DESIGN CRTERA:
a) CONTAINMENT FOR FUEL SHOULD BE 10,000 GALLONS.
a) GREEN BEACON NORMALLY ON TO SIGNAL RUNOFF IS
GOING TO STORM SYSTEM. IF THE EMERGENCY SPILL
OCCURS AND THE FLOATS ARE TRIGGERED OR A SPILL
BUTTON IS ACTIVATED THE RED BEACON WILL TURN ON
AND THE GREEN BEACON WILL TURN OFF.
VALVE STATUS PILOT LIGHT:
RED: VALVE CLOSED
GREEN: VALVE OPEN
O GREEN BEACON LIGHT:
NORMAL STORM FLOW INDICATOR
• RED BEACON LIGHT:
FUEL SPILL INDICATOR
i
BOUNDARY AREA FOR SYSTEM SCHEMATIC
APPLIED TO CONTROL PANEL DOOR. ALL
BUTTERFLY VALVES TO HAVE VALVE
STATUS PILOT LIGHT. BEACON LIGHTS TO
INDICATE CURRENT SYSTEM STATUS.
i
SYSTEM
SCALE: NONE
BLDG
7
EXISTING
VAU LT
FUEL CONTAINMENT VAULT
PROPOSED STORAGE VOLUME=5,200 GAL
TOTAL STORAGE VOLUME=11,700 GAL
I
I
of
I / J
Li
LEVEL SENSOR EMCS z
Q
URE-795 o
Q
of
ELECTRICAL
PANEL INLINE CHECK Q
VALVE
I I
BV A7-3
CB (1157-20) — — — — — — — SDMH (1162-20)
rl3V A7-2 BV A7-1
FLOW SPLITTER CATCH BASIN
I
LEVEL SENSOR EMCS I SDMH-1163-20
o CPS
OWS-0072 OIL/WATER I o
SEPARATOR I �
(816-3-CPS)
I z
a
rY
CD
c�
zl
n
MODULAR <
RTU-27-20 WETLAND
(MWS-L-8-24
-V-UG)
CB (1155-20) CB (1156-20)
I
I
INLINE CHECK VALVE
I I
CB (1158-20)
SDMH (1165-20) SDMH (1164-20)
INLINE CHECK VALVE
CONNECT STRUCTURE
TO EXISTING PIPE
FUEL SPILL DIAGRAM AND DOOR FRONT GRAPHICS
SYM
REVISION
BY
APPROVED
DATE
SYM
REVISION
BY
APPROVED
DATE
®
D
Q
ORIG
737 MAX FLIGHTLINE UTILITIES -APRON A Cl PROJECT
RT
TWN
04.13.16
-
APRON A Cl PROJECT - SITE DCN-06
RT
TWN
09.27.16
-
CITY OF RENTON PERMIT REVIEW COMMENTS
RT
TWN
05.23,16
-
RECORD DRAWING - 737 MAX FLIGHTLINE UTILITIES
RT
TWN
10.28.16
-
APRON A Cl PROJECT - SITE DCN-01
RT
TWN
06.13.16
-
APRON A SITE STORMWATER IMPROVEMENTS-30%
RT
TWN
01.17.18
-�
�FG 5
-
APRON A Cl PROJECT - SITE DCN-02
RT
TWN
07.19.16
-
APRON A SITE STORMWATER IMPROVEMENTS-60% TO IFC
RT
TWN
07.14.20
-
APRON A Cl PROJECT - SITE DCN-03
RT
TWN
08.05.16
-
APRON A SITE STORMWATER REVISIONS PER CITY COMMENTS
RT
TWN
09.29.20
C5141 C296,C450
�H
ACCEPTABILITY
THIS DESIGN AND/OR
SPECIFICATION IS APPROVED
R. TEMPLADO
TCHECKED
ENGINEER
APPROVED BY
DEPT.
DATE
T. NEU
CHECKED
sR4a
D. MURATA
��
��
APPROVED
rN
DESCRIPTION OF STORMWATER SYSTEM OPERATION
1. STORMWATER IS COLLECTED FROM THE AREA OF APRON A OUTSIDE OF THE STALLS Al -A7 AND
DIRECTED TO THE EXISTING VALVE VAULT SYSTEM. A GREEN BEACON IS NORMALLY ON.
