GENERAL NOTES
ABBREVIATIONS
ii
0
w
1. PERFORM WORK IN ACCORDANCE WITH APPLICABLE
NATIONAL AND STATE CODES AS AMENDED LOCALLY
AND ENFORCED BY THE AHJ.
2. OBTAIN AND PAY FOR PERMITS REQUIRED FOR
INSTALLATION OF WORK. ARRANGE AND SCHEDULE
REQUIRED INSPECTIONS.
3. COORDINATE WITH UTILITY COMPANIES FURNISHING
SERVICES TO PROJECT. INSTALLATION OF UTILITY
SERVICES SHALL BE IN ACCORDANCE WITH UTILITY
REQUIREMENTS. VERIFY APPLICABLE INSTALLATION
STANDARDS AND REQUIREMENTS. PROVIDE AND
SUBMIT ELECTRICAL DRAWINGS TO UTILITY FOR
APPROVAL PRIOR TO ROUGH -IN AND PRIOR TO
ORDERING EQUIPMENT.
4. DEVICE LOCATIONS ARE APPROXIMATE. COORDINATE
DEVICE LOCATIONS AND ELEVATIONS WITH
APPROPRIATE DOCUMENTS INCLUDING CASEWORK
SHOP DRAWINGS AND ARCHITECTS INTERIOR
ELEVATIONS PRIOR TO ROUGH -IN.
5. COORDINATE ELECTRICAL WORK WITH THAT OF
OTHER TRADES. REFER TO MECHANICAL,
ARCHITECTURAL, STRUCTURAL, CIVIL, AND
LANDSCAPE DRAWINGS AND SPECIFICATIONS.
COORDINATION SHALL OCCUR PRIOR TO
FABRICATION, PURCHASE, AND INSTALLATION OF
WORK.
6. COORDINATE LOCATION OF LIGHT FIXTURES AND
CEILING -MOUNTED DEVICES WITH ARCHITECTURAL
REFLECTED CEILING PLANS AND ELEVATIONS.
7. PROVIDE RATED ENCLOSURES AROUND ALL LIGHT
FIXTURES PENETRATING RATED CEILINGS.
COORDINATE WITH ARCHITECTURAL.
8. REFER TO ARCHITECTURAL AND STRUCTURAL
DRAWINGS FOR LOCATIONS OF EXPANSIONISEISMIC
JOINTS. PROVIDE RACEWAY EXPANSION/SEISMIC
JOINTS FOR RACEWAYS CROSSING BUILDING
EXPANSION/SEISMIC JOINTS.
9. DEMOLISH EXISTING SYSTEMS AS INDICATED ON
PLANS OR AS REQUIRED FOR INSTALLATION OF NEW
WORK. MATERIAL SHALL BE REMOVED FROM SITE
AND LEGALLY DISPOSED OF OFF SITE UNLESS
OTHERWISE DIRECTED. RETURN ITEMS TO OWNER IN
EXISTING CONDITION WHEN DIRECTED BY OWNER.
10. COMPLETION OF WORK SHALL BE EXECUTED IN
ACCORDANCE WITH THE PROJECT SCHEDULE.
SCHEDULE INSTALLATION WITH OTHER TRADES TO
ENSURE PROJECT MILESTONES ARE MET.
11. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW
ALL COMPONENTS REQUIRED FOR A COMPLETE
INSTALLATION. PROVIDE COMPONENTS REQUIRED
FOR COMPLETE AND OPERATIONAL SYSTEMS
INCLUDING RACEWAYS, CONDUCTORS, BOXES,
SUPPORTS AND SIMILAR ITEMS.
12. BRANCH CIRCUIT HOMERUNS ARE SHOWN TO
INDICATE CIRCUIT PROPERTIES AND CONFIGURATION.
SINGLE -CIRCUIT HOMERUNS SERVED FROM THE
SAME PAINEUBOARD MAY BE COMBINED IN
ACCORDANCE WITH THE DIVISION 26 SPECIFICATIONS,
UNLESS INDICATED OTHERWISE. EXTEND AND
CONNECT BRANCH CIRCUIT RACEWAY AND WIRING
FROM HOMERUN TO DEVICES AND EQUIPMENTWITH
CIRCUIT NUMBERS INDICATED. CONDUCTOR
QUANTITIES AND SIZES ARE INDICATED AT
HOMERUNS ONLY. SHOW ACTUAL RACEWAY
ROUTING AND CIRCUITING ON RECORD DRAWINGS.
MINIMUM CONDUCTOR SIZE #12 AWG.
13. LIGHT FIXTURES MOUNTED IN CONTINUOUS ROWS
SHALL BE THROUGH -WIRED VIA FIXTURE INTERNAL
WIREWAYS. CIRCUITS AS INDICATED ON DRAWINGS.
