _N AMP x W PAVEMENT ST IPING SO z Q Q c� HIY E co 15+13.30,11.2' RT 1� 12"x6" TEE (MJxFL) S GATE VALVE (FLxMJ) RUST BLOCnnKJJ >> A T E R EX"�N Iy EX 8" W r= TOP 12" DI ELEV.=28.8' VJ W 15+56 53 38 S M H `� i 3 F 12" D� P= 32.72 � WATER VALVE RIM - - - 2 5.6 6 I I ELEV.=32.92 - - - - - 01 CIO WATER VALVE RIM 13+99.5, 14.4' RT 13+98.8, 14.5' RT GAS V A L E _ _ _ - ELEV.=32.92 GAS _ - - 14+56.8, 14.5 RT F TOP 12" DI ELEV.=26.8' - - - - - -TOP 12" DI ELEV.=27.0' - - - - - - - - - - _ r� - - m ---- ° - - - TOP 12" DI ELEV.=28.6' - - - - G - - - WATER VALVE RIM G G 'SWAY � � HH -------- METER B ELEV.=32.93 `__-- ELEC_�COR_ SL � TA 15 .91, 14 0 RT TEL _ �� TV' - -- - DRIVEWAY SL SL � l LAM P UT IN NNECT EX 1 " P ------ELEC----------- DRIVEWAY DRIVEWAY ATER Ij PER R ST c� STA 15+13.00, 22.00 RT 00.4 jTE -X X X P - _ FIRE HYDRANT _ LAMP (1) 12 12" TEE J� TEL 128.0 CYC ONE O 12 ATE VA �(FLx ) FN CE �- T ELECTRIC TEL / EPHONE VAULTS UNDERGROUND ELEC, � Cg X TV AND TEL NOT TOP=32.06 LOCATED IN THIS AREA INV=31.0 DAVID EVANS AND ASSOCIATES INC. 20300 WOODINVILLE SNOHOMISH ROAD NORTHEAST, SUITE A. 425-415-2000 AS CONSTRUCTED FIELD INFORMATION DEPICTED ON THIS MAP REPRESENTS THE RESULTS OF A SRVEY MADE ON DEC. 13, 2017, DEC. 14, 2017, DEC. 18, 2017, JANUARY 12, 2018 AND MARCH 12, 2018 AND CAN ONLY BE CONSIDERED AS INDICATING THE GENERAL CONDITIONS EXISTING AT THAT TIME. W ILL. ANu IV �AJSUMLu APPROX: EXISTING GRADE EX. WATER SRVC W DEPTH/CONFIG.) . . . . . . . . . . . . . . . . . . . . . . . . . . . _ - _ . . -_ : _ . _ : ----. .. _ . . . . . . . . . . . . . . . . . . B(.-GAS CROSSING- C i PROP. ELEC. . . . . . . . . . . . . . . . - - - - . . . . . - . . W - CROSSING . . fW �� 2 . . . . . . . . . . . . . W � Z. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . J � U- EX. GAS X: I / i J= PROPOSED 12" QCROSSING 18 MIN. . . . . . . . . . . . . . . . . . . . . . . . WATER MAIN EX. SS 2OCROSSING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Z ' O O W m m. O CD . o O + ((/7 N .� . O + Qf LCD 15 ��� �� 1n 14+00 14+50 15+00 WATER MAIN PROFILE SCALE: HORX. 1 " = 10' VERT. 1 " = 5' design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 1► 91 REVISION (1) THRUST BLOC H � (2) 12" DI SPOOL (PExPE) 01 (3) 12" SLE�E (MJ) � W w W W Q _z 7 QI Q Q x Y W Y . 1 O Q O W m OO � > m mI. W + cx CV � Of LC) Of N 2 CD �7-- SURVEYED: DESIGNED: TTG DRAWN: TTG CHECKED: WE BY DATE APPR APPROVED: 35 30 25 LU J x o LIJ z _j O .� J Y _j 20 U _ U LWLi > OJ CC >W> O Z F_ W m� W NLLJ Ln z ?Lc)� N ~Q I_.-+ OU z "X CD CO En cn = . Z CN CN C (nU 15 15+50 15+60 SCALE: VERTICAL. NAVD 1988 1 " = 10' HORIZONTAL- NAD 1983/1991 ONE INCH DATUM AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY CALL 48 HOURS BEFORE YOU DIG! 811 } CITY OF RENTON Planning/Building/Public Works Dept. LEGEND N 1m NOTES ZLO T 0 0 CONIC THRUST BLOCKING PER COR STD PLAN 330.2 AND 330.3 GATE VALVE AND VALVE BOX PER COR STD PLAN 330.1 Mug 911NOR is?. IiT►4:r10:ayIIII10a0 role] :�811laF.11Iamew 1 " WATER SERVICE U.N.O. 12" DI CLASS 52 WATER MAIN U.N.O. 6" PVC SDR 35 ASTM 3034 SANITARY SEWER SERVICE ��X�ll:�[y_1�K�1►1�1111 TEL/DATA CONDUITS 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. SEE SHEET C6.0 FOR PAVEMENT RESTORATION PLAN. 3. VERIFY INVERTS OF ALL EX. SYSTEMS AT PROPOSED POC'S TO NEW LINES PRIOR TO ORDERING OF MATERIAL AND NOTIFY ENGINEER OF ANY DISCREPANCIES AT LEAST 4 WORKING DAYS PRIOR TO STARTING PIPE LAYING OPERATIONS. 4. COORDINATE ALL UTILITY INTERRUPTIONS WITH AFFECTED FACILITY OWNERS. PROVIDE MINIMUM 2 WEEKS ADVANCE NOTICE OF ALL INTERRUPTIONS. 5. THE CONTRACTOR SHALL TAKE THE NECESSARY PRECAUTIONS DURING TRENCH EXCAVATION TO PROTECT EXISTING UTILITIES FROM DAMAGE AND SETTLEMENT. 6. ALL CONCRETE BLOCKING FOR HORIZONTAL BENDS, TEES AND VERTICAL BENDS SHALL BE PER COR STD PLANS 330.2 AND 330.3. 7. ALL MECHANICAL JOINTS FITTINGS AND VALVES SHALL HAVE RESTRAINED GLANDS EQUAL TO MEGALUG SERIES 1100 OR ROMAC ROMAGRIP, EXCEPT WHERE SHACKLE RODS ARE INDICATED. 8. SHACKLE RODS SHALL BE INSTALLED PER COR STD PLAN 330.5. 9. PIPE JOINT DEFLECTION SHALL NOT EXCEED HALF OF THE MANUFACTURE'S ALLOWABLE DEFLECTION. 10. SCHEDULING FOR THE WATER CUT -IN CONNECTION AT S 3RD STREET SHALL BE COORDINATED BY THE CONTRACTOR WITH THE CITY PUBLIC WORKS INSPECTOR AND CITY PROJECT MANAGER. ALL CONNECTIONS TO THE EXISTING WATER MAIN NEED TO BE COMPLETED BY CITY MAINTENANCE CREWS. THE CONTRACTOR IS RESPONSIBLE FOR EXCAVATION OF THE TRENCH, SHORING OF THE TRENCH AND SUPPLYING THE MATERIALS NEEDED FOR THE CUT -IN. 0 a J O O T ri7 W W-395503 R-395507 IN COMPLIANCE WITH CITY OF RENTON STANDARDS p RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 ROW UTILITY PLAN AND PROFILE CSK 005 - 8/29/17 m z O 2 O U z O DATE: 08/02/2017 FIELDBOOK: PAGE: 1 DRAWING NO: C5.1 Iz SHEET: OF: 7 26 O 75 O U z O z W rr U U) _ o —z Q MAIN CB— OP=32.35 TOP=32.7 ,IV=29.97 INV=28.7 INV=29. � INV=29. ( �I VE Q AND G G— ICT DRIVE --- ---- ---- -- - ,UCT JgiD _— —Fi �C 12+22.56 SIDEWALK G � Tv P V 8 mTV y�r BRICK \ CONCRETE SIDEWALK WHITWORTH AVE S COORD STREET RESTORATION T FOR CAPPED WATER SRVC (RESTORATION BY COR) ME11 ST 112'+76.56 24. ';TH EX GAS VALVE R LAC EX C�CA T BE REMOV W/ PE HH. S� N T �� Q P� F cn cn O '�? 2 6.1 —TELEPHONE VAULT I11111I%ifrru design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 TV AND TEL NOT LOCATED IN THIS AREA SIDEWALK STA 13+07.34, 24.3' RT EASEMENT REPLACE EX CENTURYLINK HH W/UTILITY VAULT 466TA. SEE NOTE 4 NV=30.6 BUILDING 400 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 N0. 1 REVISION BRICK 08 18 2017 SURVEYED_ 08 29 2017 DESIGNED: 11 15 2017 DRAWN: TTG TTG CHECKED: WE BY DATE APPR APPROVED: BRICK GAS VALVE �aa TELEPHONE JAuL_ I �f j z m Q SCALE: VERTICAL: NAVD 1988 1 " = 10' HORIZONTAL.* NAD 1983/1991 ONE INCH DATUM AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY LEGEND Q L DATUM NAVD 88 RESTORE EX ACP OVER PCCP PER COR STD PLAN 110 AND 110.1 2" GRIND AND HMA OVERLAY SIDEWALK PER NOTE 6 0 SIDEWALK PER COR STD PLAN 102 W/LAMP BLACK PIGMENT TO MATCH EX. SEE NOTE 7 z CEM CONC DRIVEWAY PER COR STD PLAN 104.4 NOTES 1. SEE SHEET C1.0 AND C1.1 FOR GENERAL NOTES. 2. RESTORATION FOR ALL UTILITY CUTS IN EXISTING PVMT SHALL BE PER CITY OF RENTON TRENCH RESTORATION AND OVERLAY REQUIREMENTS. CONTRACTOR SHALL COORDINATE WITH CITY OF RENTON AS REQUIRED AND SHALL PAY ALL COSTS FOR RESTORATION. 3. REMOVE EXISTING FEATURES AS REQUIRED FOR CONSTRUCTION OF NEW IMPROVEMENTS. 4. VAULT/HH/METER BOX COVER SHALL BE AS FOLLOWS: - WATER METER BOXES: ARMORCAST POLYMER CONCRETE COVER W/ NONSKID SURFACE - STREETLIGHT/IRR: FOGTITE CITY OF SEATTLE TYPE 1 HH NONSKID GALV. COVER - ELEC/COMM/PRIVATE UTILITY: SAME FINISH AS STREETLIGHT/IRR. COVERS 5. SIDEWALK AND CURB RESTORATION SHALL BE TO THE NEAREST JOINT. 6. SIDEWALK SHALL BE MEDIUM LIGHT SANDBLAST FINISHED WITH 0.5" DEEP, 2'x2' SAWCUT SCORE JOINTS. CONSTRUCT 4'x4' MOCKUPS AS REQ. TO OBTAIN COR APPROVAL OF SANDBLAST FINISH AND SCORING PRIOR TO CONSTRUCTING PERMANENT WALK. • BLAST MEDIUM - #360 MESH SILICON CARBIDE - SEE SHEET C7.6 FOR SPEC • AIR PRESSURE - 100-110 SI • HOSE DIA - 1 " • HOSE LENGTH - BETWEEN 50'MIN-100'MAX • SPRAY NOZZLE - #5 • APPROXIMATE DISTANCE FROM NOZZLE TO BLASTING SURFACE - 1'-2' • SPRAY DURATION - 5-10 SECONDS • SPRAY PATTERN - CONSTANT CIRCULAR OVERLAPPING MOTION. • SURFACE PREPARATION - CLEAN AND DRY 7. CONTRACTOR TO CONFIRM SIDEWALK PIGMENT COLOR WITH CITY OF RENTON PRIOR TO INSTALLATION. 