HomeMy WebLinkAboutR-411513w
0
w
w
cn
3
FACE OF CURB
fi 1YC' � 1•
10R. y i R. 1:24
+ ) TOP OF
' col 1R-R. FIDADWAV
t
1 �
CEMENT CONCRETE
TRAFFIC CURB AND GUTTER
FACE OF ADJACENT CURB
$ 117 FLUSH WITH GLITTER
PAN AT SIDE WALK
RAMP ENTRANCE
1:12 1,24
TOP OF
Tn"R. ROADWAY
�. bAL
1•-0" F i
DEPRESSED CURB SECTION
AT $IWEWALK RAMPS
30,
$• CEMENTCONCRETE
112-R. " •1 1' R_ SIDEWALK RAMP
VARIES I OR LANDING
FROM j
s•rD a
e'
T
aM'FREMOLDED
JOINT FILLER
CEMENT CONCRETE
PEDESTRIAN CURB
AT SIDEWALK RAMPS AND LANDINGS
FACE OF ADJACENT CURS
SEE DEPRESSED CURB DETAIL THIS SHEET
124
TOPOP
t y- 1112, R. ROADWAY
2- 1
y
I
1 er �}
DEPRESSED CURB SECTION
AT RESIDENTIAL DRIVEWAYS ONLY.
FOR COMME NQlAL DRIVEWAYS SEE STD PLAN 104.2
FACE OF CURB
FACE OF ADJACENTCURB
r 1 d ' ' GUTTER SURFACE
P
PREMOLGEO
JOINT FILLER
E FULL -DEPTH
EXPANSION JOINT
-01rR'F~
fi Ire 1-
1 iC R. 1' R.
� TOP OF
ROADWAY
1
I
e V4-
CEMENT CONCRETE
TRAFFIC CURB
tiEPRI=SSED CURB DETAIL
AT RESIDENTIAL OR COMMERCIAL DRIVEWAYS, AND ALLEYS
GENERALNOTES:
1. See standard plans 102 and 101.1 for curb oxpansIOrl and contraction kink spacing,
2. ExpanslonJoint shall be full depth, 318' (In.) premolded ]Dint filler.
3. Far Depressed Monolithic OMway Curb 8 Gutter Section, son Slardned Plan IM.2
M. PLAN - 101
a PUBLIC WORKS CEMENT CONCRETE CURBS I'I'I" '1 I.:I:I
DEPARTMENT
f
t 10%DIFFERE
B MIN. VARIES ISEE NOTE T BMW.
(SEE NOTE S)
ISEE N01E al
LF OF PAVED
W
DRIVEWAY REIXIIRED
3V EXPANSION JOINT ICE
(SEE STD. PUN 1D21
CC
SR
�
w
1
g
SEE NOTE 5
N
x
I
gl
It
RENT
KAETE
;WALK
"v SEE NOTEt -�
CEMENT CONCRETE
R tlP WITH IN 1V
PE
SLO(TYP.) B
CUNGUTTER
SEE NO 31
1B' CONTRACTION JOWT (TYP)
(SEE STD. PLAN 1021 PLAN VIEW
VAR ES
_
ISEE NOTE 101 7
03% 1.t SEE NOTE 0(1
:I
6' PAIN
G-MIN
CEMENT CONCRETE 6 111N
DEPR SSEO LURE A GUTTER
SIDEWALK
10' EXPANSION JOINT ITYP.)
ISEE NOTE II
SECTION O
ISEE STD. PLAN 10Z
NW -
DRIVEWAYWIP
1Q RDYP.I
EXAGGERAIEDI
SIOEWALX M1ORi
15Y,
SItNE SLOPE (SLOPE SHOYM
' C .
