Loading...
HomeMy WebLinkAboutT-408305CM 00 0 T I O IZ I — DIVISION 26 -ELECTRICAL SPECIFICATIONS 1. GENERAL CONDITIONS: A. THE GENERAL CONDITIONS, SUPPLEMENTARY CONDITIONS AND SPECIAL CONDITIONS ARE A PART OF THIS CONTRACT AND APPLY TO THIS SECTION AS FULLY AS IF REPEATED HEREIN. n e+i+0%nr__ A. THIS SECTION OF SPECIFICATIONS INCLUDES, BUT IS NOT LIMITED TO: ALL LABOR, TOOLS, APPLIANCES, MATERIALS AND EQUIPMENT REQUIRED TO FURNISH AND INSTALL THE COMPLETE INSTALLATION SHOWN ON THE DRAWINGS FOR THIS SECTION OF THE WORK AND/OR IN THE FOLLOWING SPECIFICATIONS, INCLUDING THAT WHICH IS REASONABLY INFERRED. 3. CODES AND REGULATIONS: A. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH APPLICABLE REQUIREMENTS OF PUBLIC AUTHORITIES HAVING JURISDICTION AND UTILITIES FURNISHING SERVICES. B. CODES GOVERNING THIS WORK INCLUDE BUT ARE NOT LIMITED TO THE LATEST APPROVED EDITION OF THE FOLLOWING: NATIONAL FIRE PROTECTION ASSOCIATION'S NATIONAL ELECTRICAL CODE (NEC). OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA). LOCAL ORDINANCES AND REGULATIONS. CITY OF RENTON STANDARDS. 4. STANDARDS: A. ELECTRICAL MATERIAL AND EQUIPMENT SHALL HAVE BEEN TESTED AND LISTED OR LABELED AS CONFORMING TO APPROVED PUBLISHED STANDARDS BY UNDERWRITERS LABORATORIES WHERE SUCH LISTING OR LABELING SERVICE IS AVAILABLE FOR THE CLASS OF MATERIALS OR EQUIPMENT. WHERE APPLICABLE, LISTING OR LABELING SHALL APPLY TO THE COMPLETE ASSEMBLED EQUIPMENT AND NOT TO THE COMPONENTS ALONE. 5. SUBMITTALS: A. THREE COPIES OF MATERIALS LIST, SHOP DRAWINGS AND DATA SHEETS SHALL BE SUBMITTED TO ARCHITECT &/OR CONSTRUCTION MANAGER FOR REVIEW. SUBMITTALS SHALL BE MADE AND FAVORABLE REVIEW SECURED BEFORE MATERIAL AND EQUIPMENT IS INSTALLED. B. MATERIALS LIST SHALL INCLUDE FIXTURES, PANELS, DEVICES, WIREWAYS, DISCONNECTS, AND ALL OTHER SPECIFIED OR UNSPECIFIED STANDARD CATALOGED MATERIALS TO BE USED. THE LIST SHALL INCLUDE MANUFACTURER, TYPE AND SUCH OTHER DESCRIPTIVE DATA AS MAY BE REQUIRED TO DETERMINE THE ACCEPTABILITY OF EACH ITEM. C. SHOP DRAWINGS AND DATA SHEETS FOR EQUIPMENT AND SYSTEMS SHALL BE SUBMITTED WHERE REQUIRED IN THE SPECIFICATION FOR THOSE ITEMS. INCLUDE INFORMATION ON EACH COMPONENT, WIRING DIAGRAMS, LAYOUTS, DIMENSIONS AND SUFFICIENT OTHER DATA TO ESTABLISH COMPLIANCE WITH THE SPECIFICATIONS AND ACCEPTABILITY OF THE EQUIPMENT OR SYSTEM. 6. PERMITS AND DRAWINGS: A. ELECTRICAL CONTRACTOR SHALL SUBMIT TO THE LOCAL AUTHORITY THE REQUIRED DOCUMENTS TO PURCHASE AND SECURE ALL NECESSARY PERMITS AND COORDINATE REQUIRED INSPECTIONS FOR APPROVAL. 7. AS -BUILT DRAWINGS: A. ON A SET OF CONTRACT DRAWINGS, KEPT AT THE SITE DURING CONSTRUCTION, MARK ALL WORK THAT IS INSTALLED DIFFERENTLY FROM THAT SHOWN, INCLUDING ANY REVISED CIRCUITRY, MATERIAL OR EQUIPMENT. UPON CONCLUSION OF WORK, DELIVER TO OWNER'S REP. CONSTRUCTION MANAGER A SET OF SIGNED AND DATED "AS -BUILT" DRAWINGS. 