5 8. CONTRACTOR TO REPLACE RAISED PAVE NT R GS ALON R ADWAY EN LI NECESSARY PER COR STD PLAN H007 AND H007.2 CALL 48 HOURS BEFORE YOU DIG! 811 CITY OF } F RENTON Planning/Building/Public Works Dept. STREET TREE TABLE STA LOCATION TYPE 12+48.6, 22.5' RT ACER GRANDIDENTATUM 'SCHMIDTH'/ ROCKY MOUNTAIN GLOW MAPLE ��12+92.6, ACER GRANDIDENTATUM 'SCHMIDTH'/ ROCKY MOUNTAIN GLOW MAPLE N, O T CU T Q J O O T ri7 T-395501 R-395508 LU IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 ROW FRONTAGE IMPROVEMENT AND RESTORATION PLAN m U) z 0 5 2 0 CU z O DATE: 11/15/2017 FIELDBOOK: PAGE: DRAWING NO: C6.0 ,z SHEET: Q OF: 15 Ln m C'7 O I 0 W U) z 75 O 0 z O z W rr m a z J u_ IN ROW, SAWCUT AND RESTORE PAVING IN PER CITY OF RENTON TRENCH RESTORATION AND OVERLAY REQUIREMENTS EX PAVING ON SITE: IMPORTED — STRUCTURAL FILL COMPACTED IN 8" MAX LIFTS TO 95% DENSITY. IN ROW: CDF BACKFILL PER COS REQ. MIN. AGG. TYPE - 22 COMPACTED TO 95% DENSITY W MAX W=1.5 x PIPE DIA + 18"MIN FOR 6" W=27"MIN 8" W=30"MIN 12"W=36"MIN TYPICAL TRENCH SECTION NC RESTORE 1 LANDSCAPE PER LA PLANS WYE OR 1/8 BEND CLEANOUT NTS Z. 00ol NTS X < /5\ x z NOTES: 00 :5i 30" RING &COVER 1. CATCH BASINS TO BE CONSTRUCTED IN ACCORDANCE W/ ASTM C 478 (AASHTO M 199) & ASTM C 890 UNLESS OTHERWISE SHOWN ON PLANS J OR NOTED IN THE STANDARD SPECIFICATIONS. = 00 .:..:•. -' HANDHOLDS ' 2. HANDHOLDS IN RISER OR ADJUSTMENT SECTION SHALL HAVE 3" MIN. _... 30" DIAMETER '• FLAT SLAB COVER CLEARANCE, STEPS IN CATCH BASIN SHALL HAVE 6" MIN. CLEARANCE. NO STEPS ARE REQUIRED WHEN "B" IS 4' OR LESS. STEPS AND LADDER SIZE PER PANS 3. ALL REINFORCED CAST IN PLACE CONCRETE SHALL BE CLASS A. ALL =~ '' j• ' PRECAST CONCRETE SHALL OBTAIN 4000 PSI @ 28 DAYS. 4. PRECAST BASES SHALL BE FURNISHED W/ CUTOUTS OR KNOCKOUTS. KNOCKOUTS SHALL HAVE A WALL THICKNESS OF 2" MIN. m =" 5. KNOCKOUT OR CUTOUT HOLE SIZE IS EQUAL TO PIPE OUTER DIA. PLUS MORTAR >= z PRECAST BASE W/ CATCH BASIN WALL THICKNESS. MAX. HOLE SIZE IS 36" FOR 48" CATCH FILLET y' INTEGRAL RISER BASIN, 42" FOR 54" CATCH BASIN. MINIMUM DISTANCE BETWEEN ';. GRAVEL BACKFILL HOLES IS 8". 1 "J 6" ~ 1 " FOR PIPE BEDDING, 6" MIN. COMPACTED 6. RING & COVER SHALL BE IN ACCORDANCE W/ STANDARD 48 DIA.-6 54"DIA.-8" * -0" DEPTHFOR PRECAST , SPECIFICATIONS & MEET THE STRENGTH REQ'MTS OF FEDERAL SPECIFICATION RR F621D MATING SURFACES SHALL BE FINISHED BASES ONLY REINFORCING STEEL TO ASSURE NON -ROCKING FIT. (FOR PRECAST BASE W/ INTEGRAL RISER) 0.15 SO. IN/FT IN EACH DIRECTION FOR 48"DIA. 7. ALL BASE REINFORCING STEEL SHALL HAVE A MIN. YIELD STRENGTH 0.19 SQ. IN/FT IN EACH DIRECTION FOR 54"DIA. OF 60,000 PSI & BE PLACED IN THE UPPER HALF OF THE BASE "0"RING SEPARATE CAST IN PLACE OR WITH 1" MIN. CLEARANCE. SEPARATE PRECAST BASE 8, THE BOTTOM OF THE PRECAST CATCH BASIN MAY BE ROUNDED. REINFORCING STEEL (FOR SEPARATE BASE ONLY) 0.23 SQ. IN/FT IN EACH DIRECTION FOR 48"DIA. 0.19 SQ. IN/FT IN EACH DIRECTION FOR 54"DIA. ' FOR SEPARATE CAST PRECAST BASE JOINT IN PLACE ONLY. 5 CB TYPE 2 NTS 7 design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 CONCRETE PRE MOLDED JOINT FILLER 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 CASTING PER NOTE 3 PROVIDE BLOCK IN LANDSCAPED AREAS TEST PLUG RISER DIAMETER SHALL MATCH PIPE RUN nv .�nm� mnivivu� n.� MAIN SEWER JOINTS DOWNSPOUT CONNECTION NTS NO. I REVISION SURFACING PER PLAN PATIO DRAIN, JR SMITH MODEL 2010 WITH 8" TYPE A STRAINER, NICKEL BRONZE FINISH, 4" NO HUB OUTLET FERNCO STRONGBACK RC CPLG PATIO DRAIN Cx4" REDUCER C-45' BENDS 6" PVC SDR 35 ASTM 3034 @ S = 2% MIN. CONNECT TO DOWNSTREAM SD PIPE OR STRUCTURE PER PLANS STD. LIGHT DUTY BRONZE GRATE. ALL GRATES SHALL BE LOCKING 8" DIAMETER NYLOPLAST DRAIN BASIN WITH PVC OR CPEP SLOPE %\ OUTLET STUB AS MFR'D BY TO DRAIN \\HANCOR INC. OUTLET PIPE PER PLAN `D INTEGRALLY MOLDED STUB NOTES: PROVIDE ADDITIONAL STUB AS REQ'D FOR INLEfTING PIPES. RIM AND INVERT ELEVATIONS PER PLANS. AREA DRAIN NTS 00ol NTS FERNCO COUPLING TRANSITION SECTION 90° STREET ELBOW AND EXTENSION AS REQUIRED 6" PVC SDR 35 ASTM 3034 @ S = 2% MIN. TO CONNECT TO SD PER PLAN 08 18 2017 SURVEYED_ 08 29 2017 DESIGNED: 11 15 2017 DRAWN: TTG CHECKED: MJE BY DATE APPR APPROVED: THICKEN CONCRETE PAVING SECTION TO 8" AROUND STORMFILTER 2 UNIT ACCESS COVER (2) #6 REBAR d o A A dof �� a mob ° z o neI A ..e " e c I d 'i e ° e VANED INLET GRATE 2'4" 2'-4" 1(TYP) INSIDE RIM INSIDE RIM 4'-83/4" - OUTSIDE RIM PLAN VIEW FLOATABLES BAFFLE PERMANENT POOL ELEVATION FINISHED GRADE 1111111111�1111= ii11II FILTRATION BAY INLET OUTSIDE SECTION B—B STORMFILTER CB NTS SCALE: VERTICAL. NAVE) 1988 1 " = 10, HORIZONTAL- NAD 1983/1991 ONE INCH DATUM AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY LIFTING EYE (TYP. OF 4) VALL JTLET PIPE ZOM FLOWKIT CHBASIN FOOT '. OF 4) CALL 48 HOURS BEFORE YOU DIG! 811 CITY OF } F RENTON Planning/Building/Public Works Dept. STORMFIL_ CARTRIC PERMANENT POOL ELEVATION CARTR SUP[ FLO CATCHBASIN (TYP. OF 4) CATION NLET UG ON WEIR WALL SECTION A —A 1-CARTRIDGE CATCHBASIN STORMFILTER DATA STRUCTURE ID N/A WATER QUALITY FLOW RATE (cfs) .0044 PEAK FLOW RATE (<1 cfs) .021 RETURN PERIOD OF PEAK FLOW (yrs) 100 CARTRIDGE FLOW RATE (gpm) 7.5 MEDIA TYPE (CSF, PERLITE, ZPG, GAC, PHS) ZPG RIM ELEVATION 32.60 PIPE DATA: I.E. DIAMETER INLET STUB N/A N/A OUTLET STUB 29.85 8" CONFIGURATION O OUTLET 5 SLOPED LID NO SOLID COVER NO NOTES/SPECIAL REQUIREMENTS: T U O Q J AN I� R-395509 W IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 CIVIL DETAILS m C� z O O z O DATE: 11/15/2017 FIELDBOOK: PAGE: DRAWING NO: C7.0 ,z SHEET: OF: 15 WIDTH AND SLOPE VARIES Ln L!7 0� co O Nt 0 W z O 75 O U z O I- z W rr BE PLANTING PER LA PLANS 3" PLUG VALVE AND C.I. VALVE BOX SEE PLANS 4" CEM. CONC. CL. 3000 ° a a 3" CSTC COMPACTED SUBGRADE NOTE: SCORING AND SPECIAL FINISH PER ARCH AND LANDSCAPE DWGS. CEM. CONC. WALK C7.1 NTS EDGE RESTRAINT WHERE PAVERS, REF. LA FOR TYPE PAVERS ARE NOT ADJACENT AND LAYING PATTERN TO STRUCTURE/WALL 1" SAND SETTING BED EXTEND BASE 6" BEYOND 5 EDGE OF PAVERS 6" DEPTH PERMEABLE BASE a. a° a. d d GEOTEXTILE, MIRAFI 140N PROOF ROLLED SUBGRADE NOTES: 1. ALL DEPTHS SHOWN ARE COMPACTED DEPTHS. ALL WORK SHALL BE PER PAVER MFTR'S SPECIFICATIONS. 2. EDGE RESTRAINT SHALL BE "PAVE EDGE RIGID" AND SHALL BE INSTALLED PER MFTR'S RECOMMENDATIONS. 3. PERMEABLE BASE SHALL _BF -�!7Y OF. SEATTLE�MINERAL ,AGGREGATE TYPE, 4. JOINT OPENING AGGREGATE SHALL BE PER PAVER MFTR'S SPECIFICATIONS. A 5. PREPARE AND PROTECT SUBGRADE PER APWA GSP 2-06.3(3) SUBGRADE FOR PERMEABLE PAVEMENTS. COMPACT TO A DEPTH OF 6" TO 90%-92% OF MAXIMUM DENSITY PER WSDOT 2-03.3(14)D. OVER COMPACTED SUBGRADE SHALL BE SCARIFIED TO 8" MIN AND RECOMPACTED. 6. PLACEMENT OF PERMEABLE BASE SHALL BE PER APWA GSP 4-04.3(5) SHAPING AND COMPACTION 2 PERMEABLE PAVE S NTS o" nvrnn nm nlnr NOTE: PUMP POWER SHALL BE PROVIDED VIA DEDICATED CIRCUIT FROM BUILDING ELECTRICAL PANEL PER ELEC. AND NEC REQUIREMENTS. BACKUP POWER SHALL BE PROVIDED BY ON SITE PORTABLE GAS GENERATOR. n4p PLAN INLET 'E a" INLET PIPE EXTERIOR CONTROL PANEL WITH ALARM AND MANUAL GENERATOR TRANSFER SWIITCH. MOUNT TO BLDG PER PLANS RIM 33.20 12" 3" PVC SCH. 80 DISCHARGE PIPING WITH REDUCER AND UNION BEFORE ELBOW \R\ ALARM ELEV. 29.50 2ND PUMP ON ELEV. 28.50 1ST PUMP ON ELEV. 28.00 p' as . PUMP OFF ELEV. 24.33 ° WET WELL BOTTOM ELEV. 23.50 • e° *SUBMERGENCE PER MFR 1. RECOMMENDATION NOTES: SECTION A 1. LIFT STATION MANHOLE SHALL BE 60" DIA. PRECAST CONCRETE, OR APPROVED EQUIVALENT & SHALL MEET H-20 TRAFFIC LOADING CRITERIA. THE PUMPS SHALL BE DUPLEX NON -CLOG PUMPS OF THE SUBMERSIBLE QUICK -DISCONNECT TYPE. THE SYSTEM SHALL BE DESIGNED TO PERMIT GROUND LEVEL REMOVAL OF PUMPING UNITS FROM THE WET WELL FOR INSPECTION OR SERVICE. 2. PUMPS SHALL BE EXPLOSION PROOF HOMA SUBMERSIBLE MODEL TP49V24/V1FN1, 230V, SINGLE PHASE, 1.7 HP, OR APPROVED EQUIVALENT, WITH SEAL PROBE AND SIZED TO OPERATE AT'111 GPM'WITH 10.5 FEET TOTAL DYNAMIC HEAD. -/5\ 3. CONTROL PANEL SHALL BE MODEL IS-WD1P-4-1022 DUPLEX CONTROL PANEL AS MANUFACTURED BY SEEWATER INC., OR APPROVED EQUIVALENT AND SHALL PROVIDE ALTERNATING SERVICE, WITH SEAL FAILURE CIRCUIT INDICATOR, 120V AC CONVENIENCE OUTLET, ALARM LIGHT AND HORN, AND ANTI CONDENSATE HEATER. DUPLEX STORM PUMP NTS Al design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 4" DEPTH PERVIOUS CEMENT CONCRETE A 6" DEPTH PERMEABLE BASE NOTES: 1. ALL DEPTHS SHOWN ARE COMPACTED DEPTHS. 