Conditions for Permit B22004791
Building
1 Commercial Alterations for food preparation, food service, or kitchen must have King County Health Department or
State of Washington DOH Approved Plans onsite.
2 Ground Electrode System (either 1 or 2 are approved methods): 1. An electrode of at least 20 ft long bare copper,
sized in accordance with NEC. 2. An electrode of 20 ft long #4 rebar (not less than 1/2 inch in diameter) and
sized per NEC; either one shall be encased by at least 2 inches of concrete, located within and near the bottom
of a concrete footing that is in direct contact with the Earth, and shall be installed in all new residential and
commercial construction.
3 All construction, demolition and land clearing waste must be recycled at a King County licensed or approved
facility, or taken to Regional Disposal Facilities.
4 Authorized hours of construction/activity: 7:00 a.m. - 8:00 p.m. Monday Through Friday; 9:00 a.m. - 8:00 p.m.
Saturday; No work allowed on Sunday. Per Ordinance 4703, 2-2-1998
5 Approval for building permit only-separate approval and permits required for any mechanical, plumbing, electrical,
fire suppression, or hazardous materials system.
6 Erosion Control may be required upon inspection.
7 TREE PROTECTION MEASURES FOR ALL TREES IN THE CONSTRUCTION AREA OF A DEVELOPMENT
SITE. THESE MEASURES INCLUDE: 1. 6 foot high chain link fences around the trees out to and including the
drip line of the tree. 2. All the area within the fenced area needs a minimum of 3" of bark mulch. 3. Warning signs
must also be included on the fence. 4. Construction activity, parking, and storage of materials and equipment is
not allowed within the drip line (and therefore fenced) area of any tree. 5. The only new impervious surfaces
allowed within the drip line of existing trees are those shown on approved building or construction plans, which
typically should be limited to the new buildings, new driveways, new parking lots, new streets and new sidewalks.
8 Instructions for Issued permits:
1. Print full~sized plan sheets in color for field inspector, plans must have text at 1/8" or larger for inspector, print
conditions of approval and attach them to the approved set of plans for the inspector.
2. Hard copies of permit, approved plans, site plans, and conditions must remain on the job site for the inspector.
Inspections will not take place if printed plans are not on site.
Planning
9 Per LUA22-000316, a Critical Areas Exemption for the removal of pavement and restoration of the wetland buffer
shall be submitted by December 26, 2022.
Page 1 of 1
RECEIVED
09/08/2022 striplett
BUILDING DIVISION
B2
2
0
0
4
7
9
1
PROVIDE 8' WIDE ACCESSILE AISLE
OR 11' WIDE VAN STALL. PROVIDE
60" h ACCESSIBLE SIGN
PROVIDE ENGINEERED MODULAR HOLD DOWNS.
as builds and cctv video indicate a sewer stub in the general area of the parcel but there
is not a utility billing account or side sewer on record. applicant shall verify, in the
presence of a public works inspector, that the existing building is connected to the city
sewer.
if the building is not connected to the sewer than the existing on-site septic system shall
be decommissioned in accordance with King County Department of Health and City of
Renton standard 4-6-040.I.6. a new sewer stub shall be installed in accordance with COR
std. plan 406.1 with a building sewer installed in accordance with COR std. plan 406.2. a
permit will be required for installation of new sewer stub and side sewer.
utility review comments pertain to the office building only. separate
permits are required for the lumber warehouse and the site paving.
install a DCVA per
COR std. plan 340.8.
DCVA shall be
installed on private
property as close as
possible to the
existing meter.
a separate plumbing
permit is required,
contact the building
department for
assistance in
acquiring permit.
Per LUA22-000316, a
Critical Areas
Exemption for the
removal of pavement
and restoration of
the wetland buffer
shall be submitted by
December 26, 2022.
EF1
EF1
PLUMBING AND ELECTRICAL
UNDER SEPARATE PERMIT
AND PER FIELD INSPECTORS
REVIEWED
BUILDING DIVISION
By: Rick Lee
Date: 09/09/2022
THIS SET OF REVIEWED PLANS INCLUDE BOTH THE SUBMITTED
DESIGN AND ADDITIONAL CODE REQUIREMENTS MARKED IN RED.
PLANS MUST BE MADE AVAILALE ON THE JOB AT ALL TIMES
DURING CONSTRUCTION. THIS BUILDING / PROJECT IS NOT TO BE
OCCUPIED UNTIL AFTER FINAL INSPECTION BY THE RENTON
BUILDING DIVISION