ORIVEYJAY
.-MIN
D D •
Ie EurovE �' b
• "
BE
ON O
TYPE R1B - ISOMETRIC VIEW
(RESIDENTIAL, WITH BUFFER)
CEMENTCONCRETE
CURB S GUTTER
(SEE NOTE 3)
For NOTES STD. PLAN 104.2 1
ti� O STD. PLAN - 104.3
[, PUBLIC WORKS CEMENT CONCRETE DRIVEWAY
I. DEPARTMENT ENTRANCE - TYPE R1 B APR VE1
Fp t0 III
Encompass
ENGINEERING & SURVEYING
Western Washington Division
165 NE Juniper Street, Suite 201 ■ IssaQuah, WA 98027 • Phone: (425) 392-0250
Eastern Washington Division
407 Swiftwater Blvd. • Cle Elum, WA 98922 - Phone: (509) 674-7433
BEEN k 9/8"h OUNIM'i ,IOIN1
SEE NOTE2
723/8'R
-D
e
1lru
I
T = 3
+,'R- FRf:'.li1l [: .101I:T r ., ER (,!PI -
rif
LT
CEMENT CONCRETE
- - - � -
CURB AND GUTTM
I-
PIAIN t;Il N
FACE OF _ CENTERLINE OF
rS CURB �y FRAME A ORATE -
B 1 /2" 1 13•
5 1 1„ (I OB') _
FRAME ANG GRATE - NUT 14CLUDi_S
OD1 - IN CU RE AND G UTTER BID rTpA
R
ROADWAY
SLOPE
TOP OF
• _ RECEZE
ROADWAY
b 4 AOJU5 rMENT SECTION - NCrr INCLUDED
IN CURB AND GUTTER WD REM
' CATCH BAal N -NOT INCLUDED
• - IN Ck.'FW ANU GUTT!-7i &D rFEM
SEC W4 V
Y
�
The intent of this design Is to foal rate the removal
Gf a Gatch basin with minimal disturbance
of the curb,
r
The the
exparlaion joints of
adjacent sidewalk shall
be adjusted to be In
I •
line with these curb
expansion joints_
1
I I
I
II
SM. PLAN - 101.1
CEMENT CONCRETE
CURB
PR01 D:
P Jf3 IC '•',oRKs
INSTALLATION AT
s D:. PATtI N1r'N7
CATCH BASINS
LANDING
GRADE BREAK
SEE CONTRACT PLANS -
4'-0"MIN
CEMENT CONCRETE
SIDEWALK - SEE NOTE 5
FLARE (TYP,)
318" EXPANSION
JOINT (TYP.) - SEE
STANDARD PLAN F-30.10
GRADE BREAK
1k*�
CURB, OR CURB
AND GUTTER -
SEE NOTE 4
FACE OF CURB
MEASURED PARALLEL
TO CURB (TYP.)
J
0
0
Z
z
LL
m
Ix
( A CURB RAMP WIDTH 4'- 0" MIN LANDING TO MATCH
YCURB RAMP WIDTH - SEE CONTRACT PLANS
LANDING
I GRADE BREAK
CURB RAMP
SEE CONTRACT PLANS - CEMENT CONCRETE
4-0" IN. SIDEWALK - SEE NOTE 5
I
PROVIDE SMOOTH TRANSITION
TO SIDEWALK WIDTH
(TYP,) SEE CONTRACT PLANS -
* 4'- 0" MIN.
3/8" EXPANSION
JOINT (TYP.) - SEE
CURB RAMP STANDARD PLAN F-30.10
I v,
GRADE m
BREAK TRANSITION TO SIDEWALK BUFFER, IF
PRESENT OR TO BACK OF CURB (TYP.) -
Siiciii SEE CONTRACT PLANS
CURB OR CURB
1 - AND GUTTER -
DETECTABLE WARNING SURFACE - SEE NOTE 4 B
SEE STANDARD PLAN F-45.10
FACE OF CURB
DEPRESSED CURB AND GUTTER -
CROSSWALK SEE NOTE 4
1O CONTRACTION JOINT (TYP.) - SEE STANDARD PLAN F-30.10
FOR CURB RAMP LENGTHS GREATER THAN 8'- 0" PROVIDE
6• RAISED EDGE DETAIL
1 -0. 6'
SIDEWALK
LEVEL 12• EXTEND SIDEWALK TRANSVERSE
1/2' (IN) R JOINTS TO INCLUDE RAISED EDGE
1'•0' 1'-0'
3/8•(IN)PREMOLDED JOINT FILLER
TYPICAL WHERE APPLICABLE
•'
ROUT DING 2i0%
1 1? IN R.
( ) m.P)
,," •
to� v
I
FOR CURB DETAILS
SEE STD PLAN 101
1 (IN)R. ", ►••"\J •"' •t.•r: ... ,EXISTING ROADWAY
v
;►• �rlE, Ntt' __-i ��j'i.. / CRUSHEOROCKBAS
-
�,���.