2. PROTECT PERVIOUS CONCRETE DURING CURING BY COVERING W/ PLASTIC SHEETING AND MAINTAIN PLASTIC SHEETING AND/OR OTHER PROTECTION TO ENSURE NO SEDIMENT DEPOSITION OCCURS WHILE SITE, SOILS ARE�QIS_TUR ED 3. PERMEABLE BASE SHALL BE CITY OF SEATTLE MINERAL AGGREGATE TYPE 24. 4. PREPARE AND PROTECT SUBGRADE PER APWA GSP 2-06.3(3) SUBGRADE FOR PERMEABLE PAVEMENTS. COMPACT TO A DEPTH OF 6" TO 90%-92% OF MAXIMUM DENSITY PER WSDOT 2-03.3(14)D. OVER COMPACTED SUBGRADE SHALL BE SCARIFIED TO 8" MIN AND RECOMPACTED. 5. PLACEMENT OF PERMEABLE BASE SHALL BE PER APWA GSP 4-04.3(5) SHAPING AND COMPACTION PERMEABLE PAVEMENT NTS WATERTIGHT CONDUIT COUPLING AND BUSHING 30" RING AND WATERTIGHT C.I. COVER. MARKED "DRAIN". OLYMPIC FOUNDRY #MH69. UPPER RAIL SUPPORT 3" CHECK VALVE, GRUNDFOS COMPRESSION FITTING INTERMEDIATE RAIL SUPPORT 8" INLET IE 26.45 SEEN ■ A 8" OVERFLOW IE 30.00 SET RAIL BRACKETS TO PROVIDE CLEAR ACCESS FROM MH OPENING 6" INLET IE 28.44 SECTION B 4. RAIL SYSTEM: PUMPS SHALL BE INSTALLED ON A RAIL -GUIDED LIFTING ASSEMBLY. BRACKETS SHALL BE MFTR'D BY HOMA OR APPROVED EQUIVALENT, EQUIPPED WITH STAINLESS STEEL PULL RODS. PIPE RAILS AND ALL MOUNTING HARDWARE AND FASTENERS SHALL BE STAINLESS STEEL. 5. LIFTING CABLE: THE STAINLESS STEEL CABLE TO RAISE AND LOWER PUMP SHALL BE OF SUFFICIENT LENGTH TO EXTEND FROM THE PUMP TO THE MANHOLE OPENING. PROVIDE A HOOK TO ATTACH THE CHAIN OR CABLE WHEN NOT IN USE. THE LIFTING CABLE SHALL BE SIZED ACCORDING TO THE PUMP WEIGHT. 6. FLOATS / PUMP CONTROLS: PUMP LEVEL FLOAT CONTROLS AND HIGH-LEVEL ALARM FLOAT SHALL BE MECHANICAL OPERATION, SEEWATER. ALL CONTROLS SHALL BE EXPLOSION PROOF, SUITABLE FOR HAZARDOUS ATMOSPHERE. CONTROLS AND COMPONENTS SHALL BE SUITABLE FOR THE PURPOSES INTENDED AND SHALL BE ACCEPTABLE TO THE CITY/STATE ELECTRICAL INSPECTOR. 7. A FLOAT MOUNTING BRACKET SHALL BE PROVIDED WITH STRAIN RELIEFS THAT SUPPORT AND HOLD THE LEVEL CONTROL CORDS. CONTINUOUS CORDS ARE TO RUN FROM PUMPS AND LEVEL CONTROLS TO THE JUNCTION BOX. SPLICES SHALL ONLY BE ALLOWED IN THE JUNCTION BOX. THE BRACKET SHALL BE FABRICATED FROM STAINLESS STEEL, AND SHALL BE ATTACHED TO THE MANHOLE WITH STAINLESS STEEL FASTENERS. 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION 08 18 2017 SURVEYED_ 08 29 2017 DESIGNED: TTG 11 15 2017 DRAWN: TTG CHECKED: WE BY DATE APPR I APPROVED: SCALE: VERTICAL. NAVD 1988 1 " = 10' HORIZONTAL- NAD 1983/1991 ONE INCH DATUM AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY m Lf) SAWCUT JOINT Ln TIE BARS @ r `14 30" O.C. O o O d d dQ T .Q 3" CRUSHED SURFACING TOP COURSE CONTRACTION/SCORE JOINT PREMOLDED JOINT FILLER. SET FILLER CEM. CONC. CL 4000 Y2" BELOW FIN. SURFACE AND SEAL 1.75" WITH ELASTOMERIC SEALANT KEYWAY ' ^ d - L / v d d - v D ti ° a D ;, d ci D+3' D O o p T T 18 (TYP) \ 3" CRUSHED SURFACING J CONSTRUCTION JOINT TOP COURSE COMPACTED SUBGRADE. NOTE: 1. D = 6" 2. ALL DEPTHS SHOWN ARE COMPACTED DEPTHS. REFER LA FOR FINISH, COLOR, AND SCORING co O O CEM. CONC. PAVEMENT NTS T rr n 40 40 MAINTAIN 6" MIN. . AP . . . . CLEARANCE OVER CRPL13:GRADE AND PROVIDE ETHAFOAM 0- CUSHION BETWEEN CRPL. i FINISHED ckf 35 CONNECT 3rj TO CB AND 8" SD GRADE IE 30.65 I . EX 12" SD PROP. 6" 30 30 IE 28.55t 8 PVC C900 CLEANOUT . . . . SD ® 2%. FIRST 8"X4" WYE WITH 4"X3 PIPE JOINT REDUCER. CONNECT TO SHALL BE ONE : 3" PUMP .DISCHARGE LINE. 25 FULL PIPE STICK 25 APPROXIMATE SOUTH OF CB - 8" WYE CONNECTION FOR LOCATION OF EX. . . . . NO JOINTS OVER STATION OVERFLOW " 52" CEDAR RIVER ' ' ' . . . . CRPL. . . . . . .\PUMP DISCHARGE . . PIPELINE (CRPL) 20 20 STORM DRAIN PROFILE SCALE: HORZ. 1" = 10' VERT. 1" = 5' R-395510 Lu IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 CALL 48 HOURS BEFORE YOU DIG! 811 CITY OF } F RENTON Planning/Building/Public Works Dept. RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 CIVIL DETAILS m z O 73 2 O U z O DATE: 11/15/2017 FIELDBOOK: PAGE: DRAWING NO: C7.1 Iz SHEET: 10 OF: 15 v Z 5� L U Z I- Z W rr a w Q z J 1: FACE OF CURB 5 112' 1" 1/2'R. 1"R'] .. 11:24 70P OF _ - 1/2" R. ROADWAY L 1 CEMENT CONCRETE TRAFFIC CURB AND GUTTER FACE OF ADJACENT CURB FLUSH WITH GUTTER PAN AT SIDEWALK RAMP ENTRANCE 1:24 TOP OF 2" R. ROADWAY Y / T- 6" - DEPRESSED CURB SECTION AT SIDEWALK RAI 6" CEMENT CONCRETE 1i2" R. -- - I" R - SIDEWALK RAMP VARIES OR LANDING I FROM / I 6" TO 0 T --- 6 `r ° r o 3/8" PREMOLDED JOINT FILLER CEMENT CONCRETE PEDESTRIAN CURB AT SIDEWALK RAMPS AND LANDINGS FACE OF ADJACENT CURB 612' SEE DEPRESSED CURB DETAIL THIS SHEET 24 TOP OF 1 1/2" R. ROADWAY T L D ° 4 1 DEPRESSED CURB SECTION AT RESIDENTIAL DRIVEWAYS ONLY. FOR COMMERCIAL DRIVEWAYS SEE STD PLAN 104.2 FACE OF CURB TOP OF ° tD ROADWAY GUTTERSURFACE I �f 1 I 1" R. - \ R. CEMENT CONCRETE TRAFFIC CURB DEPRESSED CURB DETAIL AT RESIDENTIAL OR COMMERCIAL DRIVEWAYS, AND ALLEYS GENERAL NOTES'. ' t 1. See standard plans 102 and 101.1 for curb expansion and contraction joint spacing. 2. Not used. 3. For Depressed Monolithic Driveway Curb IS. Gutter Section see Standard Plan 1042 ��Y o STD. PLAN - 101 PUBLIC WORKS DEPARTMENT CONCRETE CURBS PR 'ED FNTO GreliZimmerman. Public Works Administrat.I l ,r_ BID ITEM (INCLUDES SIDE .. 6 MW�_ VARIES (SEE N( 10 LFOFPAVE r DRIVEWAY REQUIRED 1� 316' EXPAN510N1 JOINT m'P.I (SEE STD PlAN,1 - TSEE1 r' yI 0 m�N CONSTRUCTIONlOIRAMNT -"-' ~ i SEENOTEI CEMENT CONCRETE PSLOPEWITHI(TV J / (8' Cl1Reb GUTTER -J /�v/ ITSBE dl:, 3,Sr'D`ONTRACTION JOINT (TYP I J/ (SEE STD PLAN 102) PLAN VIEW (TYPE C3 SHOWN, C1 a C2 6 C-MAX SIMILAR) (SEE NOTE 9) ES ISEE NOTE 101 � �­: CMIN DEPRESSED CURBb GUTTER-,\ '(SEE NOTE 3) SIOEWN.K /� LB'EXIPANNJOIN'(TYP.) cl:rilrw I n 1 SE 9T0 PLAN 01 SIDEWALK VAOTN 12' FYP) Lfsx n1PN.iN M,x IEwAYJ 98`rull IN. ,GIRTH SEC ION I For NOTES see STD. PLAN 104.2 5 IA 12Y p STD. PLAN - 104.4 Q'$®� PUBLIC WORKS CEMENT CONCRETE DRIVEWAY DEPARTMENT ENTRANCE - TYPES C1 B, C2B, pPRO 1 A Tod C36, and C-MAXB (WITH BUFFER) Gregg Zimmerman, Public Works Administrator SEE NQIE2 /B'R X 5/8"D DUMMY JOINT BEE NOTE2 2'- If b r II I I I 3/8- PREMOLDED JOINT FILLER (TYP) CEMENTCGNCREIE CURB AND GUTTER PLAN VIEW FACE CENTERLINE OF CURB� FRAME b ORATE I 5 1/2", 1"MATCH 1/2- R. 1' R. ROADWAY FRAME AND ORATE - NOT INCLUDED IN CURB AND GUTTEIRSID ITEM SLOPE ° ,R. Ese TOP OF ROADWAY ,EMEC _I D N. • ° P D • 0 D p .. ADJUSTMENT SECTION NOT INCLUDED 1.' .•D' IN CURB AND GUTTER END REM • •• ` CATCH BASIN - NOT INCLUDED D . .•p ,P D, D- IN CURB AND GUTTER END ITEM SECTION / GENERAL NOTES: The intent of this design is to facilitate the removal / of a catch basin with minimal disturbance of the curb. The expansion joints of the adjacent sidewalk shall / be adjusted to be in line with these curb I expansion joints. I I I I I J ISOIVE41C VIEW Vi S3'D• PLAN - 101.1 CEMENT CONCRETE CURB PROD: +.+ PUBLIC WORKS INSTALLATION AT i DEPARTMENT CATCH BASINS DATE SEE COWRAC11 IIL ROUOING 12'IINR(TYP.1 I I _ CURB NOT INGLLI9ED IN°BID ITEM - i s. SEE RAISED EDGE •38'IPREAfOLDED •`'� 1'-0- SIDEWALK ETA THIS SHEET JCNT FILLER ` MIN. (SEE CONTRALTI ( 12-IN, R (T , WITH RAISED EDGE /6URBNOT INCLUDED INEl. ITEM - AH�.�1ER � i ..7.. :• � f f•' :' 38 (IN PR TNT FIL ER f TOP O'ED GRADE I- (INI BELOW LOTH FILLER TOP OF CONCRETE SURFACE SIDEWALK ADJACENT TO CURB t•-D' r D. MIN (SEE CONTRACT) ROU DING 1/2' (IN) R (TYP.) CURB NOT INCLUDED IN BID ITEM - _1 5°L 318-TIN) 1'•..:'�. BRIDGE OR PEDESTRIAN PREMOLDED WALL OR BARRIER RAILING JOINT FILLER ADJACENT TO CURB BARRIER - SEE SIDEWALK (STEEP FI,L SLOPESI CONTRACT PUNS ISEE CONTRACT. WALL OR BARRIER '1 1 ' 1,2- (IN] R (TYP.: -, L� FLUSH � ' L I 15ea CURB NOT INCLUDED IN BID ITEM- SIDEWALK I - VERTICALWALL- 3l8'(INI PREMOLDED ••.«� �._• •-•'Y� 1 SEE DETAIL - JOINT FILLER (TYP.) ' ►' !) 