HomeMy WebLinkAboutEx10_Lighting_Schematic_Design_PlansPROJECT LOCATION
4350 LAKE WASHINGTON BLVD N
RENTON, WA 98056
PROJECT ADDRESS
LOCATION / SITE MAP
SCALE: NOT TO SCALE
LIGHTING
a WALL SWITCH -SUBSCRIPT INDICATES:
3 = 3-WAY
4 = 4-WAY
LV = LOW-VOLTAGE
NS = NIGHT SETBACK
a = LOWER CASE LETTERS INDICATES
SWITCHING GROUP DESIGNATION
T = TIMER
OS = OCCUPANCY SENSOR
a DIMMER SWITCH
DAYLIGHT SENSOR
OCCUPANCY SENSOR, CEILING MOUNTED
OCCUPANCY SENSOR, WALL MOUNTED
F1
6a, b
LIGHT FIXTURE, SIZES VARY. REFER TO FIXTURE TYPE.
TYPICAL ALL FIXTURES:
ADJACENT NUMBER INDICATES CIRCUIT GROUPING
LOWER CASE LETTER INDICATES SWITCHING GROUP
FIXTURE ON EMERGENCY CIRCUIT
SIZE VARIES, REFER TO FIXTURE TYPE.
WALL-MOUNTED FIXTURE
SIZE VARIES, REFER TO FIXTURE TYPE.
WALL MOUNTED FIXTURE ON EMERGENCY CIRCUIT.
SIZE VARIES, REFER TO FIXTURE TYPE.
STRIP FIXTURE
SIZE VARIES, REFER TO FIXTURE TYPE.
STRIP FIXTURE ON EMERGENCY CIRCUIT
SIZE VARIES, REFER TO FIXTURE TYPE.
DOWNLIGHT ON EMERGENCY CIRCUIT
,STEP LIGHTS
PENDANT LIGHT
ILLUMINATED EXIT SIGN -FACES & DIRECTION OF
ALL ARROWS AS SHOWN, WHERE INDICATED
TRACK LIGHTING, LENGTH AS INDICATED
TROFFER
SURFACE DOWNLIGHT
LINEAR PENDANT
LINEAR WALL WASH
RECESSED DOWNLIGHT FIXTURE
RECESSED WALL WASH/ADJUSTABLE FIXTURE
,
,
WALL SCONCE,
SURFACE WALL WASH/ADJUSTABLE DOWNLIGHT
DS
OS
OS
C 2020 HENSLEY LAMKIN RACHEL, INC.
DOCUMENTS AS INSTRUMENTS OF SERVICE ARE
GIVEN IN CONFIDENCE AND REMAIN THE
PROPERTY OF HENSLEY LAMKIN RACHEL, INC.
THIS DOCUMENT AND THE INFORMATION
CONTAINED HEREIN MAY NOT BE DUPLICATED,
USED, OR DISCLOSED WITHOUT WRITTEN
CONSENT OF HENSLEY LAMKIN RACHEL, INC.
Site Plan Submittal:
Construction Set Issue:
Drawing No.
Project ID
HENSLEY LAMKIN RACHEL, INC.
DALLAS ●HOUSTON ● SEATTLE
WWW.HLRINC.NET
PH:972.726.9400
Project Title:
PROJECT MGR:
DRAWN BY:
CHECKED BY:
REVISIONS
Permit Issue:NOT FOR CONSTRUCTION07.01.2021
20485
Designer
Author
Checker
KENNYDALE
GATEWAY
RENTON,
WASHINGTON
E0.0
LIGHTING LEGENDS AND
ABBREVIATIONS
LIGHTING SHEET INDEX
SHEET
NUMBER SHEET NAME
SHEET
SCALE
MASTER SITE
PLAN
6/7/2021
E0.0 LIGHTING LEGENDS AND ABBREVIATIONS NTS X
EL0.1 LUMINAIRE SCHEDULE & SEQUENCE OF OPERATIONS NTS X
EL3.0 SITE PLAN - LIGHTING 1" = 30'-0" X
EXHIBIT 10
RECEIVED
Clark Close 12/17/2021
PLANNING DIVISION
DocuSign Envelope ID: AB259DAD-E1F4-4927-9B6D-D48F19435899
C 2020 HENSLEY LAMKIN RACHEL, INC.
