HomeMy WebLinkAboutW-3930051 n a n 11-1/4" BEND CAP r,. i Ell ,�< 22-1/2' BEND 45' BEND 90• BEND THRUST BLOCK BEARING AREA IN SQUARE FEET (SEE NOTES) FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS SOIL FIRM SILT OR FIRM SILTY SAND COMPACT SAND COMPACT SAND &GRAVEL 90' 45' BEND 11 1/4' 90' 45' BEND 11 1/4- 90' 45' BEND 11 1/4' FITTING BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG & 22 1/2' BEND TEE CAP OR PLUG & 22 1/2' BEND BEND BEND 4" 7.0 4.2 4.2 1.7 2.9 2.1 2.1 1.0 2.2 1.6 1.6 1.0 6" 13.3 9.4 9.4 3.8 6.7 4.7 4.7 1.9 5.0 3.5 3.5 1.4 8" 23.3 16.7 16.7 6.7 11.7 8.4 8.4 3.4 8.8 6.3 6.3 2.5 12" 53.0 37.5 1 37.5 15.0 26.5 18.8 18.8 7.5 20.0 14.0 14.0 5.6 AREAS CALCULATED ON 300 PSI TEST PRESSURE. 3'-O" MIN. COVER FOR WATERMAIN LESS THAN 12". 4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER. MAX. HEIGHT OF THRUST BLOCK (FT) = 0.5 x DEPTH OF TRENCH MIN. HEIGHT OF THRUST BLOCK (FT) = O.D. PIPE + 1.0' THRUST BLOCK BE. AREA REFERS TO FACE OF BLOCK M IN SQUARE FEET NOTES: 1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12'DIAMETER AND FOR SOIL TYPES DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER. 2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND. 3. ALL POURED THRUST BLOCKS SHALL BE BACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING SHALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH. 4. ALL BLOCKING SHALL BE CONCRETE CL 5 (I-s/2'). 5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA POSSIBLE, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOINT BOLTS OR GLANDS REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED. CONCRETE BLOCKING FOR STD. PLAN - 330.2 HORIZONTAL AND DOWNWARD VERTICAL BENDS Ni_1PC'Ii CONCRETE BLOCKING FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS (COR STD. PLAN 330.2) NOT TO SCALE AS -BUILT I CERTIFY THAT THE INFORMATION SHOWN HEREON WHICH WAS AS -BUILT BY AHBL ,AND MAY INCLUDE NOTICE LOCATIONS, ELEVATIONS, DEPTHS, PIPE SIZES, AND ALTERA71ONaFTxISDOCI1YENrSHALLNYAlIDA1ETIE PROFES90NAL SEAL AND SIGNATURE PUBLICATION OF AS -BUILT COMMENTS, ACCURATELY REFLECTS EXISTING THIS DOCI11E11TDOES NOT DEROGATEFROMRESERVED OINER9IP RWHiS IN IT. THIS DOCUIENT IS FOR USE FIELD CONDICTIONS AS DETERMINED BY ME OR UNDER MY �YFOR THE PRo,IEcrDENTIREDNTHE nTLEeLoac AND IS NOT TO BE USED FOR REPAIR, REMODEL OR cr. W a ✓ 1 J �� by � of wasgr� �0•p 41803 w� ��� kEGI STEV, SSIONAL I In SHACKLE RODS c^� TYPE A BLOCKING ^ ocnl^c S CONCRETE BLOCKING FOR VERTICAL STD. PLAN - 330.3 « fL + PUBLIC WORKS FITTINGS �Nzo� DEPARTMENT MARCH 2OI0 CONCRETE BLOCKING FOR VERTICAL FITTINGS (COR STD. PLAN 330.3) NOT TO SCALE _ 5 I 4 3 2 nd - T A C O M A• SEATTLE • SPOKANE •TRI-CITIES 1 2215 North 30th Street, Suite 300 Tacoma, VVA 98403 NO. 19253.383.2422 TEL 253.383.2572 FAX www.ahbl.com NEB RAMP REVISION STORM DRAINAGE REVISIONS CITY COMMENTS ADDENDUM NO. 3 ADDENDUM NO. 1 REVISION Where shown on the plans or in the specifications or required by the Engineer, joint restraint system (shackle rods) shall be used. All joints restraint materials used shall be those manufactured by Star National Products, 1323 Holly Avenue, PO Box 258, Columbus, Ohio 43216 unless on equal alternate is approved in writing by the Engineer. Materials Steel Types: High strength low -alloy steel (cor-ten), ASTM A588 heat -treated. 