7777 y ADJACENTTO CURB AND RAILING OR WALL Ig+e'Uw PREMOLDED f. JAINT FILLER SIDEWALK BUFFER STRIP (SEE CONTRALTI (SEE NOTE 10) t1 pN SIDEWALK ADJACENT TO WALL DETAIL (TYP'1 CURB NOT INCLUDED IN BID ITEM - �15% 5%MIN 6 LEVEL 1 ••• r ,'SX _� 112' (INI R FINISHED GRACE I' (IN) BELOW TOP CONCRETE SURFACE FOR PLANTING -FLUU SH IF PAVED ADJACENT TO BUFFER STRIP A" m 1 IINI R � • •'. � • G BROONIED FINISH • ` • b' 4' WIDE SMOOTH 0' 4" E �\ TROWELED PERIMETER RAISED EDGE DETAIL 12 \` \` EX END SIDEWALK TRANSVERSE JOINTS TO INCLUDE RAISED EDGE n" 4- CEMENT CONCRETE CURB ` �- (CURB ANDGUTTERSHOWNI NOT INCLUDED IN BID ITEM A' • D \, , For NOTES see STD PLAN 104.2. Paved surfaces must comply with v / STD PLAN 102.1 as applicable 31e i /- CINOSNIDTMEWC.•�. �► �II, 8'T• `• •.•=�+I' --J►-ibIlT�� 1.4 JOINT ILK ONLY B. EXPANSION JOINT IN BOTH 0 CURB AND SIDEWALK I SEE STD PLAN 1011 b ,q •, �b,°�.'•p •, Fes, JOINT AND FINISH PREMOLDED JOINT FILLER DETAIL E EXPANSION JOINT C CONTRACTION JOINT 2Y * PUBLIC WORKS CEMENT CONCRETE ppRODEP LAN - 102 O$ DEPARTMENT SIDEWALK NT AiE -- POLE -- --- - 2'-0" (LUMINAIRE ARM 10'-0" _ DIRECT ACCESS LENGTH) 3.5" DIA (LUMINAIRE ARM LENGTH) TO THE SCREWS u�-i HOLE 45' R 38" 2' TANGENT (� 2.5 R BRACKET -__ � ,.. -�.--- -_ - _. LEADS �r3 r THIS SIDE 4" OD HOLE WIREWAY 06 5/8" I TOP VIEW 12'-0" a o (LUMINAIRE ARM LENGTH) TERMINAL X BLOCK 60' R 46" CONNECTOR OE ^ 1 1/2 P" WIREWAY (LUMINAIRE ARM LENGTH) 4" OD HOLE 52" TANGENT 13.5" TERMINAL BLOCK O HOUSING DETAIL 3.5" DIA HOLE MIN 01 1 19" WIREWAY BRACKET SIDE VIEW DETAILS 6-0 (LUMINAIRE ARM LENGTH) o 7 16' R 22" C> = ROUND CAP ALUMINUM SHROUD = PIGTAIL FROM 11 4" OD HOLE (BY MANUFACTURER) FIXTURE TO MANUFACTURER TERMINAL BLOCK SHALL WELD SHROUD SHALL BE PROVIDED BY MANUFACTURER ALL THE WAY AROUND FOR TERMINAL BLOCK DETAIL, SEE THIS SHEET 8' 0" LUMINAIRE ARM (LUMINAIRE ARM LENGTH) a CLAMP -ON TO ' ¢ LUMINAIRE 30' R 30" LUMINAIRE cJ � CONDUCTORS o z Y DOME STYLE LED LUMINAIRE (WATTAGE AND OPTICS PER PLANS, 4000K CCT, 4" OD HOLE B 120-277V UNIVERSAL DRIVER, WITH FLAT GLASS LENS) BY CYCLONE (OR APPROVED EQUAL) DRIVER SHALL BE INTEGRAL TO THE FIXTURE LUMINAIRE ARM DETAILS DECORATIVE LUMINAIRE LUMINAIRE ARM MOUNTING ti Y O LUMINAIRE AND MOUNTING , TD. PLAN- 117.3 F ®� PUBLIC WORKS BRACKET DETAIL DEPARTMENT ROV D: F_171=f4 55 1/ .DATE nOnn �nA fl 0 design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION �+_ 1DLF OF PAVED DRNEWAY REQUIRED''I. - 38"E%PANSIDN J011.T ITYPI CEMENT n (SEE sm PLAN to21 T `I CONCRETE J � _ SIDEWALK o � o SEE NOTES � I I -- -- LONSTRULTIDN JOINT .. SEE NOTE RAAP WITH 12. Ir _ /l"� CEMENTCONCRETE (B' CURB& SURER SLOPE ITYP', ISEE NOTE 31 18- CONTRACTION JOINT (TYP, (SEE STO PLAN 1Q2) PLAN VIEW vxwes ~-ISEE NOTE 1.) S ]T MAX. SEE NOTE B TYP). fi'MIN �\ 6'MN CEMENT CONCRETE `. BIOEWAIK 6- MIN DEW: CU.AGUT1Hta`I� We' EXPANSION JOINT (TYP) ISEE Nnr'31 SECTION �A ISEE STO PLAN tat) DIFFERENCE IN SLOPE DRNEWAYW PpSRNE SLOPE( SLOPE SHOWN EXAGGERATE.)V7- 6 MIN. DRIVEWAY WI RELATIVE SECTION NEGATIVE BLDPE (SLOPe-� ( • -" SHOWN EXAGGERATED) , /-� F _.. - CEMENT CONCRETE SIDEWALK CEMENTCONCRETE CURB A GUTTER BEE NOTE 31 TES see STD. PLAN 104.2 t�Y O STD. PLAN - 104.1 * s� PUBLIC WORKS CEMENT CONCRETE DRIVEWAY PP �'ED: -R� DEPARTMENT ENTRANCE - TYPE R1 FNTO A Gregg Zimmerman, Public Works Administrator PAINT SPECIFICATIONS: 4' ALUMINUPOLE TOP CAP WITH (3) SET SCRM EWS 0 120' APART ALL ALUMINUM LUMINAIRE, POLE, CAST ALUMINUM " - - BASE PARTS, DECORATIVE BANNER ARMS, AND .. DECORATIVE FLOWER BASKET ARMS SHALL BE xY FACTORY PRIMED AND POWDER COATED. DOME STYLE LED LUMINAIRE 2,_D' (WATTAGE PER PLANS, ALL BANDING AND ALL OTHER MOUNTING HARDWARE 4,DOOK OCT. 120-277V _ -- SHALL BE PAINTED TO MATCH THE COLOR OF THE UNIVERSAL DRIVER, WITH LUMINAIRE POLE. RAT GLASS LENS) BY "JET CYCLONE (OR APPROVED - - FINISH COLOR: 1 9005TX BLACK" EOUAL). DRIVER SHALL BE - INTEGRAL TO THE FIXTURE. - = 4" 0.0. ' ALUMINUM POLE - FOR MOUNTING ARM DETAILS SEE STD DETAIL 117.3 _ --- ______= N4.Ti5- ROUND TUBULAR SECTION 22.25" (NO TAR) PE (2) DECORATIVE BANNER BRACKETS WITH •• ROUND TAPERED POLE SECTION SECURE TOP BANNER BRACKET PRESSURE RELEASE (0.14'/FT) IMTH THROUGH BOLTS AND SPRINGS WITH SHIM TO LEVEL PER / I PROTECTIVE RUBBER MANUFACTURER'S INSTRUCTIONS COATING. LOCKABLE OIE CAST NEMA 3R LOCKING, PRINTABLE, / 2' z 4' DECORATIVE WEATHERPROOF, IN -USE COVER, BANNER MODEL WP1010MC BY INTERMATIC (OR APPROVED 1' DECORATIVE EQUAL) MOUNTED TO GFO BANNER ARM 1WTH FINIAL RECEPTACLE, PAINT TO MATCH POLE. --- - STREET 2' 5* x 5" REINFORCED ALUMINUM LIGHT DECAL NUMBERING PER DECAL j DRIP ACCESS HANDHOLE OPENING DIRECTION ORIENTATION LOCATIONS NUMBERING DETAIL, CITY OF ON POLE WITH i6"-16 HOLE FOR A OF TRAFFIC • ALL HANDHOLE ACCESS RENTON STD. PLAN 121. GROUND CONNECTOR, FLUSH FITTING ALUMINUM DOOR AND GASKET STREET DOORS SHALL BE MOUNTED SECURE BOTTOM BANNER }SEE DECORATIVE i AT 1B0' CURB AND 0' BRACKET WITH 3 ADJUSTABLE FLOWER BASKET SIDEWALK 'RECEPTACLE SHALL BE a STAINLESS STEEL BANDS AND SEE STD DETAIL n7.5 MOUNTED AT 180' SHIM TO LEVEL PER _ < MANUFACTURER'S INSTRUCTIONS `-n 270F 9o' ' CARFLEX CONDUIT AND Ia 4 IRRIGATION HOLE SHALL BE I LOCATED AT 0' ~`0 ISO, I o IS MIN. TO 3.5' MAX POLE SHAFT FABRICATED FROM 6063-T4 ALUMINUM TUBE (POLE ASSEMBLY HEAT TREATED TO T6 CONDITION i AFTER WELDING) 6" OLD. x .250" WALL (POLE) ` TOP OF BASE ACCEPTING 6" STRAIGHT ROUND POLE SECTION. APPLY SILICON SEALANT AT INSTALLATION. 3' x 6" REINFORCED ALUMINUM HANDHOLE OPENING ON POLE WITH %,_16 HOLE FOR A GROUND CONNECTOR, RUSH FITTING ALUMINUM DOOR AND GASKET I j ASTM 356. SPLIT CAST I ALUMINUM BASE WITH 4' x B" 1 REMOVABLE ACCESS DOOR FABRICATED ALUMINUM BASE PLATE EAC!CURB - ASSEMBLY. SEESTD DETAIL 117.5 TOP OF SIDEWALK `1 J FOUNDATION CAP LUMINAIRE AND POLE DETAILS TYPICAL DOWNTOWN STREET =F_____1NTs - Y Gti� o� DOWNTOWN STD. PLAN- 117.4 + PUBLIC WORKS DECORATIVE PEDESTRAIN LUMINAIRE POLE APPROV DEPARTMENT 08Q 18 2017 SURVEYED_ DU 29 2017 DESIGNED: 11 15 2017 TTG DRAWN: TTG CHECKED: MJE BY DATE APPR APPROVED CALL 48 HOURS BEFORE YOU DIG! 811 SCALE: VERTICAL: NAVE) 1988 1 " = 10, HORIZONTAL: NAD 1983/1991AOQ%6CITY OF URI RENTON ONE INCH DATU M e AT FULL SCALE Planning/Building/Public Works Dept. IF NOT ONE INCH SCALE ACCORDINGLY KKKIy^ X CEMENT CONCRETE SIDEWALK CEMENT CONCRETE - CURB 8 GUTTER C,-�Tl (SEE NOTE 3) DEPRESSED MONOLITHIC CURB 8 GUTTER (SEE DETNL THIS SHEET) TYPE C21B, - ISOMETRIC VIEW (COMMERCIAL-, WITH BUFFER) NOTES 1. When a driveway width exceeds 15 feet, construct a full depth Expansion joint with 3 8" joint filler ale the driveway lane lines P 1 1 Ds y FACE OF CURB (see std, plan 102). Construct expansion joints parallel with the (J - etrr _ Of DEPRESSED culls DETAIL anTHssHEET centerline as required at 15' maximum spacing when driveway CONTRACTION JOINT widths exceed 30'. SM PLAN 102 s Iff I- I 6 % r R. TOPOF ROADWAY 2. See std. plan 102 for sidewalk details. - - -- -- / 3. Curb and gutter shown, other curb designs may be specified. See std. plan 101 for curb details. ,Ir "k 4. Not used. 5. The engineer will design all driveways to Include elevations at all NOTE DFBVEWAY LONGITUDINAL EXPANSION points marked with symbol "X". All elevations are at the back of JOINTS SHAM BE FULL DEPTH DEPRESSED MONOLfiHIC CURB 8 GUTTER DETAIL; Curb top on u phlll side. S. Not used. 7. For Driveway Widths see DRIVEWAY STANDARDS (See NOTE 10). The expansion joints (see Bid. plan 102) shall be spaced as shown In the corresponding Isometric view. 8. Slopes shall comply with sections 1l or R303.2.2 or _ -- FACE OF ADJACENT CURB R303.2.3 of the Revised Draft Guidelines for Accessible Public Rights -of -Way of November 23, 2005 (PROWAG). � 9. Curb returns for any Type C-MAX Driveway may be approved on / a case -by -case basis. 