DOCUMENTS AS INSTRUMENTS OF SERVICE ARE
GIVEN IN CONFIDENCE AND REMAIN THE
PROPERTY OF HENSLEY LAMKIN RACHEL, INC.
THIS DOCUMENT AND THE INFORMATION
CONTAINED HEREIN MAY NOT BE DUPLICATED,
USED, OR DISCLOSED WITHOUT WRITTEN
CONSENT OF HENSLEY LAMKIN RACHEL, INC.
Site Plan Submittal:
Construction Set Issue:
Drawing No.
Project ID
HENSLEY LAMKIN RACHEL, INC.
DALLAS ●HOUSTON ● SEATTLE
WWW.HLRINC.NET
PH:972.726.9400
Project Title:
PROJECT MGR:
DRAWN BY:
CHECKED BY:
REVISIONS
Permit Issue:NOT FOR CONSTRUCTION07.01.2021
20485
Designer
Author
Checker
KENNYDALE
GATEWAY
RENTON,
WASHINGTON
EL0.1
LUMINAIRE SCHEDULE &
SEQUENCE OF
OPERATIONS
E3 40INCH TALL BOLLARD, 360DEG GENERAL PATHWAYS FORMS + SURFACES LBHL0-603-3000K-360 LED, 3000K, 80+ CRI 424LM 40W 120-277V
INTEGRAL,
ELECTRONIC 0-10V 6"DIA X 40"H DARK GREY 1. BUG RATING - B0-U1-G0
E2 20FT TALL POST TOP LUMINAIRE WITH 3FT
MOUNTING ARM, TYPE V DISTRIBUTION ROADWAY & PARKING LUMCA
LUMINAIRE:
LIO-M-SM-A-0-5-01-36LED05-530MA-60W-120
V-L5S-30K-C80-SG
MOUNTING ARM: PM5-CF80-36
POLE: AP05-20-WB9-SG-ANCHOR BOLTS
LED, 3000K, 80+ CRI 6716LM 60W 120-277V
INTEGRAL,
ELECTRONIC 0-10V - STEEL GREY
1. BUG RATING - B3-U0-G1
2. BOTTOM OF LUMINAIRE TO BE AT 17FT
3. STRUCTURAL ENGINEER TO VERIFY ANCHOR
BOLT LENGTHS AND OVERALL POLE ASSEMBLY ARE
APPROPRIATE FOR EPA WIND SPEEDS IN
INSTALLATION AREA.
E1A
20FT TALL POST TOP LUMINAIRE WITH 3FT
MOUNTING ARM, TYPE III DISTRIBUTION
WITH HOUSE SIDE SHIELDED OPTICS
ROADWAY & PARKING LUMCA
LUMINAIRE:
LIO-M-SM-A-0-5-01-36LED05-530MA-60W-120
V-L3-30K-C80-SG-HSS
MOUNTING ARM: PM5-CF80-36
POLE: AP05-20-WB9-SG-ANCHOR BOLTS
LED, 3000K, 80+ CRI 6716LM 60W 120-277V
INTEGRAL,
ELECTRONIC 0-10V - STEEL GREY
1. BUG RATING - B1-U0-G1
2. BOTTOM OF LUMINAIRE TO BE AT 17FT
3. STRUCTURAL ENGINEER TO VERIFY ANCHOR
BOLT LENGTHS AND OVERALL POLE ASSEMBLY ARE
APPROPRIATE FOR EPA WIND SPEEDS IN
INSTALLATION AREA.
E1 20FT TALL POST TOP LUMINAIRE WITH 3FT
MOUNTING ARM, TYPE III DISTRIBUTION ROADWAY & PARKING LUMCA
LUMINAIRE:
LIO-M-SM-A-0-5-01-36LED05-530MA-60W-120
V-L3-30K-C80-SG
MOUNTING ARM: PM5-CF80-36
POLE: AP05-20-WB9-SG-ANCHOR BOLTS
LED, 3000K, 80+ CRI 6716LM 60W 120-277V
INTEGRAL,
ELECTRONIC 0-10V - STEEL GREY
1. BUG RATING - B1-U0-G1
2. BOTTOM OF LUMINAIRE TO BE AT 17FT
3. STRUCTURAL ENGINEER TO VERIFY ANCHOR
BOLT LENGTHS AND OVERALL POLE ASSEMBLY ARE
APPROPRIATE FOR EPA WIND SPEEDS IN
INSTALLATION AREA.