SEE RAISED EDGE
L
- =----
--
- I
'", SIDEWALK DETAIL TH S SHE
TYPICAL UNDER
CRUSHED SURFACING TOP COURSE (CSTC)
ALL CUT
SIDEW'ALK�OMPACT
TO 95x MODIFIED PROCTOR
riloN..
WITH RAISED EDGE
(UNLESS REQUIREMENT WANED BY
`LOPES
1/2• (IN) R. (TYP.)
ENGINEER) TYPICAL UNDER ALL CURB,
GUTTER a SIDE WALLK CSTC UNDER
1 - 1 8Y
FOR CURB DETAILS
CURB& OUTTERTOBEE ICKNE
4f�•((FR ••• • ,)
SEE STD PUN 101
MATCH EXISTING ROADWAYRUSHED ROCK
BASE, WHICHEVER IS GREATER (TYP. FOR
ALLCURBBGUTII
_ .._ _ _..___ _-
�Y•QyANY<N .1
-�Y�'
FINISHED GRADE I'(IM BELOW
�-t;•
2'-0'
SIDEWALK
TOP OF CONCRETE SURFACE
ADJACENT TO CURB
MIN.
ROU DING
1? (IN) R. (TYP.)
_z.o%
I 1.6%
FOR CURB DETAILS
SEE STD PUN 101
----•�'�YAY7"VI•
BRIDGE OR PEDESTRIAN 5~,;sM'•
''r••���
RAILING .t"
..
BARRIER -SEE SIDEWALK
FOR CURB DETAILS
SEE STD PUN 101.
ADJACENT TO CURB
(STEEP FILL SLOPES)
CONTRACT PLANS
---WALL OR BARRIER
I I 1? (IN) R. (ryp.)
�/
/ I
SIDEWALK
FLUSH
• ••
1/2• N)R
.. ;
VERTICAL WALL--._... -;'r )•:••:
SEE DETAIL *
F
PREMOLDED
JOINT FILLER
,
ADJACENT TO CURB AND RAILING OR WALL
r (INI
PRE LDED
_
JOINT FILLER
FOR SIDE BUFFER STRIP
TREATMENT SIDEWALK
SIDEWALK ADJACENT TO WALL DETAIL
HLK
SIDEWALK (SEE NOTE 10)
SECTIONS 1rz• (IM R
1 (1YP')
a
FOR CURB DETAILS
1.6% 1_,%MIN._
SEE STD PLAN 101
-BROOMEDFINISH
,�/ •'• ••'
OR MATCH EXISTING
�1
SMOOTM
7' C
TROWELED PERIMETER
FINISHED GRADE 1-(IN) BELOW 70P OF CONCRETE
SURFACE FOR PLANTING -FLUSH IF PAVED
)O'�'
CEMENT CONCRETE CURB
ADJACENT TO BUFFER STRIP
I-
_3s-,..� (�o�„�o^RURSHOWN)
va• TO 114-
NOTES
1. Four feet of the sidewalk Width shall CONTRACTION JOINT • •.yam,'
IN the minimum pedestrian SIDEWALK ONLY ► ,
accessible route (PAS) free of vertical - ► . A ro : ,
and horizontal obstructions. Gratings, ,� 3 a FULL-DEPTH,EXPANSION JOINT IN BOTH , • "•• R
Access Covers, Junction Boxes, was • "
Cable Vaults, Pull Boxes end other �.. 8. a CURB AND SIDEWALK (SEE STD PUN 101.1)
appurtenances within the sidewalk o 3Ie• C CONTRACTION JOINT
must be flush with surface, and match
grade of the sidewalk. JOINT AND FINISH
DETAIL
2. Monolithic Cement Concrete Curb and Y • •. ' ,?, Ap
Sidewalk Is not permitted In new For Other referenced NOTES See R
construction. When replacement work STD PLAN 104.2.
necessitates a Monolithic Cement PREMOLDE -
Concrete Curb build per WSDOT JOINT FILLER
Standard Plan F-30.10-03. Paved surfaces must Comply with
STD PLAN 102.1 as applicable. E FULL -DEPTH
3. Concrete to be 4,000 PSI. EXPANSION JOINT
STD. PLAN - 102
PUBLIC WORKS CEMENT CONCRETE i'I R0�'ED:
I:R)DEPARTMENT SIDEWALK
r 10�
A
NOTES
CURB RAMP WIDTH a• - o" MIN.