2. STORMWATER FLOWS THROUGH THE FLOW SPUTTER CATCH BASIN; VALVES BV A7-1 & BV A7-2
ARE NORMALLY OPEN. VALVE BV A7-3 IS NORMALLY CLOSED. (A GREEN BEACON IS ON)
3. IN THE EVENT OF A FUEL SPILL THE FLOW SPUTTER CATCH BASIN DIVERTS A SPILL TO THE FUEL
CONTAINMENT VAULT; VALVES BV A7-1 AND BV A7-2 CLOSE AND VALVE BV A7-3 OPENS. (A RED
BEACON IS ON)
4. MANUAL ACTIVATION OF THE EMERGENCY SPILL PUSH BUTTON WILL TURN OFF A GREEN BEACON
AND TURN ON A RED BEACON AND WILL CLOSE VALVES BV A7-1 AND BV A7-2 AND OPEN VALVE
BV A7-3. FLOW WILL BE DIVERTED TO THE FUEL CONTAINMENT VAULT.
5. THE FLUID LEVEL SENSOR IN THE FUEL CONTAINMENT VAULT WILL NOTIFY THE EMCS SYSTEM OF
FUEL/OIL ACCUMULATION. THE CPS OIL -WATER SEPARATOR SHOULD BE EVACUATED OF FUEL
FOLLOWING A SPILL OR IF MONTHLY INSPECTIONS INDICATED THE PRESENCE OF FUEL.
6. THERE ARE MANUALLY OPERATED GATE VALVES BEFORE AND AFTER THE OIL -WATER SEPARATOR SO
THE OIL -WATER SEPARATOR CAN BE ISOLATED.
7. THERE IS A HYDROCARBON SENSOR IN THE STORMWATER CPS OIL -WATER SEPARATOR. WHEN THERE
IS A FUEL SPILL THAT INCREASES THE OIL LEVEL IN THE SEPARATOR THE SENSOR WILL CLOSE
VALVE BV A7-1 AND BV A7-2 AND OPEN BV A7-3. THE CPS OIL -WATER SEPARATOR SENSOR IS
THE BACK UP ACTIVATION FOR THE FUEL SPILL CONTAINMENT SYSTEM.
8. IN THE EVENT OF A SPILL DURING A POWER OUTAGE ALL VALVES CAN BE OPERATED MANUALLY.
9. THE FUEL CONTAINMENT VAULT HAS A FLUID LEVEL SENSOR THAT NOTIFIES THE EMCS SYSTEM OF
ACCUMULATED FLUID IN THE VAULT. THE FUEL CONTAINMENT VAULT SHOULD BE MONITORED FOR
WATER ACCUMULATION AND WATER EVACUATED SO AS TO PRESERVE CONTAINMENT CAPACITY. THE
FUEL CONTAINMENT VAULT SHOULD BE EVACUATED OF FUEL FOLLOWING A SPILL.
15. THE OIL -WATER SEPARATOR DISCHARGES TO THE MODULAR WETLAND TREATMENT VAULT
(MWS-L-8-24-V-UG) WHICH PROVIDES ENHANCED WATER QUALITY. THE MODULAR WETLAND
SHOULD BE INSPECTED BY A BIO-CLEAN APPROVED SERVICE PROVIDER ON AN ANNUAL BASIS.
WETLAND SOILS MAY OR MAY NOT NEED TO BE REPLACED ANNUALLY.
16. CHECK AND ISOLATION VALVING IS IN THE VALVE PIT ADJACENT TO THE WET WELL.
17. PUSH BUTTON TO BE LOCATED ADJACENT TO ELECTRICAL PANEL NORTH OF THE BUILDING, OR AS
DIRECTED ON SHEET E536.
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
PERMIT SUBMITTAL
DESIGN BY DOWL
R-413740
AIL SUBTITLE
09.29.20 FUEL SPILL DIAGRAM
09.29.20
09.29.20 I TITLE APRON A -SITE STORMWATER IMPROVEMENTS (STALLS A3-A7
09 RENTON SITE
CIVIL MASTER
RENTON, WA DWG No.
W5184605
C514
DATE 09.29.20
05-APRON-A-0514
09.29.20
C37
0
N
\
N
rn
0