Loading...
HomeMy WebLinkAboutne7thstspFIRE & EMERGENCY SERVICES DEPARTMENT M E M O R A N D U M   DATE: August 27, 2012     TO: Vanessa Dolbee, Senior Planner     FROM: Corey Thomas, Plans Review Inspector     SUBJECT: NE 7th St Short Plat      1. The fire flow requirement for a single family home is 1,000 gpm minimum for dwellings up to 3,600 square feet (including garage and basements). If the dwelling exceeds 3,600 square feet, a minimum of 1,500 gpm fire flow would be required. A minimum of one fire hydrant is required within 300-feet of the proposed buildings and two hydrants if the fire flow goes up to 1,500 gpm. The existing fire hydrants are not within 300 feet of all of the proposed lots. 2. The fire mitigation impact fees are currently applicable at the rate of $488.00 per single family unit. This fee is paid prior to recording the plat. Credit will be granted for the existing homes that are to be removed. Fire department apparatus access roadways are required to be a minimum of 20-feet wide fully paved, with 25-feet inside and 45-feet outside turning radius. Fire access roadways shall be constructed to support a 30-ton vehicle with 322-psi point loading. Access is required within 150-feet of all points on the buildings. Dead end streets that exceed 150-feet in length require an approved turnaround. Proposed hammerhead appears adequate.