1 At marked crosswalks, the connection between the curb ramp and the road -
LANDING TO MATCH CURB RAMP
I WIDTH -SEE CONTRACT PLANS
way must be contained within the width of the crosswalk markings.
Y 9
I
2. Where "GRADE BREAK" is called out, the entire length of the grade break
GRADE BREAK
between the two adjacent surface planes shall be flush.
3. Do not place Gratings, Junction Boxes, Access Covers, or other appurten-
ances on any part of the Curb Ramp or Landing, or in front of the Curb
Ramp where it connects to the roadway.
2 0"
MIN SEE CONTRACT
4. See Contract Plans for the curb design specified. See Standard Plan
PLANS - 4' - 0" MIN
F•10.12 for Curb, Curb and Gutter, Depressed Curb and Gutter, and
BUFFER WIDTH - MATCH
Pedestrian Curb details.
TO CURB RAMP DEPTH
I (TYP)
5 See Standard Plan F-30.10 for Cement Concrete Sidewalk Details. See
I v.
Contract Plans for width and placement of sidewalk.
4 v
6. The Bid Item "Cement Concrete Curb Ramp Type _" does not include the
0,
adjacent Curb, Curb and Gutter, Depressed Curb and Gutter, Pedestrian
w
Curb, or Sidewalks.
7, The Curb Ramp length is not required to exceed 15 feet (unless shown
CEMENT CONCRETE
otherwise in the Contract Plans). When applying the 15-foot max. length,
PEDESTRIAN cuRe -
SEE NOTE 4
the running slope of the Curb Ramp is allowed to exceed 8.3%. Use a
single constant slope from bottom of ramp to top of ramp to match into
DETECTABLE WARNING SURFACE -
the landing Over a horizontal distance Of 15 feet. DO not include the
SEE STANDARD PLAN F-45.10
abutting landing in the 15-foot max. measurement.
DEPRESSED CURB AND GUTTER
8. Curb Ramps and Landings shall receive a broom finish. See Standard
CROSSWALK
Specifications 8-14.
L9.
Pedestrian Curb may be omitted if the ground surface at the back of the
Curb Ramp and/or Landing will be at the same elevation as the Curb
Ramp or Landing and there will not be material to retain.
PLAN VIEW CONTRACTION JOINT EQUALLY SPACED 4'- 0" MIN OC PLAN VIEW
TYPE PERPENDICULAR A TYPE PERPENDICULAR B
DETECTABLE WARNING SURFACE - (SHOWN WITH BUFFER)
SEE STANDARD PLAN F-45.10
4'- 0" MIN 15' - 0" MAX. (TYP.) GRADE BREAK
SLOPE TREATMENT - SEE CONTRACT PLANS SEE NOTE 7
COUNTER SLOPE -
SEE STANDARD PLAN F-30.10 * GRADE BREAK 5.0% MAX
* *' TOP OF ROADWAY
LANDING CURB RAMP v >
DEPRESSED CURB AND GUTTER -
1 SEE STANDARD PLAN F-10.12
SECTION OA
CEMENT CONCRETE CEMENT CONCRETE CURB RAMP "TYPE CEMENT CONCRETE CURB RAMP "TYPE
PEDESTRIAN CURB - PERPENDICULAR "A" PAY LIMIT - SEE NOTE 6 PERPENDICULAR "B" PAY LIMIT
SEE NOTE 4
DETECTABLE WARNING SURFACE -
SEE STANDARD PLAN F45.10
3" R, TYP DEPRESSED CURB AND GUTTER -
SEE NOTE 4
CEMENT CONCRETE CURB
AND GUTTER - SEE NOTE 4
CURB RADIUS DETAIL O
y, P�ILIA�
�10F WASH
4-
m ?
o
C/1) I�
ISOMETRIC VIEW
TYPE PERPENDICULAR A PAY LIMIT
3 REVISIONS PER CITY COMMENTS DATED 612312021
�;P 38375 2 REVISIONS PER CITY COMMENTS DATED 410712021
ds'r � ��� 1 REVISIONS PER CITY COMMENTS DATED 112512020
SIGNAL �
07/01/2021 NO. REVISION
LEGEND
-
SLOPE IN EITHER DIRECTION
*
1.5 OR FLATTER RECOMMENDED FOR
DESIGN/FORMWORK (2% MAX)
* *
7 5% OR FLATTER RECOMMENDED FOR
DESIGNfFORMWORK (8.3% MAX)
* * *
9.5% OR FLATTER RECOMMENDED FOR
DESIGNfFORMWORK (10% MAX.)