8. GUARANTEE: Abossein Engineering, L.L.C. A. ALL WORK SHALL BE GUARANTEED FOR A MINIMUM PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER. THE GUARANTEE PERIOD FOR CERTAIN ITEMS SHALL BE LONGER, AS INDICATED IN THE SPECIFICATION FOR THOSE ITEMS. B. SHOULD ANY MALFUNCTION DEVELOP DURING THE GUARANTEE TIME PERIOD DUE TO DEFECTIVE MATERIAL, FAULTY WORKMANSHIP, OR NON-COMPLIANCE WITH PLANS, SPECIFICATIONS, CODES OR DIRECTIONS OF THE OWNER, ARCHITECT, ENGINEER OR INSPECTOR, THE CONTRACTOR SHALL FURNISH ALL NECESSARY LABOR AND MATERIALS TO CORRECT THE MALFUNCTION WITHOUT ADDITIONAL CHARGES. MECHANICAL - ELECTRICAL CIVIL - LEED FIRE PROTECTION 18465 NE 68TH ST REDMOIND, WA. 98052 PH: (425) 462-9441 FAX: (425) 462-9451 E-Mail: cservice@abossein.com www.abossein.com ABOSSEIN #21901 r% P9 A 111 1 ^.r ^ 3. INSTALLATION AND CONNECTION OF WIRING: A. CLEAN OUT AND DRY ALL CONDUIT AND WIREWAYS BEFORE PULLING ANY WIRES. USE NO LUBRICANT EXCEPT AS RECOMMENDED BY THE WIRE OR CABLE MANUFACTURER. B. MAKE ALL CONNECTIONS AND SPLICES NECESSARY TO PROPERLY COMPLETE THE ELECTRICAL WIRING. CONNECTIONS AND SPLICES SHALL BE MADE ONLY IN PULL AND JUNCTION BOXES. ALL SPLICES SHALL BE MADE WITH UL LISTED UG TYPE EPDXY. 2. INSTALLATION OF CONDUIT: A. STANDARD WEIGHT RIGID METAL CONDUIT SHALL BE USED WHERE EXPOSED TO THE WEATHER, PLACED UNDERGROUND BELOW CONCRETE SLAB, IN CONCRETE OR MASONRY CONSTRUCTION IN CONTACT WITH EARTH, AND WHERE SHOWN ON THE PLANS. B. GALVANIZED STEEL ELECTRICAL METALLIC TUBING SHALL BE USED IN ABOVE GROUND, INTERIOR, DRY LOCATIONS PROTECTED FROM WEATHER AND PHYSICAL DAMAGE, AND MAY BE USED IN CONCRETE OR MASONRY CONSTRUCTION NOT IN CONTACT WITH EARTH. 10. UNDERGROUND STREET LIGHT JUNCTION BOXES: 11. CONDUITS AND FITTINGS: A. STANDARD WEIGHT RIGID METAL CONDUIT SHALL BE HOT DIPPED GALVANIZED, ALL FITTINGS SHALL BE OF THE SCREW THREAD TYPE. COUPLINGS, LOCKNUTS, BUSHINGS, ETC., SHALL BE HOT DIPPED GALVANIZED. B. RIGID NON-METALLIC CONDUIT SHALL BE PVC SCHEDULE 40, U.L. APPROVED. SCHEDULE 80 FOR STREET CROSSINGS. ALL COUPLINGS, FITTINGS, SOLVENT CEMENT, ETC.. 12. WIRE AND CABLE: A. WIRE AND CABLE FOR USE ON SYSTEMS OF 50 VOLTS TO 600 VOLTS SHALL BE 600 VOLT RATED TYPE THW OR THHN FOR BRANCH CIRCUITS. FEEDERS SHALL BE THHN OR THWN (SEE RISER). B. WIRE AND CABLE FOR USE ON SYSTEMS OF BELOW 50 VOLTS SHALL BE 300 VOLT PVC INSULATED AND SUITABLE FOR THE CLASS OF WIRING EXCEPT AS OTHERWISE INDICATED OR SPECIFIED. C. ALL CONDUCTORS SHALL BE COPPER, RATED 75°C MINIMUM. D. ALL WIRING TO BE COLOR CODED AS FOLLOWS: 208/120V 480/277V PHASE A - BLACK PHASE A - BROWN PHASE B - RED PHASE B - ORANGE PHASE C - BLUE PHASE C - YELLOW NEUTRAL - WHITE NEUTRAL - WHITE/TRACER OR GREY `9j"M:kIILl Eel aL 01fl*5 A. FIXTURES SHALL BE COMPLETE WITH ALL REQUIRED ACCESSORIES AND EQUIPMENT, INCLUDING LAMPS, NECESSARY FOR A COMPLETE INSTALLATION. CONTRACTOR SHALL RECEIVE, UNPACK, ASSEMBLE AND INSTALL FIXTURES AS NOTED ON DRAWINGS. 