HomeMy WebLinkAboutSummary_Preapp_Mtg_PRE12-000027h:\ced\planning\current planning\preapps\12-027.rocale\12-027 (r-8 springbrook church, detached garage).doc
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
M E M O R A N D U M
DATE:April 12, 2012
TO:Pre-Application File No. 12-027
FROM:Rocale Timmons, Associate Planner
SUBJECT:Springbrook Church of Christ (10421 SE 192nd Ave St)
General: We have completed a preliminary review of the pre-application for the above-
referenced development proposal. The following comments on development and permitting
issues are based on the pre-application submittals made to the City of Renton by the applicant
and the codes in effect on the date of review. The applicant is cautioned that information
contained in this summary may be subject to modification and/or concurrence by official
decision-makers (e.g., Hearing Examiner, Community & Economic Development Administrator,
Public Works Administrator, Planning Director, Development Services Director, and City
Council). Review comments may also need to be revised based on site planning and other
design changes required by City staff or made by the applicant. The applicant is encouraged to
review all applicable sections of the Renton Municipal Code. The Development Regulations are
available for purchase for $50.00 plus tax, from the Finance Division on the first floor of City Hall
or online at www.rentonwa.gov
Project Proposal: The subject property is located on the south side of 192nd St just west of 106th
Ave SE. The project site totals 3.16 acres in area; and is zoned Residential-8 dwelling units/acres
(R-8). The proposal is to construct an 480 square foot structure on the south side of the
property, as an accessory to the existing religious institution. Access would remain the same.
Current Use: A 5,880 square foot religious institution is currently located on site with associated
landscaping and parking..
Zoning/Density Requirements: The subject property is located within the R-8 zoning
designation. The Religious Institution use is permitted as a Conditional Use Permit granted by
the Hearing Examiner and is to comply with the requirements of the R-8 zoning designations.
Activities of existing established conditional uses directly related to the use that has already
been established, such as new construction and additions shall not require additional
Conditional Use Permit Review. However, there is no record of a Special or Conditional Use
Permit applied for in the City. It will be the applicant’s responsibility to provide proof that the
church was established legally. Otherwise a Conditional Use Permit will be required in order
to construct the proposed additions.
Development Standards: The project would be subject to RMC 4-2-110A, “Development
Standards for Single Family Zoning Designations” effective at the time of complete application
(noted as “R-8 standards” herein).
Minimum Lot Size, Width and Depth – Minimum lot size, width and depth requirements are not
applicable to the proposed project.
Springbrook Church of Christ
Page 2 of 3
April 12, 2012
h:\ced\planning\current planning\preapps\12-027.rocale\12-027 (r-8 springbrook church, detached garage).doc
Building Standards – the R-8 zone allows a maximum building coverage of 35% of the lot area or
2,500 square feet, whichever is greater for lots over 5,000 square feet in size and a maximum
impervious surface 75%. Detached accessory structures must remain below a height of 15 feet.
The gross floor area must be less than that of the primary structure. Accessory structures are
also included in building lot coverage calculations. The proposal’s compliance with the building
standards would be verified at the time of building permit review for the accessory dwelling
unit.
Building Design Standards – The proposed structure would be subject to the Residential Design
Standards outlined in RMC 4-2-115. The following are some of the standards that are applicable
to the project:
1. The visual impact of garages shall be minimized, while porches and front doors shall be
the emphasis of the front of the home. Garages shall be located in a manner that
minimizes the presence of the garage and shall not be located at the end of view
corridors.
2. Garage design shall be of similar design to the homes/existing structure on site.
3. If sides of the garage are visible from streets, lanes, sidewalks, pathways, trails, or other
homes, architectural details shall be incorporated in the design.
The proposal’s compliance with the residential design standards would be verified at the time
of building permit review.
Setbacks – Setbacks are the minimum required distance between the building footprint and the
property line and any private access easement. The required setbacks in the R-8 zone for
accessory structures are 6 feet from any other structure, 3 feet on side yards and rear yards.
