FIRE & EMERGENCY SERVICES DEPARTMENT
M E M O R A N D U M
DATE:
April 10, 2012
TO:
Rocale Timmons, Associate Planner
FROM:
Corey Thomas, Plans Review Inspector
SUBJECT:
Springbrook Church of Christ Outbuilding
1. The preliminary fire flow requirement is 1,500 gpm. A minimum of two fire hydrants are required. One fire hydrant is required within 150-feet of the proposed building and one hydrant
is required within 300-feet. There are no existing hydrants within 300-feet of the proposed building. A water availability certificate is required from Soos Creek Water and Sewer
District.
2. The fire mitigation impact fees are currently applicable at the rate of $0.52 per square foot of commercial area.
3. Fire department apparatus access roads are required to be a minimum of 20-feet wide with 25-feet inside and 45-feet outside turning radius.