DDCVA MUST BE INSTALLED IMMEDIATELY AFTER .
PIPE PENETRATION THROUGH BUILDING FLOOR SLAB.
ROOM IN WHICH DDCVA IS LOCATED SHALL: Y
A HAVE FLOOR DRAIN CONNECTED TO THE SANITARY SEWER SYSTEM
R HAVE A HEATING SYSTEM (40- F MIN, TEMP,) NO HEAT TAPE
C. NOT BE USED FOR STORAGE AROUND THE DDCVA
E HAVE CLEARLY DELINEATED ACCESS WAYS TO DDCVA AND PIVs-
A RIGHT -OF -ENTRY AGREEMENT MUST BE GRANTED TO THE
71
TY OF RENTON FOR INSPECTION OF THE DDCVA
AND METER
''.EPARATE FIRE SPRINKLER PLANS INCLUDING INSTALLATION OF DDCVA
IAUST BE SUBMITTED TO RENTON FIRE PREVENTION DEPARTMENT FOR
REVIEW AND APPROVAL.
A SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED.
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR
COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929. MUELLER
SUPER CENTURION 200. AND WATEROUS PACER MATH 6" MECHANICAL
JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2"
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR,
4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS
STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE
PAINT No 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT, FIRE HYDRANT EXTENSION TO
BE USED IF REQUIRED.
N. 18" TO 20" BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3' SIDEWALK THAT IS ADJACENT TO
CURB
4.875" A 5" STORZ
5'x5'x6" THICK CONCRETE PAD AROUND
HYDRANT, FINISH TO MATCH SIDEWALK.
V IF
fc EXPANSION JOINT AT
2.� "� BACK OF SIDEWALK
CONCRETE SIDEWALK
/--OR PLANTING STRIP
.1
36" MIN
COVER Vic;
TWO-PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD 8" TOP SECTION WITH REGULAR BASE
SECTION LENGTH TO FIT VALVE NUT EXTENSION
AS REQUIRED.
RAISED PAVEMENT MARKER TYPE 88-A
STIMSONITE TWO-WAY BLUE REFLECTIVE
ONCRETE BLOCKING
,
ONCRETIE `
T
�4MAIN
"HRUST BLOC. 4
I
LINE TEE. WITH 6" FLANGE SIDE OUTLET.
\
-
6" CATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2-3/4" CDR -TEN STEEL TIE RODS.
16" z 8" x 4' MININUM
1/2 YARD OF 1-1/4" WASHED DRAIN ROCK
CONCRETE BEARING
BLOCK UNDER HYDRANT
1' ABOVE BOOT FLANGE PLACE 8 MIL
POLYETHYLENE FILM AROUND TOP AND SIDES OF
GRAVEL.
FIRE HYDRANT ASSEMBLY
LEVEL ALL GROUND LEVEL ALL GROUND
MIN 3' RADIUS
MIN 3' RADIUS
All
t
t
ONE MAN ROCK
1
�o
6� 1.
CO
6" CONCRETE PAD 6" CONCRETE PAC'
CUT FILL
HYDRANT LOCATION IN CUT OR FILL
PUBLIC WORKS FIRE HYDRANT ASSEMBLY STD. PLAN - 310.1
t).
DEPARTMENT
MARCH 2010
RE HYDRANT
NOT TO SCALE
ANO MA'NTAINFP PRIVATELY OWNED AND MAINTAINED
-1
MAXIMUM D FEET
PIPE LENGTH FROM PROPERTY LINE
10 DDCVA Y45T NOT EXCEED 90 TEEi
CONCRETE 90I1ARD9
i3J ',10'.
-ie• •
5 FT MAX.
7
91
• 110)
81 I
9"I
(71
3 �
H
z 4 INCH N /A WCH
0 �
7
m x
BUILDING WALL
PERIMETERS OF MINIMUM CLEARANCi
TO BE PAINTED ON FLOOR IN WHITE
ENAMEL PAINT STRIPE, WITH 2 INCH
STENCILED BLACK LETTERS TO SAY
"DO NOT BLOCK ACCESS"
t. MAIN LINE TEE(MJ EM O z WITH CONCRETE BLOCKING (WATER MAIN
LOCATED IN EASEMENT ON PRIVATE PROPERTY SHALL NOT BE MORE o
THAN 50 FEET TO BUILDING) �R'
2. BRANCH VALVE (FL x MJ) WITH VALVE BOX AND COVER �4-1;�-=-�
CLASS 52 DUCTILE IRON PIPE (4 INCH MINIMUM) ALL PIPE AND Z
FITTINGS SHALL BE RESTRAINED WITH SHACKLE RODS AND CONCRETE -
THRUST BLOCKS PER NFPA AND AWWA STANDARDS.
