HomeMy WebLinkAbout320.4REGISTER SHALL BE TOUCH READ PIT LID 4" POST INDICATOR VALVE
(TR -PL) AND BE INTELLIGENT COMMUNICATION (MJxMJ) PAINTED BLUE
ENCODER TYPE (ICE). METER MUST READ IN 2-3/4" SHACKLE RODS PER CITY
CU. FT. OF RENTON SPECIFICATIONS
4" 90° BEND (MJ) L�4"
"°END (MJ)
IN TEST
2"x2"
TEE (MJxFL) 12.. 13 LF 4" D.I.NIPPLE WITH
w GATE VALVE (FLxMJ) 0 7'-0"� ESILIENT
BRASS GATE
AND 2" PLUG.
LADDER W4" FLxMJ ADAPTOR J SUPPORT BARS 2, - ADAPTOR
PER OSHA
4" or 6" D.I.
TO BUILDING
FLOW
EPDXY NON -SHRINK
GROUT • 2'-4"
4" TEE (MJxFL) —
�J WELDED STEEL COLLAR
TOUCH READ PIT LID SENSOR MOUNTED ON
STEEL PLATE COVER THROUGH 2" DIA.
DRILLED HOLE IN COVER. LOCATE HOLE 2Y2"
FROM EDGE OF PIT LID AND RIBS.
PRECAST CONCRETE VAULT WITH 2 3"x3" HINGED STEEL
PLATE COVER. OUTSIDE DIMENSIONS 4'-8"x7'-0".
(EQUAL TO PIPE INC., OR UTILITY VAULT WITH
57 -7L -B, 2 3'x3' DIAMOND PLATE DOORS)
6",4" OR 3" GATE VALVE (FLxFL)
NON -RISING STEM WITH HAND WHEEL
EQUAL TO MUELLER CO.A-2380-6.
6" OR 4" (FLxPE) CEMENT LINED
DUCTILE IRON PIPE CLASS 52 3'-6"
LONG WITH COLLAR 20" FROM P.E.
EQUAL TO THOSE SUPPLIED BY PACIFIC S' 4"
WATER WORKS CO. INC.
12" AROUND-
4" TEE
(FL)
CITY PRIVATE
PIPING PIPING
DEADMAN BLOCK
REQUIRED WITH
SHACKLING TO TEE
SENSUS MODEL 520R RADIO
wQ91
READ PIT SET SENSOR
MOUNTED ON STEEL PLATETWO
PIECE CAST IRON VALVE BOX,
COVER THROUGH 2" DIA.
EQUAL TO OLYMPIC FOUNDRY CO.
DRILLED HOLE IN COVER
STANDARD 8" TOP SECTION, WITH
REGULAR BASE SECTION LENGTH TO FI'
6",4" OR 3" COMPOUND WATER METER (FL) J
EQUAL TO SENSUS SRII COMPOUND METER WITH
TOUCHREAD PITUD I.C.E. REGISTER & SENSOR
WITH 4 WHEEL HIGH RESOLUTION (100 CUBIC ADJUSTABLE STEEL
FEET) REGISTER. FOR 3" METER, REDUCE AT PIPE SUPPORT
METER WITH 4"X3" FLxFL CONCENTRIC STANCHION BOLTED
REDUCER. TO FLOOR
e7IIaI11113maIII l26*3
ALL METERS AND BACKFLOW PREVENTION DEVICE COMBINATIONS ARE
NOT SHOWN OR INCLUDED IN THE STANDARD DETAIL DRAWINGS. IF
YOUR PARTICULAR COMBINATION IS NOT SHOWN, AN APPROVED
DRAWING WILL BE REQUIRED BY THE UTILITY ENGINEERING DEPT. FOR
ITS INSTALLATION.
