HomeMy WebLinkAbout360.2PRECAST CONCRETE VAULT WITH 3 - 3'x 3'
ONE EACH SIDE
4"x 2 1/2" FIRE DEPARTMENT DOUBLE
HINGED STEEL PLATE COVERS. DIMENSIONS
CONNECTION FOR STAND PIPE WITH
5'-8"x 11'-2"x 7'-2" EQUAL TO UTILITY
4" ADAPTER, FL.x SCREWED
BREAKABLE CAST IRON HOSE CAPS.
VAULT OR EQUAL
4"x4"x6" BULL HEAD TEE, FL.
ONE EACH SIDE EQUAL TO GRINNEL
TOUCH READ PIT LID SENSORFIG.
MOUNTED ON STEEL PLATE
6" PIPE FL.x
1682 WITH HOSE CAPS FIG. 1333.
6" SWING TYPE GRAVITY OPERATED
COVER THROUGH 2" DIA.
FL. 2'- 0" LO
CHECK VALVE, FL. EQUAL TO
DRILLED HOLE IN COVER.
MUELLER CO. A-2600-6 WITH BALL
THE BY-PASS ASSEMBLY SHALL BE
2'-6"
DRIP VALVE AT BOTTOM
INCLUDED AS PART OF THE DETECTOR
DOUBLE CHECK VALVE ASSEMBLY.
18" FOR 10" ASSEMBLY
INSTALL EPDXY NON -SHRINK
GROUT (TYP.)
5/8"x3/4" SENSUS SRII (TR/PL) METER
17 1/2" FOR 8" ASSEMBLY 1
6" PIPE, FL.x FL 3'0" LONG
WITH ICE REGISTER.
18 1/2" FOR 6" ASSEMBLY 3'-0'
ICE REGISTER
\
11'- 2"
6"& 8" ASSEMBLY. 6" SHORT
CITY PRIVATE
_
RADIUS 90° BEND FL.
Z PIPING PIPING
a
STORM DRAIN SYSTEM WITH
10" ASSEMBLY 90° 8"X6"
REDUCING BEND FL.
TEE (MJ x FL)
(2�—"
CATCH BASIN OR MANHOLE
L:3'-2"6"
VALVE (FL x MS)
E 3/� 5'- 8"
90° BEND FLGATE
2�I
m m m 1 m
m m
-TO CITY MAIN TO BUILDING
12" ALL AROUNDa2-6
DEADMAN
BLOCK
CONCRETE REQUIRED.
BLOCKING
10",8",6" FL x MJ ADAPTOR
ALL DETECTOR DOUBLE CHECK VALVE
10", 8" OR 6" FL.x P.E. ASSEMBLIES SHALL INCLUDE RESILIENT
PIPE WITH COLLAR 18" SEATED SHUTOFF VALVES AND TEST PLAN 10" ASSEMBLY 10"x10%8"TEE FL.
FROM P.E. COCKS. AND APPROVED 8" ASSEMBLY 8"x8"x6" TEE, FL. 6"
CROSS -CONNECTION CONTROL ASSEMBLY 6'x6"x6" TEE, FL.
10"- 3'-8" LONG ASSEMBLIES PER DEPARTMENT OF
8"- 3'-6" LONG HEALTH LATEST APPROVED LIST. 10", 8", OR 6" GATE VALVE, FL.x MJ,
6"- 4'-0" LONG WITH INDICATOR POST. INDICATOR
DOUBLE CHECK VALVE ASSEMBLY POST VALVE SAME SIZE AS DOUBLE
INCLUDES TWO RESILIENT SEATED CHECK VALVE (MUELLER CO. OR
SHUTOFF VALVES. EQUAL), PAINTED RED.
10", 8", OR 6" FLANGED COUPLING
ADAPTER EQUAL TO ROMAC.
10", 8", OR 6" DUCTILE IRON
CLASS 52 NIPPLE PIPE,
CEMENT LINED, LENGTH TO FIT.
TOUCH READ PIT LID SENSOR MOUNTED
ON STEEL PLATE COVER THROUGH 2" DIA.
NOTE: DRILLED HOLE IN COVER.
1. LOCATE VAULT IN PLANTING AREA, NOT IN PAVING.
2. 4" AND LARGER BENDS AND TEES TO BE CAST
IRON CEMENT LINED.
3. TEMPORARY SUPPORT SHALL BE PROVIDED UNDER
VALVES AT THE TIME OF INSTALLATION TO CENTER
THE PIPE IN VAULT OPENING. AFTER COMPLETE
INSTALLATION REMOVE THE TEMPORARY SUPPORT
AND INSTALL ADJUSTABLE PIPE SUPPORT.
4. INSTALL GALVANIZED LADDER FOR ACCESS.
5. AFTER FIELD INSTALLATION, MAIN DDCVA AND
BY-PASS DCVA MUST BE TESTED SATISFACTORILY
BY A DEPT. OF HEALTH CERTIFIED BACKFLOW
ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED
TO CITY OF RENTON WATER UTILITY ENGINEERING
DEPT. PRIOR TO ACTIVATION OF NEW LINE.
6. INSTALL BRASS Y4' FLARE TEST COCKS WITH Y4'
FLARE CAPS.
COMPACTED FOUNDATION
GRAVEL
ADJUSTABLE STEEL PIPE SUPPORT,
STANCHIONS BOLTED TO FLOOR.
CNIFI \/IC\A/
Y 6",8" & 10" DOUBLE DETECTOR CHECK STD. PLAN — 360.2
PUBLIC WORKS
+ DEPARTMENT ASSEMBLY WITH STANDPIPE OUTSIDE
�N'ro INSTALLATION MARCH 2010
3"
T
36"TO 42'
6" PIPE
FL. x SCREW
18" FOR 10" ASSEMBLY 17
1/2" FOR 8" ASSEMBLY 18
1/2" FOR 6" ASSEMBLY
2'-6"
3' 2"
5/8"x3/4" INVENSYS
TR -PL METER WITH 7'-2"
ICE REGISTER
6" MIN. DRAIN TO DAYLIGHT OR
STORM DRAIN SYSTEM WITH
6" 90° BEND FL.�
CATCH BASIN OR MANHOLE
; 2'-11"
GALVANIZED
STEEL LADDER
COMPACTED FOUNDATION
GRAVEL
ADJUSTABLE STEEL PIPE SUPPORT,
STANCHIONS BOLTED TO FLOOR.
CNIFI \/IC\A/
Y 6",8" & 10" DOUBLE DETECTOR CHECK STD. PLAN — 360.2
PUBLIC WORKS
+ DEPARTMENT ASSEMBLY WITH STANDPIPE OUTSIDE
�N'ro INSTALLATION MARCH 2010