Loading...
HomeMy WebLinkAbout330.2CAP 22-1/2' BEND 45° BEND TEE 90° BEND THRUST BLOCK BEARING AREA IN SQUARE FEET (SEE NOTES) FOR HORIZONTAL AND DOWNWARD VERTICAL BENDS SOIL FIRM SILT COMPACT SAND FIRM SILTY SAND COMPACT SAND & GRAVEL 90°45° BEND 11 1/4° 90° 45` BEND 11 1/4° 90° 45° BEND 11 1/4° FITTING BEND TEE CAP OR PLUG & 22 1/2° BEND TEE CAP OR PLUG & 22 1/2° BEND TEE CAP OR PLUG & 22 1/2° BEND BEND BEND 4" 7.0 4.2 1 4.2 1.7 2.9 2.1 2.1 1.0 2.2 1.6 1.6 1.0 6" 13.3 9.4 9.4 3.8 6.7 4.7 4.7 1.9 5.0 3.5 3.5 1.4 8" 23.3 16.7 16.7 6.7 11.7 8.4 8.4 3.4 8.8 6.3 6.3 2.5 12" 53.0 37.5 37.5 15.0 126.5 18.8 18.8 7.5 20.0 14.0 14.0 5.6 AREAS CALCULATED ON 300 PSI TEST PRESSURE. 3'-0" MIN. COVER FOR WATERMAIN LESS THAN 12". 4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER. MAX. HEIGHT OF THRUST BLOCK (FT) = 0.5 x DEPTH OF TRENCH MIN. HEIGHT OF THRUST BLOCK (FT) = O.D. PIPE + 1.0' TRUST BLOCK BE, REA REFERS TO 4CE OF BLOCK M IN SQUARE FEET NOTES: 1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND FOR SOIL TYPES DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER. 2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND. 3. ALL POURED THRUST BLOCKS SHALL BE BACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING SHALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH. 4. ALL BLOCKING SHALL BE CONCRETE CL 5 (1-1/7'). 5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA POSSIBLE, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOINT BOLTS OR GLANDS REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED. r+(ND CONCRETE BLOCKING FOR STD. PLAN - 330.2 PUBLIC WORKS DEPARTMENT HORIZONTAL AND DOWNWARD Ll VERTICAL BENDS MARCH 2010