SURFACE WATER STANDARD PLAN NOTES:
THE FOLLOWING IS A LISTING OF GENERAL NOTES THAT SHALL BE INCORPORATED IN THE DRAINAGE PLAN SET. ALL THE NOTES ON THE LIST MAY NOT PERTAIN TO EVERY
PROJECT. THE APPLICANT OR OWNER HEREBY REFERRED TO AS APPLICANT MAY STRIKE OUT IRRELEVANT NOTES IF NOT APPLICABLE TO THE PROJECT. HOWEVER THE
APPLICANT SHALL NOT RENUMBER NOR EDIT THE REMAINING NOTES. IF ADDITIONAL NOTES ARE NEEDED FOR SPECIFIC ASPECTS. THEY SHALL BE ADDED AFTER THE
SURFACE WATER STANDARD PLAN NOTES.
1. BEFORE ANY CONSTRUCTION OR DEVELOPMENT ACTIVITY OCCURS, A PRE -CONSTRUCTION MEETING SHALL BE HELD AMONG THE CITY OF RENTON, HEREBY
REFERRED TO AS THE CITY, THE APPLICANT, AND THE APPLICANT'S CONTRACTOR.
2. THE APPLICANT SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY CITY, STATE. AND FEDERAL PERMITS PRIOR TO CONSTRUCTION.
3. ALL STORM DRAINAGE IMPROVEMENTS SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE LATEST EDITION OF THE CITY OF RENTON SURFACE
WATER DESIGN MANUAL (RENTON SWDM), RENTON MUNICIPAL CODE (RMC). AND THE STANDARD SPECIFICATIONS FOR ROAD, BRIDGE AND MUNICIPAL
CONSTRUCTION PREPARED BY WSDOT AND THE AMERICAN PUBLIC WORKS ASSOCIATION (APWA). IT SMALL BE THE SOLE RESPONSIBILITY OF THE APPLICANT TO
CORRECT ANY ERROR OMISSION OR VARIATION FROM THE ABOVE REQUIREMENTS FOUND IN THE PLANS. ALL CORRECTIONS SHALL BE AT NO ADDITIONAL COST TO
THE CITY.
4. APPROVAL OF THE ROAD, GRADING, PARKING, BUILDING, AND DRAINAGE PLAN DOES NOT CONSTITUTE AS APPROVAL OF ANY OTHER CONSTRUCTION (E.G. WATER,
SEWER. GAS, ELECTRICAL. ETC.). PLANS FOR STRUCTURES SUCH AS BRIDGES. VAULTS, AND RETAINING WALLS REQUIRE A SEPARATE REVIEW AND APPROVAL BY
THE CITY PRIOR TO CONSTRUCTION. THE SURFACE WATER DRAINAGE SYSTEM SHALL BE CONSTRUCTED ACCORDING TO THE APPROVED PLANS. ANY DEVIATION
FROM THE APPROVED PLANS WILL REQUIRE COORDINATION FOLLOWED BY WRITTEN APPROVAL FROM THE CITY.
5. A COPY OF THE APPROVED PLANS SHALL BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS.
6. THE LOCATIONS OF ALL EXISTING UTILITIES SHOWN HEREON HAVE BEEN ESTABLISHED BY FIELD SURVEY OR OBTAINED FROM AVAILABLE RECORDS AND SHALL
THEREFORE BE CONSIDERED APPROXIMATE ONLY AND NOT NECESSARILY COMPLETE, IT IS THE SOLE RESPONSIBILITY OF THE APPLICANT AND THE APPLICANTS
CONTRACTOR TO INDEPENDENTLY VERIFY THE ACCURACY OF ALL UTILITY LOCATIONS SHOWN. AND TO FURTHER DISCOVER AND AVOID ANY OTHER UTILITIES NOT
SHOWN HEREON THAT MAY BE AFFECTED BY THE IMPLEMENTATION OF THIS PLAN. THE APPLICANT SHALL RECORD ON THE AS -BUILT DRAWINGS ALL
UNDOCUMENTED UTILITIES DISCOVERED AND ANY CHANGES TO THE APPROVED PLANS, THE APPLICANT SHALL IMMEDIATELY NOTIFY THE ENGINEER OF RECORD IF A
CONFLICT EXISTS.
7. VERTICAL DATUM SHALL BE NAVD 88 AND HORIZONTAL DATUM SHALL BE NAD 83 (WA STATE PLANE, NORTH), UNLESS OTHERWISE APPROVED BY THE CITY.
REFERENCE BENCHMARK, DATUM, AND ELEVATIONS SHALL BE NOTED ON THE PLANS.
8, ALL UTILITY TRENCH BACKFILL AND ROADWAY SUBGRADE SHALL BE COMPACTED TO 95%MAXIMUM DRY DENSITY PER SECTION 2-03.304)D - COMPACTION AND
MOISTURE CONTROL TESTS OF THE WSDOT STANDARD SPECIFICATIONS. IN PERMEABLE PAVEMENT AND OTHER INFILTRATION AREAS. ALL TRENCH BACKFILL SHALL
BE FIRM AND UNYIELDING BUT IN NO CASE SHALL BE COMPACTED TO MORE THAN 92% OF MAXIMUM DRY DENSITY.
9. OPEN CUTTING OF EXISTING ROADWAYS FOR STORM DRAINAGE WORK IS NOT ALLOWED UNLESS SPECIFICALLY APPROVED BY THE CITY AND NOTED ON THESE
APPROVED PLANS- ANY OPEN CUT SHALL BE RESTORED IN ACCORDANCE WITH THE CITY TRENCH RESTORATION STANDARDS.
10. ALL PIPE AND STRUCTURES SHALL BE STAKED FOR SURVEY LINE AND GRADE PRIOR TO THE START OF CONSTRUCTION. WHERE SHOWN ON THE PLANS OR WHERE
DIRECTED BY THE CITY, THE EXISTING MANHOLES, CATCH BASINS, OR INLETS SHALL BE ADJUSTED TO THE GRADE AS STAKED.