EXTERIOR LIGHTING
TYPE IMAGE DESCRIPTION LOCATION MANUFACTURER PRODUCT NO. LAMP, CCT, CRI
LUMENS
(DELIVERED) WATTS VOLTAGE DRIVER DIMMING SIZE FINISH NOTES
General Notes:
1. Emergency egress lighting to be provided via inverter unless otherwise noted.
2. All luminaire finishes to be verified by owner/architect/interior designer.
3. CCT = Correlated Color Temperature (measured in Kelvin, K)
4. CRI = Color Rendering Index (higher number is better rendering)
LUMINAIRE SCHEDULE
EXTERIOR LIGHTING
ASTRONOMICAL TIME-CLOCK
EXTERIOR PHOTOCELL
INTELLIGENT CONTROL.
NETWORKED FOR ALL
EXTERIOR LIGHTING,
TIED TO BUILDING
LIGHTING HEAD END.
DIMMING
ACUITY FRESCO TOUCH
SCREEN (OR EQUAL)
ALL EXTERIOR LIGHTING TO BE DIMMABLE.
ALL EXTERIOR LIGHTING TO BE PROVIDED WITH MANUAL ON/OFF CONTROL.
ASTRONOMICAL TIME CLOCK AND PHOTOCELL FOR AUTOMATIC EXTERIOR LIGHTING CONTROL.
SET TIME CLOCK TO THE FOLLOWING.
30 MIN AFTER SUNRISE: TRIGGER EXTERIOR LIGHTING OFF SCENE.
30 MIN BEFORE SUNSET: TRIGGER EXTERIOR LIGHTING ON SCENE.
ALL EXTERIOR LIGHTING TO DIM TO 30% OUTPUT BETWEEN MIDNIGHT AND 6AM.
BUILDING FACADE, SITE AND LANDSCAPE LIGHTING WILL REMAIN ON DURING NON-DAYLIGHT HOURS FOR OCCUPANT
SAFETY /SECURITY IN 24 HOUR OCCUPIED BUILDING.
LOCATE EXTERIOR PHOTOCELL ON ROOF. CONFIRM EXACT SENSOR LOCATION WITH SELECTED LIGHTING CONTROL
MANUFACTURER TO ENSURE OPTIMAL PERFORMANCE. PHOTOCELL TO OVERRIDE TIME CLOCK SETTINGS WHEN MINIMAL
DAYLIGHT IS DETECTED DURING DARK WEATHER PATTERNS.
PROVIDE OVERRIDE SWITCH IN LEVEL 1 ELECTRICAL ROOM FOR ON/OFF OVERRIDE CONTROL OF ALL EXTERIOR
LIGHTING. LABEL SWITCH "EXTERIOR LIGHTING OVERRIDE."
MANUAL DIMMING CONTROLS FOR SELECT EXTERIOR LIGHTING WILL BE PROVIDED AS DESIGN DEVELOPS. LOCATE
DIMMING TOUCH SCREEN IN ELECTRICAL ROOM AT EACH FLOOR LEVEL WHERE EXTERIOR LIGHTING WILL BE DIMMED.
LABEL SWITCH WITH EXTERIOR ZONE NAMES.
...
SPACE TYPE CONTROL TYPE TOPOLOGY CONTROL SWITCH LIGHTING CONTROL ZONES NOTES
1. ELECTRICAL CONTRACTOR AND SELECTED LIGHTING CONTROL MANUFACTURER TO PROVIDE SHOP DRAWINGS AND WIRING DIAGRAMS BASED ON LIGHTING CONTROL SEQUENCE OF OPERATIONS SCHEDULE. SHOP DRAWINGS SHALL INCLUDE RECOMMENDED QUANTITIES AND LOCATIONS FOR SENSORS, RELAYS, PANELS,
SWITCHES, AND OTHER EQUIPMENT REQUIRED TO ACHIEVE CONTROL FUNCTIONS DESCRIBED IN SEQUENCE SCHEDULE. MANUFACTURER RECOMMENDATIONS SHALL SUPERSEDE SENSOR QUANTITIES AND LOCATIONS ILLUSTRATED ON LIGHTING PLANS.
