HomeMy WebLinkAboutR-408333DIVISION 26 - ELECTRICAL SPECIFICATIONS 0%r\I rrf A 1 Abossein Engineering, L.L.C. MECHANICAL - ELECTRICAL CIVIL - LEED FIRE PROTECTION 18465 NE 68TH ST REDMOIND, WA. 98052 PH: (425) 462-9441 FAX: (425) 462-9451 E-Mail: cservice@abossein.com www.abossein.com 1. GENERAL CONDITIONS: A. THE GENERAL CONDITIONS, SUPPLEMENTARY CONDITIONS AND SPECIAL CONDITIONS ARE A PART OF THIS CONTRACT AND APPLY TO THIS SECTION AS FULLY AS IF REPEATED HEREIN. 2. SCOPE: A. THIS SECTION OF SPECIFICATIONS INCLUDES, BUT IS NOT LIMITED TO: ALL LABOR, TOOLS, APPLIANCES, MATERIALS AND EQUIPMENT REQUIRED TO FURNISH AND INSTALL THE COMPLETE INSTALLATION SHOWN ON THE DRAWINGS FOR THIS SECTION OF THE WORK AND/OR IN THE FOLLOWING SPECIFICATIONS, INCLUDING THAT WHICH IS REASONABLY INFERRED. 3. CODES AND REGULATIONS: A. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH APPLICABLE REQUIREMENTS OF PUBLIC AUTHORITIES HAVING JURISDICTION AND UTILITIES FURNISHING SERVICES. B. CODES GOVERNING THIS WORK INCLUDE BUT ARE NOT LIMITED TO THE LATEST APPROVED EDITION OF THE FOLLOWING: NATIONAL FIRE PROTECTION ASSOCIATION'S NATIONAL ELECTRICAL CODE (NEC). OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA). LOCAL ORDINANCES AND REGULATIONS. CITY OF RENTON STANDARDS. 4. STANDARDS: A. ELECTRICAL MATERIAL AND EQUIPMENT SHALL HAVE BEEN TESTED AND LISTED OR LABELED AS CONFORMING TO APPROVED PUBLISHED STANDARDS BY UNDERWRITERS LABORATORIES WHERE SUCH LISTING OR LABELING SERVICE IS AVAILABLE FOR THE CLASS OF MATERIALS OR EQUIPMENT. WHERE APPLICABLE, LISTING OR LABELING SHALL APPLY TO THE COMPLETE ASSEMBLED EQUIPMENT AND NOT TO THE COMPONENTS ALONE. 5. SUBMITTALS: A. THREE COPIES OF MATERIALS LIST, SHOP DRAWINGS AND DATA SHEETS SHALL BE SUBMITTED TO ARCHITECT &/OR CONSTRUCTION MANAGER FOR REVIEW. SUBMITTALS SHALL BE MADE AND FAVORABLE REVIEW SECURED BEFORE MATERIAL AND EQUIPMENT IS INSTALLED. B. MATERIALS LIST SHALL INCLUDE FIXTURES, SWITCHGEAR, PANELS, DEVICES, WIREWAYS, DISCONNECTS, LAMPS AND ALL OTHER SPECIFIED OR UNSPECIFIED STANDARD CATALOGED MATERIALS TO BE USED. THE LIST SHALL INCLUDE MANUFACTURER, TYPE AND SUCH OTHER DESCRIPTIVE DATA AS MAY BE REQUIRED TO DETERMINE THE ACCEPTABILITY OF EACH ITEM. C. SHOP DRAWINGS AND DATA SHEETS FOR EQUIPMENT AND SYSTEMS SHALL BE SUBMITTED WHERE REQUIRED IN THE SPECIFICATION FOR THOSE ITEMS. INCLUDE INFORMATION ON EACH COMPONENT, WIRING DIAGRAMS, LAYOUTS, DIMENSIONS AND SUFFICIENT OTHER DATA TO ESTABLISH COMPLIANCE WITH THE SPECIFICATIONS AND ACCEPTABILITY OF THE EQUIPMENT OR SYSTEM. 