11. ALL FLOW CONTROL FACILITIES SHALL BE INSTALLED AND IN OPERATION PRIOR TO, OR IN CONJUNCTION WITH, ANY CONSTRUCTION ACTIVITY UNLESS OTHERWISE
APPROVED BY THE CITY.
12. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH THE CURRENT STATE OF WASHINGTON STANDARD
SPECIFICATION FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION
MATERIAL, AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL SE
SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE, ALL PIPE BEDDING AND BACKFILL SHALL BE AS SHOWN ON THE CITY STANDARD PLAN 220.00, 220,10. AND
22D.20,
13. STEEL PIPE SHALL BE ALUMINIZED. OR GALVANIZED WITH ASPHALT TREATMENT 1. 2. OR 51NSIDE AND OUTSIDE,
14. ALL DRAINAGE STRUCTURES SUCH AS CATCH BASINS AND MANHOLES SHALL BE FITTED WITH DUCTILE IRON, BOLT -LOCKING LIDS PER THE CITY STANDARD PLAIN
204.10 20620. 204.30 204.40 AND ZD4.50. STRUCTURES SHALL HAVE:
• RECTANGULAR OR ROUND, SOLID LIDS WHEN NOT COLLECTING RUNOFF, AND OUTSIDE OF THE ROADWAY.
• ROUND, SOLID LIDS WHEN NOT COLLECTING RUNOFF, AND LOCATED WITHIN THE ROADWAY, BUT OUTSIDE OF THE CURBIGUTTER LINE.
• ROUND, SOLID LIDS DISPLAYING THE CITY LOGO WHEN WITHIN THE PUBLIC RIGHT-OF-WAY OR IN AN EASEMENT TO THE CITY. PRIVATE STRUCTURE LIDS OUTSIDE
PUBLIC RIGHT-O WAY AND EASEMENTS TO THE CITY SHALL NOT DISPLAY THE CITY LOGO,
15. BUILDINGS AND OTHER STRUCTURES SHALL BE PLACED IN ACCORDANCE WITH TABLE 4.1 EASEMENT WIDTHS AND BUILDING SETBACKS LINES OF THE RENTON SWDM.
16. LIDS OF MANHOLESICATCH BASINS WITHIN PUBLIC RIGHT-OF-WAY SHALL NOT BE ADJUSTED TO FINAL GRADE UNTIL AFTER PAVING. ALL MANHOLEICATCH BASIN RIMS
SHALL BE ADJUSTED TO BE FLUSH WITH FINAL FINISHED GRADES. UNLESS OTHERWISE SHOWN.
17. ALL DRIVEWAY CULVERTS LOCATED WITHIN CITY RIGHT-OF-WAY SHALL BE OF SUFFICIENT LENGTH TO PROVIDE A MINIMUM 3:1 SLOPE FROM THE EDGE OF THE
DRIVEWAY TO THE BOTTOM OF THE DITCH.
STD. PLAN - 267.00
PUBLIC WORKS SURFACE WATER STANDARD PLAN e68a(AM,Jby:
DEPARTMENT NOTES (1 OF 2) Martin Pastucha8/13/2020
DATE
DocuSign Envelope ID: 3B1B34D3-7EOA-476C-ADB3-4329FFEOC108
%E1
4• FLAT FACE GOTHIC
�9'DIA 4&1/8'DI-I3f18'DIA1/rDIA(2) 3/8•-16 SS SOCKET HEAD CAP 15" DIA (1) OPEN PICKHOLSCREW(ALLENHEAD) W/WSHRS 5/8•
ON A 8" DIA BOLT CIRCLE
PLAN VIEW FRAME SECTION COVER SECTION
1 8:4E
CAST IRON FRAME AND PAVED AREA (TYR)
COVER, SEE NOTE 3
12 EXTEND DEIGN P RISER
IH•�{f 2' ABOVE DESIGN PONDING
ELEVATION OR PER PLAN FERNCO GASKETED
V OUIK CAP OR SIMILAR
a DESIGN PONDING
ELEVATION PERWSDOT"3..11(2)
8' CLASS "B' PER WSDOT 9-03.11(2)
ASPHALT, SEE NOTE 4
4" COMPACTED SAND OR C
GRAVEL BACKFILL FOR DRAINS
PER WSDOT 9-03.12(4) o
CLEANOUT RISER, SEE NOTE 2 I'I=
CLEANOI T RISL
SOIL TIGHT 45° BEND SEE NOTE 2 -
WYE
SOIL TIGHT =
COUPLER
UNDERDRAIN, FOOTING
DRAIN COLLECTOR, OR -;✓�
ROOF DRAIN COLLECTOR
PIPE, SEE NOTED '1 CLEANOUT RISER LOCATED WITHIN
BIORETENTION PONDING AREA
.-� (III
TO OVERFLOW ;.
STRUCTURE OR
STORM MAIN ':tiJ Yam"
MECHANICAL PLUG OR
CONTINUED CONNECTION
TYPICAL CLEANOUT CONFIGURATION
NOTES:
1. DIAMETER TO BE 6-INCHES MINIMUM PRIVATE, 8-INCHES MINIMUM PUBLIC. LINDERMAIN PIPE PER STD. PLAN 262.10.
Z CLEANOUT RISER SHALL BE SAME MATERIAL AS CONNECTED UNDERDRAIN, FOOTING DRAIN COLLECTOR, OR ROOF DRAIN COLLECTOR PIPE.
3. FRAME AND COVER SHALL BE EJ PRODUCTS 3675ZIPT AND 3675APT OR APPROVED EQUAL. COVER TO BE LOCKING WITH ALLEN HEAD BOLT. MARKED 'STORM. OR
•DRAIN.