,I POST -INDICATOR VALVE (MJ) WITH TAMPER SWITCH
2-90' BENDS (FL x FL) WITH FLANGED DUCTILE IRON PIPE SPOOL
18" LONG SPOOL (FL x PE)
FLANGE COUPLING ADAPTOR FINISH FLOOR LEVEL
4 APPROVED DDCVA ON MAW LINE IN HORIZONTAL POSITION ONLY. (PER
LATEST DEPT OF HEALTH APPROVED LIST OF BACKFLOW PREVENTION ELEVATION VIEW OF DDCVA
DEVICES) BOTTOM OF DDCVA SHALL BE A MINIMUM OF 24 INCH ABOVE
FLOOR LEVEL AND NOT HIGHER THAN 3 FEET MAXIMUM. INSTALL 3
CONCRETE PADS OR ADJUSTABLE PIPE SUPPORT COLUMNS UNDER
DDCVA ADJUSTABLE STEEL PIPE SUPPORT,
3 O.S & Y VALVES TO BE RESILIENT SEATED WITH TAMPER SWITCHES. STANCHIONS BOLTED TO FLOOR.
ADD WIRING IN ACCOROAN[E WITH L & I
!0. METERED 3/4 INCH BY-PASS DCVA - BY-PASS METER SHALL BE A
3/4 INCH SENSUS-ECR" SR POSITIVE DISPLACEMENT METER EQUIPPED
ICE REGISTER WITH A REMOTE READ SENSOR PLATE MOUNTED ON THE
OUTSIDE OF THE BUILDING WALL (WALL MOUNT TYPE)
iI. SWING TYPE GRAVITY CHECK VALVE, FLANGE WITH BALL DRIP IN VAULT
OR OUTSIDE BUILDING
4"x 4" x 6' BULL ELBOW, THREADED
'3. UL LISTED FIRE DEPT. CONNECTION, UL LISTED BREAK AWAY CAPS.
LOCATE WITHIN 50 FEET MAXIMUM OF A PUBLIC FIRE HYDRANT.
AFTER FIELD INSTALLATION, MAIN DDCVA AND BY-PASS DCVA
MUST BE TESTED SATISFACTORILY BY A DEPARTMENT OF HEALTH
CERTIFIED BACKFLOW ASSEMBLY TESTER, TEST REPORT MUST BE
SUBMITTED TO CITY OF RENTON WATER UTILITY ENGINEERING
DEPARTMENT PRIOR TO ACTIVATION OF NEW UNE IN57ALL
BRASS A FLARE TEST COCKS WITH Y." FLARE CAPS.
PUBLIC WORKS INSIDE BUILDING INSTALL FOR 3" AND STD. PLAN - 360.5
DEPARTMENT LARGER DETECTOR DOUBLE CHECK
VALVE ASSEMBLY MARCH 2O10
6" DCDA IN BUILDING
1
NOT TO SCALE
RECORD WATER UTILITY DETAILS
FOR
CHICK=FIL=A RENTON
SECTION 18, TWP. 23 N., RGE 5 EAST, W. M.
CITY OF RENTON, KING COUNTY, STATE OF WASHINGTON
LLI 120 VOLT ELECTRICAL OUTLET FOR
Z HEAT TAPE.
INSTALL HEAT TAPE
}
J > FOR FREEZE
PROTECTION
CENTER BACKFLOW
3
PREVENTER IN
O REDUCED PRESSURE
ENCLOSURE
0, BACKFLOW ASSEMBLY
(RPBA)
3" MIN.
o
I I
3" MIN.
3" MIN.
INSULATED ENCLOSUR
"HOT BOX" OR EQUAL
3/8" X 4" ANCHOR
BOLTS PER
MANUFACTURER —
3" MIN.
CONCRETE SLAB
z
UNION z FINISHED
N GRADE
FINISHED
GRADE 1
-
f, 21
DRAIN
"a ? SEE NOTE 4
6" MINIMUM SLEEVE
FREE DRAINING > (TYR)
GRAVEL Z
CONNECT TO N
WATER METER
IMMEDIATELY
ADJACENT TO
RPBA
FLOW
INSTALLED W/ APP'D. TO OWNERS ELECTRICAL PANEL FRONT VIEW
MATERIAL PER UPC DIRECT BURIAL OR IN RIGID METER SIDE
(SIZE AS REQ.) CONDUIT PER ELECTRICAL
SIDE VIEW PERMIT REQUIREMENTS.
NOTES:
1. ALL REDUCED PRESSURE BACKFLOW ASSEMBLIES (RPBA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW
PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF
WASHINGTON DEPARTMENT OF HEALTH.