2. LUMINAIRES IN PRIMARY AND SECONDARY DAYLIGHT ZONES TO AUTOMATICALLY DIM FROM 100% POWER TO 15% POWER (MAXIMUM DIMMING THRESHOLD) WHEN PHOTOCELL DETECTS ADEQUATE DAYLIGHT AS DESCRIBED BELOW. BASELINE DESIGNED LIGHT LEVELS SHALL BE DETERMINED BY RECORDING ILLUMINANCE
LEVELS WITH ALL LIGHTS ON AT 100% POWER, WITH NO CONTRIBUTING DAYLIGHTING. AUTOMATIC DAYLIGHT DIMMING SHALL OCCUR WHEN LIGHT LEVELS SHALL MEET OR EXCEED BASELINE DESIGN LEVELS AT ALL TIMES OF OCCUPANCY, INCLUDING WHEN LIGHTS ARE DIMMED VIA DAYLIGHT SENSOR.
3. ALL INTELLIGENT CONTROLS SHALL BE DIGITAL AND MAY BE TIED TO A NETWORK BACKBONE AS NOTED IN SEQUENCE SCHEDULE. STANDALONE LIGHTING CONTROLS CAN BE LOW VOLTAGE OR LINE VOLTAGE (AS REQUIRED PER FUNCTIONS IN SCHEDULE) AND ARE NOT TIED TO A NETWORK BACKBONE.
4. ALL LIGHTING CONTROL DEVICES SHALL BE COMPATIBLE WITH TYPES OF DIMMING NOTED IN APPROVED LIGHTING PRODUCT SUBMITTAL PACKAGE. LIGHTING PRODUCT SUBMITTAL SHALL BE APPROVED BY LIGHTING DESIGNER, ARCHITECT /INTERIOR DESIGNER, AND OWNER.
5. PROVIDE UL924 BYPASS RELAY DEVICES FOR ALL DESIGNATED EMERGENCY EGRESS LIGHTING WITH MANUAL OR AUTOMATIC CONTROLS TO ALLOW ILLUMINATION TO RAISE TO FULL OUTPUT DURING AN EVENT OF POWER LOSS.
6. LIGHTING CONTROL PROGRAMMING AND OWNER TRAINING FOR CONTROL SYSTEM SHOULD BE INCLUDED IN CONTRACTOR BASE BID AND NOT BE INCLUDED AS A CHANGE ORDER.
7. CONTRACTOR SHALL SCHEDULE A PRE CONSTRUCTION MEETING TO REVIEW LIGHTING CONTROL SHOP DRAWINGS WITH THE MANUFACTURER AGENT (INCLUDING DESIGNER /ENGINEER - AS NEEDED) PRIOR TO PRODUCT RELEASE.
...