ISOMETRIC VIEW
TYPE PERPENDICULAR B PAY LIMIT
SCOpp 1fASd�ll
AA.
�0 20680 V4 Q•��
'p `01 STB�Q ♦{
�s's70NAL Y�G
ko 'I'Ilin `rI \\I
PERPENDICULAR
CURB RAMP
STANDARD PLAN F-40.15-03
SHEET 1 OF 1 SHEET
APPROVED FOR PUBLICATION
I :, 1: n
„_1�I,iI,_n,'>I
- STATE DESIGN ENGINEER
Washington stare Department of Trcnsportaticn
MAP
SURVEYED:
SDM
DESIGNED:
NEM
CP
0710112021
CP
0410812021
DRAWN. TLK
PMD
1111212020
CHECKED:
EDM
BY
DATE
AP P R
APPROVED:
CA
NOTES
1. Not used.
2. All ramp and landing edges shall be separately formed.
3. Utilities structures that must remain are to be made non -slip or non-skid.
Route PAR of the
4. Utilities structures such as vaults and unction boxes shall not be located in the Pedestrian Access Ro
1( )
Pedestrian Circulation Route.
5. Drainage appurtenances, such as manholes, catch basins, etc. shall not be located in the PAR. These should be located
in the street or the buffer strip.
6. Accessible pedestrian access shall be provided for during construction.
ticY -a STD. PLAN - 102.1
PUBLIC WORKS UTILITY PLACEMENT IN PPR 'ED:
DEPARTMENT CEMENT CONCRETE SIDEWALK 0�1
SPECIAL NOTE
IN THE EVENT TRANSVERSE PATCHES EXIST
WITHIN THE AFFECTED STREET, THE LENGTH
OF THE PATCH SHALL BE EXTENDED TO
INCLUDE ANY EXISTING PATCH WITHIN 10
FEET OF THE EDGE OF THE PATCH REQUIRED
FOR THE NEW CROSSING AND ANY
SUBSEQUENT PATCH EDGE WITHIN 10 FEET
OF THE EDGE OF THE SECOND PATCH AND
SO ON UP TO A TOTAL OF 300 FEET,
1' 1' VARIES 1' 1'
MIN MIN � MIN MIN
j
T I
I
TRAFFIC FLOW I ,f
I
2" HMA I L
2" TO 8" HMA
6.5' MIN.
2" DEPTH OF
PLANING OR SAWCUT AND REMOVE
VARIES: 6.5' MIN. --
1 1 -{ 1 1
VARIES
MIN MIN I I MIN I MIN
2" SAWCUT AND REMOVE
OR PLANE, SEAL WITH
AR-400DW
(EACH SIDE)
2" HMA
SAWCUT AFTER BACKFILL -
(EACH SIDE)
WIDTH OF TRENCH AS REQUIRED BY SIZE OF PROPOSED
IMPROVEMENT (SEE STANDARD SPECIFICATION 2-09.4)
PLUS AN ALLOWANCEE FOR FOR ANY SHORING, SHORING, IF
NEEDED, SHALL MEET THE REQUIREMENTS OF WSDOT
STANDARD SPECIFICATION 7-08.3(1)B
TRENCH WIDTH
SCALE:
1 aT=30)
FACE OF GUTTER OR
EDGE OF PAVEMENT
CENTER LINE OR
LANE LINE
DEPTH OF EXISTING PAVEMENT
2" - 6" MIN. HMA (SEE NOTE 2)
6" CRUSHED SURFACING TOP COURSE (CSTC)
(9-03.9(3)) PER WSDOT STANDARD
SPECIFICATIONS, COMPACTED TO 957 MODIFIED
PROCTOR.
CSTC, BANK RUN GRAVEL FOR TRENCH BACKFILL
(9-03.19), GRAVEL BORROW (9-03.14(i)) PER
WSDOT STANDARD SPECIFICATIONS OR NATIVE
MATERIAL IF APPROVED IN WRITING BY ENGINEER
BASED ON GEOTECH REPORT, COMPACTED TO 95%
MODIFIED PROCTOR.