6. PERMITS AND DRAWINGS: A. ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE LOCAL AUTHORITY THE REQUIRED DOCUMENTS TO PURCHASE AND SECURE ALL NECESSARY PERMITS AND COORDINATE REQUIRED INSPECTIONS FOR APPROVAL. 7. AS -BUILT DRAWINGS: A. ON A SET OF CONTRACT DRAWINGS, KEPT AT THE SITE DURING CONSTRUCTION, MARK ALL WORK THAT IS INSTALLED DIFFERENTLY FROM THAT SHOWN, INCLUDING ANY REVISED CIRCUITRY, MATERIAL OR EQUIPMENT. UPON CONCLUSION OF WORK, DELIVER TO OWNER'S REP. CONSTRUCTION MANAGER A SET OF SIGNED AND DATED "AS —BUILT" DRAWINGS. 8. GUARANTEE: A. ALL WORK SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER. THE GUARANTEE PERIOD FOR CERTAIN ITEMS SHALL BE LONGER, AS INDICATED IN THE SPECIFICATION FOR THOSE ITEMS. B. SHOULD ANY MALFUNCTION DEVELOP DURING THE GUARANTEE TIME PERIOD DUE TO DEFECTIVE MATERIAL, FAULTY WORKMANSHIP, OR NON-COMPLIANCE WITH PLANS, SPECIFICATIONS, CODES OR DIRECTIONS OF THE OWNER, ARCHITECT, ENGINEER OR INSPECTOR, THE CONTRACTOR SHALL FURNISH ALL NECESSARY LABOR AND MATERIALS TO CORRECT THE MALFUNCTION WITHOUT ADDITIONAL CHARGES. PRODUCTS EXECUTION O m 1. INSTALLATION AND CONNECTION OF WIRING: m 1. INSTALLATION AND CONNECTION OF ELECTRICAL A. CLEAN OUT AND DRY ALL CONDUIT AND WIREWAYS BEFORE PULLING ANY EQUIPMENT: (D WIRES. USE NO LUBRICANT EXCEPT AS RECOMMENDED BY THE WIRE OR CABLE MANUFACTURER. A. EQUIPMENT SHALL BE COMPLETELY CONNECTED TO THE ELECTRICAL SYSTEM r AS NOTED ON DRAWINGS AND PER MANUFACTURER INSTALLATION B. MAKE ALL CONNECTIONS AND SPLICES NECESSARY TO PROPERLY COMPLETE REQUIREMENTS. U THE ELECTRICAL WIRING. CONNECTIONS AND SPLICES SHALL BE MADE ONLY IN PULL AND JUNCTION BOXES. ALL SPLICES SHALL BE MADE WITH B RIGID NON—METALLIC CONDUIT MAY BE USED FOR ALL UNDERSLAB OR UL LISTED UG TYPE EPDXY. UNDERGROUND WORK IN PLACE OF STANDARD WEIGHT RIGID METAL AND 2. INSTALLATION OF CONDUIT: WHERE SPECIFICALLY SPECIFIED. ALL RUNS OF RIGID NON—METALLIC CONDUIT SHALL CONTAIN A SEPARATE GREEN GROUND WIRE ADEQUATELY A. STANDARD WEIGHT RIGID METAL CONDUIT SHALL BE USED WHERE EXPOSED SIZED FOR SERVICE INTENDED. WHERE REQUIRED TO CONTINUE ABOVE TO THE WEATHER, PLACED UNDERGROUND BELOW CONCRETE SLAB, IN SLAB, STUB NON—METALLIC CONDUIT 6" ABOVE SLAB THEN MAKE PROPER CONCRETE OR MASONRY CONSTRUCTION IN CONTACT WITH EARTH, AND TRANSITION TO METAL CONDUIT. WHERE SHOWN ON THE PLANS. C ALL RIGID STEEL CONDUIT INSTALLED IN THE GROUND SHALL BE WRAPPED B. GALVANIZED STEEL ELECTRICAL METALLIC TUBING SHALL BE USED IN ABOVE WITH HUNT'S PROCESS