14. NAMEPLATES AND LABELS: A. NAMEPLATES SHALL BE PROVIDED TO IDENTIFY EACH LIGHT POLE AND SIMILAR ITEMS WHICH ARE FURNISHED OR INSTALLED UNDER THIS SECTION AS REQUIRED BY CITY OF RENTON STANDARDS. B. NAMEPLATES SHALL BE ENGRAVED LAMINATED PLASTIC WITH CHARACTERS CUT THROUGH THE BLACK TOP LAYER TO WHITE LAYER BELOW. BASE MAP/TOPOGRAPHY PROVIDED BY A8� OTHERS. DCG CANNOT BE HELD LIABLE WA FOR ACCURACY. CONTRACTOR SHALL FIELD VERIFY GRADES, UTILITIES AND ALL OTHER EX FEATURES & �21891 NDITIONS. IF CONDITIONS ARE NOT �SS�ONALEN�\ AS SHOWN &/OR PLANS CANNOT BE CONSTRUCTED AS SHOWN, CONTACT S— ZD DCG PRIOR TO CONSTRUCTION. rVr^1 ITI/1\1 1. INSTALLATION AND CONNECTION OF ELECTRICAL EQUIPMENT: A. EQUIPMENT SHALL BE COMPLETELY CONNECTED TO THE ELECTRICAL SYSTEM AS NOTED ON DRAWINGS AND PER MANUFACTURER INSTALLATION REQUIREMENTS. B. RIGID NON-METALLIC CONDUIT MAY BE USED FOR ALL UNDERSLAB OR UNDERGROUND WORK IN PLACE OF STANDARD WEIGHT RIGID METAL AND WHERE SPECIFICALLY SPECIFIED. ALL RUNS OF RIGID NON-METALLIC CONDUIT SHALL CONTAIN A SEPARATE GREEN GROUND WIRE ADEQUATELY SIZED FOR SERVICE INTENDED. WHERE REQUIRED TO CONTINUE ABOVE SLAB, STUB NON-METALLIC CONDUIT 6" ABOVE SLAB THEN MAKE PROPER TRANSITION TO METAL CONDUIT. C. ALL RIGID STEEL CONDUIT INSTALLED IN THE GROUND SHALL BE WRAPPED WITH HUNT'S PROCESS NO. 3, PVC COATED OR ENCASED IN 3" CONCRETE ON ALL SIDES. D. THE MINIMUM SIZES OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER AND SIZE OF CONDUCTORS, UNLESS A LARGER SIZE IS SHOWN, IN WHICH CASE SUCH LARGER SIZE SHALL BE USED. G. THE MINIMUM SIZES OF CONDUIT SHALL BE CODE SIZE FOR THE NUMBER AND SIZE OF CONDUCTORS, UNLESS A LARGER SIZE IS SHOWN, IN WHICH CASE SUCH LARGER SIZE SHALL BE USED. 4. GROUNDING: A. MAKE GOOD MECHANICAL AND ELECTRICAL CONTACT AT ALL POLES, JUNCTION BOXES, AND WHEREVER THE CONDUIT RUN IS CONNECTED. PERMANENTLY AND EFFECTIVELY GROUND ALL CONDUIT, FIXTURES, AND OTHER EQUIPMENT AS REQUIRED BY ALL APPLICABLE CODES, REGULATIONS AND STANDARDS. NEC 250. REFER TO J013 CITY OF RENTON STANDARD GROUNDING DETAIL. 5. CLEANING AND PROTECTION OF PRODUCTS AND PREMISES: A. AT FREQUENT INTERVALS DURING THE TIME OF CONSTRUCTION, THE CONTRACTOR SHALL CLEAN UP AFTER HIS WORK AND REMOVE HIS DEBRIS FROM THE PREMISES, LEAVING THE BUILDING AND GROUNDS CLEAN TO THE OWNER'S SATISFACTION. B. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT ALL MATERIALS, EQUIPMENT AND PROPERTY, WHETHER ELECTRICAL OR NOT, FROM DAMAGE AS A RESULT OF HIS WORK. 6. CHECKING AND TESTING OF EQUIPMENT AND SYSTEMS: A. SYSTEMS SHALL BE TESTED FOR SHORT CIRCUITS, OPEN CIRCUITS AND WRONG CONNECTIONS AND SHALL BE FREE FROM MECHANICAL AND ELECTRICAL DEFECTS. CIRCUITS SHALL BE TESTED FOR PROPER NEUTRAL AND GROUND CONNECTIONS. 9. TEMPORARY CONSTRUCTION POWER & TELEPHONE: A. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, COST AND MATERIALS REQUIRED FOR INSTALLATION AND MAINTENANCE OF TEMPORARY CONSTRUCTION POWER AND TELEPHONE AS NECESSARY FOR PROJECT COMPLETION. PERMIT SUBMITTAL 03-13-19 SURVEYED: SCALE: VERTICAL: NAVD 1988 PERMIT SUBMITTAL WITH CIVIL CHANGES 08-05-19 DESIGNED: AS NOTED HORIZONTAL: NAD 1983/1991 PERMIT SUBMITTAL CITY COMMENTS 02-05-19 JBw DRAWN: ONE INCH DATUM CHECKED: AT FULL SCALE AA IF NOT ONE INCH N 0. REVISION BY DATE APPF APPROVED: SCALE ACCORDINGLY CITY OF RENTON STANDARD Conduit, Innerduct, and Outerduct The conduit PVC - non-metallic shall be of the two types indicated below: 1. Schedule 80 Extra heavy wall PVC conforming to ASTM, Standards, to be used in all installations under roadways. 