4. FOR CLEANOUTS FULLY OR PARTIALLY WITHIN UNPAVED AREAS OUTSIDE OF BIORETENTION PONDING AREA. POUR 8" THICK, r#' SQUARE CONCRETE COLLAR
AROUND FRAME. CONCRETE COLLAR SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,ODO PSI.
GENERAL NOTES:
1. CLEANOUTS FOR UNDERDRAIN, FOOTING DRAIN COLLECTOR, AND ROOF DRAIN COLLECTOR PIPES SHALL BE INSTALLED AT A MINIMUM OF EVERY 100 FEET, AT
EVERY 90 DEGREE OR SECOND 45 DEGREE BEND. AT THE END OF EVERY COLLECTOR PIPE, AND AT EACH END OF AN UNDERDRAIN PIPE NOT CONNECTED TO AN
OVERFLOW STRUCTURE, CLEANOUTS SHALL BE INSTALLED TO ALLOW FOR MAINTENANCE ACCESS TO ALL PIPES.
2. ALL FITTINGS SHALL BE SOIL TIGHT.
3- CLEANOUT RISER SHALL BE LOCATED OUTSIDE OF SIORETENTION PONDING WHERE POSSIBLE.
4. CLEANOUTS SHALL NOT BE LOCATED WITHIN THE STREET TRAVEL LANE, UNLESS OTHERWISE APPROVED BY THE CITY.
UNLESS OTHERWISE NOTED, DRAWING IS NOT TO SCALE (NTS;
STD. PLAN - 226.00
� PUBLIC WORKS ARosDnea y:
� DEPARTMENT STORM SYSTEM CLEANOUT artin Pastucha s/13/20 (
-�lj.8�;��:1.1>jLS8BAg90... DA?L
■E7
DocuSign Envelope ID: 3B1B34D3-7EOA-476C-ADB3-4329FFEOC108
A PORTION OF THE NW 1/4 OF THE NE 1/4 OF SECTION 08,
TOWNSHIP 23 NORTH, RANGE 05 EAST, WILLAMETTE MERIDIAN
CITY OF RENTON, COUNTY OF KING, STATE OF WASHINGTON
DRAINAGE NOTES AND DETAILS
SURFACE WATER STANDARD PLAN NOTES:
THE FOLLOWING IS A LISTING OF GENERAL NOTES THAT SHALL BE INCORPORATED IN THE DRAINAGE PLAN SET. ALL THE NOTES ON THE LIST MAY NOT PERTAIN TO EVERY
PROJECT. THE APPLICANT OR OWNER. HEREBY REFERRED TO AS APPLICANT. MAY STRIKE OUT IRRELEVANT NOTES IF NOT APPLICABLE TO THE PROJECT. HOWEVER, THE
APPLICANT SHALL NOT RENUMBER NOR EDIT THE REMAINING NOTES. IF ADDITIONAL NOTES ARE NEEDED FOR SPECIFIC ASPECTS. THEY SHALL BE ADDED AFTER THE
SURFACE WATER STANDARD PLAN NOTES.
18. ROCK FOR EROSION PROTECTION OF ROADSIDE DITCHES, WHERE REQUIRED. SHALL BE OF SOUND QUARRY ROCK PLACED TO A MINIMUM DEPTH OF ONE (1) FOOT
AND SHALL MEET THE FOLLOWING SPECIFICATIONS:
• 4-BINCH ROCK K)-71%PASSING-
2-41NCH ROCK/ 30- 40% PASSING: AND
• LESS THAN 2 INCH ROCK 110-20%PASSING
.
19 FOOTING DRAINAGE SYSTEMS AND ROOF DOWNSPOUT SYSTEMS SHALL NOT BE INTERCONNECTED AND SHALL SEPARATELY CONVEY COLLECTED FLOWS TO THE
CONVEYANCE SYSTEM OR FLOW CONTROL FACILITY ON THE SITE. UNLESS APPROVED BY THE CITY. FOOTING DRAINS SMALL NOT BE CONNECTED TO ON-SRE BMPS.
20. THE END OF EACH STORM DRAIN STUB SMALL BE CAPPED. A CLEANOUT TOPPED WITH A BOLT -LOCKING LID MARKED'STORM- OR `DRAIN' SHALL BE LOCATED AT THE
PROPERTY LINE OR AT THE POINT OF CONNECTION OF A PRIVATE STORM DRAINAGE CONVEYANCE SYSTEM PER THE CRY STANDARD PLAN 22TM
21. ALL STORM SYSTEM EXTENSIONS SHALL BE STAKED FOR LINE AND GRADE BY A SURVEYOR LICENSED IN WASHINGTON STATE, AND CUT SHEETS SMALL BE PROVIDED
TO THE CRY PRIOR TO CONSTRUCTION.
22. ALL NEWLY4 STALLED AND NEWLY -REHABILITATED (PUBLIC AND PRIVATE) STORM CONVEYANCE SYSTEMS SHALL BE INSPECTED BY MEANS OF REMOTE CCTV
ACCORDING TO THE CITY STANDARD PLAN 266.00. CCTV INSPECTIONS AND REPORTS SHALL BE SUBMITTED TO THE CITY PRIOR TO RECEIVING APPROVAL TO INSTALL
PROJECT CURBS. GUTTERS AND/OR PAVEMENT.
23- ALL STORM SYSTEMS AND CONNECTIONS TO EXISTING MAINS SMALL BE TESTED IN ACCORDANCE WITH SECTION 7.04.3(1) OF THE WSDOT STANDARD SPECIFICATIONS
AND IN THE PRESENCE OF A REPRESENTATIVE OF THE CRY. STORM DRAIN STUBS SHALL BE TESTED FOR ACCEPTANCE AT THE SAME TIME THE MAIN STORM IS
TESTED.