THE PRINCIPAL REQUIREMENTS REGARDING VAULT SIZING ARE THE
LENGTH OF FITTINGS OR THEIR CLEARANCE FROM THE VAULT WALLS,
(WHICH CLEARANCE SHALL BE A MINIMUM OF 12" FROM THE ENDS AND
THE SIDE CLEARANCE SHOULD BE AS TYPICALLY SHOWN ON THE
VARIOUS STANDARD DETAILS).
NOTE: DEADMAN BLOCK SHALL BE DESIGNED AND INSTALLED SO IT
BEARS AGAINST SUFFICIENT UNDISTURBED EARTH SO AS TO SUPPORT
THE DESIGNED THRUST.
VALVE NUT EXTENSION IF REQUIRED
(DWG BR46/PAGE 8090)
6", 4" OR 3" GATE VALVE
(FLxMJ) EQUAL TO
MUELLER CO. A-2380-20.
TO BUILDING
CITY PRIVAI
PIPING PIPING
6" OR 4" PExPE CEMENT
LINED DUCTILE IRON PIPE
CLASS 52. LENGTH TO FIT.
6" OR 4" FLEXIBLE FLANGED
COUPLING ADAPTOR, ROMAC
OR APPROVED EQUAL.
ZY
+ er< �+ PUBLIC WORKS 3", 4" & 6" COMPOUND DOMESTIC STD. PLAN — 320.4
�O DEPARTMENT WATER METER ASSEMBLY
N,yp MARCH 2010
wQ91
III II IJP '
1�7 e
S
6",4" OR 3" COMPOUND WATER METER (FL) J
EQUAL TO SENSUS SRII COMPOUND METER WITH
TOUCHREAD PITUD I.C.E. REGISTER & SENSOR
WITH 4 WHEEL HIGH RESOLUTION (100 CUBIC ADJUSTABLE STEEL
FEET) REGISTER. FOR 3" METER, REDUCE AT PIPE SUPPORT
METER WITH 4"X3" FLxFL CONCENTRIC STANCHION BOLTED
REDUCER. TO FLOOR
e7IIaI11113maIII l26*3
ALL METERS AND BACKFLOW PREVENTION DEVICE COMBINATIONS ARE
NOT SHOWN OR INCLUDED IN THE STANDARD DETAIL DRAWINGS. IF
YOUR PARTICULAR COMBINATION IS NOT SHOWN, AN APPROVED
DRAWING WILL BE REQUIRED BY THE UTILITY ENGINEERING DEPT. FOR
ITS INSTALLATION.
THE PRINCIPAL REQUIREMENTS REGARDING VAULT SIZING ARE THE
LENGTH OF FITTINGS OR THEIR CLEARANCE FROM THE VAULT WALLS,
(WHICH CLEARANCE SHALL BE A MINIMUM OF 12" FROM THE ENDS AND
THE SIDE CLEARANCE SHOULD BE AS TYPICALLY SHOWN ON THE
VARIOUS STANDARD DETAILS).
NOTE: DEADMAN BLOCK SHALL BE DESIGNED AND INSTALLED SO IT
BEARS AGAINST SUFFICIENT UNDISTURBED EARTH SO AS TO SUPPORT
THE DESIGNED THRUST.
VALVE NUT EXTENSION IF REQUIRED
(DWG BR46/PAGE 8090)
6", 4" OR 3" GATE VALVE
(FLxMJ) EQUAL TO
MUELLER CO. A-2380-20.
TO BUILDING
CITY PRIVAI
PIPING PIPING
6" OR 4" PExPE CEMENT
LINED DUCTILE IRON PIPE
CLASS 52. LENGTH TO FIT.
6" OR 4" FLEXIBLE FLANGED
COUPLING ADAPTOR, ROMAC
OR APPROVED EQUAL.
ZY
+ er< �+ PUBLIC WORKS 3", 4" & 6" COMPOUND DOMESTIC STD. PLAN — 320.4
�O DEPARTMENT WATER METER ASSEMBLY
N,yp MARCH 2010