HomeMy WebLinkAboutR-419279cq GENERAL NOTES ABBREVIATIONS ii 0 w 1. PERFORM WORK IN ACCORDANCE WITH APPLICABLE NATIONAL AND STATE CODES AS AMENDED LOCALLY AND ENFORCED BY THE AHJ. 2. OBTAIN AND PAY FOR PERMITS REQUIRED FOR INSTALLATION OF WORK. ARRANGE AND SCHEDULE REQUIRED INSPECTIONS. 3. COORDINATE WITH UTILITY COMPANIES FURNISHING SERVICES TO PROJECT. INSTALLATION OF UTILITY SERVICES SHALL BE IN ACCORDANCE WITH UTILITY REQUIREMENTS. VERIFY APPLICABLE INSTALLATION STANDARDS AND REQUIREMENTS. PROVIDE AND SUBMIT ELECTRICAL DRAWINGS TO UTILITY FOR APPROVAL PRIOR TO ROUGH -IN AND PRIOR TO ORDERING EQUIPMENT. 4. DEVICE LOCATIONS ARE APPROXIMATE. COORDINATE DEVICE LOCATIONS AND ELEVATIONS WITH APPROPRIATE DOCUMENTS INCLUDING CASEWORK SHOP DRAWINGS AND ARCHITECTS INTERIOR ELEVATIONS PRIOR TO ROUGH -IN. 5. COORDINATE ELECTRICAL WORK WITH THAT OF OTHER TRADES. REFER TO MECHANICAL, ARCHITECTURAL, STRUCTURAL, CIVIL, AND LANDSCAPE DRAWINGS AND SPECIFICATIONS. COORDINATION SHALL OCCUR PRIOR TO FABRICATION, PURCHASE, AND INSTALLATION OF WORK. 6. COORDINATE LOCATION OF LIGHT FIXTURES AND CEILING -MOUNTED DEVICES WITH ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS. 7. PROVIDE RATED ENCLOSURES AROUND ALL LIGHT FIXTURES PENETRATING RATED CEILINGS. COORDINATE WITH ARCHITECTURAL. 8. REFER TO ARCHITECTURAL AND STRUCTURAL DRAWINGS FOR LOCATIONS OF EXPANSIONISEISMIC JOINTS. PROVIDE RACEWAY EXPANSION/SEISMIC JOINTS FOR RACEWAYS CROSSING BUILDING EXPANSION/SEISMIC JOINTS. 9. DEMOLISH EXISTING SYSTEMS AS INDICATED ON PLANS OR AS REQUIRED FOR INSTALLATION OF NEW WORK. MATERIAL SHALL BE REMOVED FROM SITE AND LEGALLY DISPOSED OF OFF SITE UNLESS OTHERWISE DIRECTED. RETURN ITEMS TO OWNER IN EXISTING CONDITION WHEN DIRECTED BY OWNER. 10. COMPLETION OF WORK SHALL BE EXECUTED IN ACCORDANCE WITH THE PROJECT SCHEDULE. SCHEDULE INSTALLATION WITH OTHER TRADES TO ENSURE PROJECT MILESTONES ARE MET. 11. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION. PROVIDE COMPONENTS REQUIRED FOR COMPLETE AND OPERATIONAL SYSTEMS INCLUDING RACEWAYS, CONDUCTORS, BOXES, SUPPORTS AND SIMILAR ITEMS. 12. BRANCH CIRCUIT HOMERUNS ARE SHOWN TO INDICATE CIRCUIT PROPERTIES AND CONFIGURATION. SINGLE -CIRCUIT HOMERUNS SERVED FROM THE SAME PAINEUBOARD MAY BE COMBINED IN ACCORDANCE WITH THE DIVISION 26 SPECIFICATIONS, UNLESS INDICATED OTHERWISE. EXTEND AND CONNECT BRANCH CIRCUIT RACEWAY AND WIRING FROM HOMERUN TO DEVICES AND EQUIPMENTWITH CIRCUIT NUMBERS INDICATED. CONDUCTOR QUANTITIES AND SIZES ARE INDICATED AT HOMERUNS ONLY. SHOW ACTUAL RACEWAY ROUTING AND CIRCUITING ON RECORD DRAWINGS. MINIMUM CONDUCTOR SIZE #12 AWG. 13. LIGHT FIXTURES MOUNTED IN CONTINUOUS ROWS SHALL BE THROUGH -WIRED VIA FIXTURE INTERNAL WIREWAYS. CIRCUITS AS INDICATED ON DRAWINGS. FIXTURES NOT LISTED FOR THROUGH WIRING SHALL BE WIRED VIA SEPARATE RACEWAY AND WIRING SYSTEM EXTERNAL TO THE FIXTURES. PROVIDE RACEWAYS, WIRING AND CONNECTIONS FOR A COMPLETE AND OPERATIONAL SYSTEM. 