24. FOR ALL DISTURBED PERVIOUS AREAS (COMPACTED. GRADED, LANDSCAPED, ETC.) OF THE DEVELOPMENT SITE, TO MAINTAIN THE MOISTURE CAPACITY OF THE SOIL
EITHER STOCKPILE AND REDISTRIBUTE THE EXISTING DUFF LAYER AND NATIVE TOPSOIL OR AMEND THE SOIL WITH COMPOST IN ACCORDANCE WITH STANDARD PLAN
264.00.
25. ISSUANCE OF THE BUILDING OR CONSTRUCTION PERMITS BY THE CITY DOES NOT RELIEVE THE APPLICANT OF THE CONTINUING LEGAL OBLIGATION AND/OR LIABILITY
CONNECTED WITH STORMWATER DISPOSAL. THE CITY DOES NOT ACCEPT ANY OBLIGATION FOR THE PROPER FUNCTIONING AND MAINTENANCE OF THE STORM
SYSTEM PROVIDED DURING CONSTRUCTION.
26. ADEQUATE SAFEGUARDS, SAFETY DEVICES. PROTECTIVE EQUIPMENT, FLAGGERS. AND ANY OTHER ACTIONS NEEDED TO PROTECT THE LIFE. HEALTH, AND SAFETY OF
THE PUBLIC, AND TO PROTECT PROPERTY IN CONNECTION WITH THE PERFORMANCE OF WORK SHALL BE PROVIDED. ANY WORK WITHIN THE TRAVELED
RIGHT-O WAY THAT MAY INTERRUPT NORMAL TRAFFIC FLOW SHALL REQUIRE A TRAFFIC CONTROL PLAN APPROVED BY THE CITY. ALL SECTIONS OF THE WSDOT
STANDARD SPECIFICATIONS 1-10 TEMPORARY TRAFFIC CONTROL SHALL APPLY.
27. PROJECTS LOCATED WITHIN THE CFTYS AQUIFER PROTECTION AREA LAPA) SHALL COMPLY WITH SPECIAL REQUIREMENT 06 OF THE RENTON SWDM AND AQUIFER
PROTECTION REGULATIONS (RMC 4-34150).
28, PLACEMENT OF SURFACE APPURTENANCES (CATCH BASIWMANHOLE LIDS, CLEANOUTS. INLETS, ETC.) IN THE STREET TRAVEL LANE WHEEL PATH, INTERSECTIONS OF
STREET TRAVEL LANES, BIKE LANES. SIDEWALKS, AND CROSSWALKS SHALL BE AVOIDED WHENEVER POSSIBLE. ANY SURFACE APPURTENANCE PLACED IN A
SIDEWALK OR CROSSWALK SHALL BE FITTED WITH A NONSLIP OR NONSKID LID PER ADA REQUIREMENTS.
29. CLEARLY LABEL PUBLIC AND PRIVATE SYSTEMS ON THE PLANS. PRIVATE SYSTEMS SHALL BE MAINTAINED BY THE APPLICANT.
30. MINIMUM COVER OVER STORM DRAINAGE PIPE SMALL CONFORM TO TABLE 42.1 A2 OF THE RENTON SWDM.
31. CONSTRUCTED PERMEABLE PAVEMENT SHALL BE PERMEABLE ENOUGH TO ABSORB WATER AT A MINIMUM RATE OF 20 INCHES PER HOUR IMMEDIATELY AFTER THE
PAVEMENT SURFACE HAS BEEN WETTED CONTINUOUSLY FOR AT LEAST 10 MINUTES. COMPLIANCE WITH THIS MINIMUM RATE SHALL BE CHECKED PRIOR TO
CONSTRUCTION APPROVAL OF THE PAVEMENT. COMPLIANCE MAY BE CHECKED USING A SIMPLE BUCKET TEST IN WHICH 5 GALLONS OF WATER IS POURED ONTO THE
PAVEMENT SURFACE ALL AT ONCE. IF ONLY A MINOR AMOUNT OF WATER PONDS OR RUNS OFF THE SURFACE, THEN THE PAVEMENT IS CONSIDERED TO MEET THE
MINIMUM RATE OF ABSORPTION. AT LEAST ONE TEST SHALL BE CONDUCTED PER 1,ODO SQUARE FEET OF PERMEABLE PAVEMENT, IF THIS TEST IS NOT CONCLUSIVE,
THEN ANOTHER TEST PER ASTM C1701 SHALL BE CONDUCTED. FOR LARGE AREAS (E.G.. PARKING AREAS). TESTING OBSERVATION MAYBE ACCOMPLISHED WHILE
WALKING BEHIND A SLOWLY MOVING WATER TRUCK DISCHARGING WATER AT A RATE SIMILAR TO THE BUCKET TEST. PERMEABLE PAVERS SMALL BE TESTED USING
ASTM C1781.
STD. PLAN - 267.10
PUBLIC WORKS SURFACE WATER STANDARD PLAN l by:
DEPARTMENT NOTES (2 OF 2) artin PastuchV4397a/13/2ozo
DATE
DocuSign Envelope ID: 3B1B34D3-7EOA-476C-ADB3-4329FFEOC108
OPTIONAL PARALLEL TANK
TERMINAL END
I 136 MINA �
IN PIPE ACCESS RISERS. SEE NOTE 4 F
(BACKUP SYSTEMS, I SAME SIZE AS INLET PIPE.
i
L-------------------------------J TY
WHERE Si I/I I I 1r MIN. DIA.
Ill ZMIN.
II II
ACCESS RISERS PER 1 FLOW Al
A �-� O STD. PLAN 235.10 O �-W
OUTLET PIPE INLET PIPE
(FLOW THROUGH)
CONTROL
STRUCTURE WITH 36" MIN. CONNECTOR PIPE
SOLID LOCKING LID PLAN TYPE 2 CATCH BASIN (CB)
'FLOW -THROUGH' SYSTEM SHOWN SOLID. REQUIRED FOR FLOW THROUGH
DESIGNS FOR TLOW BACKUP' SYSTEM AND SYSTEM ONLY PER STD. PLAN 201 t:
PARALLEL TANKS SHOWN DASHED
FINISH GRADE
W MAX. 100' MAX.