NO. 3, PVC COATED OR ENCASED IN 3" CONCRETE GROUND, INTERIOR, DRY LOCATIONS PROTECTED FROM WEATHER AND ON ALL SIDES. PHYSICAL DAMAGE, AND MAY BE USED IN CONCRETE OR MASONRY CONSTRUCTION NOT IN CONTACT WITH EARTH. D THE MINIMUM SIZES OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER AND SIZE OF CONDUCTORS, UNLESS A LARGER SIZE IS SHOWN, IN WHICH C. LIQUIDTIGHT FLEXIBLE METAL CONDUIT SHALL BE USED FOR FINAL CASE SUCH LARGER SIZE SHALL BE USED. ELECTRICAL CONNECTIONS TO ROOF TOP OR OTHER EQUIPMENT EXPOSED TO THE ENVIORNMENT. G. THE MINIMUM SIZES OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER D. RIGID NON—METALLIC CONDUIT MAY BE USED FOR ALL UNDERSLAB OR AND SIZE OF CONDUCTORS, UNLESS A LARGER SIZE IS SHOWN, IN WHICH UNDERGROUND WORK IN PLACE OF STANDARD WEIGHT RIGID METAL AND CASE SUCH LARGER SIZE SHALL BE USED. WHERE SPECIFICALLY SPECIFIED. ALL RUNS OF RIGID NON—METALLIC Cy) CONDUIT SHALL CONTAIN A SEPARATE GREEN GROUND WIRE ADEQUATELY 4. GROUNDING: Lid SIZED FOR SERVICE INTENDED. WHERE REQUIRED TO CONTINUE ABOVE N SLAB, STUB NON—METALLIC CONDUIT 6" ABOVE SLAB THEN MAKE PROPER A. MAKE GOOD MECHANICAL AND ELECTRICAL CONTACT AT ALL POLES, 0 TRANSITION TO METAL CONDUIT. JUNCTION BOXES, AND WHEREVER THE CONDUIT RUN IS CONNECTED. O PERMANENTLY AND EFFECTIVELY GROUND ALL CONDUIT, FIXTURES, AND 00OTHER E. ALL RIGID STEEL CONDUIT INSTALLED IN THE GROUND SHALL BE WRAPPED EQUIPMENT AS REQUIRED BY ALL APPLICABLE CODES, REGULATIONS WITH HUNTS PROCESS NO. 3, PVC COATED OR ENCASED IN 3 CONCRETE AND STANDARDS. NEC 250 r ON ALL SIDES. Q J 3. UNDERGROUND STREET LIGHT JUNCTION BOXES: 5. CLEANING AND PROTECTION OF PRODUCTS AND PREMISES: A. PER CITY OF RENTON STANDARDS. 4. CONDUITS AND FITTINGS: A. AT FREQUENT INTERVALS DURING THE TIME OF CONSTRUCTION, THE CONTRACTOR SHALL CLEAN UP AFTER HIS WORK AND REMOVE HIS DEBRIS A. STANDARD WEIGHT RIGID METAL CONDUIT SHALL BE HOT DIPPED FROM THE PREMISES, LEAVING THE BUILDING AND GROUNDS CLEAN TO THE GALVANIZED, ALL FITTINGS SHALL BE OF THE SCREW THREAD TYPE. OWNER'S SATISFACTION. COUPLINGS, LOCKNUTS, BUSHINGS, ETC., SHALL BE HOT DIPPED GALVANIZED. B. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT ALL MATERIALS, EQUIPMENT AND PROPERTY, WHETHER ELECTRICAL B. RIGID NON—METALLIC CONDUIT SHALL BE PVC SCHEDULE 40, U.L. OR NOT, FROM DAMAGE AS A RESULT OF HIS WORK. APPROVED. ALL COUPLINGS, FITTINGS, SOLVENT CEMENT, ETC.. O 6. CHECKING AND TESTING OF T EQUIPMENT AND SYSTEMS: O 5. WIRE AND CABLE: O O A. SYSTEMS SHALL BE TESTED FOR SHORT CIRCUITS, OPEN