1° R--CiU1TER SURFACE 10. STREET STANDARDS = Renton Municipal Code (RMC) -Vill Title IV Development Regulations I ° , •� CHAPTER 6 STREET AND UTILITY STANDARDS Section 4-6-060 STREET STAN DARDS DEPRESSED CURB DETAIL AT RESIDENTIAL OR COMMERCIAL DRIVEWAYS, AND ALLEYS DRIVEWAY STANDARDS = Renton Municipal Code (RMC)_- Title IV Development Regulations Driveway Example: TYPE C1B I CHAPTER 4 R=Resklen6el, C=Comrtlercial CITY-WIDE PROPERTY DEVELOPMENT STANDARDS Number of Lanes, Section 4-4-M PARKING, LOADING AND DRIVEWAY (Ml Lane Commercial) REGULATIONS S=BuRer(Plartin9Sbip) Blank=NOBufler -� * PUBLIC WORKS ■` DEPARTMENT CEMENT CONCRETE DRIVEWAY ENTRANCES - NOTES AND DETAILS LAN - 104.2 PSRO �D: T ;r - Gregg Zimmerman, Public Works Administrator -- CONSTRUCTION NOTES -�R F(IMAlibN C016UCM - _)4`FLEXIBLE - rc 3� JL-AI S SZE SM - 1172 CONDUIT FOR JI' FLEXIBLE IRRIGATION CONDUIT FOR 2" CONDO III BELL I SCH 80 REDUCER IRRIGATION --4 (S X T) Lill SCH 80 REDUCER - = I" CONDUIT FOR 2" CONDUIT PATH BELL END IS X T) - W CI,AMFER IRRIGATION MICROTUBING II SEE TYPICAL LIGHTING 1' CONDUIT FOR IRRIGATION � � MICROTU8ING UNDERGROUND D SYSTEM, CITY OF RENTON STD, PLAN 119, MICROTUBING SEE TYPICOUND TING UNDERGRSYSTEM, CITY �_ FOR JUNCTION BOX AND �° O,AAIFER NICRONBING _.. OF RENTON S�. PLAN 119, - .J � PARING CONFIGURATION. RECEPTACLE WIRING PER 6' FOUNDATION FOR JUNCII BOX AND MIRING - COItl(?GURA 11)N. RECEPTACLE L �7� � `51QEWACT( PLANS _ CAP Iji PER PLA�1S ° - IRRIGATION CONIXIIT SHALL BE yy11 _- -- a ROUTED TO IRRIGATION VALVE 4 91 = BOX. IRRIGATION EQUIPMENT ° o110Al10N CONDUIT SHALL BE _ SHALL NOT BE INSTALLED IN st= ROUi"�0 TOI4tR ATION VALVE ELECTRICAL JUNCTION BOXES T BOX. Ar[GATI EQUIPMENT SHALL NOT BE STALLED Bf r ANCHOR BOLT, ALL THREAD, 4 _ ELECTI�CAL JACYI� BOXER v - - TOTAL,'' OIA, 28" LONG (TYP) ° - ANCHOR BOLT, 4 4 1ANCHOR BOLT TEMPLATE $' d _ TOTAL. %" OA (TYP) --- THICK STEEL PLATE. SIZE TO - -- FIT ANCHOR BOLTS AND BOLT ANCHOR BOLT TEMPLATE Y+" - Q;RCLE THICK STEEL PLATE. 5'ZE TO 3V HEX NUTS, STEEL (6 FIT ANCHOR BOL-S A%D B0-' _ - 4 4 REO'D PER ANCHOR BOLD), ORCLFr _ _ ° a II� FLAT WASHERS (6 REOD PER 3f" HEX NUTS, STEEL (6 ° ANCHOR BOLT) PER ANCHOR BQ'-D), 1-1 FA Fk3LWA�EgS (6 REOb PER 4 ANG'!pR Ell -- 4 GONDUMMUCHOR BOLT DETAIL FOR SPREAD FOUNOAT110 CONDUIT/ANCHOR BOLT DETAIL FDRSHAMOUNDATION A. 18° SPLIT CAST e<3 ALUMINUM BASE 8 WITH REMOVABLE ° ACCESS ODOR r�l IT I IMF ALUMINUM POLE SHAFT SPLIT CAST ((((((���ALUMINUM BASE / WITH REMOVABLE / ACCESS DOOR TOP OF r'_._-. ..... x m � LLUMI!NUM HE ALLOY) 3 IOLTS It 1 3C LG. X XTHK. 'L GUSSETS LLOY) 50° WALL OLE DECORATIVE FLOWER BASKET DETAIL- G1�Y o� DOWNTOWN STD. PLAN- 117.5 PUBLIC WORKS DECORATIVE PEDESTRAIN LUMINAIRE POLE pp VED: DEPARTMENT DETAILS FNTo J ATE T- 39550 2 R - 395511 w IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 m Cn Z 75 2 DATE: U RENTON COMMONS LLC FIELD15/2017 z 215 WHITWORTH AVE S, RENTON, WA 98057 10 PAGE: DRAWING NO: COR STD DETAILS 7 2 ui SHEET: 11 OF: 15 T J T n� LO LO C'7 I ^I III W Z 5O 5G G O U Z O I- Z W rr il.i Q Z J lL FRAME AND VANED GRATE 3r` D 30+ 5 \ S+ OR IT \L ONE 93 BAR HOOP FOR 6" HEIGHT TWO #3 BAR HOOPS FOR 12" HEIGHT RECTANGULAR ADJUSTMENT SECTION a/ #3 BAR EACH CORNEF #3 BAR EACH SIDE #3 BAR EACH .... PRECAST BASE SECTION #3 BAR EACH CORNER 18" MIN. #3 BAR HOOP PIPE ALLOWANCES MAXIMUM PIPE MATERIAL INSIDE DIAMETER REINFORCED OR 12" PLAIN CONCRETE ALL METAL PIPE 15" CPSSP* 12" (STD. SPEC. 9-05.20) SOLID WALL PVC 15" (STD. SPEC. 9-05.120)) PROFILE WALL PVC 15" (STD. SPEC. 9-05.12(2)) * CORRUGATED POLYETHYLENE STORM SEWER PIPE NOTES 1. As acceptable altematives to the rebar shown in the PRECAST BASE SECTION, fibers (placed according to the Standard Specifications), or wire mesh having a minimum area of 0.12 square inches per foot shall be used with the minimum required rebar shown in the ALTERNATIVE PRECAST BASE SECTION. Wire mesh shall not be placed in the knockouts. 2. The knockout diameter shall not be greater than 20". Knockouts shall have a wall thickness of 2" minimum to 2.5" maximum. Provide a 1.5" minimum gap between the knockout wall and the outside of the pipe. After the pipe is installed, fill the gap with joint mortar in accordance with Standard Specification 9-04.3. 3. The maximum depth from the finished grade to the lowest pipe invert shall be 5'. 4. The frame and grate must be installed with the flange down. 5. The Precast Base Section may have a rounded floor, and the walls may be sloped at a rate of 1:24 or steeper. 6. The opening shall be measured at the top of the precast base section. 7. All pickup holes shall be grouted full after the basin has been placed. 8. All grade rings and castings shall be set in mortar in accordance with Standard Specification 9-04.3. SEE NOTE 1 ALTERNATIVE PRECAST BASE SECTION PUBLIC WORKS CATCH BASIN TYPE 1 STD. PLAN - 200.00 DEPARTMENT �t:N,tp MARCH 2O08 4'MIN i' DEPTH 2"- 4'ROCK 3 2' SETTLING DEPTH . r 1.F SEDIMENT STORAGE 1' DEPTH 3/4" - 1-112" WASHED GRAVEL CROSS SECTION NTS V OVERFLOW DEPTH OUTFLOW CHANNELIF -- - CONSTRUCTED BY g EXCAVATION. &MAX -IiO FILTER FABRIC FENCING NOTE: MAY BE CONSTRUCTED BY EXCAVATION OR BY BUILDING A BERM ��Y o PUBLIC WORh� SEDIMENT TRAP STD. PLAN - 211.00 DEPARTMENT P�NTp$ MARCH 2O08 NOTES TOP 1. This frame is designed to accommodate 20" x 24" grates or covers 2. Provide two holes in the frame that are vertically aligned with Ithe grate or cover slots. Tap each hole to accept 24 1/4" a 5/8" - 11 INC x 2"alien head cap screw. 11fi Location of bolt down holes varies among different y� manufacturers. WPM 3. Refer to Standard Specification 9-05.15(2) for additional r r requirements. SECTION RECESSED ALLEN HEAD CAP SCREW ,� 7i_ /8"_I 1/8" 5/8" - 11 NC x 2" \(WWI- IIIBII i - y ISOMETRIC VIEW 1 5/8" -I- \ FRAME r w z v2" SECTION BOLT -DOWN DETAIL DETAIL B SEE NOTE 2 iy PUBLIC WORKS RECTANGULAR FRAME STD. PLAN - 204.00 DEPARTMENT MARCH 2O08 JOINTS IN FILTER FABRIC SHALL BE SPLICED AT POSTS. USE STAPLES, WIRE RINGS, OR EQUIVALENT TO ATTACH FABRIC TO POSTS. 6' MAX. wI POST SPACING MAY BE INCREASED TO 8' IF WIRE BACKING IS USED 2"x2" BY 14 Ga. WIRE OR EQUIVALENT, IF STANDARD STRENGTH FABRIC USED ' FILTER FABRIC i li III � MINIMUM 4"x4"TRENCH BA.KFILL TRENCH WITH NATIVE SOIL , \ / D D2"x4" WOOD POSTS, STEEL FENCE POSTS, REBAR, OR EQUIVALENT NOTES 1. CONDITION OF USE 1.1. SILT FENCE MAY BE USED DOWNSLOPE OF ALL DISTURBED AREAS. 1.2. SILT FENCE IS NOT INTENDED TO TREAT CONCENTRATED FLOWS, NOR IS INTENDED TO TREAT SUBSTANTIAL AMOUNTS OF OVERLAND FLOW. ANY CONCENTRATED FLOW MOST BE CONVEYED THROUGH THE DRAINAGE SYSTEM TO A SEDIMENT TRAP OR POND. 2. DESIGN AND INSTALLATION SPECIFICATIONS 2.1. THE GEOTEXTILE USED MOST MET THE STANDARD LISTED BELLOW. A COPY OF THE MANUFACTURER'S FABRIC SPECIFICATIONS MOST BE AVAILABLE ON SITE. 30-100SIEVESIZE(0.60-1.11MM)FORSILTFILM AOS(ASTM D4751) 50-100 SIEV E SIZE (0,30-0.15MM) FOR OTHER FABRICS WATER PERMITTIVITY (ASTM D491) 0.025EC^-1 MINIMUM GRAB TENSILE STRENCHT(ASTM D4632) 180LBS. MIN. FOR EXTRASTRENGH FABRIC 100LBS. MIN. FOR STANDARD STRENGHT FABRIC GRAB TENSI LE ELONGATION ASTM D4632 30%MAX. ULTRAVIOIATE RESISTANCE(ASTM D435S) 70%MIN. 2.2. STANDARD STRENGTH FABRIC REQUIRES WIRE BACKING TO INCREASE THE STRENGTH OF THE FENCE. WIRE BACKING OR CLOSER POST SPACING MAY BE REQUIRED FOR EXTRA STRENGTH FABRIC IF FIELD PERFORMANCE WARRANTS A STRONGER FENCE. 2.3. WHERE THE FENCE IS INSTALLED, THE SLOPE SHALL NOT BE STEEPER THAN 2H:1V 2.4. IF A TYPICAL SILT FENCE IS USED, THE STANDARD 4X4 TRENCH MAY NOT BE REDUCED AS LONG AS THE BOTTOM 8 INCHES OF THE SILT FENCE IS WELL BURIED AND SECURE IN A TRENCH THAT STABILIZES THE FENCE AND DOES NOT ALLOW WATER TO BYPASS OR UNDERMINE THE SILT FENCE. 3. MAINTENANCE STANDARDS 3A. ANY DAMAGE SHALL BE REPAIR IMMEDIATELY. 3.2. IF CONCENTRATED FLOES ARE EVIDENT UPHILL OD THE FENCE, THEY MUST BE INTERCEPTED AND CONVEYED TO A SEDIMENT TRAP OR POND. 3.3. IT IS IMPORTANT TO CHECK THE UPHILL SIDE OF THE FENCE FOR SIGNS OF THE FENCE CLOGGING AND ACTING AS A BARRIER TO FLOW AND THEN CAUSING CHANNELIZATION OF FLOWS PARALLEL TO THE FENCE. IF THIS OCCURS, REPLACE THE FENCE OR REMOVED THE TRAP SEDIMENT. 