T MIN. DIA, AIR VENT PIPE
ACCESS RISERS, SEE WELDED TO TANK (REQUIRED
STD. PLAN 235.10 IF NO ACCESS RISER ON TANK)
r MAx.
® 2' MIN,
SEE NOTE 10 DETENTION TANK
ITYP) (SIZE AS REQUIRED)
-\ 6'SEDIMENT STORAGE •. ^FLOW
r MIN.
r MIN. 36" MIN. DIA. (TYR) SEE NOTE 10 (TYPJ
CONTROL STRUCTURE (FROP-T SECTION A
SHOWN). MIN. 54• DIA. TYPE 2 CB
PER STD. PLAN 237.00
NOTES: FLOW RESTRICTOR PER STD. PLAN 237.00
1. THIS DETAIL IS A SCHEMATIC REPRESENTATION ONLYACTUALCONFIGURATION WILL VARY DEPENDING ON SPECIFIC SITE CONSTRAINTS AND APPLICABLE
DESIGN CRITERIA.
2. MINIMUM TANK DIAMETER IS 16 INCHES.
3. METAL PARTS PREFERRED TO BE STAINLESS STEEL, ALUMINIZED STEEL. OR ALUMINUM. ALL OTHER STEEL PARTS MUST BE GALVANIZED WITH TREATMENTS 1,
2. OR 5.
4. ACCESS RISERS REQUIRED WITHIN 50 FEET FROM ANY LOCATION IN THE DETENTION TANK AND WITHIN 5 FEET OF EACH TERMINAL END. ANY LOCATION WITHIN
THE DETENTION TANK SHALL HAVE A DIRECT LINE OF SIGHT FROM AN ACCESS POINT, UNOBSTRUCTED BY ANY RESTRICTIONS SUCH AS A WALL OR BAFFLE.
5. H-20 LIVE LOADS MUST BE ACCOMMODATED FOR TANKS LYING UNDER PARKING AREAS, ROADWAYS, AND ACCESS ROADS.
6. BEDDING OF THE PIPE SHALL BE IN ACCORDANCE WITH STD. PLAN 220.00.
7. PRIOR TO STARTUP, DETENTION TANK SHALL PASS LEAK TEST.
S. PIPE MATERIAL, JOINTS, AND PROTECTIVE TREATMENT FOR TANKS SHALL BE IN ACCORDANCE WITH SECTIONS 7-04 AND 9-05 OF THE WSDOT/APWA STANDARD
SPECIFICATION.
9. ALL TANK ACCESS OPENINGS MUST BE READILY ACCESSIBLE BY MAINTENANCE VEHICLES.
10. WHEN CONNECTING TO ANEW PIPE, USE A FLEXIBLE CONNECTOR (KOR-N-SEAL BOOT WITH CORRUGATED PIPE ADAPTER OR APPROVED EQUAL). WHEN
CONNECTING TO AN EXISTING PIPE, USE A FABRICATED SAND COLLAR OF THE SAME MATERIAL AS THE CONNECTING PIPE.
11. SEE CONSTRUCTION PLANS FOR SPECIFIC PROJECT REQUIREMENTS. UNLESS OTHERWISE NOTED, DRAWING B NOT TO SCALE NITS)
STD. PLAN - 235.00
• PUBLICWORKS DIRIUMIlMB by:
DEPARTMENT TYPICAL DETENTION TANK ayyrt�gqimyn�� �P�astucha 8/13/202
44A1:4AXWA4YD.. DATE
Abbey Road Group
Land Development
Services Company, LLC
2102 E MAIN AVE, SUITE 109
PUYALLUP, WA 98372
P.O. Box 1224, Puyallup, WA 98371
(253) 435-3699, Fax (253) 446-3159
F W,�
8:48
1 8:4
DocuSign Envelope ID: 6EECF5B6-602A-4E4A-B436-A317AA638878
6. IT, OR 24-
ONE R3 BAR HOOP FOR W HEIGHT
INCREMENT (SPACED EQUALLY),
SLL-tI 1
RECTANGULAR ADJUSTMENT SECTION
6
PIPE ALLOWANCES
MAXIMUM
PIPE MATERIAL
INSIDE
DIAMETER
REINFORCED OR PLAIN
12'
CONCRETE
ALL METAL PIPE
/6
CPSSP',
12'
STD. SPEC. 9-05.20
SOLID WALL PVC,
STD. SPEC. 9-05.12 1
()
15'
PROFILE WALL PVC,
STD. SPEC. 9-05.12(2)
15'
'CORRUGATED POLYETHYLENE STORM
SEWER PIPE
NQt� NOTES:
sFF�,
'0 � _ 8 �! 1 AS ACCEPTABLE IN THE PRECAST BASE SECTION
ON FIBERS IVES TO THE REBAR (PLACED
OWN
03 BAR EACH CORNER 1 I
I I i
f
I
43 BM EACH SIDE
R3 BAR EACH WAY
PRECAST BASE SECTION
03 BAR HOOP
ACCORDANCE WITH STANDARD SPECIFICATION
9-05.50(9)), OR WIRE MESH HAVING A MINIMUM AREA OF
0.12 SQUARE INCHES PER FOOT SHALL BE USED WITH
THE MINIMUM REQUIRED REBAR SHOWN IN THE
ALTERNATIVE PRECAST BASE SECTION. WIRE MESH
SHALL NOT BE PLACED IN THE KNOCKOUTS. AS AN
ACCEPTABLE ALTERNATIVE TO THE REBAR SHOWN IN
THE RECTANGULAR ADJUSTMENT SECTION, WIRE MESH
HAVING A MINIMUM AREA OF 0.12 SQUARE INCHES PER
FOOT MAY BE USED.
