HomeMy WebLinkAboutLund FireFIRE & EMERGENCY SERVICES DEPARTMENT
M E M O R A N D U M
DATE:
August 28, 2012
TO:
Rocale Timmons, Associate Planner
FROM:
Corey Thomas, Plans Review Inspector
SUBJECT:
Lund Short Plat
1. The fire flow requirement for a single family home is 1,000 gpm minimum for dwellings up to 3,600 square feet (including garage and basements). If the dwelling exceeds 3,600 square
feet, a minimum of 1,500 gpm fire flow would be required. A minimum of one fire hydrant is required within 300-feet of the proposed buildings and two hydrants if the fire flow goes
up to 1,500 gpm. There are two existing hydrants within 300-feet of the proposed plat and these hydrants are up to current code. A water availability certificate is required from
Soos Creek Water and Sewer District.
2. The fire mitigation impact fees are currently applicable at the rate of $488.00 per single family unit. This fee is paid prior to recording the plat. Credit would be granted for
the one existing home to be removed.
Fire department apparatus access roadways appears adequate.