NE 15th and Kirkland Townhomes
1. The preliminary fire flow is 3,500 gpm. A minimum of four hydrants are required. One within 150-feet and three within 300-feet of the proposed buildings. A looped fire main is
required around the buildings as the fire flow exceeds 2,500 gpm. Existing hydrants can be used to satisfy the requirements as long as they meet current code including 5-inch storz
fittings.
2. Fire mitigation impact fees are currently applicable at the rate of $388.00 per multi-family unit. This fee is paid at time of building permit issuance.
3. Fire department apparatus access roadways are required within 150-feet of all points on the building. Fire lane signage required for the onsite roadway. Required turning radius
is 25-feet inside and 45-feet outside. Roadways shall be a minimum of 20-feet wide. Roadways shall support a minimum of a 30-ton vehicle and 322-psi point loading.
4. An electronic site plan is required prior to occupancy for pre-fire planning purposes.