14. LOCATIONS OF RACEWAY, PATHWAY AND SIMILAR ITEMS ARE SHOWN SCHEMATICALLY. COORDINATE INSTALLATION, INCLUDING BUT NOT LIMITED TO CABLING, TELECOMMUNICATION PATHWAYS AND SPACES, AND EXACT LOCATION OF HORIZONTAL AND BACKBONE CABLING WITH LOCATIONS OF FIXED CASEWORK AND BUILDING CONDITIONS AFFECTING THE WORK OF THIS CONTRACT. 15. COORDINATE TELECOMMUNICATIONS WORK WITH THAT OF OTHER TRADES. REFER TO ELECTRICAL, MECHANICAL, ARCHITECTURAL, STRUCTURAL, CIVIL, AND LANDSCAPE DRAWINGS AND SPECIFICATIONS. COORDINATION SHALL OCCUR PRIOR TO FABRICATION, PURCHASE, AND INSTALLATION OF WORK. 16. NEW CABLING INSTALLATIONS SHALL BE CONCEALED IN WALL, CEILINGS, AND BELOW RAISED FLOOR SPACES UNLESS OTHERWISE NOTED ON THE DRAWINGS. CABLING IN ACCESSIBLE CEILING SPACES SHALL BE INSTALLED AS OPEN CABLING NEAR STRUCTURES AND WALLS OR AS SPECIFICALLY NOTED ON DRAWINGS. SEE SPECIFICATIONS FOR SUPPORT REQUIREMENTS. 17. PROVIDE FIRESTOPPING SYSTEMS FOR CONDUIT AND RACEWAY SYSTEMS AT PENETRATIONS, SLEEVES AND SLOTS OF FIRE RATED CONSTRUCTION FOR HORIZONTAL AND INTRABUILDING PATHWAYS AND SPACES. 18, INTRABUILDING OPTICAL FIBER CABLING SHALL BE CLEARLY AND VISIBLY IDENTIFIED IN PULLBOXES, ENTRANCE POINTS, EACH RISER ROOM, AND F-0- BEFORE ENTERING A FREE STANDING RACK UTILIZING AN OPTICAL FIBER CABLE MARKER TAG SYSTEM. 19, CATEGORY 616A CABLING: MAINTAIN A MINIMUM SPACING OF 12* FROM ELECTRICAL FEEDERS AND BRANCH CIRCUIT WIRING AND 12" FROM AUXILIARY SYSTEM CABLING. 20. MINIMUM SPACING FROM ELECTRICAL APPARATUS SUCH AS MOTOR DRIVEN EQUIPMENT AND TRANSFORMERS SHALL BE V-0". SPACING REQUIREMENTS SHALL APPLY TO OPEN CABLING PATHWAYS WHERE EQUIPMENT IS LOCATED ON THE SAME FLOOR, FLOOR ABOVE, FLOOR BELOW, OR IN ROOMS ADJACENT TO SUCH EQUIPMENT AS THOUGH WALLS AND FLOORS DID NOT EXIST. EXCEPTION. BUILDING CONSTRUCTION THAT RESULTS IN CONTINUOUS METALLIC BARRIER BETWEEN ELECTRICAL APPARATUS AND CABLE PATHWAYS SHALL BE CONSIDERED AS SUITABLE SEPARATION. 21. PRIOR TO STARTING TELECOMMUNICATIONS INSTALLATION, CAREFULLY INSPECT INSTALLED WORK OF OTHER TRADES AND VERIFY THAT SUCH WORK IS COMPLETE TO THE POINT WHERE WORK MAY PROPERLY COMMENCE. NOTIFY THE ARCHITECT AND ENGINEER IN WRITING OF CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY COMPLETION OF THE WORK. 22. DO NOT BEGIN TELECOMMUNICATIONS INSTALLATION UNTIL ALL UNSATISFACTORY CONDITIONS ARE RESOLVED. BEGINNING WORK CONSTITUTES ACCEPTANCE OF CONDITIONS AS SATISFACTORY. 