1. Tiebolt: ASTM A588, Grade 8, Cor-Ten, equal to SuperStar Tielbolt SST 7 5/8" for 2" and 3" mechanical joints (M.J.) with eye for 5/8" rod SST 7 3/4" for 4" to 12" M.J. with eye for 3/4" rod SST 756 : 3/4" for 14" to 24" M.J, with eye for 3/4" rod SST 747 3/4" for 4" to 12" M.J. with eye for 7/8" and 1" rod SST 757 3/4" for 14" to 24" M.J. with eye for 7/8" and 1" rod SST 778: 1" for 30" to 36" M.J. with eye for 1" rod 2.Tienut: Hex Nut ASTM A588, Grade B, Cor-Ten, equal to SuperStar Tienut SS8 for 5/8", 3/4", 7/8 1" Tiebolt and Tierod 3.Tiecoupling with Tiestop Pin ASTM A588, Grade B. Cor-Ten, equal to SuperStar Tiecoupling SS10 for 5/8", 3/4", 7/8", 1" Tierod 4. Tierod: Continuous threaded rod for cutting to desired lengths ASTM A588, Grade B, Cor-Ten, equal to SuperStar Tierod SS12 for 5/8", 3/4", 7/8", 1" 5. Tiewosh er ASTM A588, Grade B, Cor-Ten, equal to SuperStar Tiewosher SS17 for 5/8", 3/4", 7/8", 1" round flat washer Instollation: Install the joint restraint system in accordance with the Manufacturer's instructions so all joints are mechanically locked together to prevent joint separation. Tiebolts shall be installed to pull against the mechanical joint body and not the M.J. follower. Torque nuts at 75-90 foot pounds for 3/4" nuts. Install tiecouplings with both rods threaded equal distance into tiecouplings. Arrange tierods symmetrically around the pipe. Where a Manufacturer's mechanical joint valve or fitting is supplied with slots for "T" bolts instead of holes a flanged valve with o flange b 9 9 Y mechanical joint adaptor shall be used instead, so as to provide adequate space for locating tiebolt. Where a continuous run of pipe is required to be restrained, no run of restrained pipe shall be greater than 60 feet in length betwee fittings. Insert long body solid sleeves as required on longer runs to keep tierod lengths to the 60 foot maximum. Pipe used in continuously restrained runs shall be mechanical joint pipe and tiebolts shall be installed as rod guides at each joint. Pipe Size Inches Test Pressure PSI 2 4 Number and Size of Rods 6 8 10 12 14 24 2 250 3/4" 3 250 3/4" 4 250 3/4" 6 250 3/4" 6 250 3/4" 10 250 3/4" 12 250 3/4" 14 250 3/4" 16 250 3/4" 18 250 3/4" 23 250 3/4' 24 250 3/4" 30 200 3/4" 35 200 1" d2 200 1" 48 200 V. MIN l� V 4 STD. PLAN - 330.5 PUBI IC WORKS SHACKLE RODDS DEPARTMENT AND TIE BOLTS N _ 'MARCI-3 ?OI O SHACKLE RODS AND TIE BOLTS (COR STD. PLAN 330.5) NOT TO SCALE WJF 2/22/18 WJF SURVEYED: D. FOLLANSBEE WJF 12/13/17 WJF DESIGNED: G. TAUSCHECK WJF 4/21/17 WJF WJF 3/17/17 WJF DROWN: F. KATONA WJF 3/1/17 WJF CHECKED: W. FIERST BY DATE APPR APPROVED: S. COMFORT PRECAST CONCRETE VAULT WITH 3 - 3'x 3' ONE EACH SIDE HINGED STEEL PLATE COVERS. DIMENSIONS 5'-8"x ll'-2"x 7'-2" EQUAL TO UTILITY 4" ADAPTER, FL.x SCREWED VAULT OR EQUAL 4"x4"x6" BULL HEAD TEE, FL.-\ TOUCH READ PIT LID SENSOR MOUNTED ON STEEL PLATE COVER THROUGH 2" DIA. 6" PIPE FL.x DRILLED HOLE IN COVER. FL. 2'-0" LO THE BY-PASS ASSEMBLY SHALL BE \ INCLUDED AS PART OF THE DETECTOR a DOUBLE CHECK VALVE ASSEMBLY. 18" FOR 10" ASSEMBLY 5/8"x3/4" SENSUS SRII (TR/PL) METER 17 1/2" FOR 8" ASSEMBLY WITH ICE REGISTER. 