HomeMy WebLinkAbout310.1FIRE HYDRANT SHALL BE COREY—TYPE EQUAL TO IOWA F-5110 OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2" HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR, 4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT. KELLY— MOORE/PRESERVATIVE PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED. MIN. 18" TO 20" BEHIND BACK OF CURB OR 12" BEHIND BACK OF 3' SIDEWALK THAT IS ADJACENT TO CURB 4.875" x 5" STORZ 5'x5'x6" THICK CONCRETE PAD AROUND HYDRANT. FINISH TO MATCH SIDEWALK. E EXPANSION JOINT AT 2`1 BACK OF SIDEWALK fCONCRETE SIDEWALK OR PLANTING STRIP 36" MIN COVER TWO—PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION WITH REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION AS REQUIRED. RAISED PAVEMENT MARKER TYPE 88—A STIMSONITE TWO—WAY BLUE REFLECTIVE CONCRETE BLOCKING CONCRETE � ' �. THRUST BLOCK�MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET. 6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT 6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT 2-3/4" COR—TEN STEEL TIE RODS. 16" x 8" x 4" MININUM X1/2 YARD OF 1-1/4" WASHED DRAIN ROCK CONCRETE BEARING 1' ABOVE BOOT FLANGE. PLACE 8 MIL BLOCK UNDER HYDRANT POLYETHYLENE FILM AROUND TOP AND SIDES OF GRAVEL. 1 O� FIRE HYDRANT ASSEMBLY CUT D ONE MAN ROCK - 1 6 TE PAD LEVEL ALL GROUND MIN 3' RADIUS a elk 6" CONCRETE PAD FI LL HYDRANT LOCATION IN CUT OR FILL ZY STD. PLAN — 310.1 + e� �+ PUBLIC WORKS FIRE HYDRANT ASSEMBLY �O DEPARTMENT N,yp MARCH 2010