23. ROUTE CATEGORY 6/6A CABLES TO THEIR ASSIGNED CROSS -CONNECT PER THE IDENTIFICATION LABEL AT EACH TELECOMMUNICATIONS WORKSTATION DEVICE. TERMINATE ALL CABLES ON 48-PORT PATCH PANELS ON RACKS UNLESS OTHERWISE NOTED. 24. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONDUIT, OUTLET BOXES, JUNCTION BOXES, RACEWAY SYSTEMS, ETC. FOR A COMPLETE AND OPERATIONAL PATHWAY SYSTEM FOR ALL TELECOMMUNICATIONS SYSTEMS PER THE SCOPE OF WORK INDICATED ON THE CONSTRUCTION DRAWINGS AND BID SPECIFICATIONS. 25. CABLE TRAY PATHWAYS ABOVE ACCESSIBLE CEILINGS SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. CABLE TRAY PATHWAYS BELOW RAISED FLOOR SPACES SHALL BE PROVIDED BY THE TELECOMMUNICATIONS CONTRACTOR. NO, I REVISION A AMPERE AIR CONDITIONING; ALTERNATING CURRENT; AC ABOVE COUNTER AF AMP FUSE: AMP FRAME AEC AVAILABLE FAULT CURRENT ARE ABOVE FINISHED FLOOR AG ABOVE GRADE AHJ AUTHORITIES HAVING JURISDICTION AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CURRENT AL ALUMINUM ANSI AMERICAN NATIONAL STANDARDS INSTITUTE AS AMP SWITCH AT AMP TRIP ATM ASYNCHRONOUS TRANSFER MODE ATS AUTOMATIC TRANSFER SWITCH AV AUDIO VISUAL AWG AMERICAN WIRE GAUGE SAS BUILDING AUTOMATION SYSTEM BATT BATTERIES BIL BASIC IMPULSE INSULATION LEVEL SKIED BACKBOARD BKR BREAKER BLDG BUILDING c CONDUIT; DEGREES CELSIUS CAB CABINET CAT CATEGORY CATV COMMUNITY ANTENNA TELEVISION CB CIRCUIT BREAKER CcTV CLOSED CIRCUIT TELEVISION OILS CEILING CM CEILING -MOUNTED CO CONDUIT ONLY cow COMPUTER ON WHEELS OR CONTROLLED RECEPTACLE OFF CURRENT TRANSFORMER CU COPPER D DEDICATED DDC DIRECT DIGITAL CONTROL DEMARC DEMARCATION POINT DISC DISCONNECT DIST DISTRIBUTION DSL DIGITAL SUBSCRIBER LINE DING DRAWING (E) EXISTING EA EACH EF EXHAUSTFAN EIA ELECTRONIC INDUSTRIES ASSOCIATION ELEV ELEVATION EM EMERGENCY EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EPM ELECTRONIC POWER METER EPO EMERGENCY POWER OFF EQUIP EQUIPMENT ETR EXISTING TO REMAIN EWC ELECTRIC WATER COOLER F FUSE; DEGREES FAHRENHEIT FA FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FACE FIRE ALARM CONTROL PANEL RED FURNISHED BY OWNER FC FOOT-CANDLE FURNISHED BY OWNER INSTALLED BY FOIC CONTRACTOR FOIO FURNISHED BY OWNER INSTALLED BY OWNER RED FIRE SMOKE DAMPER G GROUND GB GROUND FAULT CIRCUIT BREAKER SIR GROUND FAULT CIRCUIT INTERRUPTER GFP GROUND FAULT PROTECTION GND GROUND ORB GALVANIZED RIGID STEEL SMFC SURFACE -MOUNTED OPTICAL FIBER CABINET ISO INTERNATIONAL BUILDING CODE SMR SURFACE METAL RACEWAY IC INTERMEDIATE CROSS CONNECT BONET SYNCHRONOUS OPTICAL NETWORK OF INTERMEDIATE DISTRIBUTION FRAME SP SERVICE PROVIDER IEEE INSTITUTE OF ELECTRICAL AND ELECTRONIC BED SURGE PROTECTIVE DEVICE ENGINEERS SPEC SPECIFICATIONS IG ISOLATED GROUND BEST SINGLE