2. THE KNOCKOUT DIAMETER SHALL NOT BE GREATER
THAN 201. KNOCKOUTS SHALL HAVE A WALL THICKNESS
OF r MINIMUM TO 2.5' MAXIMUM. PROVIDE A 1.5•
MINIMUM GAP BETWEEN THE KNOCKOUT WALL AND THE
OUTSIDE OF THE PIPE. AFTER THE PIPE IS INSTALLED,
FILL THE GAP WITH JOINT MORTAR IN ACCORDANCE WITH
STANDARD SPECIFICATION 9-04 3.
3- THE MAXIMUM DEPTH FROM THE FINISHED GRADE TO
THE LOWEST PIPE INVERT SHALL BE 5 FEET.
4. THE FRAME AND GRATE MUST BE INSTALLED WITH THE
FLANGE DOWN.
5. THE PRECAST BASE SECTION MAY HAVE A ROUNDED
FLOOR, AND THE WALLS MAY BE SLOPED AT A RATE OF
1 H:24V OR STEEPER.
6, THE OPENING SHALL BE MEASURED AT THE TOP OF THE
PRECAST BASE SECTION.
7. ALL PICKUP HOLES SHALL BE GROUTED FULL AFTER THE
INLET HAS BEEN PLACED. USE GROUT TYPE 2 FOR
k3 BAR EACH NON -SHRINK APPLICATIONS IN ACCORDANCE WITH
STANDARD SPECIFICATION 9-20. 2.
CORNER 18' MIN. 3( )
8- ALL GRADE RINGS AND CASTINGS SHALL BE SET IN
MORTAR IN ACCORDANCE W ITH STANDARD
SPECIFICATION 9-04.3. THEN APPLY MORTAR TO INSIDE
AND OUTSIDE OF ALL JOINTS. RINGS. RISERS, AND
FRAMES.
9. MORTAR SHALL REMIXED AND APPLIED PER
MANUFACTURERS DIRECTIONS.
10. FRAME SHALL BE ADJUSTED TO PAVEMENT GRADE BY
TAPPING UNTIL FRAME IS FLUSH WITH PAVEMENT AS
DETERMINED WITH A STRAIGHT EDGE OF SUFFICIENT
LENGTH.
11_ ALL MORTAR JOINTS SHALL BE TRIMMED FLUSH AND
SEE NOTE 1 REMAIN VISIBLE UPON COMPLETION.
ALTERNATIVE PRECAST BASE SECTION
UNUSS OTHERWISE NOTED, DRAWING IS NOT TO STeIc (TUTS)
STD. PLAN - 200.00
CRIPUBLIC WORKS APPR ET
DEPARTMENT CATCH BASIN TYPE 1 GAZ 9/28/2018 I
DATE
DocuSign Envelope ID: 3B1B34D3-7EOA-476C-ADB3-4329FFEOC108
1 ICITY OF RENTON REDLINES 3.18.21
2 CITY OF RENTON REDLINES 5.24.21
3 ICITY OF RENTON REDLINES 7.21.21
STANDARD TYPE 2, 60' DIA CATCI
BASIN (CB) CONCRETE TOP SLAB
LADDI
36"CARP R4
24-INCH BOLT LOCKING RING AND COVER ADJUSTMENT RINGS
AS NECESSARY. PER STANDARD PLANS 204 40 AND 204.50 -
CRUSHED SURFACING TOP COURSE
COMPACTED WSDOT STD. SPEC 9-03.9(3)
TO 95% MAX DENSITY(TYP.) /
MANHOLE STEPS. 1r O.C. J/
WELD OR BOLT STANDARD MANHOLE STEPS J
NO. I REVISION
LOCKING LID LMARKED'DRAIN')
ED OVER 24' DIA. ECCENTRIC OPENING
MAINTAIN 1' GAP BETWEEN BOTTOM OF
SLAB AND TOP OF RISER. PROVIDE
PLIABLE GASKET TO EXCLUDE DIRT
41
PLACE CEMENT MORTAR SEAL BETWEEN
TOP SLAB AND MANHOLE, SEE NOTE 6
RISER, 36 DIA MIN.. SAME MATERIAL AND
GAUGE AS TANK WELDED OR FUSED TO TANK
DETENTION TANK
SECTION
:45 AI
NOTES:
1. USE ADJUSTING BLOCKS AS REWIRED TO BRING FRAME TO GUIDE,
2. METAL PARTS PREFERRED TO BE STAINLESS STEEL. ALUMINIZED STEEL, OR ALUMINUM. ALL OTHER STEEL PARTS
MUST BE GALVANIZED WITH TREATMENTS 1. 2, OR 5.
3. MUST BE LOCATED FOR ACCESS BY MAINTENANCE VEHICLES.
4- MAY SUBSTITUTE WSDOT SPECIAL TYPE IV MANHOLE (RCP ONLY).
S. TOP SLAB SHALL BE RATED FOR HS-20 LOADING.
6. ALL GRADE RINGS AND CASTINGS SHALL BE SET IN MORTAR IN ACCORDANCE WITH STANDARD SPECIFICATION 9-04.3.
UNLESS OTHERWISE NOTED, DRAWING IS NOT TO SCALE INTS)
STD. PLAN - 235.20
PUBLIC WORKS �e6 by:
DEPARTMENT DETENTION TANK ACCESS Martin Pastucha 8/13/20z I 8:,
"1�'i�b98B4490.. DATE
DocuSign Envelope ID: 6EECF5B6-602A-4E4A-B436-A317AA638878
CATCH RASIN FRAME AND VANED
GRATE PER STD. PLAN 204.00
RECTANGULAR OR CIRCULAR ADJUSTMENT
SECTION O SECTIONS MAX.)(TWO
MORTAR, (TYP.), SEE NOTE 5
4' MIN.