FIXTURES NOT LISTED FOR THROUGH WIRING SHALL
BE WIRED VIA SEPARATE RACEWAY AND WIRING
SYSTEM EXTERNAL TO THE FIXTURES. PROVIDE
RACEWAYS, WIRING AND CONNECTIONS FOR A
COMPLETE AND OPERATIONAL SYSTEM.
14. LOCATIONS OF RACEWAY, PATHWAY AND SIMILAR
ITEMS ARE SHOWN SCHEMATICALLY. COORDINATE
INSTALLATION, INCLUDING BUT NOT LIMITED TO
CABLING, TELECOMMUNICATION PATHWAYS AND
SPACES, AND EXACT LOCATION OF HORIZONTAL AND
BACKBONE CABLING WITH LOCATIONS OF FIXED
CASEWORK AND BUILDING CONDITIONS AFFECTING
THE WORK OF THIS CONTRACT.
15. COORDINATE TELECOMMUNICATIONS WORK WITH
THAT OF OTHER TRADES. REFER TO ELECTRICAL,
MECHANICAL, ARCHITECTURAL, STRUCTURAL, CIVIL,
AND LANDSCAPE DRAWINGS AND SPECIFICATIONS.
COORDINATION SHALL OCCUR PRIOR TO
FABRICATION, PURCHASE, AND INSTALLATION OF
WORK.
16. NEW CABLING INSTALLATIONS SHALL BE CONCEALED
IN WALL, CEILINGS, AND BELOW RAISED FLOOR
SPACES UNLESS OTHERWISE NOTED ON THE
DRAWINGS. CABLING IN ACCESSIBLE CEILING
SPACES SHALL BE INSTALLED AS OPEN CABLING
NEAR STRUCTURES AND WALLS OR AS SPECIFICALLY
NOTED ON DRAWINGS. SEE SPECIFICATIONS FOR
SUPPORT REQUIREMENTS.
17. PROVIDE FIRESTOPPING SYSTEMS FOR CONDUIT AND
RACEWAY SYSTEMS AT PENETRATIONS, SLEEVES
AND SLOTS OF FIRE RATED CONSTRUCTION FOR
HORIZONTAL AND INTRABUILDING PATHWAYS AND
SPACES.
18, INTRABUILDING OPTICAL FIBER CABLING SHALL BE
CLEARLY AND VISIBLY IDENTIFIED IN PULLBOXES,
ENTRANCE POINTS, EACH RISER ROOM, AND F-0-
BEFORE ENTERING A FREE STANDING RACK UTILIZING
AN OPTICAL FIBER CABLE MARKER TAG SYSTEM.
19, CATEGORY 616A CABLING: MAINTAIN A MINIMUM
SPACING OF 12* FROM ELECTRICAL FEEDERS AND
BRANCH CIRCUIT WIRING AND 12" FROM AUXILIARY
SYSTEM CABLING.
20. MINIMUM SPACING FROM ELECTRICAL APPARATUS
SUCH AS MOTOR DRIVEN EQUIPMENT AND
TRANSFORMERS SHALL BE V-0". SPACING
REQUIREMENTS SHALL APPLY TO OPEN CABLING
PATHWAYS WHERE EQUIPMENT IS LOCATED ON THE
SAME FLOOR, FLOOR ABOVE, FLOOR BELOW, OR IN
ROOMS ADJACENT TO SUCH EQUIPMENT AS THOUGH
WALLS AND FLOORS DID NOT EXIST. EXCEPTION.
BUILDING CONSTRUCTION THAT RESULTS IN
CONTINUOUS METALLIC BARRIER BETWEEN
ELECTRICAL APPARATUS AND CABLE PATHWAYS
SHALL BE CONSIDERED AS SUITABLE SEPARATION.
21. PRIOR TO STARTING TELECOMMUNICATIONS
INSTALLATION, CAREFULLY INSPECT INSTALLED
WORK OF OTHER TRADES AND VERIFY THAT SUCH
WORK IS COMPLETE TO THE POINT WHERE WORK
MAY PROPERLY COMMENCE. NOTIFY THE ARCHITECT
AND ENGINEER IN WRITING OF CONDITIONS
DETRIMENTAL TO THE PROPER AND TIMELY
COMPLETION OF THE WORK.
22. DO NOT BEGIN TELECOMMUNICATIONS INSTALLATION
UNTIL ALL UNSATISFACTORY CONDITIONS ARE
RESOLVED. BEGINNING WORK CONSTITUTES
ACCEPTANCE OF CONDITIONS AS SATISFACTORY.
23. ROUTE CATEGORY 6/6A CABLES TO THEIR ASSIGNED
CROSS -CONNECT PER THE IDENTIFICATION LABEL AT
EACH TELECOMMUNICATIONS WORKSTATION DEVICE.
TERMINATE ALL CABLES ON 48-PORT PATCH PANELS
ON RACKS UNLESS OTHERWISE NOTED.
24. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
CONDUIT, OUTLET BOXES, JUNCTION BOXES,
RACEWAY SYSTEMS, ETC. FOR A COMPLETE AND
OPERATIONAL PATHWAY SYSTEM FOR ALL
TELECOMMUNICATIONS SYSTEMS PER THE SCOPE OF
WORK INDICATED ON THE CONSTRUCTION DRAWINGS
AND BID SPECIFICATIONS.
25. CABLE TRAY PATHWAYS ABOVE ACCESSIBLE
CEILINGS SHALL BE PROVIDED BY THE ELECTRICAL
CONTRACTOR. CABLE TRAY PATHWAYS BELOW
RAISED FLOOR SPACES SHALL BE PROVIDED BY THE
TELECOMMUNICATIONS CONTRACTOR.
NO, I REVISION
A
AMPERE
AIR CONDITIONING; ALTERNATING CURRENT;
AC
ABOVE COUNTER
AF
AMP FUSE: AMP FRAME
AEC
AVAILABLE FAULT CURRENT
ARE
ABOVE FINISHED FLOOR
AG
ABOVE GRADE
AHJ
AUTHORITIES HAVING JURISDICTION
AHU
AIR HANDLING UNIT
AIC
AMPERE INTERRUPTING CURRENT
AL
ALUMINUM
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
AS
AMP SWITCH
AT
AMP TRIP
ATM
ASYNCHRONOUS TRANSFER MODE
ATS
AUTOMATIC TRANSFER SWITCH
AV
AUDIO VISUAL
AWG
AMERICAN WIRE GAUGE
SAS
BUILDING AUTOMATION SYSTEM
BATT
BATTERIES
BIL
BASIC IMPULSE INSULATION LEVEL
SKIED
BACKBOARD
BKR
BREAKER
BLDG
BUILDING
c
CONDUIT; DEGREES CELSIUS
CAB
CABINET
CAT
CATEGORY
CATV
COMMUNITY ANTENNA TELEVISION
CB
CIRCUIT BREAKER
CcTV
CLOSED CIRCUIT TELEVISION
OILS
CEILING
CM
CEILING -MOUNTED
CO
CONDUIT ONLY
cow
COMPUTER ON WHEELS
OR
CONTROLLED RECEPTACLE
OFF
CURRENT TRANSFORMER
CU
COPPER
D
DEDICATED
DDC
DIRECT DIGITAL CONTROL
DEMARC
DEMARCATION POINT
DISC
DISCONNECT
DIST
DISTRIBUTION
DSL
DIGITAL SUBSCRIBER LINE
DING
DRAWING
(E)
EXISTING
EA
EACH
EF
EXHAUSTFAN
EIA
ELECTRONIC INDUSTRIES ASSOCIATION
ELEV
ELEVATION
EM
EMERGENCY
EMT
ELECTRICAL METALLIC TUBING
ENCL
ENCLOSURE
EPM
ELECTRONIC POWER METER
EPO
EMERGENCY POWER OFF
EQUIP
EQUIPMENT
ETR
EXISTING TO REMAIN
EWC
ELECTRIC WATER COOLER
F
FUSE; DEGREES FAHRENHEIT
FA
FIRE ALARM
FAAP
FIRE ALARM ANNUNCIATOR PANEL
FACE
FIRE ALARM CONTROL PANEL
RED
FURNISHED BY OWNER
FC
FOOT-CANDLE
FURNISHED BY OWNER INSTALLED BY
FOIC
CONTRACTOR
FOIO
FURNISHED BY OWNER INSTALLED BY OWNER
RED
FIRE SMOKE DAMPER
G
GROUND
GB
GROUND FAULT CIRCUIT BREAKER
SIR
GROUND FAULT CIRCUIT INTERRUPTER
GFP
GROUND FAULT PROTECTION
GND
GROUND
ORB
GALVANIZED RIGID STEEL
SMFC
SURFACE -MOUNTED OPTICAL FIBER CABINET
ISO
INTERNATIONAL BUILDING CODE
SMR
SURFACE METAL RACEWAY
IC
INTERMEDIATE CROSS CONNECT
BONET
SYNCHRONOUS OPTICAL NETWORK
OF
INTERMEDIATE DISTRIBUTION FRAME
SP
SERVICE PROVIDER
IEEE
INSTITUTE OF ELECTRICAL AND ELECTRONIC
BED
SURGE PROTECTIVE DEVICE
ENGINEERS
SPEC
SPECIFICATIONS
IG
ISOLATED GROUND
BEST
SINGLE POLE SINGLE THROW
lmc
INTERMEDIATE METALLIC CONDUIT
ST
SHUNT TRIP
ISDN
INTEGRATED SERVICES DIGITAL NETWORK
STE