Except for garages, in order to ensure that there is adequate vehicular turning radius, garages
on alleys shall be located as follows: 9 foot garage doors shall be at least 26 foot from the back
edge of the alley, or 6 foot garage doors shall be at least 24 foot from the back edge of the alley.
The setbacks for the new structure would be reviewed at the time of building permit.
Driveways: The maximum driveway slopes cannot exceed 15%, provided that driveways
exceeding 8% are to provide slotted drains at the lower end of the driveway. If the grade
exceeds 15%, a variance is required.
Landscaping – Except for critical areas, all portions of the development area not covered by
structures, required parking, access, circulation or service areas, must be landscaped with
native, drought-resistant vegetative cover. The development standards require that all pervious
areas within the property boundaries be landscaped. The minimum on-site landscape width
required along street frontages is 10 feet.
Please refer to landscape regulations (RMC 4-4-070) for further general and specific landscape
requirements (enclosed). A conceptual landscape plan shall be submitted at the time of
Preliminary Plat application.
Significant Tree Retention: A tree inventory and a tree retention plan along with a tree
retention worksheet shall be provided with the formal land use application. The tree retention
plan must show preservation of at least 30 percent of significant trees. The applicant will also
be required to demonstrate how proposed building footprints would be sited to accommodate
Springbrook Church of Christ
Page 3 of 3
April 12, 2012
h:\ced\planning\current planning\preapps\12-027.rocale\12-027 (r-8 springbrook church, detached garage).doc
preservation of significant trees that could and would be retained. If the trees cannot be
retained, they may be replaced with minimum 2 inch caliper trees at a ratio of six to one.
Critical Areas: The site does not appear to contain any critical areas.
Environmental Review: Environmental (SEPA) Review is required for projects nine lots or
greater, or on sites that contain critical areas. Therefore SEPA would not be required for the
project.
Permit Requirements:
The applicant would need only to apply for a building permit and possible utility construction
permits. And if the applicant has not provided proof of that the use was legally established a
Conditional Use Permit would be required to be granted by the Hearing Examiner.
Fees: Please contact the main counter of the Development Services Division at (425) 430-7200
for building permit information including fees. A handout listing all of the City’s Development
related fees in attached for your review.
Expiration: The preliminary plat approval is valid for five years with a possible one-year
extension.
FIRE & EMERGENCY SERVICES DEPARTMENT
M E M O R A N D U M
DATE:April 10, 2012
TO:Rocale Timmons, Associate Planner
FROM:Corey Thomas, Plans Review Inspector
SUBJECT:Springbrook Church of Christ Outbuilding
1. The preliminary fire flow requirement is 1,500 gpm. A minimum of two
fire hydrants are required. One fire hydrant is required within 150-feet of
the proposed building and one hydrant is required within 300-feet. There
are no existing hydrants within 300-feet of the proposed building. A water
availability certificate is required from Soos Creek Water and Sewer
District.
2. The fire mitigation impact fees are currently applicable at the rate of
$0.52 per square foot of commercial area.
3. Fire department apparatus access roads are required to be a
minimum of 20-feet wide with 25-feet inside and 45-feet
outside turning radius.
H:\CED\Planning\Current Planning\PREAPPS\12-027.Rocale\Plan Review Comments PRE 12-027.doc
DEPARTMENT OF COMMUNITY
AND ECONOMIC DEVELOPMENT
M E M O R A N D U M
DATE:April 9, 2012
\g June 14, 2010
TO:Rocale Timmons, Planner
FROM:Jan Illian, Plan Review
SUBJECT:Springbrook Church of Christ
10421 – SE 192 Street
PRE 12-027
NOTE: The applicant is cautioned that information contained in this summary is preliminary and non-
binding and may be subject to modification and/or concurrence by official city decision-makers. Review
comments may also need to be revised based on site planning and other design changes required by
City staff or made by the applicant.
I have completed a preliminary review for the above-referenced proposal. The following comments are
based on the pre-application submittal made to the City of Renton by the applicant.
Water
1. Water and sewer is provided by Soos Creek Water and Sewer District.
2. A plumbing permit will be required for the water service connection to the out building.