2r MAX. 16' MAX. - FLAT SLAB TOP
48", 54'. 60", 71�4
96, 12P ORE
NOTE 6, TYP.
MAX FOR
MT
MAINTENANCE
STEPS OR
LADDER
1r (TYP.)Tr
rMININ24"
2.5'MAORCING
STEEL, (TYP.)
MIN.GRAVEL
12'BEDDING
BACKFILL FOR PIPE ZONE
PER WSDOT STD.
SPECIFICATION SECTION 9-03.12(3)
SEPARATE BASE
PRECAST
PRECAST WITH RISER
NOTES:
1 _ NO STEPS ARE REQUIRED WHEN HEIGHT IS 4' OR LESS.
2. THE BOTTOM OF THE PRECAST CATCH BASIN MAY BE
SLOPED TO FACILITATE CLEANING,
3, THE RECTANGULAR FRAME AND GRATE MUST BE
INSTALLED WITH THE FLANGE DOWN. THE FRAME MAY BE
CAST INTO THE ADJUSTMENT SECTION.
4. KNOCKOUTS SHALL HAVE A WALL THICKNESS OF 2'
MINIMUM T02S MAXIMUM. PROVIDE A 1.5' MINIMUM GAP
BETWEEN THE KNOCKOUT WALL AND THE OUTSIDE OF THE
PIPE. AFTER THE PIPE IS INSTALLED. FILL THE GAP WITH
JOINT MORTAR IN ACCORDANCE WITH STANDARD
SPECIFICATION 9-04.3.
5. ALL GRADE RINGS, RISERS, AND CASTINGS SHALL BE SET
IN MORTAR IN ACCORDANCE WITH STANDARD
SPECIFICATION 9-04.3.
6, WHEN CONNECTING TO A NEW PIPE, USE A FLEXIBLE
CONNECTOR (KOR-WSEAL BOOT WITH CORRUGATED PIPE
ADAPTER OR APPROVED EQUAL). WHEN CONNECTING TO
AN EXISTING PIPE, USE A FABRICATED SAND COLLAR OF
THE SAME MATERIAL AS THE CONNECTING PIPE.
T MORTAR SHALL BE MIXED AND APPLIED PER
MANUFACTURER'S DIRECTIONS.
8. FRAME SHALL BE ADJUSTED TO PAVEMENT GRADE BY
TAPPING UNTIL FRAME IS FLUSH WITM PAVEMENT AS
DETERMINED WITH A STRAIGHT EDGE OF SUFFICIENT
LENGTH.
9. ALL MORTAR JOINTS SHALL BE TRIMMED FLUSH AND
REMAIN VISIBLE UPON COMPLETION.
• PUBLIC WORKS
DEPARTMENT
CATCH BASIN DIMENSIONS
CATCH BASIN
DIAMETER
MIN. WALL
THICKNESS
MIN. BASE
THICKNESS
MAXIMUM
KNOCKOUT SIZE
MINIMUM
DISTANCE
BETWEEN
KNOCKOUTS
48'
4-
6'
3V
8'
54'
4S"
6
42'
8•
60•
5'
6
48'
8"
12'
6'
8'
6D'
12'
84'
6
12'
7r
12'
96
6
12'
84"
12'
Tr
/0'
1r
96'
1T
144"
12"
12"
108'
IT
PIPE ALLOWANCES
CATCH BASIN
PIPE MATERIAL WITH MAXIMUM INSIDE DAMETER
DIAMETER
CONCRETE
ALL METAL
CPSSP'
SOLD WALL
PVC
PROFILE WALL
PVC 3
48"
24'
30'
24•
30'
30'
54"
30'
36"
30'
36'
36'
60•
36'
42"
36'
42•
42'
72'
1 42'
1'
42'
48"
48'
84"
54
60'
S4'
48"
48'
96"
SO"
72'
6D'
48"
48'
12W
66'
84
60"
4W
48'
144"
78'
96•
60"
48'
48'
'CORRUGATED POLYETHYLENE STORM SEWER PIPE (STD. SPEC. 9-05.20)
2 STD. SPEC. 9-05.12(1)
3 STD. SPEC. 9-05A2(2)
STD. PLAN - 201.00
CATCH BASIN TYPE 2 GAZ 9/28/2018 I
DATE
DocuSign Envelope ID'. 3B1B34D3-7EOA476C-ADB34329FFEOC108
ADDITIONAL LADDER RUNGS (IN SETS) TO
T MIN. CLEARANCE TO �✓ \` ALLOW ACCESS TO TANKS OR VAULTS
ANY PORTION OF FLOW RESTRICTOR i N WHEN CATCH IS FILLED WITH WATER
TEE INCLUDING ELBOWS /
REM VABLE WATERTIGHT
COUPLING OR FLANGE 2' MIN, A
ELBOW RESTRICTOR.
SEE DETAIL AND NOTE 10
/ ANGLE AS /
NECESSARY, /
SEE NOTE 7 j
6 MIN. �
7 MN.
s' MAx.
PLATE WELDEDTOELBOW WITH PLAN VIEW
ORIFICE AS SPECIFIED. SEE NOTE 3
ELBOW RESTRICTOR DETAIL
ELEVATION PER PLANS
12- MIN. UNDER FRAME 8 SOLID COVER MARKED --IN- WITH
PAVEMENT LOCKING BOLTS PER STD. PLANS 204.40 AND 204,50
16' MAX.
VERTICAL BAR GRATE FOR
SECONDARY INLET
6'MIN. DESIGN WATER
ELBOW RERICTOR, SURFACE
SEE DETAID NOTE 10 HANDHOLDS. STEPS, OR LADDER
PIPE SPORTS. SEE NOTE 6 r 1r (TYP.)
