HomeMy WebLinkAbout119LUMINAIRE WARES WILL BE A CONTINUOUS RUN
FROM FUSE HOLDER TO FIXTURE WITH
NO SPLICES. �
FUSE KITS WICK DISCONNECT
3 AMP IN UNE FUSE KITS
S.E.C. OR EQUAL
REFER TO WSOOT LOCKING UO STANDARD
DUTY JUNCTION BOX TYPES 1 & 2
STANDARD PLAN J-40.10-03
GROUND LUG
SPLLICE KITS CLEAR EPDXY
2" MIN. GROUT
WIRE RUNS ON ALL THRU
UNDER POLE BA'
4" CONCRETE PAD
5" 9•
sr
2' MIN. 08 BARE COPPER
GROUND WIRE
1
GROUND
CLAMP
I -/8 EQUIPMEN
NREW/GREEN INSULATION
2" PVC CONDUIT
FROM SERVICE CABINET
SYSTEM
2 - LIGHTING SYSTEM
WIRES TO CONTACTOR
(SIZED AS REOV)
CONCRETE -
FOIINDATION
5/8°x8' COPPER CLAD
GROUND ROD
GROUND ROD
LUMINAIRE
LUMINAIRE WIRES WILL BE 112
AWG IN A JACKETED CABLE.
I GREEN INSULATED WIRE
0 FIXTURE GROUND LUG
1/4'
DRAM
7 S0. OR DIA.
NOTES:
1. EQUIPMENT GROUND WIRE & BARE WIRE SHALL BE
SECURELY FASTENED TO THE GROUND LUG INSIDE THE
POLE HANDHOLE. ALL BONDING & GROUNDING CONNECTIONS
SHALL REMAIN ACCESSIBLE FOR INSPECTION AND
MAINTENANCE.
2. IF THE FIXTURE MANUFACTURER HAS MADE PROVISION FOR
THE ATTACHMENT OF A GROUND WIRE A GREEN INSULATED
WIRE OF THE SAME SIZE SHALL BE RUN FROM THE FIXTURE
TO THE GROUND LUG INSIDE THE POLE HANDHOLE. IF THE
FIXTURE MANUFACTURER HAS A GROUND LUG A #8 GREEN
INSULATED WIRE SHALL BE RUN FROM THE FIXTURE
GROUND LUG TO THE POLE GROUND LUG.
OF CONCRETE FOUNDATION TO
LEVEL WITH TOP OF SIDEWALK
CURB,
STD. PLAN — 119
[_(4 PUBLIC WORKS TYPICAL LIGHTING APPROVEDU
DEPARTMENT UNDERGROUND SYSTEM 4o