3.4s SEDIMENT MOST BE REMOVED WHEN SEDIMENT IS 6 INCHES HIGH. 3.6 IF THE FILTER FABRIC (GEOTEXTILE) HAS DETERIORATED DUE TO ULTRAVIOLET BREAKDOWN, IT SHALL BE REPLACED. STD. PLAN - 214.00 �. PUBLIC WORD SILT FENCE DEPARTMENT MARCH 2008 nOnn WA fl 0 nn design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 NO. I REVISION e 21/2" BOLT -DOWN SL( DETAIL AND NOl TOP "' SECTION (B)i NOTES 1 Provide two slots in the cover that are vertically aligned with the holes in the frame.Location of bolt -down slots varies among different manufacturers. � a Alternative reinforcing designs are acceptable in lieu of the rib design. 3. Refer to Standard Specification 9-05.15(2) for additional requirements 39" R - SEE NOTE 2 4, For Frame details, see City of Renton SECTION Standard Plan 204.00. 5 3/4" 3/4" 5/8" 9" �-{ 3/4" DIAM. HOLE - 1 1/4" 112" DIAM. HANDLE 518 SECTION (�) I L i _ BOLT"DOWN SLOT DETAIL SEE NOTE 1 ISOMETRIC try PUBLIC WORKS RECTANGULAR SOLID STD. PLAN - 204.10 DEPARTMENT METAL COVER MARCH 2O08 EX�S"\NG ,0 PO R=25'MIN. DRIVEWAYS SHALL BE PAVED TO THE EDGE OF R-O-W PRIOR TO INSTALLATION OF THE CONSTRUCTION ENTRANCE TO AVOID DAMAGING OF THE ROADWAY IT IS RECOMMENDED THAT THE ENTRANCE BE CROWNED SO THAT \ RUNOFF DRAINS OFF THE PAD �O. INSTALL DRIVEWAY CULVERT IF THERE D IS A ROADSIDE DITCH PRESENT, AS PER CITY ROAD STANDARDS 4"-8" QUARRY SPALLS / GEOTEXTILE / 12"MIN. THICKNESS --�. �a PROVIDE FULL WIDTH OF NOTES INGRESS/EGRESS AREA 1. CONDITION OF USE 1.1. CONSTRUCTION ENTRANCE SHALL BE STABILIZED WHEREVER TRAFFIC WILL BE LEAVING A CONSTRUCTION SITE AND TRAVELING ON PAVED ROADS OR OTHER PAVED AREAS WITHIN 1,000 FEET OF THE SITE. GRAB TENSILE STREBNGTH(ASTM D4751) 1200 PSI MIN. GRAB TENSILE ELONGATION(ASTM D4632) 30%MAX. MULLEN BURST STRENGTH ASTM D3786-80A) 140OPSIMIN. ADS (ASTM D4751) 20-45 (U.S. STANDARD SIEVE SIZE) 2. DESIGN AND INSTALLATION SPECIFICATIONS 2.1. HOG FUEL (WOOD BASED MULCH) MAY BE SUBSTITUTED FOR OR COMBINED WITH QUARRY SPALLS IN ARES THAT WILL BOT BE USED FOR PERMANENT ROADS. HOG FUEL IS NOT RECOMMENDED FOR ENTRANCE STABILIZATION IN URBAN AREAS. THE INSPECTOR MAY AT ANYTIME REQUIRE THE USE OF QUARRY SPALLS IF THE HOG FUEL IS NOT PREVENTING SEDIMENT FROM BEING TRACKED ONTO PAVEMENT OR IF THE HOG FUEL IS BEING CARRIED ONTO PAVEMENT. 2.2. FENCING SHALL BE INSTALLED AS NECESSARY TO RESTRICT TRAFFIC TO THE CONSTRUCTION ENTRANCE. 2.3. WHENEVER POSSIBLE, THE ENTRANCE SHALL BE CONSTRUCTED ON A FIRM, COMPACTED SUBGRADE. THIS CAN SUBSTANTIALLY INCREASE THE EFFECTIVENESS OF THE PAD AND REDUCE THE NEED FOR MAINTENANCE. 3. MAINTENANCE STANDARDS 3.1. QUARRY SPALLS SHALL BE ADDED IF THE PAD IS NO LONGER IN ACCORDANCE WITH THE SPECIFICATIONS. 3.2. IF THE ENTRANCE IS NOT PREVENTING SEDIMENT BEING TRACKED ONTO PAVEMENT, THEN ALTERNATIVE MEASURES TO KEEP THE STREETS FREE OF SEDIMENT SHALL BE USED. THIS MAY INCLUDE STREET SWEEPING, AN INCREASE IN THE DIMENSIONS OF THE ENTRANCE, OR THE INSTALLATION OF THE WHEEL WASH. IF WASHING IS USED, IT SHALL BE DONE ON AN AREA COVERED WITH CRUSHED ROCK, AND WASHED WATER SHALL DRAIN TO A SEDIMENT TRAP OR POND. 3.3. ANY SEDIMENT THAT IS TRACKED ONTO PAVEMENT SHALL BE REMOVED IMMEDIATELY BY SWEEPING. THE SEDIMENT COLLECTED BY SWEEPING SHALL BE REMOVED OR STABILIZED ON SITE. THE PAVEMENT SHALL NOT BE CLEANED BY WASHING DOWN THE STREET, EXCEPT WHEN SWEEPING IS INEFFECTIVE AND THERE IS A THREAT TO PUBLIC SAFETY. IF IT NECESSARY TO WASH THE STREETS, A SMALL SUMP MUST BE CONDUCTED. THE SEDIMENT WOULD THEN BE WASHED INTO THE SUMP WHERE IT CAN BE CONTROLLED AND DISCHARGED APPROPRIATELY. 3.4. ANY QUARRY SPALLS THAT ARE LOOSENED FROM THE PAD AND END UP ON THE ROADWAY SHALL BE REMOVED IMMEDIATELY. 3.5. IF VEHICLES ARE ENTERING OR EXITING THE SITES AT POINTS OTHER THAN THE CONSTRUCTION ENTRANCE(S), FENCING SHALL BE INSTALLED TO CONTROL TRAFFIC. STD. PLAN - 215.10 PUBLIC WORKS STABILIZED DEPARTMENT CONSTRUCTION ENTRANCE �sNTp MARCH 2O08 08Q 18 2017 SURVEYED_ DU 29 2017 DESIGNED: 11 15 2017 TTG DRAWN: TTG CHECKED: WE BY DATE APPR APPROVED O 4 � of U ❑ 0 o � a O LU LU F \ W \ Z Z of 0 Z) 0 LLLJ DD D D OUTFACE TO STREAM DUMP ND POLLUTI L I TOP NOTES 1. Provide two slots in the grate that are vertically aligned with the holes in the frame. Location of bolt -down slots varies among different manufacturers. Refer to Standard Specification 9-05.15(2) for additional requirements. 9, The thickness of the grate shall not exceed 1 5/8". 4. Unless otherwise specified, vaned grates shall be used with standard frame in the travel way, gutter or shoulder. vaned grates shall not be located within crossroads. Use vaned grates along rolled curbs. a 0 �e0 0C- ISOMETRIC D SLOT - SEE DETAIL \ AND NOTE 1 3/8" (9mm) RECESSED LETTERING 1 114" BOLT -DOWN SLOT DETAIL SEE NOTE 1 ��Y o PUBLIC WORKS RECTANGULAR STD. PLAN - 204.40 DEPARTMENT HERRINGBONE GRATE MARCH 2O08 - � 5" MAX. DRAINAGE GRATE TRIM GRATEFRAME o a ° o SEDIMENT AND DEBRIS OVERFLOW BYPASS D D BELOW INLET GRATE DEVICE FILTERED o WATER o A A A A SECTION VIEW DRAINAGE GRATE - RECTANGULAR GRATE SHOWN BELOW INLET GRATE DEVICE RETRIEVAL SYSTEM (TYP.) OVERFLOW BYPASS(TYP.) ISOMETRIC VIEW NOTES I. Size the Below Inlet Grate Device (BIGD) for the storm water structure it will service. 3. The BIGD shall have a built-in high -flow relief system (overflow bypass). (3, The retrieval system must allow removal of the BIGD without spilling the collected material. 4. Perform maintenance in accordance with Standard Specification 8-01.3(15). tity O PUBLIC WORKS CATCH BASIN FILTER PLAN - 218.30 �= $ DEPARTMENT �1 N tp MARCH 2O08 CALL 48 HOURS BEFORE YOU DIG! 811 SCALE: 1" = 10, HORIZONTAL: NAD 1983/1991 CITY OF RENTON ONE INCH DATU M AT FULL SCALE Planning/Building/Public Works Dept. IF NOT ONE INCH SCALE ACCORDINGLY LO T 0 I T E1 �J J T rr R-395512 W V ) IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 COR STD DETAILS m Cn Z O 5 2 O U Z O DATE: 11/15/2017 FIELDBOOK: PAGE: I-_ DRAWING NO: C7.3 ,z SHEET: OF: DF: 15 LI,I Q z J 1 SHACKLE RODS (TYP) i R I TURNBUCKLES THREAD 6"_ 4 m A' a = < o a o m a w � I o qa a m ,a z w L a 5 TYPE A TYPE B BLOCKING FOR 45' VERTICAL BENDS VB S d L a_ 0 C, N z w mw w 0 z H y w�, W C. J U, 17N z 0 O w OHN w U K a Q 0 0 U O f- p w _ "W U W w U U NZ !n- d UwOz m woZ O1- Z CO�0 o _C, d ~ w > OO N 0 4" 27 3 6' 300 45 64 4 3/4 20 8" 125 5 30 TYPE A BLOCKING ,FOR 111/4' & 221/2' VERTICAL BENDS VB S d L d w w w z C o , Z W w Y N O N Z w w- mm w w (Yj m 0, 1- Q NN _ "w O~ N m C w W U N �� O" J Q O W 10 Um wOw w 0] U1U O L`UU O Z Z Vn- 1- n F=p w U O Z W 0 w Z 0 0- Z O- H U > Oz 0 N a ~ p o 4" 300 111/4 8 2 3/4 18 221/2 12 21/4 24 6" 300 111 /4 12 21/4 3/a 24 221/z 27 3 8" 300 111/a 16 21/2 3/4 24 221 /z 43 31 2 111/4 64 4 1 24 12" 300 221/2 125 5 1 T 36 `R 'INSIDE RADIUS OF SHACKLE ROD BEND 'SHACKLE RODS' S TYPE B `�Y O n PUBLIC WORKS DEPARTMENT CONCRETE BLOCKING FOR VERTICAL FITTINGS STD. PLAN - 330.3 MARCH 2O10 RECESSED LIFT POCKET e SEWER e O � O 10-1/2" 1/4"12-1/2„ 1° I 2-1/4" 14" 2-3/4 Not to Scale FRAME 9,-n" nlAL.rTro 9'_n J )R {I )ABLE I 6'I 11 12 -1 CAST IRON RING AND L NOTES: 1. 8" AND 6" CLEAN -OUT RINGS AND COVERS ON SEWER MAINS SHALL BE EAST JORDAN IRON WORKS, INC. No. 3698 (PRODUCT NO. 00369803) OR APPROVED EQUAL. CLEAN OUT SHALL BE A WATER TIGHT ASSEMBLY', 2. IN UNIMPROVED AREAS, POUR A 1'-0" THICK, 2'- 0" SQUARE CONCRETE, CLASS 3000, PAD AROUND THE RING AND COVER. STD. PLAN - 403.1 .�• PUBLIC WORKS 8" OR 6" CLEANOUT APPROVED:- "` DEPARTMENT FOR SANITARY SEWER MAIN cVASIVaua D We N "n L TOP SECTION VIEW 8" 2'-0" V-6" V-6" V-6" 2 10" 2'-e 1'-6' 1'-6` V-6" 2 12" 2'-s" 2-fY 1'-6 1'-6° 4 16" T-0" 2'-6" 2'-D• V-6" 4 NOTES: 1. CONCRETE SHALL 3000 P.S.I. READY MIX POURED IN PLACE 2 REINFORCED BARS SHALL BE DEFORMED BARS AND TIED TOc ER. 3, FOR FORK AT FADE OF ANCHOR :AU. BE RE COVED. BACKFILL AT FACE OF ANCHOR WLL MUST BEPACTED TO R5%MAX DRY DENSITY BASED AS V557 PRIOR TO REINSTATING SERVICE OF THE WATER MAIN. ELEVATION VIEW NOT TO SCALE N. V RESAR AT 8" ON CENTER O O7HOENDTA SNDARD HOOKS lzY CONCRETE DEADMAN BLOCK STD. PLAN - 330.4 + PUBLIC WORKS DEPARTMENT MARCH 2O16 W (SEE NOTE 7) LIMITS OF PIPE ZONE �Ir BEDDING MATERIAL FOR SANITARY SEWER PIPE O.D. OF PIPE (SEE NOTE 5) FOUNDATION LEVEL / 6" BEDDING FOR SANITARY SEWER NOTES : 1. PROVIDE UNIFORM SUPPORT UNDER BARREL. 