WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST
EDITION OF THE CITY OF RENTON PUBLIC WORKS STANDARD
SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD
SPECIFICATIONS, LATEST EDITION AS AMENDED BY THE CITY OF RENTON. A
SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE
WHENEVER CONSTRUCTION IS IN PROGRESS. A PRE -CONSTRUCTION
CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION.
THE CONTRACTOR AND OR DEVELOPER SHALL BE RESPONSIBLE FOR
SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION
UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL CALL
1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING
EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM
IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND "CATALOG CUTS"
FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF
RENTON PRIOR TO BRINGING ANY MATERIALS ON -SITE.
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON
PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND CPIPE JOINTS SHALL
BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE
FITTINGS SHALL BE CLASS 250 AS PER ANSI/AWWA C110/A21.10-82.
ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL
BLACK, TUBE -TYPE, POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS.
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL
BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS AND 48
INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER
FOR ALL WATER MAINS SHALL BE 60 INCHES. ANY DEVIATIONS MUST BE
APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE
UTILITY CONFLICTS OCCUR, THE PROFILE OF THE WATER MAIN SHALL BE
ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM
COVER. PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE
MAN UFACTURER'SSPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY
AS DETERMINED BY THE MODIFIED PROCTOR TEST METHOD (MOD) IN
ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND
85 PERCENT MOD IN UNPAVED AREAS. ALL PIPE ZONE COMPACTION
SHALL BE 95 MOD.
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED
AND POURED IN PLACE IN ACCORDANCE WITH CITY OF RENTON STANDARD
DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL
AND HORIZONTAL BENDS, FITTINGS AND BASE OF HYDRANTS. MEGA -LUGS
(OR SIMILAR PRODUCT) MAY BE REQUIRED ON ALL MECHANICALJOINTS IN
ADDITION TO CONCRETE BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL
HAVE A FOAM PIPE PIG
RUN THROUGH THEM PRIOR TO BEING FLUSHED, DISINFECTED, AND
TESTED. CLEANING, PRESSURE AND PURITY TESTING
SHALL BE DONE IN
THE PRESENCE OF AND UNDER THE SUPERVISION
OF A CITY OF RENTON
UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND
REMOVE PLUGS, CORPORATION STOPS, BLOW -OFF
ASSEMBLIES, AND
THRUST RESTRAINT/ BLOCKING FOR TESTING AND
PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW
MAIN OR BETWEEN THE
NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL
THE NEW PIPING HAS
BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND
PASSED BOTH
PRESSURE AND PURITY TESTING.
8. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A
STATIC PRESSURE OF 150 PSI ABOVE WORKING PRESSURE WITH A
MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A
MAXIMUM OF 5 PSI PRESSURE DROP DURING THE ENTIRE TEST PERIOD.
UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE
SHALL BE DISINFECTED, FLUSHED, AND THEN WATER SAMPLES SHALL BE
TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR.
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND
MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING DAYS PRIOR TO
MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR
SHALL EXPOSE THE EXISTING WATER MAIN AND FITTINGS AT THE
CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND
FITTINGS REQUIRED FOR THE FINAL CONNECTION. THE CONTRACTOR SHALL
EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE
CONNECTION TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL
PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE
SURFACE RESTORATION.
MECHANICAL - ELECTRICAL
Ab o s s e in
CIVIL - LEED
FIRE PROTECTION
Engineering,
18465 NE 68TH ST
REDMOINDD, TA. 98052
PH: (425) 462-9441
L•L'C'
FAX: (425) 462-9451
E-Vail: cseMce®abossein.com
www.abossein.com
POURAZARI #39659
WATER UTILITY NOTES AND SPECIFICATIONS (THESE NOTES SHALL APPEAR ON PROJECTS FOR THE WATER UTILITY)
1. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE
STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON
PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE
LATEST EDITION OF THE WSDOT/APWA STANDARDS AND
SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF
RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A
SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL
TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE
LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS
OTHERWISE APPROVED IN WRITING BY THE PUBLIC WORKS
DEPARTMENT AT
(425) 430-7301. THE POLICE DEPARTMENT, FIRE DEPARTMENT,
AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY
WORK IN THE RIGHT OF WAY.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE
AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID
DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48-HOUR
LOCATORS 800-424-5555.
4. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE
SUBMITTED AT THE PRE -CONSTRUCTION MEETING.
5. DATUM FOR VERTICAL CONTROL SHALL BE NORTH AMERICAN
VERTICAL DATUM 1988 METERS, AND FOR HORIZONTAL CONTROL
SHALL BE NORTH AMERICAN DATUM 1983/1991 METERS UNLESS
OTHERWISE APPROVED BY THE CITY OF RENTON PUBLIC WORKS
DEPARTMENT. REFERENCE BENCHMARK AND ELEVATIONS ARE
NOTED ON THE PLANS.
6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON
PIPE CONFORMING TO AWWA CLLO AND CL 11 OR LATEST
REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND
SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST
REVISION. PIPE JOINTS TO BE PUSH -ON OR MECHANICAL JOINT.
BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND
FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA
C105/A21.5-93 STANDARDS.
7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT
LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN
ACCORDANCE WITH ANSI/AWWA C110/A21.10-87. CEMENT LINING
SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/421/4-90.
IF FITTINGS ARE 3 TO 12 INCHES IN DIAMETER AND HAVE
MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH
EITHER ANSI/AWWA C110-A21.10-87 OR ANSI/AWWA
C153/A21.53-94. THREE (3) INCH TO 12 INCH DIAMETER
FITTINGS, WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED
JOINTS, SHALL BE IN ACCORDANCE WITH ANSI/AWWA
C11O/A21.10.87 OR A COMBINATION OF ANSI/AWWA
C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT
THE PORTION OF THE FITTING WITH A MECHANICAL JOINTS) MAY
BE WITH ANSI/AWWA C153/A21.53-94 AND THAT PORTION OF
THE FITTING WITH FLANGED JOINTS) SHALL BE IN ACCORDANCE
WITH AWWA C110/A21.10-87. ACCEPTANCE TESTING
IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA SECTION
10-4.3 OF ANSI/AWWA C110/A21.10-87 SHALL BE OBTAINED
BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER.
8. GATE VALVES SHALL BE IRON BODY, BRONZED -MOUNTED,
DOUBLE DISC WITH BRONZE WEDGING DEVICE AND 0-RING
STUFFING BOX (AWWA C500) OR OF RESILIENT SEATED TYPE
(AWWA C509).
VALVES SHALL BE DESIGNED FOR A MINIMUM WATER
OPERATING PRESSURE OF 200 PSI. GATE VALVES SHALL BE
CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H.
BASE MAP/TOPOGRAPHY PROVIDED BY
PQU
ll
OTHERS. ABOSSEIN ENGINEERING (AE)
CANNOT BE HELD LIABLE FOR
OF s&,
ACCURACY. CONTRACTOR SHALL FIELD
VERIFY GRADES, UTILITIES AND ALL
0-4
*OTHER EX FEATURES & CONDITIONS. IF
41
CONDITIONS ARE NOT AS SHOWN &/OR
°110 �p�,�l �
PLANS CANNOT BE CONSTRUCTED AS
ST
$'Sr�NAL `�
SHOWN, CONTACT AE PRIOR TO
CONSTRUCTION.
9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE
PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST
PRESSURE) CONFORMING TO AWWA C-502-85 WITH A 6 INCH
MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.)
OF 5-1/4 INCH, TWO 2-1/2 INCH HOSE NOZZLES WITH
NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND
ONE 4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN
6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE
DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER 4.6263.
HYDRANTS SHALL HAVE A 1-1/4 INCH PENTAGON OPERATING
NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
10. THE TWO 2-1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH
CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME
DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS
SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR
POSITIVE WATER TIGHTNESS UNDER TEST PRESSURES.
11. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ
ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH STORZ. STORZ
ADAPTER SHALL BE FORGED AND/OR EXTRUDED 6061-T6
ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION
SHALL HAVE NO LUGS AND TWO SET SCREWS 180 DEGREES
APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER.
STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET, AND
SHALL BE ATTACHED TO HYDRANT ADAPTER WITH 1 /8 INCH,
COATED, STAINLESS STEEL, AIRCRAFT CABLE.
12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT.
PRESERVATIVE PAINT NUMBER 43- 655 SAFETY YELLOW OR
APPROVED EQUAL.
13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON
STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION.
15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A
MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL
WATERMAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM
OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS
OCCUR, WATERMAINS ARE TO BE LOWERED TO CLEAR.
16. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL
BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO
DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES
AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY
FOAM WITH 90A DUROMETER URETHANE RUBBER COATING ON
THE REAR OF "PIG" ONLY.
17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR
SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING
OPERATION.
18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED
TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING
PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE
CITY OF RENTON AND THE WASHINGTON STATE HEALTH
DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE
PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE
QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT EXCEED
THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF
RENTON
STANDARD PLANS & SPECIFICATIONS 7-1 1.3(1 1). THE LOSS IN
PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST
PERIOD.
19. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE
INJECTION OF A 50 PPM (MINIMUM CONCENTRATION)
CHLORINE/WATER SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL
PERMIT SUBMITTAL SURVEYED: GEODETIC SURVEYING SCALE:
SERVICE
DAS INDICATED
DESIGNED: SP
ON DRAWING
DRAWN: S P
ONE INCH
CHECKED: S P AT FULL SCALE
IF NOT ONE INCH
NO. REVISION BY DATE APPR APPROVED: SCALE ACCORDINGLY
NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE
METERED/INJECTED IN ACCORDANCE WITH SECTION 7-
11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS
REFERENCED ABOVE.
20. A PRE -CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO
ANY CONSTRUCTION. A MINIMUM OF FIVE
(5) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR
TO STARTING NEW CONSTRUCTION.
22.IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE
ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION.
23.INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES
AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE
AGREEMENTS, METER APPLICATIONS, CONSTRUCTION PERMITS,
AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF
RENTON.
24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED
BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE
MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR
APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL
NECESSARY EXCAVATION AND MATERIALS ARE TO BE SUPPLIED
BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY
NOTIFICATIONS.
25.INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF
THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY
FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL
CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE ENGINEERS,
SHALL KEEP AS -BUILT DRAWINGS.
26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF
ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO
FINAL TIE-IN.
27. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS,
ETC.) SHALL BE AS MANUFACTURED BY THE STAR
MANUFACTURING COMPANY OF COLUMBUS OHIO, OR EQUAL,
APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT.
28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO
A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY
BE SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT,
SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL
BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES OR
REMOVED TO AN EXISTING EXPANSION JOINT.
29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON
THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED
PATCH TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN 10
DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT
OF FINAL PATCH.
30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC
PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE
SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN UNIMPROVED AREAS
AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS.
VERTICAL NAVD 1988
HORIZONTAL- NAD 1983/1991
DATUM
CALL 811 (2) BUSINESS DAYS
BEFORE YOU DIG
(UNDERGROUND UTILITY
LOCATIONS ARE APPROXIMATE)
CITY OF
JW RENTON
Planning/Building/Public Works Dept.
W-408303
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DEVELOPMENT ENGINEERING %rr
11
Nathan Janders 03/19/2020
FIRST UKRAINIAN PENTECOSTAL CHURCH
3811 NE 21 ST ST
RENTON, WA 98056
FIRE SPRINKLER EXTENSION PLAN NOTES
DATE:
01-30-20
FIELDBOOK:
PAGE
DRAWING NO:
C6.2
SHEET: OF.
18 65
O
M
O
O
O
u
co
LO
N
O
O
ao
T
Q
J
CU
CU
a
O
U
W
Z
w
0-
Z
a
Z
Q
or
V J
H