CIRCUITS AND A. WIRE AND CABLE FOR USE ON SYSTEMS OF 50 VOLTS TO 600 VOLTS WRONG CONNECTIONS AND SHALL BE FREE FROM MECHANICAL AND SHALL BE 600 VOLT RATED TYPE THW OR THHN FOR BRANCH CIRCUITS. ELECTRICAL DEFECTS. CIRCUITS SHALL BE TESTED FOR PROPER NEUTRAL T BRANCH WIRING SHALL BE THHN OR THWN. AND GROUND CONNECTIONS. B. WIRE AND CABLE FOR USE ON SYSTEMS OF BELOW 50 VOLTS SHALL BE 300 VOLT PVC INSULATED AND SUITABLE FOR THE CLASS OF WIRING EXCEPT AS OTHERWISE INDICATED OR SPECIFIED. 9. TEMPORARY CONSTRUCTION POWER & TELEPHONE: C. ALL CONDUCTORS SHALL BE COPPER, RATED 75°C MINIMUM. A. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, COST AND MATERIALS REQUIRED FOR INSTALLATION AND MAINTENANCE OF TEMPORARY D. ALL WIRING TO BE COLOR CODED AS FOLLOWS: CONSTRUCTION POWER AND TELEPHONE AS NECESSARY FOR PROJECT COMPLETION. 240/120V PHASE A — BLACK PHASE B — RED NEUTRAL — WHITE 6. LIGHTING FIXTURES: A. FIXTURES SHALL BE COMPLETE WITH ALL REQUIRED ACCESSORIES AND EQUIPMENT, INCLUDING LAMPS, NECESSARY FOR A COMPLETE INSTALLATION. CONTRACTOR SHALL RECEIVE, UNPACK, ASSEMBLE AND INSTALL FIXTURES AS NOTED ON DRAWINGS. REFERENCE FIXTURE SCHEDULE ON SHEET ES2.0 7. NAMEPLATES AND LABELS: A. NAMEPLATES SHALL BE PROVIDED TO IDENTIFY EACH LIGHT POLE AND SIMILAR ITEMS WHICH ARE FURNISHED OR INSTALLED UNDER THIS SECTION AS REQUIRED BY CITY OF RENTON STANDARDS. B. NAMEPLATES SHALL BE ENGRAVED LAMINATED PLASTIC WITH CHARACTERS CUT THROUGH THE BLACK TOP LAYER TO WHITE LAYER BELOW. R-408333 IN COMPLIANCE WITH CITY OF RENTON STANDARDS CALL 811 (2) BUSINESS DAYS BEFORE YOU DIG ABOSSEIN #219017 (UNDERGROUND UTILITY BASE MAP/TOPOGRAPHY PROVIDED BY F'R A8 O OTHERS. DCG CANNOT BE HELD LIABLE LOCATIONS ARE APPROXIMATE) wAsy'ti� FOR ACCURACY. CONTRACTOR SHALL PERMIT SUBMITTAL 03-13-19 SURVEYED: SCALE: DATE: z FIELD VERIFY GRADES, UTILITIES ANDVERTICAL: PERMIT SUBMITTAL WITH CIVIL CHANGES 08-05-19 DESIGNED: NAVD ,988 AS NOTED HORIZONTAL: NAD 1983/1991 CITY OF Q FIRST UKRAINIAN PENTECOSTAL CHURCH 2/5/20 . ALL OTHER EX FEATURES & CITY COMMENTS 11-25-19 JBW �' RENTON 3811 NE 21ST ST PAGE:FIELDOOK: o ��� CONDITIONS. IF CONDITIONS ARE NOT CITY COMMENTS 02-05-20 DRAWN: RENTON, WA 98056 DRAWING NO: �SS�aNAL G AS SHOWN &/OR PLANS CANNOT BE CHECKED: ONE INCHvallp AT FULL SCALE DATUM Planning/Building/Public Works Dept. SPECIFICATIONS E4. CONSTRUCTED AS SHOWN, CONTACT AA IF NOT ONE INCH 5-�-� DCG PRIOR TO CONSTRUCTION. N0. REVISION BY DATE APP APPROVED: SCALE ACCORDINGLY SHEET: 36 OF: 65 U U J Q U) 0 CU W Z W 0- Z Q Z Q VJ IIr H