Loading...
HomeMy WebLinkAboutPre-application # 12-012Airport Taxiway B system rehabilitation.Arnie, Ryan: I have looked at the pre-application information for the Airport Taxiway B system rehabilitation. If the applicant (Renton Airport) is planning on replacing a portion of the existing water line along the east side of the runway as part of this project, then the new water line shall be connected to an existing City water main located at the southeast corner of the site as shown on the attached map. The size of the new line shall be 12-inch minimum and the new flush-type hydrants shall be connected to this new line. The new line cannot be connected to the existing line within the airport that is fed by the Boeing private fire system. The airport property is within the City’s water service area and as such any new water main extension, including hydrants, shall be connected to the City’s water system as required by City Code for all development/redevelopment projects within the City’s water service area. Let me know if you have any questions, Abdoul Gafour Water Engineering Supervisor City of Renton Public Works 1055 S Grady Way Renton, WA 98057 425-430-7210 agafour@rentonwa.gov