2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
F THE INSTALLATION F TH P A A PIPING, THE OWNER HA FURNISH, IN TA AN MAINTAIN TH
0 E0 E RPBA AND G. E O E SHALLINSTALL D E
RPBA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN.
3. THE RPBA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST
REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER
UTILITY CROSS -CONNECTION CONTROL SPECIALSIT, FAX NO. 425-430-7241.
4. DRAIN SHALL BE SIZED IN ACCORDANCE WITH AWWA CROSS CONNECTION CONTROL MANUAL STANDARDS
3" DRAIN FOR 1" OR SMALLER RPBA's, 4" DRAIN FOR 1.5" TO 2" RPBA's, 6" FOR 3" RPBA'S.
5. RPBA AND ENCLOSURE SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER.
STD. PLAN - 350.2
PUBLIC WORKS REDUCED PRESSURE BACKFLOW
Qt)
DEPARTMENT ASSEMBLY IN HOT BOX
MARCH 2010
NOT TO SCALE
Barghausen
Consulting Engineers, Inc.
18215 72nd Avenue South
Kent, WA 98032
425.251.6222 barghausen.com
AS -BUILT PLANS
REVISION
�MARKEF MARKER
I /' • •
I
LANL
MARKER TO INDICATE
WHICH SIDE OF STREET
HYDRANT IS ON (4" FROM
DOTS OR PAINTED LINE)
MARKER
I I T
JJR LANE ROAD OFFSET
MARKER TO INDICATE WHICH
SIDE OF STREET HYDRANT IS
ON (4" FROM DOTS OR
PAINTED LANE DIVIDER)
HYDRANT MARKERS
7•
��
�+- 4'
RAISED PAVMENT MARKER TYPE 88 AB
STIMSONITE TWO-WAY (BLUE)
MARKER
r__
ON SIDE STRL:_ -:Jr-ERE THE
HYDRANT IS WITHIN 20' OF A
MAIN TRAVELED STREET, THE
MARKER IS TO BE INSTALLED
ON THAT MAIN STREET
IMARKER
FIVE LANE ROAD OFFSET
MARKER TO INDICATE WHICH
SIDE OF STREET HYDRANT IS
ON (4" FROM DOTS OR
PAINTED LANE DIVIDER)
STD. PLAN - 310.3
PUBLIC WORKS HYDRANT MARKER LAYOUT
DEPARTMENT
U.OK
STARCH 2010
RANT MARKER
NOT TO SCALE
SURVEYED: RLH
DESIGNED JC
DRAWN: CMS
MM 3/15/21 CRJ CHECKED: AEM
,A I t Hrr'R APPROVeU: CRJ
W
Z_
J
I—
I �
�w
Flo
a DIRECTION OF FLOW
2
IY 0 I
(MIN.)
6" MIN.
6"MIN.(TYP.) UNION (TYP.)
PLAN
3"MAX.
Z CO Z
M O
6"MIN.
TO CITY
METER STACKED METER SECTION 6" MIN. FREE
BOXES DRAINING GRAvL
NOTES:
1. ALL DOUBLE CHECK VALVE ASSEMBLIES (DCVA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW PREVENIII_
ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF WASHINGTON
DEPARTMENT OF HEALTH.
2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
OF THE INSTALLATION OF THE DCVA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE
DCVA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN,
3. THE DCVA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TES1
REPORT SHALL BE SENT OR FAKED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER
UTILITY CROSS -CONNECTION CONTROL SPECIALIST, FAX NO. 425-430-7241,
4. DCVA AND METER BOX SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER,
34" TO 2" DOUBLE CHECK VALVE STD. PLAN - 340.8
* PUBLIC WORKS ASSEMBLY FOR IRRIGATION OR
DEPARTMENT RESIDENTIAL FIRE SPRINKLER
MARCH 2010
1" DCVA FOR IRRIGATION
NOT TO SCALE
RF5 JEA1
G pF W y� ti
z
,p 47671
�c�s F01 S T
sIONA L FN-5I��Iti
SCALE
N/A
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
83/1
CITY 0 F
-
RENTON
•...,.
ONE INCH
-- - •-
Planning/Building/ I uIJIIc Works Dept.
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
0® Know what's below.
p Call before you dig.
1 Dial 811
W- 406 303
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
U 12/19/2019
RECORD WATER UTILITY DETAILS FIELDBOOK:
0 FOR PAGE:
CHICK-FIL-A RENTON DRAWING NO:
® 375 RAINIER AVE S RENTON, WA 98055 C9.2
STORE NO.:04249 SHEET:17 OF:24