HomeMy WebLinkAboutRAM 015 01 Bid Item B17 Hydrant Assembly - Response12/22/15
015.01
9-30.2(1)3, 11
Gasket thickness shall be 1/8 in.
10
No catalog cut sheets submitted.
Std Plan 310.1
9-30.5SP 3, 6
x
3
Please use WSDOT form 350-109 when submitting the Certificate of Materials Origin for the above materials.
Justin Sencer
1/4/16
9.
Rev. 8-04 Shaded area indicates changes
MUELLER® SUPER CENTURION®
FIRE HYDRANT
❏ Super Centurion 250™ 3-way catalog numbers
(approved to UL 246, FM 1510, ANSI/AWWA C502 Standards) -
A-421 4-1/2" main valve opening three way (two hose nozzles and one pumper nozzle)
A-423 5-1/4" main valve opening three way (two hose nozzles and one pumper nozzle)
Super Centurion 200™ 2-way catalog numbers
(approved to ANSI/AWWA C502 Standards) -
A-420 4-1/2" main valve opening two way (two hose nozzles)
A-422 5-1/4" main valve opening two way (two hose nozzles)
A-425 5-1/4" main valve opening two way (two pumper nozzles)
Super Centurion 200™ 1-way catalog number
(approved to ANSI/AWWA C502 Standards)-
A-424 4-1/2" main valve opening one way (one pumper nozzle)
❏ 10 year limited warranty on material and workmanship
❏ Meets all applicable parts of ANSI/AWWA C502 Standard
❏ Post type dry barrel design
❏ Dry top design with O-ring sealed oil reservoir
❏ Traffic feature with stainless steel safety stem coupling
❏ Compression-type main valve closes with pressure for positive seal; it is made of rubber
and is conveniently reversible providing a spare for long service life
❏ Operating nut available in wide variety of shapes and sizes-open left or right
❏ Field replaceable hose and pumper nozzles
❏ Hose and pumper nozzles have large radius, full flow openings for low friction loss
❏ Contoured shoe is designed for full flow
❏ Dual bronze drain valves provide effective barrel drainage
❏ 250 psig (1723 kPa) maximum working pressure, 500 psig (3447 kPa) static test pressure for 3-way hydrants;
200 psig (1379 kPa) maximum working pressure, 400 psig (2758 kPa) static test pressure for 2-way and 1-way hydrants
Dimensions
Non-rotating
bolt design:
cast-in pads elimi-
nate need
for anti-rotation bolts.
Front view detail
of Mechanical joint
(Standard only)
Vertical
Flange*
Mechanical joint
standard and D-150
Flange
ANSI 125/150 or
PN 10/16 Drilling
Slip-on
* 4" Vertical shoe available for
A-420 and A-421 hydrants.
SEE PAGE 9.28 FOR ORDERING INSTRUCTIONS