GENERAL NOTES
LIGHTING CONTROL SEQUENCE OF OPERATIONS
DocuSign Envelope ID: AB259DAD-E1F4-4927-9B6D-D48F19435899
RECYCLECHUTEWASTECHUTERECYCLECHUTE
WASTECHUTE
SSS
TRASH
STAIR
STAIR
LOBBY/MAIL
RETAIL
BIKE STORAGE
COURTYARD
COURTYARD
B1100
1,500 SF
A770
A770
A770
A770
S550A665
STAIRSTAIRLOADING
STAIR
LEASING/LOBBY2,330 SF
CLUB
1,874 SF
FITNESS
1,468 SF
MAIL/PACKAGES1,100 SF
STAIRCOURTYARD
COURTYARD
LOADING
AD800
B1100
S550
B1100
S550STAIRLOBBY/MAIL925 SF
S550
S550 S550
GARAGEENTRY
COVEREDOUTDOORAMENITY
HC
HC
8 SPACES
6 SPACES
6 SPACES
9 SPACES
7 SPACES5 COMPACTSPACES5 SPACES4 SPACES
18 SPACES
4 SPACES
8 SPACES8 SPACES5 COMPACTSPACES
5 COMPACTSPACES
7 COMPACT
SPACES
7 COMPACT
SPACES 6 SPACES10 CARPORT SPACES8 CARPORT SPACES6 CARPORT SPACES5 CARPORT SPACES7 COMPACT
SPACES
8 COMPACT
SPACES
A770
A770
A770
STAIR
B1100 B1100
A770A770
A770
STAIR
HC
VAN HC
4 SPACES
4 SPACES
GARAGE
ENTRYGARAGE
ENTRY
GARAGE
ENTRY GARAGEENTRYMAY CREEK
TRAIL
CONNECTION 7 SPACES7 SPACES4 SPACES6 SPACESLK. WASHINGTON BLVD.I
-405TK - EVOLUTION3500 - SEISMIC 33'-1 1/2"3'-6"8'-8" CLR.6'-11" CLR.TK - EVOLUTION4500 FREIGHT -SEISMIC8'-3" CLR.9'-6 1/2" CLR.1'-1 1/2"4'-6"TK - EVOLUTION4500 FREIGHT -
SEISMIC
8'-3" CLR.9'-6 1/2" CLR.1'-1 1/2"4'-6"
TK - EVOLUTION3500 - SEISMIC 3
3'-1 1/2"
3'-6"
8'-8" CLR.6'-11" CLR.7707707701100770110011001100
TK - EVOLUTION3500 - SEISMIC 3
3'-1 1/2"
3'-6"
8'-8" CLR.6'-11" CLR.TK - EVOLUTION4500 FREIGHT -
SEISMIC
8'-3" CLR.9'-6 1/2" CLR.1'-1 1/2"4'-6"(53)(52)(51)(49)(48)(47)(44)(43)(42)(39)(50)(45)12' CWM W
S
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3
E3E3
E3
E3
E3
E3 E3
E3
E3 E3 E3 E3
E3 E3 E3 E3
E1A
E1A
E1A
E1
E1
E2
E1E1
E1
E1
E1
E1
E1
E1
E1
E1 E1 E1 E1 E1 E1 E1 E1
E1
E1
E1
E1
A. REFER TO SHEET EL0.1 FOR LUMINAIRE SCHEDULE.
B. REFER TO SHEET EL0.1 FOR LIGHTING CONTROL SEQUENCE OF
OPERATIONS.
C. LIGHTING DRAWINGS TO BE REVIEWED IN CONJUNCTION WITH
LUMINAIRE CUT SHEET PACKAGE PROVIDED AS SUPPLEMENT TO
DRAWING PACKAGE.
GENERAL NOTES:
C 2020 HENSLEY LAMKIN RACHEL, INC.
DOCUMENTS AS INSTRUMENTS OF SERVICE ARE
GIVEN IN CONFIDENCE AND REMAIN THE
PROPERTY OF HENSLEY LAMKIN RACHEL, INC.
THIS DOCUMENT AND THE INFORMATION
CONTAINED HEREIN MAY NOT BE DUPLICATED,
USED, OR DISCLOSED WITHOUT WRITTEN
CONSENT OF HENSLEY LAMKIN RACHEL, INC.
Site Plan Submittal:
Construction Set Issue:
Drawing No.
Project ID
HENSLEY LAMKIN RACHEL, INC.
DALLAS ●HOUSTON ● SEATTLE
WWW.HLRINC.NET
PH:972.726.9400
Project Title:
PROJECT MGR:
DRAWN BY:
CHECKED BY:
REVISIONS
Permit Issue:NOT FOR CONSTRUCTION07.01.2021
20485
Designer
Author
Checker
KENNYDALE
GATEWAY
RENTON,
WASHINGTON
EL3.0
SITE PLAN - LIGHTING
1" = 30'-0"01 SITE PLAN - LIGHTING
N
FLAG NOTES
DocuSign Envelope ID: AB259DAD-E1F4-4927-9B6D-D48F19435899