1.5 X D }I SEE NOTE 9 (TYPJ
MIN. rMIN,
I
D I 4--
"AN
ISOMETRIC i �'I�
OUTLET PIPE, SEE T INLET PIPE
NOTES 1 S 5 2'
INVERT AND MIN. SHEAR GATE WITH CONTROL ROD FOR
ELEVATION PER PLANS CLEANOUT/DRAIN (ROD BENT AS REQUIRED
FOR VERTICAL ALIGNMENT WITH COVER)
12' SECTION OF PIPE ATTACHED BV PER STD. PLAN 237.30
GASKETED BAND TO ALLOW REMOVAL r
r MIN.
WELDED RESTRICTOR PLATE WITH
ORIFICE DIA AS SPECIFIED, SEE NOTE 10
NOTES: SECTION A
1. USE A MIMIMUM OF A SC DIAMETER TYPE 2 CATCH BASIN.
2. OUTLET CAPACITY: IWYEAR DEVELOPED PEAK FLOW.
3. METAL PARTS PREFERRED TO BE STAINLESS STEEL, ALUMINIZED STEEL. OR ALUMINUM. ALL OTHER STEEL PARTS MUST BE GALVANIZED WITH TREATMENTS 1, 2, OR 5.
4. FRAME AND LADDER OR STEPS OFFSET SO:
A. CLEANOUT GATE IS VISIBLE FROM TOP.
B. CLIMB -DOWN SPACE IS CLEAR OF RISER AND CLEANOUT GATE.
C. FRAME IS CLEAR OF CURB.
S IF METAL OUTLET PIPE CONNECTS TO CEMENT CONCRETE PIPE: OUTLET PIPE TO HAVE SMOOTH O.D. EQUAL TO CONCRETE PIPE I.D. LESS 1/4•.
6. PROVIDE AT LEAST ONE 3X.090 GAGE SUPPORT BRACKET ANCHORED TO CONCRETE WALL. (MAXIMUM T-O' VERTICAL SPACING).
7. LOCATE ELBOW RESTRICTOR(S) AS NECESSARY TO PROVIDE MINIMUM CLEARANCE AS SHOWN.
8. LOCATE ADDITIONAL LADDER RUNGS IN STRUCTURES USED AS ACCESS TO TANKS AND VAULTS TO ALLOW ACCESS WHEN CATCH BASIN IS FILLED WITH WATER.
9. WHEN CONNECTING TO ANEW PIPE. USE A FLEXIBLE CONNECTOR (KOR4N-SEAL BOOT WITH CORRUGATED PIPE ADAPTER OR APPROVED EQUAL). WHEN CONNECTING
TO AN EXISTING PIPE, USE A FABRICATED SAND COLLAR OF THE SAME MATERIAL AS THE CONNECTING PIPE.
10, IF TEE SECTION IS USED ONLY FOR SPILL CONTROL, THEN ELBOW RESTRICTORS AND RESTRICTOR PLATES WITH ORIFICES ARE NOT REQUIRED.
UNLESS OTHERWISE NOTED, DRAWING IS NOT TO SCALE INTS)
STD. PLAN - 237.00
PUBLIC WORKS FLOW CONTROL STRUCTURE - ° 'aoetlbl!
j� DEPARTMENT RESTRICTORTEE artwAian"Pastucha 8/1s/zo c
N td.WABA¢BD... DATE
4/16/2021
GH
SURVEYED:
SCALE:
L. WALKER
5/27/2021
GH
DESIGNED:
J. BROWN
7/27/2021
GH
DRAWN:
H.JASTRZEMBSKI
ONE INCH
CHECKED:
J. BROWN
AT FULL SCALE
IF NOT ONE INCH
BY
DATE
APPR
SCALE ACCORDINGLY
APPROVED:
G. HULSMANN
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
:45 AI
C TY OF
1110
Planning/Building/Public Works Dept
1 8:
THE CONTRACTOR SHALL VERIFY THE LOCATION
OF ALL EXISTING UTILITIES PRIOR TO ANY
CONSTRUCTION. AGENCIES INVOLVED SHALL BE
NOTIFIED WITHIN A REASONABLE TIME PRIOR TO
THE START OF CONSTRUCTION.
CALL BEFORE YOU DIG (811)
WWW.WASH I NGTON811.COM
48" FLOW SPLITTER
12' STAND PIPE
IE: 237.80'
i\4JA7 -
(D INLET PIPE IE; 237.80'
12 BYPASS STAND PIPE _ !
1NcT USED 1
FII13H FLEW BYPASS AIPE t
J+CCeB$ STEP$
17 PIPE TO MATE, OL rAUTY FKIUTY
(b RISER PIPE; TOP OF PIPE AT DESIGN
ELEVATION FOR WATER QUALITY
FLOWS
VANE GRATE LID
(9) REMOVABLE 'TEE, SECTION FOR CLEAN
QV1
�¢ RI$ER PIPIT DRIPIC6 $iI$ED 1`01R WATER
QUALITY FLOWS AND-GAI.CULATED FLOW CONTROL
RI M: 243.25'
IE: 237.00'
1 T STAI CI PIPE
IF: 237.00'
f��e= t>
IFIGE 1.59-
1.63'
DETENTION TANK FLOW CONTROL
STRUCTURE ELEVATION EXHIBIT
54" MANHOLE
237.00'
'. NOTCH WIDTH: 0.019'
_______
236.35'
N
A
5' A
� m
IE: 232.00' 36" CMP (E) 24" IE: 232.00' 12" PVC (W)
BOTTOM ORIFICE`
DIAM 042 24
7.
REFER TO CITY OF RENTON DETAIL STD. PLAN 237.00 FOR
CONSTRUCTION STANDARDS.
R-417212
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DEVELOPMENT ENGINEERING III,+% SURFACE WATER UTILITY
NJanders 12/20/2021 J Farah 12/20/2021
MEI LIN VIEW
1833 NE 12TH ST
RENTON, WA 98056
DRAINAGE NOTES AND DETAILS