PIPE ZONE BEDDING. MATERIAL- SEE STANDARD
PLAN 110.1,
FOR NOTES, SEE STANDARD PLAN 110.1
TYPICAL TRANSVERSE PATCH FOR STD. PLAN - 110
• PUBLIC WORKS PPR '"Eta
DEPARTMENT FLEXIBLE PAVEMENT OR RIGID
PAVEMENT WITH OVERLAY
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
Know what's below.
Call before you dig.
C1 TY OF
RENTON
[;R
Planning/Building/Public Works Dept.
0EMENT
CONCRETE
SIDEWALK
DEPRESSED MONOLITHIC
CURB 8 GUTTER
(SEE DETAIL THIS SHEET)
TYPE C2B - ISOMETRIC VIEW
(COMMERCIAL, WITH BUFFER)
CEMENT CONCRETE
CURB tl GUTTER
(SEE NOTE 3)
NOTES
1. When a driveway width exceeds 15 feet, construct a full depth
expansion joint with 3/8" joint filler along the driveway lane lines FACE OF CURB
(see aid, plan 102). Construct expansion joints parallel with the (J BEE DEPRE85ED CURB DETAIL
centerllne as required at 15' maximum spacing when driveway CONTRACTION JOINT ° 12 °" THIS SHEET
widths exceed W. BU To PLAN 102 s t? . 1• _
OF
bI 1?R ._ ROADWAY
2. See std. plan 102 for sidewalk details,
3. Curb and gutter shown, other curb designs may be specified.
See aid. plan 101 for curb details. +Ir
4. Not used.
5. The engineer will design all driveways to Include elevations at all NOTE DRIVEWAY LONGITUDINAL EXPANSION
points marked with symbol "X". All elevations era at the hack of JOINTS SHALL BE FULL DEPTH
curb top On uphill Side. DEPRESSED MONOLITHIC CURB 8 GUTTER DETAIL
6. Not used.
7. For Driveway Widths see DRIVEWAY STANDARDS
(See NOTE 10). The expansion joints (see aid. plan 102) shall be
spaced as shown In the corresponding Isometric view.
8. Slopes shall comply with sections R303.2.1 or R303.2.2 or FACE OF ADJACENT CURB
R303.2.3 of the Revised Dmft Guidelines for Accessible Public
Rights of --Way of November 23, 2005 (PROWAO). j �"
9. Curb returns for any Type C-MAX Driveway may be approved on ` �,
a case -by -case basis. , - �/-L--GLrr ER SURFACE
' 1.
10. ° r.
10. STREET STANDARDS = Renton Municipal Code (RMC)
? r
Title IV Development Regulations o
CHAPTER 6 STREET AND UTILITY STANDARDS o
Section 4 6-060 STREET STANDARDS DEPRESSED CURB DETAIL
AT RESIDENTIAL OR COMMERCIAL DRIVEWAYS, AND ALLEYS
DRIVEWAY STANDARDS = Renton Municipal Code (RMC)
Title IV Development Regulations Drivemy Example: TYPE C1 B
l 1
CHAPTER 4 R=ReaWmsd, C=CommaRsal
CITY-WIDE PROPERTY DEVELOPMENT STANDARDS Number of l snos,
Section 4PARKING, LOADING AND DRIVEWAY ( � Lane Commercial)
REGULATIONS B-Buffer (Plerd)ng Strip). BlenimNo Buffer
STD. PLAN - 104.2
PUBLIC WORKS CEMENT CONCRETE DRIVEWAY PROS D:
DEPARTMENT ENTRANCES - NOTES AND DETAILS
Ovy
LANE LINE
MARKING
VARIES: 4.5' MIN.
SAWCUT AFTER BACKFILL
DEPTH OF EXISTING PAVEMENT
2" - 6" HMA
(SEE NOTE 2) 1'
1' EDGE OF PAVEMENT, EDGE
OF CURB & GUTTER, OR
MIN.