18 1/2" FOR 6" ASSEMBLY CITY PRIVATE I \ 11'- 2'= z PIPING PIPING TEE (MJ x FL) GATE VALVE (FL x MS) y ) 5'- _TO CITY MAIN 12" ALL AROUND CONCRETE BLOCKING �� �� _ • • ■ 1`II ���II�� �II�\PFMMMIM1 II�� INN NNNI1=®IN0�I����I�� It�-fig N �■� ' ALL DETECTOR DOUBLE CHECK VALVE P.E. ASSEMBLIES SHALL INCLUDE RESILIENT 10", 8" OR 6" FL.x PIPE WITH COLLAR 18" SEATED SHUTOFF VALVES AND TEST PLAN FROM P.E. COCKS. AND APPROVED CROSS -CONNECTION CONTROL 10"- 3'-8" LONG ASSEMBLIES PER DEPARTMENT OF 8"- 3'-6" LONG HEALTH LATEST APPROVED LIST. 6"- 4'-0" LONG DOUBLE CHECK VALVE ASSEMBLY INCLUDES TWO RESILIENT SEATED SHUTOFF VALVES. 10", 8% OR 6" FLANGED COUPLING ADAPTER EQUAL TO ROMAC. TOUCH READ PIT LID SENSOR MOUNTED ON STEEL PLATE COVER THROUGH 2" DIA. NOTE: DRILLED HOLE IN COVER. 1. LOCATE VAULT IN PLANTING AREA, NOT IN PAVING. 2. 4" AND LARGER BENDS AND TEES TO BE CAST IRON CEMENT LINED. 18" FOR 10" ASSEMBLY 17 3. TEMPORARY SUPPORT SHALL BE PROVIDED UNDER 1/2" FOR 8" ASSEMBLY 18 VALVES AT THE TIME OF INSTALLATION TO CENTER 1/2" FOR 6" ASSEMBLY THE PIPE IN VAULT OPENING. AFTER COMPLETE 5/8"x3/4" INVENSYS{� INSTALLATION REMOVE THE TEMPORARY SUPPORT TR-PL METER WITH 7'-2" AND INSTALL ADJUSTABLE PIPE SUPPORT. ICE REGISTER 4. INSTALL GALVANIZED LADDER FOR ACCESS. 6" MIN. DRAIN TO DAYLIGHT OR STORM DRAIN SYSTEM WITH 5. AFTER FIELD INSTALLATION, MAIN DDCVA AND CATCH BASIN OR MANHOLE BY-PASS DCVA MUST BE TESTED SATISFACTORILY BY A DEPT. OF HEALTH CERTIFIED BACKFLOW fi ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT. PRIOR TO ACTIVATION OF NEW LINE. 3" r-4"x 2 1/2" FIRE DEPARTMENT DOUBLE CONNECTION FOR STAND PIPE WITH BREAKABLE CAST IRON HOSE CAPS. ONE EACH SIDE EQUAL TO GRINNEL FIG. 1682 WITH HOSE CAPS FIG. 1333. 6" SWING TYPE GRAVITY OPERATED CHECK VALVE, FL. EQUAL TO MUELLER CO. A-2600-6 WITH BALL DRIP VALVE AT BOTTOM INSTALL EPDXY NON -SHRINK GROUT (TYP.) 6" PIPE, FL.x FL. 3'0" LONG 6 f.. '&&8' ASSEMBLY. 6" SHORT US 90' [RAD10' IREDUCINGMBDEND90FL. 8"X6" TO BUILDING DEADMAN BLOCK REQUIRED. 10",8",6" FL x MJ ADAPTOR 10" ASSEMBLY 10"x10"x8"TEE FL. 8" ASSEMBLY 8"xB"x6" TEE, FL. 6" ASSEMBLY 6'x6"x6" TEE, FL. 10", 8", OR 6" GATE VALVE, FL.x MJ, WITH INDICATOR POST. INDICATOR POST VALVE SAME SIZE AS DOUBLE CHECK VALVE (MUELLER CO. OR EQUAL), PAINTED RED. 10", 8", OR 6" DUCTILE IRON CLASS 52 NIPPLE PIPE, CEMENT LINED, LENGTH TO FIT. 6" PIPE FL. x S 2'-6" 3' 2'-11" 6" 90' BEND FLU "-GALVANIZED STEEL LADDER COMPACTED FOUNDATION 6. INSTALL BRASS Y4" FLARE TEST COCKS WITH Y4" GRAVEL FLARE CAPS. ADJUSTABLE STEEL PIPE SUPPORT, STANCHIONS BOLTED TO FLOOR. END VIEW 6",8" & 10" DOUBLE DETECTOR CHECK STD. PLAN - 360.2 w PUBLIC WORKS + �•` + DEPARTMENT ASSEMBLY WITH STANDPIPE OUTSIDE ��ii rod INSTALLATION MARCH 2O10 DOUBLE CHECK DETECTOR CHECK ASSEMBLY WITH STANDPIPE OUTSIDE INSTALLATION (COR STD. PLAN 360.2) NOT TO SCALE CONSTRUCTION RECORD DRAWINGS SCALE: AS SHOWN HORIZONTAL: NAD U 983/11991 `� Z Uhl , CITY OF 51r,lv.RENTON ONE INCH DATUM AT FULL SCALE Planning/Building/Public Works Dept. IF NOT ONE INCH SCALE ACCORDINGLY BY: BY: BY: BY: APPROVED FOR CONSTRUCTION SUBJECT TO ERRORS AND OMISSIONS DATE: DATE: DATE: DATE: SARTORI ELEMENTARY SCHOOL RENTON SCHOOL DISTRICT WATER NOTES AND DETAILS II 05/04/2017 PAGE: C7.6 SHEET:OF: 36 43 �i W-393005