POLE SINGLE THROW lmc INTERMEDIATE METALLIC CONDUIT ST SHUNT TRIP ISDN INTEGRATED SERVICES DIGITAL NETWORK STE SHIELDED TWISTED PAIR SVGA SUPER VIDEO GRAPHICS ARRAY i JUNCTION Sw SWITCH SWBD SWITCHBOARD K KIRK KEY KCMIL THOUSAND CIRCULAR MILS TBB TELECOMMUNICATIONS BONDING BACKBONE kVA KILOVOLT AMPERE TEL TELEPHONE KVAR KILOVOLT AMPERE REACTIVE TELCO TELEPHONE COMPANY kW KILOWATT TGB TELECOMMUNICATIONS GROUNDING BUSBAR TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION LAN LOCAL AREA NETWORK TELECOMMUNICATIONS MAIN GROUNDING LCP LIGHTING CONTROL PANEL TMGB BUSBAR LEC LOCAL EXCHANGE CARRIER TP TAMPERPROOF LT LIGHT TR TELECOMMUNICATIONS ROOM LTG LIGHTING TTB TELEPHONE TERMINAL BOARD TV TELEVISION M METER TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION MAN METROPOLITAN AREA NETWORK TYP TYPICAL M METER MAN METROPOLITAN AREA NETWORK UG UNDERGROUND MAX MAXIMUM UL UNDERWRITERS LABORATORIES Mc MAIN CROSS CONNECT; METAL CLAD (CABLE) JOIN UNLESS OTHERWISE NOTED MOB MAIN CIRCUIT BREAKER UPS UNINTERRUPTIBLE POWER SUPPLY MCC MOTOR CONTROL CENTER USB UNIVERSAL SERIAL BUS MDF MAIN DISTRIBUTION FRAME UTP UNSHIELDED TWISTED PAIR MDP MAIN DISTRIBUTION PANEL LIV UNITVENTILATOR MFR MANUFACTURER MH MANHOLE V VOLTS MIN MINIMUM VA VOLTAMPERES MILO MAIN LUGS ONLY VFD VARIABLE FREQUENCY DRIVE MIA MULTIMODE MPOE MAIN POINT OF ENTRY W WATT; WIRE MPOP MAIN POINT OF PRESENCE W/ WITH MTD MOUNTED W/o WITHOUT MTS MANUAL TRANSFER SWITCH WA WORKSTATION AREA WAN WIDE AREA NETWORK (N) NEW WG WIRE GUARD N NEUTRAL WH WATT HOUR METER NAC NOTIFICATION APPLIANCE CIRCUIT WE WEATHERPROOF NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS XMFR TRANSFORMER ASSOCIATION NIF NON -FUSED Y WYE NIC NOT IN CONTRACT NIL NIGHT LIGHT Z IMPEDANCE OFC OPTICAL FIBER CABLE OHL OVERHEAD LINE OIL OVERLOAD OS OCCUPANCYSENSOR OSP OUTSIDE PLANT p POLE PBX PRIVATE BRANCH EXCHANGE RE POWER FACTOR PH PHASE FIR PASSIVE INFRARED PIV POST INDICATING VALVE PNL PANEL RE PATCH PANEL PT POTENTIAL TRANSFORMER Pvc POLYVINYL CHLORIDE RC ROOM CONTROLLER ROE REFLECTED CEILING PLAN REC RECEPTACLE REF REFER TO REV REVISION RM ROOM RTRC REINFORCED THERMORESETTING RESIN CONDUIT RU RACK UNIT HC HORIZONTAL CROSS CONNECT HID HIGH INTENSITY DISCHARGE SB STANDBY HE HORSEPOWER BHT SHEET HTR HEATER SLC SIGNALING LINE CIRCUIT Hz HERTZ SIM SINGLEMODE NONE VEW� IIW CITY OF DESI�D KSR RENTON DWN. KSR P anning/Building/Public Works Dept. CHRXIM, TSV IF NCYF � 1� BY DATE APPR �F�D S� �01�y 31 T-419202 IN COMPLIANCE WITH CITY OF RENTON STANDARDS .j 0q) 00 N ,It CD c\I A C/) z LLJ Q 0 NEW ELEMENTARY NO. 16 I WE, AR 2022 CHELAN AVE NE RENTON, WA 98059 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES (r w I 11w 79 1471 (L