MIN. CENTER OF LANE MARKING
2" HMA (SEE NOTE 2)
6" CRUSHED SURFACING TOP COURSE
(CSTC) (9-03.9(3)) PER WSDOT STANDARD
2" SAWCUT AND REMOVE
SPECIFCATIONS, COMPACTED TO 95%
OR PLANE, SEAL WITH
MODIFIED PROCTOR
AR-4000W
CSTC, BANK RUN GRAVEL FOR TRENCH BACKFILL
(9-03.19), GRAVEL BORROW (9-03.14(1)) PER
WSDOT STANDARD SPECIFICATIONS OR NATIVE
MATERIAL IF APPROVED IN WRITING BY ENGINEER
BASED ON GEOTECH REPORT, COMPACTED TO
WIDTH OF TRENCH AS REQUIRED BY SIZE OF
O
95% MODIFIED PROCTOR.
PROPOSED IMPROVEMENT (SEE WSDOT
STANDARD SPECIFICATION 2-09.4) PLUS AN
PIPE ZONE BEDDING MATERIAL AND COMPACTION AS
ALLOWANCE FOR ANY SHORING. SHORING, IF
REQUIRED BY THE WSDOT STANDARD SPECIFICATIONS
NEEDED, SHALL MEET THE REQUIREMENTS OF
FOR THE TYPE OF IMPROVEMENT INSTALLED, EXCEPT:
WSDOT STANDARD SPECIFICATION 7-08.3(1)B
* FOR STORM AND WATER PIPE, PER STD PLAN 220.0
* FOR SANITARY SEWER, PER STD PLAN 405
TRENCH WIDTH
* FOR JOINT UTILITY TRENCH, SAND WITH 95%
PASSING A #4 SIEVE AND LESS THAN 5% PASSING
A #200 SIEVE
NOTES:
1. WHEN EXISTING PAVEMENT IN A LANE REQUIRING A FULL WIDTH REPLACEMENT IS BROKEN OR DETERIORATED
TO A PAVEMENT CONDITION INDEX RATING OF 70 OR LESS, THE EXISTING PAVEMENT IN THAT LANE, AND
FOR THAT DISTANCE SO CLASSIFIED, SHALL BE REMOVED AND REPLACED WITH HMA MATCHING THE DEPTH
USED IN THE EXISTING STREET OR THE DEPTH PER CITY STANDARD, WHICHEVER IS GREATER.
2. PRINCIPAL/ MINOR/COLLECTOR, ARTERIAL, & INDUSTRIAL ACCESS STREETS - MATERIAL AND THICKNESS
SHALL BE HMA CL J" PG 64-22 AND MATCH EXISTING THICKNESS AND IN NO CASE LESS THAN 6".
RESIDENTIAL ACCESS STREETS - HMA CL "" PG 64-22. THE THICKNESS SHALL BE THAT OF THE EXISTING
PAVEMENT SECTION AND IN NO CASE LESS THAN 4".
3. WHEN THE "SAWCUT AFTER BACKFILL" ENCROACHES INTO AN ADJACENT LANE, CURB & GUTTER OR
SHOULDER, THE AFFECTED LANE SHALL BE PLANED AND OVERLAID WITH HMA FULL WIDTH, THE CURB &
GUTTER SHALL BE REMOVED AND REPLACED, OR THE SHOULDER SHALL BE PLANED OR REMOVED AND
OVERLAID WITH HMA.
4. IF TRENCH UNDERMINES EXISTING SIDEWALK AND/OR CURBS, THEN THE SIDEWALK AND/OR CURB SHALL BE
REPLACED FROM EXPANSION JOINT TO EXPANSION JOINT.
5. IF TRENCHING THROUGH EXISTING DRIVEWAY OR SIDEWALK RAMP, THE DRIVEWAY OR SIDEWALK RAMP SHALL
BE REPLACED TO MEET ADA STANDARDS.
TYPICAL LONGITUDINAL PATCH STD. PLAN - 110.1
1► PUBLIC WORKS FOR FLEXIBLE PAVEMENT OR fY \1'I)
DEPARTMENT )Q ��
RIGID PAVEMENT WITH OVERLAY
R-411511
7
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
Q
J
DEVELOPMENT ENGINEERING 4 �'
Brianne Bannwarth 07/01/2021
SKYHORSE SHORT PLAT
PR 17-000438
CONSTRUCTION DETAILS
O
LLJ
C/
DATE:
1111212020
O
FIELDBOOK:
PAGE:
DRAWING NO:
1460.3
J
SHEET: 13 OF:19