2. HAND TAMP UNDER HAUNCHES. 3. COMPACT BEDDING MATERIAL TO 95% MAX. DENSITY EXCEPT DIRECTLY OVER PIPE. HAND TAMP ONLY. 4. PIPE INSTALLATION SHALL BE PER SECTION 7-08 OF THE STANDARD SPECIFICATIONS. 5. PIPE ZONE MATERIAL SHALL BE PER SECTION 9-03.12(3)' OF THE STANDARD SPECIFICATIONS OR PEA GRAVEL. 6. PIPE MUST BE ANCHORED IN SUCH A MANNER AS TO ENSURE FLOW LINE IS MAINTAINED. 7. TRENCH WIDTH SHALL BE PER SECTION 2-09.4 OF THE STANDARD SPECIFICATIONS. STD. PLAN - 40S •�• PUBLIC WORKS PIPE BEDDING AP P OVED: "` DEPARTMENT FOR SANITARY SEWERS 6 weep w",�, DATE nOnn WA fl 0 nn design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 2 BID ADDENDUM # 1 3 BID ADDENDUM 2 5 CONSTRUCTION ASI-1 N0. 1 REVISION L'L_Hly TO CITY METER STACKED METER SECTION 6" MIN. FREE BOXES DRAINING GRAVEL NOTES: 1. ALL DOUBLE CHECK VALVE ASSEMBLIES (DCVA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASHINGTON DEPARTMENT OF HEALTH. 2, THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION OF THE INSTALLATION OF THE DCVA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE DCVA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN. 3. THE DCVA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT, ATTN: WATER UTILITY CROSS -CONNECTION CONTROL SPECIALIST, FAX NO. 425-430-7241. 4. DCVA AND METER BOX SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE WATER METER. Y GT ° 34" TO 2" DOUBLE CHECK VALVE STD. PLAN - 340.8 a + PUBLIC WORKS ASSEMBLY FOR IRRIGATION OR f- DEPARTMENT RESIDENTIAL FIRE SPRINKLER �NTp MARCH 2O10 -EX. SEWER MAIN }, PROPERTY LINE ---SPOOL (LENGTH AS NEEDED) Z a ( I 6" SEWER STUBE ;;, FUTURE 4" SIDE SEWER 2"x 4" STUD MARKING POST PAINTED SEWER MAIN TEE X 6" TEE I 6" CAP J WHITE WITH THE WORD 'SEWER" STENCILED IN 3" HIGH BLACK LETTERS AND #6 WIRE w I WRAPPED AROUND THE STUD AND 7 EXTENDED TO THE TOP OF THE STUD. try � COUPLING (TYP.) a 3 0I II 6"X5"X5" SURFACE CLEANOUT WITH CAST IRON RING AND COVER _ ( (EAST JORDAN IRON WORKS PRODUCT NO. 00367502 OR O ' APPROVED EQUAL, SPECIFY "SEWER" ON LID), (SEE STD. PLAN 403.1 FOR INSTALLATION) rT -_ -------------------------- LJ JM EAGLE THREADED CLEAN -OUT ADAPTER HUB --- BEND AS &PLUG (OR APPROVED EQUAL) REQUIRED EXISTING SANITARY SEWER MAIN -2.0% MIN. SLOPE \ ` FUTURE 4" SIDE SEWER oa SEWER STUB 6"X5"X6" WYE FUTURE 6"x 4" REDUCER `SEWER MAIN SIZE X 6" TEE ACCEPTABLE PROCEDURES FOR SIDE SEWER CONNECTIONS TO EXISTING SEWER MAIN j4 s�1 I A. VITRIFIED CLAY MAIN - CUT IN A NEW PVC "TEE" USING "STRONG -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL). 8, CONCRETE MAIN - CUT IN A NEW PVC "TEE" USING "STRONG -BACK" FLEXIBLE COUPLINGS (FERNCO OR APPROVED EQUAL). C. PVC k C900 PVC MAIN - CUT IN NEW TEE USING RIGID COUPLINGS OR CORE -DRILLED WITH A ROMAC SADDLE (OR APPROVED EQUAL). D. DUCTILE IRON MAIN - CORE -DRILLED WITH A ROMAC SADDLE (OR APPROVED EQUAL) E. MANHOLE CONNECTION - ALL CONNECTIONS TO MANHOLES SHALL BE AT MANUFACTURED KNOCK -OUTS OR TIE_ STRUCTURE SHALL BE CORE -DRILLED. boos 3000 PSI MIX /ph CONCRETE -� i P O�K�NG BLOCKING �!� 45 MAN __--____2X MIN SLOPE 6" TEE HORIZONTAL 6" MIN. SEWER SEWER MAIN MAIN CONCRETE BLOCKING ANGLE OF TEE AT MAIN BETWEEN 25' AND 45' TYPICAL SIDE SEWER NOTE: UNLESS OTHERWISE SHOWN ON PLAN, SIDE SEWER SHALL HAVE A MINIMUM 2.5' COVER AT PROPERTY LINE OR 3-5' LOWER THAN THE LOWEST HOUSE ELEVATION, WHICHEVER IS LOWER. +V STANDARD SIDE SEWER STD. PLAN -406.1 .o PUBLIC WORKS APPR VED: ��� DEPARTMENT INSTALLATION O (SEWER MAIN TO PROPERTY LINE) DAT 08Q 18 2017 SURVEYED_ OU 29 2017 DESIGNED: 11 15 2017 TTG DRAWN: TTG CHECKED: MJE BY DATE APPR APPROVED 4" FL.xP.E. DUCTILE IRON CLASS 52 CEMENT LINED PIPE WITH COLLAR 18" FROM P.E. AS SUPPLIED BY PACIFIC WATER WORKS SUPPLY CO INC. PRIVATE CITY PIPING PIPING 12 3'-4" '] [� Z LONG 7 -L a TEE (MJ x FL) GATE VALVE �.. (FL x MS) -4" 12 � 2' 4,_8„ o O THE BY-PASS ASSEMBLY SHALL BE INCLUDED AS PART OF THE DETECTOR AS PART OF THE DOUBLE CHECK VALVE ASSEMBLY. TOUCH READ PIT LID SENSOR MOUNTED ON STEEL PLATE COVER THROUGH 2" DIA. DRILLED HOLE IN COVER. INSTALL EPDXY NON -SHRINK GROUT 4" DUCTILE IRON CLASS 53 P.E.xP. E. PIPE, CEMENT LINED, LENGTH TO FIT. DEADMAN BLOCK REQUIRED TO BUILDING bJ CONCRETE BLOCKING 12" ALL AROUND 4" GATE VALVE (MJ) WITH INDICATOR POST. INDICATOR POST VALVE SAME SIZE AS DOUBLE CHECK VALVE, PAINTED RED. 4" FLANGED COUPLING ADAPTER EQUAL TO ROMAC. ALL DETECTOR DOUBLE CHECK VALVE ASSEMBLIES SHALL INCLUDE RESILIENT SEATED SHUTOFF DOUBLE CHECK VALVE ASSEMBLY INCLUDES TWO VALVES AND TEST COCKS AND CAPS. AND RESILIENT SEATED SHUTOFF VALVES. APPROVED CROSS -CONNECTION CONTROL ASSEMBLIES PER D.S.H.S. LATEST APPROVED LIST. PLAN TOUCH READ PIT LID SENSOR U UPRECAST CONCRETE VAULT WITH 2 - 3'x3' HINGED MOUNTED ON STEEL PLATE STEEL PLATE COVER. DIMENSION 4'-8" x 7'-0" x 7'-0" COVER THROUGH 2" DIA. UTILITY VAULT CO. 577-LA OR EQUAL. GALVANIZED STEEL LADDER DRILLED HOLE IN COVER. r3' I k_,TTO48" INSTALL EPDXY q•_3" NON -SHRINK GROUT (TYP.) 2" 41 �12„ 2 _9_L' 7. CONCRETE SUPPORT PADS OR ADJUSTABLE PIPE SUPPORTS. ELEVATION NOTE: 6" MIN. DRAIN TO DAYLIGHT OR STORM DRAIN SYSTEM INSTALL GALVANIZED LADDER FOR ACCESS. AFTER FIELD INSTALLATION, MAIN DDCVA AND BY-PASS COMPACTED FOUNDATION DCVA MUST BE TESTED SATISFACTORILY BY A DEPT. OF GR_AyEL HEALTH CERTIFIED BACKFLOW ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT. PRIOR TO ACTIVATION OF NEW LINE. INSTALL.. Y4" FLAR,E.. TEST COCKS WITH Ya' FLARE CAPS, �Y PUBLIC WORKS 4" DDCV ASSEMBLY WITHOUT STD' PLAN - 360.3 DEPARTMENT STANDPIPE OUTSIDE INSTALLATION MARCH 2O10 2 1 MAX. SLOPE _ ICI i _ -III III I I I-1 I I-1 I I- I I I 3 LEVEL BOTTOM 11 1' MIN. _ 2' MIN. SWALE SPACING DEPENDS ON SLOPE GRADIENT NOTES 1. CONDITION OF USE 1.1. REQUIRED AT: 1.1.1. THE TOP OF ALL SLOPES IN EXCESS OF 3HAV AND WITH MORE THAN 20 FEET OF VERTICAL RELIEF. 1.1.2. AT INTERVALS ON ANY SLOPES THAT EXCEEDS THE DIMENSIONS SPECIFIED BELLOW. 2. DESIGN AND INSTALLATION SPECIFICATIONS ` FOR SLOPES STEEPER THAN 2H:1V WITH MORE THAN 10 FEET OF VERTICAL RELIEF, BENCHES MAY BE CONSTRUCTED OR CLOSER SPACED INTERCEPTOR SWALES MAY BE USED. THE DESIRE MEASURE MOST BE DESIGNED BY AN ENGINEER TO EFFECTIVELY INTERCEPT THE HIGH VELOCITY RUNOFF TO A SEDIMENT POND OR TRAP. '2.2. CONSTRUCTION TRAFFIC OVER TEMPORARY SWALES SHALL BE MINIMIZED. 3. MAINTENANCE STANDARDS 3.1. DAMAGE RESULTING FROM RUNOFF OR CONSTRUCTION ACTIVITY SHALL BE REPAIRED IMMEDIATELY. 3.2. IF THE FACILITY DO NOT REGULARLY RETAIN STORM RUNOFF, THE CAPACITY AND/OR FREQUENCY OF THE SWALES SHALL BE INCREASED. ��Y O STD. PLAN - 217.10 .�j PUBLIC WORKS INTERCEPTOR SWALE DEPARTMENT MARCH 2O08 SCALE: VERTICAL: NAVD 1988 1 " = 10, HORIZONTAL: NAD 1983/1991 ONE INCH DATU M AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY AVERAGE SLOPE SLOPE PERCENT FLOWPATH LENGTH 20H:1V 3-8% 300 FEET (10 T020)H:1V 8-10% 200 FEET (4T010)H:1V 10-25% 100 FEET (2T04)H:1V 25-SO% SOfEET CALL 48 HOURS BEFORE YOU DIG! 811 CITY OF RENTON Planning/Building/Public Works Dept. T, S Q D J 0 S-395503 W-395505 R-395513 � IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0 RENTON COMMONS LLC 215 WHITWORTH AVE S, RENTON, WA 98057 COR STD DETAILS m Cn Z O 5 2 O U z O DATE: 11/15/2017 FIELDBOOK: PAGE: 1 DRAWING NO: C7.5 ,z Ir SHEET: 1 4 OF: 15 LO LO M co I 0 `W 1 Z 5O CL G O U Z O I- Z W rr 1;i a z J M Kramer Industries, Inc. 140 Ethel Road West phone: 888-515-9443 Unit U fax: 732-650-0556 Piscataway, NJ 08854 www.KramerindustriesOnline.com "Right From The Start" Silicon Carbide Grit #360 Mesh Typical Physical Properties Color Black Grain Shape Angular Magnetic Content 0.2 - 0.5 % Hardness 9.5 Mohs Specific Gravity 3.2 Proximate Chemical Analysis Sic 98.58 % Fe 0.11 % c 0.05 ( Al 0.02 % Si 0.80 % CaO 0.03 % S1102 0.30 % Mg0 0.05 % Particle Size Distribution Specification (microns) Size Distribution Lower Limit Upper Limit Result2 Ds 33 0.0 41.1 39.58 Ds 504 20.1 23.1 22.57 Ds 945 11.6 100.0 12.08 Notes: FEPA42.GB.1984 R-1993 (Sedigraph) ' Results obtained using Sedigraph settling test. 2 Results of a recent batch. a DS 3 result indicates that 3% of distribution is the result and larger. DS 50 result is median of particle size distribution. 