2. Schedule 40 heavy wall PVC conforming to ASTM Standards. Standard Duty Junction Boxes Junction boxes shall be reinforced concrete with galvanized steel frame anchored in place and galvanized steel cover plate (Diamond pattern). Grounding lugs shall be stainless steel and shall be mechanically and electrically bonded. Junction boxes for copper wire shall incorporate a locking lid per City of Renton Standard Plan. Junction boxes placed in the sidewalks shall have non-skid lids. Luminaires Roadway and pedestrian luminaires shall be LED type, wattages similar to the wattages shown in the luminaire schedules on the Plans. The Contractor shall be responsible for verifying that the performance of the LED luminaires is adequate to comply with the City illumination standards without modifying illumination and signal pole locations shown on the Plans. IES files shall be provided, by the Contractor upon the request, by the Engineer. Optical assembly/reflector shall be made of pre -anodized aluminum, segmented in multiple facets, ventilated perforations and heat sinks to maximize heat dissipation. Reflector shall produce full cut-off Type IV optics to meet the design/performance criteria, 4000K CCT. LED driver module rated for 120V-277V operation, high power factor (90%), with a minimum starting temperature of -40 Degrees Fahrenheit, secured on a tool less access tray with quick disconnects. Individual LED chips or modules shall be removable by means of tool less access in the event they need to be replaced. LED driver not to exceed 750 MA. All fixtures shall be of the some manufacturer and external appearance. Color shall use paint code RAL9005TX Follow standard 121 for street lighting identification numbers. Obtain pole number scheme from Transportation Maintenance Manager Eric Cutsholl 425-430-7423. Photoelectric Controls Photoelectric controls shall be a plug-in device, rated to operate on 120 volts, 60 Hz. The unit shall consist of a light sensitive element connected to necessary control relays. The unit shall be so designed that a failure of any electronic component will energize the lighting circuit. M1 co N O CD CD 00 T a J The photo cell shall be a solid state device with stable turn_on values in the temperature range of C) -55 degrees C to +70 degrees C. In a contactor controlled system, the photo cell to control the (.0 system shall be mounted on the luminaire nearest to the service/contactor cabinet. The photo cell T shall be rated as a 10-year (or higher) life expectancy. CD O O I T 0- U IZ E) U J T-408305 U) 0 U IN COMPLIANCE WITH CITY OF RENTON STANDARDS W DEVELOPMENT ENGINEERING Z W CALL 811 (2) BUSINESS DAYS Nathan Janders 03/19/2020 BEFORE YOU DIG z Q (UNDERGROUND UTILITY CURRENT PLANNING �� z LOCATIONS ARE APPROXIMATE) Angelea Weihs 07/23/2019 Q C TY OF FIRST UKRAINIAN PENTECOSTAL CHURCH DATE: 2/14/20 cc �e FIELDBOOK: PAGE: [;R RENTON 3811 NE21STST 1421V RENTON, WA 98056 DRAWING NO: Planning/Building/Public works Dept. STREET LIGHTING SPECIFICATIONS ESL4.0 Cr SHEET: 41 OF: 65 ILL