SHIELDED TWISTED PAIR
SVGA
SUPER VIDEO GRAPHICS ARRAY
i
JUNCTION
Sw
SWITCH
SWBD
SWITCHBOARD
K
KIRK KEY
KCMIL
THOUSAND CIRCULAR MILS
TBB
TELECOMMUNICATIONS BONDING BACKBONE
kVA
KILOVOLT AMPERE
TEL
TELEPHONE
KVAR
KILOVOLT AMPERE REACTIVE
TELCO
TELEPHONE COMPANY
kW
KILOWATT
TGB
TELECOMMUNICATIONS GROUNDING BUSBAR
TIA
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
LAN
LOCAL AREA NETWORK
TELECOMMUNICATIONS MAIN GROUNDING
LCP
LIGHTING CONTROL PANEL
TMGB
BUSBAR
LEC
LOCAL EXCHANGE CARRIER
TP
TAMPERPROOF
LT
LIGHT
TR
TELECOMMUNICATIONS ROOM
LTG
LIGHTING
TTB
TELEPHONE TERMINAL BOARD
TV
TELEVISION
M
METER
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSION
MAN
METROPOLITAN AREA NETWORK
TYP
TYPICAL
M
METER
MAN
METROPOLITAN AREA NETWORK
UG
UNDERGROUND
MAX
MAXIMUM
UL
UNDERWRITERS LABORATORIES
Mc
MAIN CROSS CONNECT; METAL CLAD (CABLE)
JOIN
UNLESS OTHERWISE NOTED
MOB
MAIN CIRCUIT BREAKER
UPS
UNINTERRUPTIBLE POWER SUPPLY
MCC
MOTOR CONTROL CENTER
USB
UNIVERSAL SERIAL BUS
MDF
MAIN DISTRIBUTION FRAME
UTP
UNSHIELDED TWISTED PAIR
MDP
MAIN DISTRIBUTION PANEL
LIV
UNITVENTILATOR
MFR
MANUFACTURER
MH
MANHOLE
V
VOLTS
MIN
MINIMUM
VA
VOLTAMPERES
MILO
MAIN LUGS ONLY
VFD
VARIABLE FREQUENCY DRIVE
MIA
MULTIMODE
MPOE
MAIN POINT OF ENTRY
W
WATT; WIRE
MPOP
MAIN POINT OF PRESENCE
W/
WITH
MTD
MOUNTED
W/o
WITHOUT
MTS
MANUAL TRANSFER SWITCH
WA
WORKSTATION AREA
WAN
WIDE AREA NETWORK
(N)
NEW
WG
WIRE GUARD
N
NEUTRAL
WH
WATT HOUR METER
NAC
NOTIFICATION APPLIANCE CIRCUIT
WE
WEATHERPROOF
NEC
NATIONAL ELECTRICAL CODE
NEMA
NATIONAL ELECTRICAL MANUFACTURERS
XMFR
TRANSFORMER
ASSOCIATION
NIF
NON -FUSED
Y
WYE
NIC
NOT IN CONTRACT
NIL
NIGHT LIGHT
Z
IMPEDANCE
OFC
OPTICAL FIBER CABLE
OHL
OVERHEAD LINE
OIL
OVERLOAD
OS
OCCUPANCYSENSOR
OSP
OUTSIDE PLANT
p
POLE
PBX
PRIVATE BRANCH EXCHANGE
RE
POWER FACTOR
PH
PHASE
FIR
PASSIVE INFRARED
PIV
POST INDICATING VALVE
PNL
PANEL
RE
PATCH PANEL
PT
POTENTIAL TRANSFORMER
Pvc
POLYVINYL CHLORIDE
RC
ROOM CONTROLLER
ROE
REFLECTED CEILING PLAN
REC
RECEPTACLE
REF
REFER TO
REV
REVISION
RM
ROOM
RTRC
REINFORCED THERMORESETTING RESIN
CONDUIT
RU
RACK UNIT
HC
HORIZONTAL CROSS CONNECT
HID
HIGH INTENSITY DISCHARGE
SB
STANDBY
HE
HORSEPOWER
BHT
SHEET
HTR
HEATER
SLC
SIGNALING LINE CIRCUIT
Hz
HERTZ
SIM
SINGLEMODE
NONE
VEW� IIW
CITY OF
DESI�D
KSR
RENTON
DWN.
KSR
P anning/Building/Public Works Dept.
CHRXIM,
TSV
IF NCYF � 1�
BY
DATE
APPR
�F�D
S� �01�y
31
T-419202
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
.j
0q)
00
N
,It
CD
c\I
A
C/)
z
LLJ
Q
0
NEW ELEMENTARY NO. 16
I WE,
AR 2022
CHELAN AVE NE
RENTON, WA 98059
ELECTRICAL ABBREVIATIONS AND GENERAL NOTES
(r
w
I 11w 79 1471
(L