HomeMy WebLinkAboutFire comments FIRE & EMERGENCY SERVICES DEPARTMENT M E M O R A N D U M   DATE: January 27, 2012     TO: Rocale Timmons, Associate Planner     FROM: Corey Thomas, Plans Review Inspector     SUBJECT: Sunset Terrace Development      1. The preliminary fire flow requirement is 3,000 gpm based on a fully fire sprinklered building. A minimum of four fire hydrants are required. One fire hydrant is required within 150-feet of the proposed building and three hydrants are required within 300-feet. One hydrant is required within 50-feet of the fire department connections. Existing hydrants can be counted toward the requirements as long as they meet current code. It appears adequate fire flow is available in this area. Looped fire mains are required all around the building when fire flows exceed 2,500 gpm. 2. The fire mitigation impact fees are currently applicable at the rate of $388.00 per residential unit and $0.52 per square foot of commercial area. No charge for parking garage areas. Credit will be granted for the existing buildings to be removed. 3. An approved fire alarm, fire sprinkler system and dry standpipe system are required throughout the building. Separate plans and permits are required to be submitted to the Renton Fire Department for review and permitting. Fire alarm system shall be fully addressable and full detection is required. A direct outside door is required to the fire sprinkler riser control room. 4. An annual place of assembly permit is required for occupancies exceeding 50 persons. An automatic external defibrillator (AED) is required if the occupancy exceeds 300 persons. 5. Fire department apparatus access roads are required to be a minimum of 20-feet wide with 25-feet inside and 45-feet outside turning radius. The proposed 13-feet wide street is not acceptable. 6. All buildings equipped with an elevator in the City of Renton are required to have at least one elevator meet the size requirements for a bariatric size stretcher. Car size shall accommodate a minimum of a 40-inch by 84-inch stretcher and car width shall be a minimum of 80-inches wide with a center opening door. 7. The building shall comply with the City of Renton Emergency Radio Coverage ordinance. Testing shall verify both incoming and outgoing minimum emergency radio signal coverage. If inadequate, the building shall be enhanced with amplification equipment in order to meet minimum coverage. Separate plans and permits are required for any proposed amplification systems. 8. An electronic site plan is required to be submitted to the Renton Fire Department for pre-fire planning purposes prior to occupancy of the building. See below for the format in which to submit your plans. In an effort to streamline our pre-fire process, we are requesting that you submit a site plan of your construction project in one of the following formats which we can then convert to VISIO.vsd. This is required to be submitted prior to occupancy. ABC Flowcharter.af3  ABC Flowcharter.af2  Adobe Illustrator File.ai  AutoCad Drawing.dwg  AutoCad Drawing.dgn  Computer Graphics Metafile.cgm  Corel Clipart Format.cmx  Corel DRAW! Drawing File Format.edr  Corel Flow.cfl  Encapsulated Postscript File.eps  Enhanced Metafile.emf  IGES Drawing File Format.igs  Graphics Interchange Format.gif  Macintosh PICT Format.pct  Micrografx Designer Ver 3.1.drw  Micrografx Designer Ver 6.0.dsf  Microstation Drawing.dgn  Portable Network Graphics Format.pnf  Postscript File.ps  Tag Image File Format.tif  Text.txt  Text.csv  VISIO.vsd  Windows Bitmap.bmp  Windows Bitmap.dib  Windows Metafile.wmf  Zsoft PC Paintbrush Bitmap.pcx