5 DS 94 result indicates that 94% of distribution is the result and larger. SILICON CARBIDE BLAST MEDIA SPEC design PLLC A CIVIL ENGINEERING COMPANY 219 First Avenue S., Suite 401 Seattle WA 98104 206 402 4644 L 1/12� � ° . .4f a✓bP 4 --F O r • ,� a ■ bW a 'SI9'S/8 P P )r 10" tEA rig TYPE "A" BLOCK �0a c¢ v J L . i5 TYP E 1 b. TYPE 2 S' 0.08" 4"'- 0.08 4"t 4"t r it SECTION A -A SECTION B-B 2 :. TYPE "r," PI rlr,ll RPM TYPE 2 RAISED FACE COLORS Type 2a White and Red Type 2c Yellow and Red Type 2d Yellow and Yellow Type 2e White - One Side Only Type 2f Yellow - One Side Only Raised Pavement Markers and Precast Block RAISED PAVEMENT MARKERS (RPM) q.- Traffic Curbs 2 BID ADDENDUM # 1 3 BID ADDENDUM # 2 5 CONSTRUCTION ASI-1 N0. 1 REVISION U'A CITY OF RENTON _ STANDARD PLANS LST DATE:2.Oct-87 DWG NAME: IM-08 SP PAGE: H007 18/2017 1/15/2017 BY I DATE 1' 1' VARIES MIN I MIN MIN I MIN -rxar�r.Sr� IN THE EVENT TRANSVERSE PATCHES EXIS' WITHIN THE AFFECTED STREET, THE LENGD OF THE PATCH SHALL BE EXTENDED TO INCLUDE ANY EXISTING PATCH WITHIN 10 FEET OF THE EDGE OF THE PATCH REQUIR FOR THE NEW CROSSING AND ANY SUBSEQUENT PATCH EDGE WITHIN 10 FEET OF THE EDGE OF THE SECOND PATCH AND SO ON UP TO A TOTAL OF 300 FEET. TRAFFIC FLO 2" HMA 2" TO 8" H )F GUTTER OR )F PAVEMENT :ENTER LINE OR ANE LINE r� 6.5' MIN. --"i 2" DEPTH OF PLANING OR SAWCUT AND REMOVE VARIES: 6.5' MIN. T.111N I1VARIES �I DEPTH OF EXISTING PAVEMENT MIN I MIN I MIN % -{- 2" SAWCUT AND REMOVE OR PLANE, SEAL WITH AR-4000W (EACH SIDE) 2" HMA SAWCUT AFTER BACKFILL - (EACH SIDE) WIDTH OF TRENCH AS REQUIRED BY SIZE OF PROPOSED IMPROVEMENT (SEE STANDARD SPECIFICATION 2-09-4) PLUS AN ALLOWANCEE FOR FOR ANY SHORING. SHORING, IF NEEDED, SHALL MEET THE REQUIREMENTS OF WSDOT STANDARD SPECIFICATION 7-08.3(1)B TRENCH WIDTH 2" - 6" MIN. HMA (SEE NOTE 2) 6" CRUSHED SURFACING TOP COURSE (CSTC) (9-03.9(3)) PER WSDOT STANDARD SPECIFICATIONS, COMPACTED TO 95X MODIFIED PROCTOR, BANK RUN GRAVEL FOR TRENCH BACKFILL 19), GRAVEL BORROW (9-03.14(1)) PER STANDARD SPECIFICATIONS OR NATIVE IAL IF APPROVED IN WRITING BY ENGINEER ON GEOTECH REPORT, COMPACTED TO 95X =D PROCTOR. PIPE ZONE BEDDING: MATERIAL- SEE STANDARD PLAN 110.1. FOR NOTES, SEE STANDARD PLAN 110.1 TYPICAL TRANSVERSE PATCH FOR PUBLIC WORKS SM.' PLAN - 110 • DEPARTMENT FLEXIBLE PAVEMENT OR RIGID PAVEMENT WITH OVERLAY 16 VARIES: 4.5' MIN. LANE LINE MARKING SAWCUT AFTER BACKFILL - DEPTH OF EXISTING PAVEMENT 2" - 6" HMA (SEE NOTE 2) 1 1. EDGE OF PAVEMENT,�EDGE OF CURB & GUTTER, OR MIN. MIN. CENTER OF LANE MARKING 2" HMA (SEE NOTE 2) 6" CRUSHED SURFACING TOP COURSE (CSTC) (9-03.9(3)) PER WSDOT STANDARD 2" SAWCUT AND REMOVE SPECIFCATIONS, COMPACTED TO 95% OR PLANE, SEAL WITH MODIFIED PROCTOR AR-4000W CSTC, BANK RUN GRAVEL FOR TRENCH BACKFILL (9-03.19). GRAVEL BORROW (9-03.14(1)) PER WSDOT STANDARD SPECIFICATIONS OR NATIVE MATERIAL IF APPROVED IN WRITING BY ENGINEER BASED ON GEOTECH REPORT, COMPACTED TO WIDTH OF TRENCH AS REQUIRED BY SIZE OF 95% MODIFIED PROCTOR. 0 PROPOSED IMPROVEMENT (SEE WSDOT . STANDARD SPECIFICATION 2-09.4) PLUS AN PIPE ZONE BEDDING MATERIAL AND COMPACTION AS ALLOWANCE FOR ANY SHORING. SHORING, IF REQUIRED BY THE WSDOT STANDARD SPECIFICATIONS NEEDED, SHALL MEET THE REQUIREMENTS OF FOR THE TYPE OF IMPROVEMENT INSTALLED, EXCEPT: WSDOT STANDARD SPECIFICATION 7-08.3(1)B L I + FOR STORM AND WATER PIPE, PER STD PLAN 220. • FOR SANITARY SEWER, PER STD PLAN 405 TRENCH WIDTH ' FOR JOINT UTILITY TRENCH, SAND WITH 95% PASSING A #4 SIEVE AND LESS THAN 5% PASSING A #200 SIEVE N 0 TES: 1. WHEN EXISTING PAVEMENT IN A LANE REQUIRING A FULL MOTH REPLACEMENT IS BROKEN OR DETERIORATED TO A PAVEMENT CONDITION INDEX RATING OF 70 OR LESS, THE EXISTING PAVEMENT IN THAT LANE, AND FOR THAT DISTANCE SO CLASSIFIED, SHALL BE REMOVED AND REPLACED WITH HMA MATCHING THE DEPTH USED IN THE EXISTING STREET OR THE DEPTH PER CITY STANDARD, WHICHEVER IS GREATER. 2. PRINCIPAL/ MINOR/COLLECTOR, ARTERIAL, & INDUSTRIAL ACCESS STREETS - MATERIAL AND THICKNESS SHALL BE HMA CL }" PG 64-22 AND MATCH EXISTING THICKNESS AND IN NO CASE LESS THAN 6". RESIDENTIAL ACCESS STREETS - HMA CL }" PG 64-22. THE THICKNESS SHALL BE THAT OF THE EXISTING PAVEMENT SECTION AND IN NO CASE LESS THAN 4". 3. WHEN THE "SAWCUT AFTER BACKFILL" ENCROACHES INTO AN ADJACENT LANE, CURB & GUTTER OR SHOULDER, THE AFFECTED LANE SHALL BE PLANED AND OVERLAID WITH HMA FULL WIDTH, THE CURB & GUTTER SHALL BE REMOVED AND REPLACED, OR THE SHOULDER SHALL BE PLANED OR REMOVED AND OVERLAID WITH HMA. 4. IF TRENCH UNDERMINES EXISTING SIDEWALK AND/OR CURBS, THEN THE SIDEWALK AND/OR CURB SHALL BE REPLACED FROM EXPANSION JOINT TO EXPANSION JOINT. 5. IF TRENCHING THROUGH EXISTING DRIVEWAY OR SIDEWALK RAMP, THE DRIVEWAY OR SIDEWALK RAMP SHALL BE REPLACED TO MEET ADA STANDARDS. TYPICAL LONGITUDINAL PATCH STD, PLAN - 110.1 PUBLIC WORKS FOR FLEXIBLE PAVEMENT OR PPR VGll DEPARTMENT RIGID PAVEMENT WITH OVERLAY D.E s: "+ 5Ta kk. r '� , �� c ; R ° -'q c c, '� P v..' 1 t . ig '' ,gW3'Y,s r er't 5.s` t - ' •a'r+T,* U a .. .. Lane Line .: `..: ..'.., .1... NOTES; - NO �., ':. ..r • -< : - ° Y air Right Edge Line ' 1. Recessetl pavement morkers, when specified, sholl be installed at the I 30' 110' 40' d ' 15" _I - locations shown for Type 2W RPM's on multilane one way roadways, an o o type 2YY RPM's on two lane two way roadways. 80, J MULTILANE ONE WAY TRAFFIC M-1. For lane lines. Type 2W RPM'S shall be spaced at 80' intervals on ° Type 2W RPM `Type 2Y RPM Left Edge Line " tangents and horizontal curves with a radius of 5000' or more, and (See Note M-1 (See Note M-2) and M- 3) 40' intervals on horizontol curves having rodii of less than 5000 RPM POSITIONING GUIDE SPACING FOR MULTILANE ONE WAY TRAFFIC M-2. When specified • Type 2Y RPM's shall be placed outside the left edge line. Placement is shorn on "Left Edge of Lone Placement". TWO LANE TWO WAY TRAFFIC Skip Center Line Type 2YY RPM Edge Line -'. x T-l. For center lines, Type 2YY RPM's shall be spaced at 80' intervals on tangents and horizontal curves with o radius of 5000' or more, and 40 nterva Is on hor zontal curves having rad less than 5000' 10'30' 10' 1.IS' IS' 10" 30' 10' 15' Type 2YY RPM's are to be centered between skip lines. ' 1 BO' 80' (See Note T 1) n y rk� s Edge Line ti, RPM POSITIONING GUIDE SPACING FOR TWO LANE TWO WAY TRAFFIC r ...,•... )Ye .+" %. <„ _ _s Toper Length Flat Toper Length Traffic Lane Type 2 RPM Raised Face Colors �7. e YY ellow and ellow p� D•R,C'� Marker 4 pe 2W white - one side onl �O A�o1 rASHv'17 I. Recess Length Type 2Y RPM ype 2Y iyello. - one side only PLAN vlEw LEFT EDGE OF LANE PLACEMENT type 1 RPM Colors (see Note M-2) a IN whlte Top of Pavement Marker pe IY ye ow �0A f 2+ass 60 Top of Pavement Type 2YY RPM (Two wOyl E' C, S7bo• Type 2W RPM lone way) /ONAL 1 t 40 Adhesive 40 EZPtRES OCTOBER 26. 2000 0 MIN MAX: RAISED PAVEMENT ELEVATION vtew MARKING DETAILS - RECESSED PAVEMENT MARKER DETAILS STANDARD PLAN H-3 ADOPTED a CITY OF RENTON STANDARD PLANS aw.a+ LAST DATE: 04/14/2000 a s ���^.T''�•a�, aziX,'~� �,a' '�s �r}bT,�t� gi'� s.. i t �N,LO r, p SP PAGE H007.2 R-395514 IN COMPLIANCE WITH CITY OF RENTON STANDARDS CALL 48 HOURS BEFORE YOU DIG! 811 SURVEYED: SCALE: DATE: VERTICAL: 1983/1991 CITY OF RENTON COMMONS LLC 11/15/2017 DRAWN: DTTG 1 = 10 215 WHITWORTH AVE S, RENTON, WA 98057 PAGE: DRAWN: RENTON PAGE: TTG ONE INCH DATU M • DRAWING NO: CHECKED: AT FULL SCALE Planning/Building/Public Works Dept. COR STD DETAILS C7.6 MJE IF NOT ONE INCH AP P R APPROVED SCALE ACCORDINGLY SHEET: 15 OF: 15 LO LO T 0 0 T W1 LJ T n W 0 m Cn Z O 73 2 O U Z O I- Z W Ir