HomeMy WebLinkAboutT-4214167n 0 z a E3 Eli A is 0 �ysT AIT Z� S GRADY WAY -- D_ E- m H I Or.ATION MAP IB STATION PANEL:# VOLTAGE RATING: 120 VOLTS,1 PHASE, 2 WIRE BUS RATING: 100 AMPS MAIN BREAKER: 60 AMPS FEED: BOTTOM FAULT CURRENT: _AMPS INTERRUPTING CAPACITY: 22,000 AMPS CIRCUIT DESCRIPTION VA CKT BRKR TECH PYLON 84 1 ti20 SHELTER LIGHTS 20 2 1;28 SPACE 3 SPACE 4 SPACE 5 SPACE 6 GFCI 1 180 7 1/20 CONNECTED LOAD = (84+20+180) = 284 VA= 2.367 AMPS AVERAGE CONTINUOUS LOAD = ((84+20)*1.25+180) = 310 VA = 2.583 AMPS AVERAGE WIRING SCHEDULE RUN NO. X CONDUIT SIZE SHELTER LIGHTS TECH PYLON GROUND SERVICE PULLTAPE REMARKS 1 2" RGS METRO SERVICE 244 2" RGS METRO ELEC. #12-3TC 248 #8G 2 2" RGS METRO ELEC. 1 SPARE LABEL CONDUCTORS WITH "SHELTER 3 3/4" RGS METRO ELEC. #12-3TC LIGHTS" LABEL CONDUCTORS WITH'TECH 4 1" RGS METRO ELEC. 248 #BG PYLON" 5 1.5" PVC METRO ITS 1 SPARE 0 2"PVC METRO ITS 1 SPARE 60% SUBMITTAL TP Jacobs V�' o4'vggpi C,Y, 2 ~ 92 g ��concord Nc. REVISION BY APP'N DATE �fONAL ENGINEERING 248, #8G EXISTING PSE UNDERGROUND #12-3TC 2-#8, #8G ELECTRICAL WIRING SCHEMATIC PSEUNDERGROUND TRANSFORMER VAULT v EXISTING UNDERGROUND POWER �I 2-#4 L1 King County METRO PSESECONDARY JUNCTION BOX GENERAL NOTES 1. THE 60% DESIGN REFLECTS THE ASSUMPTION THAT PSE WILL PROVIDE CONDUIT(S) FROM THE PRIMARY SERVICE POINT TO A SECONDARY SERVICE JUNCTION BOX FOR STATION SERVICE CONNECTIONS PRIOR TO I LINE RAPIDRIDE CONSTRUCTION. 2. HAND DIGGING OR EXCAVATION BY VACTOR MAY BE REQUIRED FOR CONDUIT INSTALLATION IN AREAS WHERE EXISTING UNDERGROUND UTILITIES AND/OR TREE ROOTS ARE PRESENT, 3. SEE 1S1.09 FOR STATION PLANS AND AMENITIES DETAILS. CONSTRUCTION NOTES OTRENCH AND INSTALL CONDUIT. ADJUST ROUTING OF TRENCH AND CONDUIT TO AVOID UTILITIES. OBORE AND INSTALL CONDUIT. ADJUST BORE TO AVOID UTILITIES AS NEEDED. RESTORE AREA DISTURBED BY BORING OPERATIONS BACK TO PRECONSTRUCTION CONDITION. OPROVIDE AND INSTALL 60A, 120V METRO NON -METERED ELECTRICAL SERVICE PEDESTAL, SEE 1E2.01 FOR MOUNTING AND FOUNDATION DETAIL. THE FRONT DOOR OF THE CABINET SHALL BE ORIENTED AS SHOWN BY "F" ON THE PLANS. O4 PROVIDE AND INSTALL WSDOT TYPE 2 JUNCTION BOX PER WSDOT STANDARD PLAN J40.10-04. LABEL JUNCTION BOX "METRO". LEGEND 9 METRO ELECTRICAL SERVICE PEDESTAL 10 JUNCTION BOX TYPE 2 BURIED I CONCEALED CONDUIT METRO BUS SHELTER A METRO TECHNOLOGY PYLON 0' 10, 20' METRO TRANSIT CAPITAL DIVISION RAPIDRIDE 1 LINE RENTON SEGMENT ELECTRICAL SITE PLAN ID# 59841 SCALE: 1"=10' dhPJ4A1.1411�004 DRAWNGNO 1E1.01 SHEETNO'. OF 467 Xxxx T-4214167 R-4214467